Professional Documents
Culture Documents
Technical Specifications - Simple Written Format
Technical Specifications - Simple Written Format
-AND-
TECHNICAL DESCRIPTION
1
PROJECT : Proposed Site Development of Sol Oriente Heights Condominium
Project
LOCATION : Blk 56 Lot 17 Kapayapaan Village, Palao Canlubang, Laguna
SECTION DIV.:
101. NOTE: This specification is prepared in concise manner with the intention to
save time and to simplify specifications elaborateness. All work covered in
this contract shall be executed in the highest form of workmanship and
quality of materials.
102. The drawings and specifications are intended to explain each mutually, and
anything shown or called for in one and not in the other shall be executed as
part of the contract as though both are shown and specified.
The Contractor shall be responsible to check all the numbers and units as may
be indicated on the specifications or drawings and shall supply the actual
required units called for.
The Contractor shall visit the site of the work and examine the premises so as
to fully understand all of the existing conditions relative to the work. No
increase in cost of extension in performance time will be considered for
failure to know its condition.
202. Clearing:
204. Debris:
2
a. Remove as it accumulates, debris resulting from demolition operation
may not be burned on the site.
b. Wood and other debris resulting from demolition operation may not
be burned on the site.
205. Cleaning:
301. Sidewalk pavement 2,500 psi 4” thick, with 10 mm 0 bar at 0.60 o.c.b.w.
plain non-skid finish for sidewalk. See Road Plan for further details.
402. Excavation and Grading – Visit site and accept as is, include clearing and
grabbing, all excavation and grading as shown on the drawings.
403. Uniform depth of excavation from natural grade line is 2.00 mts (verify).
Refer to Structural Plan.
404. Soil Poisoning – Apply soil treatment to all area enclosed by the bldg.
Perimeter against ground pests like subterranean termites and others. Use
Chlordane as per manufacturer’s specification.
501. 1-part escombro, 2-part lastillas or barrow earth for all filling job done in 6”
layers, compacted.
502. Ground floor slab on fill – 0.15 M. thick reinforced with No. 10 mm 0 bars
specified at 0.30 meter on center bothways, 2,500 psi. Refer to Foundation
Plan.
601. Test – Steel bars, cement, gravel and concrete samples, shall be tested or as
required by the ENGINEER’S OFFICE OF THE CITY OF CAVITE,
samples and fees to be born by the Contractor.
3
a. All concrete mixture shall be ready mixed concrete delivered to site
by Transit mixer. Refer to structural specifications on plan.
b. All columns, footings, tie beams, pile caps, reinforced concrete walls,
stair – f’c = 20.68 Mpa (3,000 psi) at 28 days.
c. All suspended slabs, beams & girders = f’c = 27.58 Mpa (4,000 psi)
at 28 days = f’c = 20.68 Mpa (3,000 psi) at stressing.
d. All wall footings 3,000 psi. ground floor slab on fills, 2,500 psi at 28
days.
701. Use Davco K-10 waterproofing product for T & B, canopy and balcony.
801. Concrete Hollow Blocks – 5” thk for column side along exterior, 5” thick for
wall with pipe vent and exposed surface. 4” thick for all interior partitions
unless otherwise noted. Use Security Blocks or other steam cured CHB
approved by Architect. 700 psi required. 5” HOLLOW BLOCK 700PSI FOR
FLUSH AT ALL COLUMN FOR ALL FLOORS.
4
803. Walls along hallways, toilets and where pipe line is located, use 6” concrete
hollow blocks walls.
804. Exterior wall finishes as per schedule on plans. Paint finish for interior walls.
Cement plaster shall be in two (2) coats.
901. Tanguile, kiln dried free from defects – For all wood plate in contact with
concrete.
902. Tanguile solid - kiln dried – for main door jamb, door casing and window
casing, toilet doors and bedroom doors.- by Contractor.
903. Tanguile Solid Door and Jamb – for all bedroom doors and toilet door for
main house except for maids room door and toilet: - see plan by contactor.
904. Tanguile, kiln dried free from defects – All door jambs for bedroom toilet,
window jambs ( some area ) etc. by ASIAN TIMBER – Contractor supply.
Note: all doors must be 2.40m height (at some areas) & 2.10m height at
rest. (Verify on door schedule)
Note : Tanguile casing and filler for some window & door opening
including
1001. Analok Brown Aluminum Framing – For windows and sliding doors.
1002. Poly-Vinyl Chloride Doors – For all toilet doors by UPSON. For maids and
driver rm.
a. All window class (vary on sized and type) – Analok Brown Aluminum
Schedule of Windows)
1004. with narra casing and filler for all window and door opening
DIV. 1100: GLASS AND GLAZING / aluminum windows and aluminum doors
5
OWNER SUPPLY
1203. 60x60 White Glazed and Polished tiles for living area, dining area and clean
kitchen
1204. 60x60 Non-Skid tiles for storage, dirty kitchen and maid’s rm.
1207. Refer to floor plan and floor pattern for further details.
1208. Wooden Style Tiles (Specified for Stairs) – For all stairs – by Contractor.
Note: all owner supply ( OSCI ) tile the Contractor must supply all consumable
(cement, sand, grout and tile trim ) –only applies if possible.
1301. Interior partitions – Enclosing toilet and hallway use 4” concrete hollow
blocks.
1303. exterior wall – with wooden style pattern accent made of Acrytex Paint
Fin.
1305. 8” x 8” glazed tiles – For toilets. Verify section & plan detail. – OWNER
SUPPLY
1306. Flexibond w/ fiber mesh and final coat acrytex paint– For building firewall at
right side, rear side and left side portions & provide flushing on perimeter
abutment.
6
1502. Use ½” thk. Gypsum Board – Ceiling with Metal Furring with Hanger Rod.
Refer to ceiling plan.
1601. Hardwares for counter, shelves, cabinet, drawer, closet, etc. – All necessary
hardware for all type of woodwork such as bolts, automatic catches, cylinder
locks, drawer pull, cabinet and closet door pulls, knobs, push or cover plates,
strikes, holders, indicators, push or pull bar, drawer locks, metal drawer
guide, etc. shall be of chromium finished nickel plated of approved samples,
shall be provided for operative function. All shall be of Japan made or its
equivalent.
1602. Butt hinge – 4 pcs. 3 ½” x 3 ½” loose pin butt hinges per set of wooden door,
Stanley dull bronze finish 5 pcs. for main door.
1603. Locksets:
a. Main door – Use Pitcher Type Door Knob with Deadbolt locking system.
b. Bedrooms, balcony, patio & laundry doors – Use Schlage A53PD. Toilet
doors – Use Schlage A40S.
c. For steel gate doors – Yale # 1610 night latch. For service door, with
barrel bolt padlock locking device using ¾” 0 bolt.
d. Sliding glass door – Use Yale hoodbolt lock #2856 with thumbturn
cylinder #2870.
1701. General – All fixtures shall be installed completely with accessories, shut off
valves, angle valves, pressure relieve valves, etc. – use Pozzi Brand
1801. NOTE: All underground pipes to be coated with hot asphalt and wrap with
jute sack as protective cover against rust.
1802. Cold and Hot water line – For hot and cold water line – use NELTEX PIPE (
desotherm ) pipe only.
1803. G.I. valves and fittings – U.S. made 125 lbs. working pressure KITZ,
CRANE, or RED & WHITE brand.
7
1806. Vent, Sewer line & fittings – 2”-4” 0 PVC pipes and fittings Geberit - submit
two estimate
1810. Catch Basin Cover – PVC by dexterton 12” x 12” for heavy traffic.
1811. Trench Drain Cover – PVC by dexterton verify size- for heavy traffic
1812. Roof Drain – METMA brand 250-D for roof deck, 305 for parapet drain 45
degree outlet. Submit sample for approval.
1813. Stand Pipe – METMA brand Model 3532, verify location and required
number by local Fire Department.
NOTE : pls. include REDI drainage pvc check valve on all outlet to main
sewer and strorm drain
1901. General – Furnish and provide all items, articles, materials, operations or
methods listed, implied, mentioned or scheduled on the drawings and/or
therein, including all labor, materials, equipments necessary and required for
their completion.
1903. Permits & Licenses – The Contractor shall pay and secure all permits and
licenses including inspection fees. He shall hire and Electrical Engineer for
the preparation and computation of the electrical plans and pay for all
necessary expenses. The Owner shall pay for the deposit of the meter/meters
required by the Contractor and the Owner.
The Contractor shall prepare and submit to the Architect two (2) copies of the
electrical riser diagram and distribution plans, properly designed and signed
by the licensed Electrical Engineer before the start of the work. The Architect
shall make necessary corrections and final approval of the work.
1904. Materials:
8
All materials and workmanship shall follow all provisions as provided by the
latest edition of the National Electrical Code.
c. Outlet Boxes – Hot dipped galvanized steel sheets, clean, rust free, and
provided with standard locknuts, ga. 16 or Atlanta PVC boxes
d. Junction boxes – Hot dipped galvanized steel sheets, clean, rust free, ga.
16 or Atlanta PVC boxes.
1905. Wiring methods – All wiring shall be in concealed PVC conduits, husky
powerguard including those in double walls and inside ceilings, all
underground conduits shall be properly waterproofed.
1906. Size of Wires: No wire shall be smaller than A W G gauge No.1.6 MM 0 for
all lighting circuits with a run of less than 100 Ft. For circuits with a run of
more than 100 Ft., minimum size shall be A W G ga. No. 2.0 mm 0 only.
Use A W G gauge No. 8.0 mm 0 wires or larger as per design for electric
range circuits.
Note: all wires must be THHN and stranded type by Philflex Pipes
(1/2”).
1907. Limit of Outlets – No more than twelve (12) outlets shall be allowed per
circuit of 30 amperes.
1908. Stand by or Extra Circuits – For future expansion at two (2) extra circuits per
apartment or a proportion of one (1) extra circuit to six (6) working circuits.
1909. Telephone System – Strict compliance with provision and requirements of
the local telephone company. Complete telephone connections and outlets in
PVC underground conduits from entrance outlet shall be with plug in Modula
Jack.
1910. Door Bell System – Provide one (1) waterproofed type push button on
strategic location each apartment unit with TW wire connected to bells or
buzzers inside apartment.
9
1911. Electrical Fixtures – Electrical fixtures, lights, water pumps, heaters, lamps,
bulbs, fluorescents, chandeliers shall be furnished by Owner. Mounting and
installation of fixtures shall be done by the Contractor.
1912. Intercom System – Airphone by Owner, wiring and cable by Contractor.
1913. Cable TV line – by Contractor
1914. Electrical Work – By Phases Electrical Contractor.
a. All masonry wall cement finished surface – Three (3) coats. Acrytex
Arcycast finish for 4 side exterior wall and semigloss finish for
interior wall.
b. Plywood surfaces, ceiling or wall – Three (3) coats semi-gloss enamel or
acrytex. Refer to ceiling and floor plans.
c. Doors, door jambs, woodwork, cabinet, counter, closets (interior and
exterior) – Putty and seal spray with automotive lacquer, polished.
Alternate – Varnish finish.
d. All Steel and metal work ( steel window and gate ) – Two (2) coats
epoxy paint and two (2) coats quick drying enamel. (Contractor shall
paint all steel works including owner supply material).
2005. Extra Coats – shall be applied to achieve desired finish, follow Architect’s
instructions.
2006. Flexybond w/ mesh – By BOYSEN. For fire wall and all 4 side exterior wall.
2007. for all exterior – flexibond then complete application of acrytex with close
putty application using acrytex cast.
3001. Use Pre-painted Long Span Rib-Type Roofing @ 0.50 thickness – use
SteelTech Brand
3002. For insulation – single foil single bobble.- felport
3003. Use #24 stainless for valley gutter.
3004. tile roof will be owner supply.
NOTE: Include all necessary accessories needed in completing the said roofing w/o any leeks.
( gutter flushing, inside gutter and etc. )
10
7001. Kitchen cabinet – for clean kitchen use of ¾ Marine Plywood - Contractor will
coordinate and supervise. (specially with regards to outlet and switches not
additional charge ).
7002. walk in closet – ¾ Marine Plywood - Contractor will coordinate and supervise.
(specially with regards to outlet and switches not additional charge ).
7003. Dirty kitchen - by owner but Contractor will coordinate and supervise.
(specially with regards to outlet and switches not additional charge ).
11
g. CHB/Rebars/Concrete testing
h. Spacer for footing-broken concrete cylinder (3 x 3 in.)
i. Beam/slab-concrete cubes spacers (2 & 1 in.)
j. Provide sleeve for beams if necessary
a. Equal & more than 3 in. dia. – B.I. or G.I. pipe
b. Less than 3 inches diameter – use PVC pipe
k. 1 bagger mixer – standby equipment in case of emergency of less than 3
cum concrete volume lacking
l. 2 sets of vibrator (AC / DC)
m. 1 set of power water sprayer
n. 3 sets of reserve concrete cylinder for testing
o. Provide one box of sand for concrete sample material handling to lab
testing
12
13