RELEASE NOTE

RTU500 Series
Release 12.4

RTU500 12.4
Release Note
Introduction
This RTU Release 12.4 includes several new features and corrections for functional issues in
RTU500 series related to Central user account management, Cyber security, Protocol
improvements, testing of encrypted communication channels.

Technical requirements and supported products


This Release is supported by the RTU500 series with the product lines RTU560, RTU540 and
RTU520.

Ordering and delivery information


The new Release 12.4 is available for download in the ABB Library and Partner portal.

More information will be provided by the responsible sales manager link or your local ABB sales
representative and during the offered webinars.

Documentation
Following documentation is available for download:
 Updated Cyber security deployment guide
 Updated MODBUS protocol description
 Updated Function descriptions
 RTU500 Release 12.4 release notes

For Firmware and software download please go to:


ABB library link,
RTU Partner portal  link
RTU External pages  link

RTU500 12.4


RTU500 12.4 release (2018-10)
New functions:

Central user account management (CAM): the support of active directory server based on LDAP
(IEC 62351-8) is supported by RTU500. For ABB offering SDM600 1.2 FP1 is available as LDAP server for CAM.
Support of standard roles according to IEC 62351-8
Support of customer defined roles
Local role to right mapping based on RTU password file
Configurable Fall back solution: no fall back, redundant CAM server, RTU password file
Support of external Active directory server (LDAP, 3rd Party systems)
IEC 60870-5-104 protocol (bi-directional communication, peer to peer) is now supported together with TLS
1.2 based on IEC 62351-3. Certificates based on X.509 are used. (secure IEC 60870-5-104)

MODBUS improvements:
Increase baud rate of serial MODBUS up to 115 kBaud
Reduce 25-30 ms delay on serial MODBUS to <= 10 ms
Reduce polling cycle of MODBUS TCP/IP down to 10 ms
Broadcast support for MODBUS SCI (Address 0)
Support transparent data channel function (TDC) to speed up the PLC response time in Microgrid and
BESS applications
Diagnosis interface for encrypted communication:
For diagnosis of encrypted communication channels a diagnosis interface is now available. Interface can be
enabled if requested. It works for the VPN tunnel applications in RTU500 series.

Improved encryption for VPN: The following new hash algorithm are supported:
SHA256, SHA384, SHA512
Improved cyber security by exclusively TLS1.2 support:
RTU500 Webserver do not support any more TLS1.0/1.1 for webserver communication. TLS1.0/1.1 are no
more secure from cyber security point of view.
Automatic logout for integrated HMI: Automatic logout based on inactivity can be enabled and configured
in RTUtil500 for the integrated HMI

SINAUT host and sub device communication: The SINAUT protocol is now supported for the following CMU
types: 540CID01, 540CMD01 and 560CMR02

Speed up of disturbance file up load: RTU500 support the fast transmission of disturbance file to SCADA
system. During tests it was possible to collect up to 40 disturbance files from different IED's within 90
seconds and transmit to SCADA. The SCADA system uses this information together with the network model
to detect fault locations and investigate power quality issues.

Improved Communication: RTU500 accept only TLS1.2 communication, TLS1.0/1.1 is no more supported
since this release. This will improve the acceptance for customers running prequalification
process/homologation together with consultants or IT departments.
Alarm blocking based on local signals: During RTU engineering blocking groups for monitoring direction
can be defined Block/enable of the groups is possible by local signals (key switch, PLC logic). Engineering
complexity is reduced dramatically.
DNP3 Queue monitoring: RTU500 is monitoring the filling state of the DNP3 queue. In case of overstepping
a configurable filling state (e.g. 80%) a system event is generated.

Configurable TCP/IP port for IEC104 secure (IEC62351-3): RTU500 supports now a configurable port
number for IEC870-5-104 secure based on IEC 62351-3 (TLS) in case SCADA system do not follow the
requirements of the standard.

Indactic 33 protocol in Rel. 12 is now supported by the new CMU platform (540CID01, 540CMD01 and
560CMR02). Existing RTU installations can now be migrated to Rel. 12.


ABB AG
Power Grids
P.O. Box 10 03 51
68128 Mannheim, Germany
Phone: +49 621 381-3000
Fax: +49 621 381-7622
Email: rtu-sales-support@de.abb.com
www.abb.com/remote-terminal-units

© Copyright 2018 ABB. All rights reserved.