DSEGenset

DSE4510/20 ENVIRONMENTAL TESTING STANDARDS

AUTO START AND AUTO MAINS FAILURE ELECTRO-MAGNETIC COMPATIBILITY

CONTROL MODULES BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
FEATURES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
The DSE4510 Auto Start Control Electronic J1939 (CAN) and non- ELECTRICAL SAFETY
Module and the DSE4520 Auto electronic (alternator sensing) *AVAILABLE VARIANTS BS EN 60950
Safety of Information Technology Equipment,
Mains (Utility) Failure Control engine support for diesel, gas and 4510-01 Auto Start
including Electrical Business Equipment
Module are suitable for a wide petrol engines all in one variant.
4510-02 Auto Start with current measurement TEMPERATURE
variety of single gen-set With a number of flexible inputs, BS EN 60068-2-1
applications. outputs and protections, the 4510-03 Auto start with current measurement Ab/Ae Cold Test -30 oC
modules can be easily adapted to & real time clock BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
Whilst maintaining functions suit a wide range of applications 4510-04 Auto start with current measurement,
included within higher end including lighting towers with the real time clock & heated display VIBRATION
BS EN 60068-2-6
controllers, such as generator or added option for staged loading Ten sweeps in each of three
4520-01 Auto Mains Failure
load power monitoring, the outputs. major axes
DSE45xx range of especially 4520-02 Auto Mains Failure with current 5 Hz to 8 Hz @ +/-7.5 mm,
measurement 8 Hz to 500 Hz @ 2 gn
compact controllers provide the Through USB Communication both
user with the ultimate size to modules can be easily configured 4520-03 Auto Mains Failure with current HUMIDITY
BS EN 60068-2-30
feature ratio. using the DSE Configuration Suite measurement & real time clock
Db Damp Heat Cyclic 20/55 oC
PC Software or can be fully @ 95% RH 48 Hours
4520-04 Auto Mains Failure with current
Monitoring engine speed, oil configured through the module's measurement, real time clock &
BS EN 60068-2-78
Cab Damp Heat Static 40 oC
pressure, coolant temperature, front panel editor. heated display
@ 93% RH 48 Hours
frequency, voltage, current, power
SHOCK
and fuel level, the modules will give All DSE products are supported by BS EN 60068-2-27
comprehensive engine and the DSE global technical support Three shocks in each of three major axes
alternator protection. This will be team which gives our customers 15 gn in 11 mS
indicated on the largest back-lit and end users access to 24 hour DEGREES OF PROTECTION
LCD icon display in its class via an system help and advice. PROVIDED BY ENCLOSURES
BS EN 60529
array of warning, electrical trip and IP65 - Front of module when installed into the
shutdown alarms. control panel with the optional sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 4 3

USB CONFIGURABLE DC OUTPUT ANALOGUE SENDERS DC POWER


PORT INPUTS (2 for DSE4510) SUPPLY

DEUTZ
DSE4510/20 ISUZU

*SEE AVAILABLE VARIANTS ABOVE


PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) DC OUTPUT GENERATOR / DC OUTPUT GENERATOR CHARGE FUEL AND START ELECTRONIC
SENSING 4520 1 OF 4 LOAD CURRENT 4510 1 OF 2 SENSING ALTERNATOR OUTPUTS ENGINE CAN
(DSE4520) 4520 1 OF 4 (Flexible with CAN)

VOLTS VOLTS
D+ +
+ + W/L

1ph 1 1ph 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N

ISSUE 1
®

DSEGenset

DSE4510/20 SPECIFICATION

DC SUPPLY
AUTO START AND AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CONTROL MODULES CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
FEATURES supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
DSE4520 without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


85 mA at 12 V, 96 mA at 24 V

DSE4510 MAXIMUM STANDBY CURRENT


51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT


35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT


<10 uA at 12 V, <10 uA at 24 V

MAINS (UTILITY) DSE4520 ONLY


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

KEY BENEFITS • IP65 rating (with optional • Fuel and start outputs OUTPUT B (START)
• Ultimate size to feature ratio gasket) offers increased (configurable when using CAN) 10 A short term, 5 A continuous,
at supply voltage
• Automatically transfers between resistance to water ingress • 4 configurable DC outputs (2 for
mains (utility) and generator DSE4510) AUXILIARY OUTPUTS C & D
(DSE4520 only) KEY FEATURES • 3 configurable analogue/digital 2 A DC at supply voltage
• Hours counter provides accurate • Largest back-lit icon display in inputs AUXILIARY OUTPUTS E & F DSE4520
information for monitoring and its class • 4 configurable digital inputs 2 A DC at supply voltage
maintenance periods • Current sensing, real time clock • Configurable staged loading
GENERATOR
• User-friendly set-up and button & heated display options outputs VOLTAGE RANGE
layout for ease of use available • CAN and alternator speed 15 V to 415 V AC (Ph to N)
• Multiple parameters are • Fully configurable via the fascia sensing in one variant 26 V to 719 V AC (Ph to Ph)
monitored simultaneously which or PC using USB • 3 engine maintainance alarms FREQUENCY RANGE
are clearly displayed on the communication • Engine speed protection 3.5 Hz to 75 Hz
largest back-lit icon display in • Extremely efficient power save • Engine hours counter
DIMENSIONS
its class mode • Engine pre-heat OVERALL
• The module can be configured • 3 phase generator sensing • Engine run-time scheduler 140 mm x 113 mm x 43 mm
to suit a wide range of • 3 phase mains (utility) sensing • Engine idle control for starting & 5.5’’ x 4.4” x 1.7”
applications (DSE4520 only) stopping PANEL CUT-OUT
• Compatible with a wide range • Compatible with 600 V ph - ph • Battery voltage monitoring 118 mm x 92 mm
of CAN engines, including tier 4 nominal systems • Start on low battery voltage 4.6’’ x 3.6”
engine support • Generator/load power • Configurable remote start input MAXIMUM PANEL THICKNESS
• Uses DSE Configuration Suite monitoring (kW, kV A, kV Ar, pf) • 1 alternative configuration 8 mm
PC Software for simplified • Generator overload protection • Comprehensive warning, 0.3”
configuration (kW) electrical trip or shutdown STORAGE TEMPERATURE RANGE
• Licence-free PC software • Generator/load current protection upon fault condition -40°C to +85°C
monitoring and protection • LCD alarm indication
OPERATING TEMPERATURE RANGE
• Event log (15) -30°C to +70°C
-40°C to +70°C (for heated display variant)
RELATED MATERIALS
TITLE PART NO’S OPTIONAL PARTS
DSE4510/20 Installation Instructions 053-157
DSE4510/20 Operator Manual 057-171 PART PART NUMBER
DSE4510/20 Configuration Suite PC Manual 057-172 IP65 Gasket 020-282

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708