Question
What parameters need to be set for the dynamic brake resistor to function on a PowerFlex 70/700 Drive?

Environment
20A PowerFlex 70 drive
20B PowerFlex 700 drive

Answer
Parameters that need to be set for the dynamic brake resistor to function on a PowerFlex 70/700 Drive are
listed below:

For bus regulation:

Parameter 161 [Bus Reg Mode A] - Must be set to either option 2 [Dynamic Brak], 3 [Both-DB 1st], or
4 [Both-Frq 1st].
Parameter 162 [Bus Reg Mode B] - Only used if a digital input such as Parameter 363 [Digital In3
Sel] is set to 14 [Bus Reg Mode B]. If this is true then it must be set to either option 2 [Dynamic Brak],
3 [Both-DB 1st], or 4 [Both-Frq 1st]
Parameter 163 [DB Resistor type] - Selects whether the internal or an external DB resistor used.
Parameter 164 [Bus Reg Kp] - Proportional gain for the bus regulator. Used to adjust regulator
response (not usually adjusted).
Parameter 165 [Bus Reg Kd] - Derivative gain for the bus regulator. Used to control regulator overshoot
(not usually adjusted).
Parameter 155 [Stop Mode A] - Typically this is set to 1 [Ramp].
Parameter 156 [Stop Mode B] - Only used if a digital input such as Parameter 364 [Digital In4 Sel] is
set to 13 [Stop Mode B].
Parameter 145 [DB While Stopped] - Enables/disables dynamic brake operation. 0 [Disabled]
operates only when the drive is running. 1 [Enabled] operates whenever the drive is energized.
Parameter 153 [Regen Power Limit] - When flux vector control (FVC) is used this sets the maximum
power limit transfer from the motor to the DC bus. An acceptable value is -800%.

For more information please refer to:

PowerFlex 70 Adjustable Frequency AC Drives Users Manual


(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20a-um001_-en-p.pdf) -
Publication 20A-UM001.
PowerFlex 700 AC Drives – Frames 0...10 User Manual
(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20b-um002_-en-p.pdf) -

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/508407 1/2
20/02/2019 508407 - PowerFlex 70/700 drive: Parameters to Configure Dynamic Braking Resistor

Publication 20B-UM002.
PowerFlex 70/700 Adjustable Frequency AC Drives Reference Manual
(http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/pflex-rm001_-en-e.pdf) -
Publication PFLEX-RM001.

Note: Parameter 161 [Bus Reg Mode A] will need to be set to a 0 of any type of external Regen Supply,
Regen Brake, Active Front End or an external Brake/Chopper module is used.

Attachments
Answer - Paramaters needing to be set for Dynamic brake on a PowrFlex 700 or 70 drive.mht
(/ci/fattach/get/963113/0/filename/Answer+-
+Paramaters+needing+to+be+set+for+Dynamic+brake+on+a+PowrFlex+700+or+70+drive.mht)
(54.61 KB)

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or
subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not
intended to constitute application, design, software or other professional engineering advice or services.
Before making any decision or taking any action, which might affect your equipment, you should consult a
qualified professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY


OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY
TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY
IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF
ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE,
EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN


RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE
IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-
INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus,
this disclaimer may not apply to you.

This page is best viewed in Internet Explorer 11, Edge, Firefox 41, Chrome 46, Safari 9 or newer.

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/508407 2/2

You might also like