Low Voltage Alternator - 4 Pole: Installation and Maintenance
Low Voltage Alternator - 4 Pole: Installation and Maintenance
TAL 044
Low Voltage Alternator - 4 pole
This manual concerns the alternator which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
2
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
CONTENTS
1 - RECEIPT............................................................................................................................4
1.1 - Standards and safety measures...................................................................................4
1.2 - Inspection.....................................................................................................................4
1.3 - Identification................................................................................................................. 4
1.4 - Storage........................................................................................................................4
1.5 - Applications.................................................................................................................. 4
1.6 - Usage restrictions........................................................................................................ 4
2 - TECHNICAL CHARACTERISTICS....................................................................................5
2.1 - Electrical characteristics...............................................................................................5
2.2 - Mechanical characteristics...........................................................................................5
3 - INSTALLATION................................................................................................................ 11
3.1 - Assembly.................................................................................................................... 11
3.2 - Checks prior to first use..............................................................................................12
3.3 - Terminal connection diagrams....................................................................................12
3.4 - Commissioning.......................................................................................................... 15
3.5 - Setting up...................................................................................................................15
4 - SERVICING - MAINTENANCE.........................................................................................16
4.1 - Safety measures........................................................................................................ 16
4.2 - Routine maintenance.................................................................................................16
4.3 - Bearings.....................................................................................................................17
4.4 - Mechanical defects....................................................................................................17
4.5 - Electrical faults........................................................................................................... 18
4.6 - Dismantling, reassembly............................................................................................20
4.7 - Installation & maintenance of the PMG......................................................................21
4.8 - Table of characteristics...............................................................................................22
5 - SPARE PARTS................................................................................................................. 24
5.1 - First maintenance parts..............................................................................................24
5.2 - Technical support service...........................................................................................24
5.3 - Accessories................................................................................................................ 24
5.4 - Exploded view, parts list and tightening torque...........................................................25
3
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
1 - RECEIPT 1.4 - Storage
1.1 - Standards and safety Prior to commissioning, machines should
measures be stored:
- away from humidity (< 90%); after a long
Our alternators comply with most period of storage, check the machine
international standards. insulation. To prevent the bearings from
See the EC Declaration of Incorporation on becoming marked, do not store in an
the last page. environment with significant vibration.
1.2 - Inspection 1.5 - Application
On receipt of your alternator, check that it This alternator is mainly designed to
has not suffered any damage in transit. If produce electricity in the context of
there are obvious signs of knocks, contact applications involving the use of
the transporter (you may be able to claim generators.
on their insurance) and after a visual
check, turn the machine by hand to detect 1.6 - Usage restrictions
any malfunction. Use of the machine is restricted to operating
conditions (environment, speed, voltage,
1.3 - Identification power, etc) compatible with the characteri-
The alternator is identified by means of a stics indicated on the nameplate.
nameplate fixed on the machine (see
drawing).
Make sure that the nameplate on the
machine conforms to your order.
So that you can identify your alternator
quickly and accurately, we suggest you fill in
its specifications on the nameplate below.
LSA
TAL IP RATINGS
N°: Date : Voltage V
r.p.m. Hz Weight : kg Phase
LSA 000-1-006 e
27°C. A
C US
166631 Made in ............................
IEC 60034 - 1 & 5. / ISO 8528 - 3. / NEMA MG1 - 32 & 33. Moteurs Leroy-Somer - Boulevard Marcellin Leroy,
CS 10015 - 16915 Angoulême Cedex 9 - France
4
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
2 - TECHNICAL CHARACTERISTICS 2.2 - Mechanical characteristics
2.1 - Electrical characteristics - Steel frame
This machine is an alternator without - End shields in aluminum
sliprings and revolving field brushes, wound - Greasable ball bearings
as “2/3 pitch”; 4, 6 or 12-wire, with class H - Mounting arrangement: single bearing with
insulation and a field excitation system standard feet and SAE flanges/coupling
available in either SHUNT, AREP+ or PMG discs
version. The alternator complies with EN - Drip-proof machine, self-cooled
61000-6-3, EN 61000-6-2, EN 55011.
• Electrical options
- Space heaters
- R791 interference suppression
MAIN FIELD
T1 T3
EXCITER U1 U5
Armature
Varistor
T2 T4
Exciter field
U2 U6
- + Rotating rectifiers
yellow
black
red
blue
2 kOhms
HR / CW
UF 0E UF S V
5
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• SHUNT three-phase 6-wire
MAIN FIELD
T1 T2 T3
EXCITER U1 V1 W1
T4 T5 T6
Exciter field
U2 V2 W2
+ - Rotating rectifiers
black
red
connection
yellow
green * Delta
Star
blue connection
*
* For delta connection (1PH – 3PH):
use terminals N and U, connect N and N1
F2 F1 N U N1 V
FUSE
SL UF 0E UF S V
6
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• SHUNT three-phase 12-wire
EXCITER
T3-W1
T9-W5
T7-U5
T1-U1
T2-V1
T8-V5
Armature
Varistor
Exciter field
- + Rotating rectifiers
T11-V6
T12-W6
T6-W2
T5-V2
T4-U2
T10-U6
black
red
3 PH 1 PH
D A F FF G
blue
T10 T3 T2 T10 T2
yellow
T1 T1 T1 T1 T3
white
N.C. T2 N.C. N.C. N.C.
green
T2 N.C. N.C. N.C. N.C.
*
F2 F1 N U N1 V * For F, FF and G connections:
connect N and N1
FUSE
SL UF 0E UF S V
7
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• AREP+ three-phase 6-wire
STATOR: 6-wire (T1 to T6 identification)
Winding H3
T3-W1
T1-U1
T2-V1
MAIN FIELD
EXCITER
Varistor
Armature
Exciter field
T6-W2
T5-V2
T4-U2
Rotating rectifiers
- +
Optional: //CT
green
yellow
white
black
1 kOhm 1W mini
blue
red
red
red
ST
6- 5+ 11 12 3 2 8 7 9 10
*
or
// CT
TI04: In / 1A
(D) "Star" only
T4
TI04 P2 P1
Neutral
8
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• AREP+ three-phase 12-wire
STATOR: 12-wire (T1 to T12 identification)
Winding H3
T3-W1
T9-W5
T7-U5
T1-U1
T2-V1
T8-V5
MAIN FIELD
EXCITER
Varistor
Armature
Exciter field
T11-V6
T6-W2
T12-W6
T5-V2
T4-U2
T10-U6
Rotating rectifiers
- +
black
white
blue red
Optional: //CT
6- 5+ 11 12 8 7
1 kOhm 1W mini
ST
3 PH 1 PH
A-D-F FF G
red 3 T3 T10 T3
*
or
red
* 2 T2 T1 T2
3 PH 1 PH
D A-F FF G
yellow 10 T11 T3 T1 T3
green 9
T2 T2 T10 T2
* Detection according to voltage:
V/W for high voltage (380-480V)
L1/L2 for low voltage (190-240V)
Consult manual ref.5599 OPTIONAL
External remote voltage trimmer
(remove ST)
// CT
TI04: In / 1A
(D) "Star" only
T10
TI04 P2 P1
Neutral
9
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• PMG three-phase 6 or 12-wire
STATOR: 12-wire (T1 to T12 identification)
T3-W1
T9-W5
T7-U5
T1-U1
T2-V1
T8-V5
MAIN FIELD
PMG
EXCITER
Varistor
Armature
Exciter field
T11-V6
T6-W2
T12-W6
T5-V2
T4-U2
T10-U6
Rotating rectifiers
- +
red
red
red
white
T3-W1
T1-U1
T2-V1
blue
6- 5+ 14 15 16 8 7 STATOR: 6-wire
1 kOhm 1W mini
ST
T6-W2
T5-V2
T4-U2
Option: // CT
3 PH 1 PH
A**– D – F FF** G**
red 3 T3 T10 T3
*
or
red
* 2 T2 T1 T2
** A, FF and G connections:
possible with 12-wire only
// CT
TI04: In / 1A
(D) "Star" only
T10 or
T4
TI04 P2 P1
Neutral
10
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
3 - INSTALLATION The TAL 044 is equipped with two air
Personnel undertaking the various deflectors that prevent access to the upper
operations indicated in this section must and lower holes of the flange. Coupling for
wear personal protective equipment this machine should be done with screws in
appropriate for mechanical and electrical the eight accessible holes, disregarding the
hazards. ones that cannot be accessed because of
the deflectors.
3.1 - Assembly
11
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
3.2 - Checks prior to first use 3.3 - Terminal connection diagrams
• Electrical checks To modify the connection, change the
position of the stator cables on the terminals.
The winding code is specified on the
nameplate.
• Mechanical checks
Before starting the machine for the first time,
check that:
- all fixing bolts are tight,
- the length of bolt and the tightening torque
are correct,
- the cooling air is drawn in freely,
- the protective grille and housing are cor-
rectly in place,
- the standard direction of rotation is clock-
wise as seen from the drive end (phase
rotation in order 1 - 2 - 3).
For anti-clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the
site operating voltage (see section 3.3).
12
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• SHUNT three-phase 6-wire
Connection codes Voltage / Detection Factory connection
Winding 50 Hz 60 Hz DE
D 3PH L1(U)
T1 6S 380 - 415 380 - 480 T6
Star T5
N
8S - 380 - 416 T4
T4 W(3)-L3
T3
T6 T5
V(2)-L2
R120 : T2
U(1)-L1
T3 T2 N => T5, U => T1, V => T2 T1
L3(W) L2(V)
NDE
Winding 50 Hz 60 Hz
F 1PH DE
or
Delta L1(U)
3PH
6S 220 - 240 220 - 240
3ph (1ph)
T6 T1 8S - 220 - 240 T5
W(3)-L3
T3
T4
V(2)-L2 (L)
T3 T4 T2
R120 : U(1)-L1(L)
L3(W) L2(V) N => T2, U => T1, V => n.c. T1
T6
L T5 T2 L N => N1
NDE
L3(W) L2(V)
NDE
Winding 50 Hz 60 Hz
F 1PH DE
or
Delta L1(U)
3PH
6S 220 - 240 220 - 240
3ph (1ph)
T6 T1 8S - 220 - 240 T5
W(3)-L3(L)
T3
T4
V(2)-L2 (L)
T3 T4 T2
R180 : U(1)-L1
L3(W) L2(V) L1 => T2, L2 => T3 T1
T5 T2 T6
L L
NDE
13
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• SHUNT, AREP+ or PMG three-phase 12-wire
Connection codes Voltage / Detection Factory connection
Winding 50 Hz 60 Hz
A 3PH L1(U) DE
T12
Parallel Star
T1 T7
6 190 - 208 190 - 240 T11 *
T6
8 - 190 - 208 T5 T10
T4
T4
T10
T12
N T5 R120 :
U => T1, N1 => T2, N => T3, V => n.c.
T9 T2
T11
T6 R180 :
L1 => T2, L2 => T3
L3(W) T3 T8 L2(V) NDE
L1(U) Winding 50 Hz 60 Hz
D 3PH T1
T12
DE
Series Star T4
6 380 - 415 380 - 480 T11 *
T7
8 - 380 - 416 T10
T10
T12 R120 :
T9 U => T1, V => T2, N => T10, N1 => n.c.
T11 T5
T3 T6 T8 T2 R180 :
V => T2, W => T3
L3(W) L2(V) NDE
Winding 50 Hz 60 Hz
F L1(U) 1PH DE
or
Series Delta
T12 T1
3PH
6 220 - 240 220 - 240
T11 *
T9 T4 8 - 220 - 240 T3
T6 T7 (L)
T10
R120 : (L)
T3 T10
U => T1, N1 => T2, N => T3, V => n.c.
L3(W) L2(V)
T11 T8 T5 T2
L L R180 : NDE
M
Voltage LM = 1/2 voltage LL
L1 => T2, L2 => T3 * If counter clockwise, L2 and L3 inverted
Winding 50 Hz 60 Hz DE
FF 1PH T11
T2 T6 T8 T12 6 220 - 240 220 - 240
T3
T4
T3
8 - 220 - 240 T10
T5 T11 T9
R120 : T2
T1 T4 T7 T10 T12 T6
L L
U => T10, N => T1, N => N1, V => n.c.
M
R180 :
Voltage LM = 1/2 voltage LL L1 => T1, L2 => T10 T5 NDE
Winding 50 Hz 60 Hz DE
G 1PH T5 T11
T4
T6 T1 6 220 - 240 220 - 240
T10
T12 T7
8 - 220 - 240
T3 T4
T5 T2 R120 :
T9 T10
T11 T8 N => T2, U => T3, N1 => n.c., V => n.c.
L M L
R180 :
Voltage LM = 1/2 voltage LL L1 => T2, L2 => T3 NDE
14
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• Connection checks 3.4 - Commissioning
15
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
4 - SERVICING - MAINTENANCE WARNING
4.1 - Safety measures Do not use: trichlorethylene, perchlo-
Servicing or troubleshooting must be
rethylene, trichloroethane or any alkaline
carried out strictly in accordance with
products.
instructions so as to avoid the risk of
accidents and to maintain the machine in
its original state.
These operations must be performed at a
cleaning station, equipped with a vacuum
system that collects and flushes out the
All such operations performed on the products used.
alternator should be undertaken by
The insulating components and the
personnel trained in the commissioning,
impregnation system are not at risk of
servicing and maintenance of electrical
damage from solvents. Avoid letting the
and mechanical components, who must
wear personal protective equipment cleaning product run into the slots.
appropriate for mechanical and electrical Apply the product with a brush, sponging
hazards. frequently to avoid accumulation in the
housing. Dry the winding with a dry cloth. Let
Before any intervention on the machine,
ensure that it cannot be started by a manual any traces evaporate before reassembling
or automatic system and that you have the machine.
understood the operating principles of the • Mechanical servicing
system.
WARNING
Cleaning the machine using water or a
highpressure washer is strictly prohi-
Warning : During and after running, the
bited. Any problems arising from such
alternator will reach temperatures hot
treatment are not covered by our
enough to cause injury, such as burns.
warranty.
Degreasing: Use a brush and detergent
4.2 - Routine maintenance (suitable for paintwork).
Dusting: Use an air gun.
• Checks after start-up
If the machine is fitted with air inlet and outlet
After approximately 20 hours of operation,
filters, the maintenance personnel should
check that all fixing bolts on the machine are
clean them routinely at regular intervals. In
still tight, plus the general state of the
machine and the various electrical the case of dry dust, the filter can be cleaned
connections in the installation. using compressed air and/or replaced if it is
clogged.
• Electrical servicing After cleaning the alternator, it is essential to
Commercially-available volatile degreasing check the winding insulation (see sections
agents can be used. 3.2 and 4.5).
16
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
4.3 - Bearings
The bearings are permanently greased Approximate life of the grease (depending on use) = 20,000
hours or 3 years.
- System short-circuit
- Misparalleling
Alternator damaged by a Possible consequences
Abnormal - Broken or damaged coupling
significant impact, followed by
noise - Broken or bent shaft end
humming and vibration
- Shifting and short-circuit of main field
- Fan fractured or coming loose on shaft
- Irreparable damage to rotating diodes/AVR, surge suppressor
17
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
4.5 - Electrical faults
Fault Action Effect Check/Cause
The alternator builds up and
its voltage is still correct - Lack of residual magnetism
when the battery is removed
Connect a new
battery of 4 to 12 The alternator builds up but - Check the connection of the voltage reference
No volt- its voltage does not reach to the AVR
volts to termi-
age at no the rated value when the - Faulty diode
nals F1 and F2,
load on battery is removed - Armature short-circuit
respecting the
start-up polarity, for 2 to 3
The alternator builds up but -- Faulty
seconds AVR
Field windings open circuit (check winding)
its voltage disappears when - Main field winding open circuit (check the
the battery is removed resistance)
Check the AVR connections (possible AVR failure)
- Field windings short-circuited
Correct speed - Rotating diodes burnt out
Voltage Check the drive - Main field winding short-circuited (check the
too low speed resistance)
Increase the drive speed (do not touch the AVR
Speed too low voltage pot. before running at the correct speed)
Voltage Adjust AVR volt- Adjustment ineffective Faulty AVR
too high age potentiometer
- Check the speed : possibility of cyclic irregularity
Voltage Adjust AVR stabil- - Loose connections
oscilla- ity potentiometer - Faulty AVR
tions - Speed too low when on load
Voltage between F1 and F2
Voltage (DC)
correct Run at no load - Check the speed
SHUNT < 20V
at no load and check the AREP+/PMG < 10V
and too voltage between
low when F1 et F2 on the - Faulty rotating diodes
Voltage between F1 and F2
on load AVR - Short-circuit in the main field (check the
SHUNT > 30V
(*) resistance)
AREP+/PMG > 15V - Faulty exciter armature (check the resistance)
(*) Warning : During single-phase operation, check that the sensing wires from the AVR are connected to the
correct output terminals.
Check the AVR.
Voltage the surge - Exciter winding open circuit
disap- suppressor, the The voltage does not return - Faulty exciter armature
pears rotating diodes, to the rated value - Faulty AVR
during and replace any - Main field open circuit or short-circuited
operation defective
components
(**) Warning : The AVR internal protection may cut in (overload, lost connection, short circuit).
18
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• Checking the winding Assembly A: Connect a 12 V battery in
You can check the winding insulation by series with a rheostat of approximately
performing a high voltage test. In this case, 50 ohms - 300 W and a diode on both exciter
you must disconnect all AVR wires. field wires (5+) and (6-).
ASSEMBLY A
6 - Field 5+
WARNING
1A diode Rh. 50 -300W
Damage caused to the AVR in such
conditions is not covered by our
warranty. +
-
• Checking the diode bridge
A diode in good working order should allow
12V battery
the current to flow only in the anode-to-
cathode direction.
Assembly B: Connect a “Variac” variable
+
Anode
-
Cathode
power supply and a diode bridge on both
+ - exciter field wires (5+) and (6-).
+ -
Both these systems should have
characteristics which are compatible with
A C
A C the field excitation power of the machine
(see the nameplate).
3) Run the unit at its rated speed.
4) Gradually increase the exciter field
current by adjusting the rheostat or the
variac and measure the output voltages on
L1 - L2 - L3, checking the excitation voltage
and current at no load (see the machine
nameplate or ask for the factory test report).
When the output voltage is at its rated value
and balanced within 1% for the rated
excitation level, the machine is in good
working order. The fault therefore comes
• Checking the windings and rotating from the AVR or its associated wiring (ie.
sensing, auxiliary windings).
diodes using separate excitation
ASSEMBLY B
6 - Field 5+
40
50 60 +
30
70
1A diode
During this procedure, make sure that
20
80
90
0 100
19
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
4.6 - Dismantling, reassembly - Refit the modules.
- Refit the air intake grille [51].
WARNING
• Access to connections and the
During the warranty period, this operation regulation system
should only be carried out in an approved The terminals are accessed directly by
workshop or in our factory, otherwise the removing the terminal box lid [48].
warranty may be invalidated.
Whilst being handled, the machine • Replacing the NDE bearing on single
should remain horizontal (rotor not bearing machines
locked when moved). Check how much Dismantling
the machine weighs before choosing the - Remove the terminal box lid [48].
lifting method. - Unscrew the fixing clamps on the power
output cables, remove the connector from
the exciter.
- Remove the 4 nuts on the tie rods.
- Remove the NDE shield [36] using a puller:
eg. U.32 - 350 (FACOM).
- Remove the antifriction bearing [70] using
a screw puller.
• Tools required
To fully dismantle the machine, we Reassembly
recommend using the tools listed below: - Heat the inner slipring of a new bearing by
- 1 ratchet spanner + extension induction or in a drying oven at 80°C (do not
- 1 torque wrench use an oil-bath) and fit it to the machine.
- 1 set of flat spanners: 7, 8, 10, 12 mm - Place the preloading wavy washer [79] in
- 1 socket set: 8, 10, 13, 16, 18, 21, 22, the shield and fit a new O ring seal [349].
24 mm Refit the NDE shield and pass the bundle of
- 1 Allen key: size 5 (eg. Facom: ET5), size 6 wires between the top bars of the shield.
(ET6), size 10 (ET10), size 14 (ET14) - Refit the fixing clamps on the cables and
- 1 T20 and T30 TORX bit the exciter connector.
- 1 puller (U35)/(U32/350)
• Screw tightening torque
See section 5.4.
• Access to diodes
- Remove the air intake grille [51].
- Check all 3 modules using an ohmmeter or
a battery lamp.
20
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
- Replace the terminal box lid [48] and also Reassembling the revolving field coil
the earth continuity screw [29]. - Follow the dismantling procedure in reverse
order.
Take care not to knock the windings when
NDE shield
refitting the rotor in the stator.
Rotor - Refit the fan with its fixing screws on the
Threaded rod hub.
Follow the procedure for refitting the
bearings.
WARNING
When dismantling the shields, you will
need to change the antifriction bearings,
the “O” ring seal, the preloading (wavy)
washer and adhesive paste.
21
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
4.8 - Table of characteristics • Three-phase: 4-pole AREP+ excitation
Table of average values: Resistances at 20 °C (Ω)
Alternator - 4 pole - 50 Hz - Standard winding Stator Exciter Exciter
No. 6S (6-wire) and M or M1 (4-wire) Type Rotor
L/N field armature
connected in dedicated single-phase (400 V A-B 0.067 2.07 7.26 0.791
for the excitation values). C-D 0.050 2.35 7.26 0.791
The voltage and current values are given for
E-H 0.034 2.89 8.07 0.920
no-load operation and operation at rated
load with separate field excitation. J 0.029 3.15 8.07 0.920
All values are given to within ± 10% and may K 0.024 3.43 8.07 0.920
be changed without prior notification (for L-M 0.019 4.04 4.82 1.051
exact values, consult the test report).
For 60 Hz machines, the “i exc” values are Resistance of auxiliary windings at
approximately 5 to 10 % lower. 20 °C (Ω)
Type X1, X2 Z1, Z2
• Three-phase: 4-pole SHUNT excitation A-B 0.450 0.657
Resistances at 20 °C (Ω) C-D 0.436 0.627
Stator Exciter Exciter E-H 0.365 0.575
Type Rotor
L/N field armature J 0.308 0.480
A-B 0.067 2.07 11.65 0.791 K 0.417 0.611
C-D 0.050 2.35 11.65 0.791 L-M 0.238 0.547
E-H 0.034 2.89 12.94 0.920
J 0.029 3.15 12.94 0.920 Field excitation current i exc (A)
K 0.024 3.43 12.94 0.920 400V - 50 Hz
L-M 0.019 4.04 7.88 1.051 “i exc”: excitation current of the exciter field
Type No load At rated load
Field excitation current i exc (A) A 1.08 3.35
400V - 50 Hz
B 1.08 3.80
“i exc”: excitation current of the exciter field
C 1.03 3.54
Type No load At rated load D 1.03 3.96
A 0.84 2.60 E 0.87 3.31
B 0.84 2.95 H 0.87 3.59
C 0.80 2.75 J 0.85 3.60
D 0.80 3.08 K 0.88 3.63
E 0.67 2.57 L 0.82 3.46
H 0.67 2.78 M 0.82 3.88
J 0.66 2.79
K 0.68 2.82
L 0.64 2.69
M 0.64 3.01
22
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
• Dedicated single-phase M: 4-pole • Table of weights
SHUNT excitation - 50 Hz (values given for information only)
Resistances at 20 °C (Ω) - Series Three-phase: SHUNT/AREP+
connection
Type Total weight (kg) Rotor (kg)
Stator Exciter Exciter
Type Rotor A-B 247 114
L/N field armature
C-D 280 128
C 0.012 2.07 11.65 0.791
E-H 353 160
D1 0.009 2.35 11.65 0.791
J 383 172
J 0.007 3.15 12.94 0.920
K 418 187
Field excitation current i exc (A) L-M 539 228
230V - 50 Hz
“i exc”: excitation current of the exciter field Dedicated single-phase M: SHUNT
Type No load At rated load Type Total weight (kg) Rotor (kg)
C 0.70 1.50 C 289 121
D1 0.70 1.50 D1 332 139
J 0.60 1.30 J 391 166
23
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
5 - SPARE PARTS
5.1 - First maintenance parts
Emergency repair kits are available as an
option. After operational testing, it is essential to
They contain the following items: replace all access panels or covers.
Emergency kit SHUNT 4941330
AVR R120 (6 and 12-wire) - 5.3 - Accessories
Diode bridge assembly - • Space heater for use when stopped
Emergency kit AREP+/PMG 5080206 The space heater must run as soon as the
AVR R180 (6 and 12-wire) - alternator stops. It is installed at the rear of
Diode bridge assembly - the machine. Its standard power is 100W
with 220V or 100W with 110V on request.
Single bearing kit 4879454
Non drive end bearing -
«O» ring -
Preloading (wavy) washer -
24
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
5.4 - Exploded view, parts list and tightening torque
• Single bearing
25
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
Screw Torque Screw Torque
Ref. Qty Description Ref. Qty Description
Ø N.m Ø N.m
Non drive end (NDE)
1 1 Stator assembly - - 70 1 bearing - -
Preloading (wavy)
4 1 Rotor assembly - - 79 1 - -
washer
15 1 Fan M6 5 90 1 Exciter field (stator) M6 10
Lifting eye (only with Exciter armature
21 1 M10 40 100 1 - -
TAL 044 L and M) (rotor)
28 1 Earth terminal M6* 10** 107 1 Diode support ring M5 6
Earth continuity
29 1 M6 10 124 1 Terminal block M6 5
screws
30 1 Drive end (DE) shield M12 69 144 1 Terminal box - -
Voltage regulator
32 1 S.A.E. adaptor ring - - 198 1 M5 3.6
(AVR)
33 2 Protective grille M6 5 320 1 Coupling sleeve - -
26
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
Disposal and recycling instructions All materials listed above need special
We are committed to limiting the treatment to separate waste from
environmental impact of our activity. We reclaimable materials and should be
continuously monitor our production entrusted to specialist recycling companies.
processes, material sourcing and product
design to improve recyclability and minimise The oil and grease from the lubrication
our environmental footprint. system should be treated as hazardous
These instructions are for information waste and must be treated in accordance
purposes only. It is the user’s responsibility with local legislation.
to comply with local legislation regarding
product disposal and recycling. Our alternators have a specified lifetime of
20 years. After this period, the operation of
Recyclable materials the product should be stopped, regardless
Our alternators are mainly constructed from of its condition. Any further operation after
iron, steel and copper materials, which can this period will be under the sole responsi-
be reclaimed for recycling purposes. bility of the user.
These materials can be reclaimed through a
combination of manual dismantling,
mechanical separation and melting
processes. Our technical support depart-
ment can provide detailed directions on how
to dismantle products on request.
27
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
28
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
LSA 40 – LSA 42.3 – LSA 44.3 – LSA 46.3 – LSA 47.2 – LSA 49.1 – LSA 49.3 – LSA 50.1 – LSA 50.2 – LSA
51.2 – LSA 52.2 – LSA 52.3 – LSA 53.1 – LSA 53 – LSA 53.2 – LSA 54 – LSA 54.2 – TAL 040 – TAL 042 – TAL
044 – TAL 046 – TAL 047 – TAL 0473 – TAL 049 – LSAH 443 as well as their derivatives, manufactured by
Leroy-Somer or on Leroy-Somer's behalf, comply with the following International Standards and Directive:
Furthermore, these generators, designed in compliance with the Machine Directive Nr 2006/42, are therefore
able to be incorporated into Electrical Gen-Sets complying with the following International Directives:
WARNING:
The here mentioned generators should not be commissioned until the corresponding Gen-Sets have been
declared in compliance with the Directives Nr 2006/42/EC, 2014/30/EU and 2011/65/EU, as well as with other
relevant Directives.
Leroy-Somer undertakes to transmit, in response to a reasoned request by the national authorities, relevant
information on the generator.
Technical Managers
J.P. CHARPENTIER Y. MESSIN
Moteurs Leroy-Somer
Siege social : Boulevard Marcellin Leroy CS 10015 - 16915 Angoulême cedex 9 - France
4152 en - 2020.04 / q
SAS au capital de 38 679 664 € - RCS Angoulême 338 567 258
The contractual EC Declaration of compliance and incorporation can be obtained from your contact on
request.
29
Electric Power Generation Installation and maintenance 5226 en - 2020.06 / l
TAL 044
Low Voltage Alternator - 4 pole
30
Service & Support
Life Extension
•Reconditioning Start-up
•System upgrade
•Commissioning
•Training
Optimisation
•Monitoring Operation
•System audit •Genuine spare parts
•Repair services
Contact us:
Americas: +1 (507) 625 4011
Europe & Rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
Middle East: +971 4 5687431 Scan the code or go to:
service.epg@leroy-somer.com www.lrsm.co/support
www.leroy-somer.com/epg
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
5226 en - 2020.06 / l