1MRS 750400-MBG
Issued: July 1998
Status: New
Version: B/09.11.2001
Data subject to change without notice
1
Voltage regulator SPAU 341 C
1MRS 750400-MBG
Application The voltage regulator SPAU 341 C is used the voltage regulators need to measure
intended to be used in distribution substations both voltage and current. Further, a means of
for automatic and manual voltage regulation communication between the regulators must
for power transformers with on-load tap- be provided. When two transformers are run-
changers. The regulator can be used in associ- ning in parallel three operating principles can
ation with a single power transformer by be selected, i.e. the master/slave principle, the
measuring voltage alone. When two or three negative reactance principle or the minimiz-
power transformers are run in parallel and ing circulating current principle.
more sophisticated regulating principles are
Design The fully equipped voltage regulator includes When the minimizing current principle is
four modules: a connection module, an I/O used the number of parallel power transform-
module, an automatic voltage regulating ers maximum is three. Each voltage regulator
module and a manual voltage regulating mod- module transmits its own current and phase
ule. The regulator modules are multi-func- shift values to the other modules operating in
tional microprocessor-based plug-in units. parallel. The modules calculate the total value
The voltage regulator is available in two ver- of the busbar current and the phase shift and
sions: with or without the manual voltage compare this value with their own values.
regulating module. The regulator modules are
provided with local man-machine communi-
cation interfaces.
Manual voltage regulating
module SPCU 1D56
When the voltage regulator is set for manual
Automatic voltage regulator operation the tap changer of the power trans-
module SPCU 1D50 former can be controlled via the push-buttons
The automatic voltage regulator module is of the manual voltage regulating module. If a
used for automatic control of the tap changers raise or lower command cannot be executed
of power transformers. The module can con- because of an overcurrent situation or exter-
trol parallel transformers in three different nal blocking, the operator will be notified by
ways, i.e. using the master/slave, the negative means of the LED indicators marked I> or
reactance and the minimizing circulating cur- BLOCK. The display of the module shows
rent principle. setting values, tap-changer positions and
measured values.
When the master/slave principle is used the
number of parallel power transformers is
unlimited. One regulator acts as the master
Data communication
and calculates the voltage drop on the basis of The relay is provided with a serial interface
on the rear panel. By means of a bus connec-
its own measurements, assuming that the
tion module type SPA-ZC 17 or SPA-ZC 21
power transformers are equally loaded. In this
application a direct wiring is required the relay can be connected to the fibre-optic
SPA bus. The bus connection module type
between the voltage regulators.
SPA-ZC 21 is powered from the host relay,
When the negative reactance principle is used whereas the bus connection module SPA-
ZC 17 is provided with a built-in power unit,
the module compares the actual phase shift
which can be fed from an external secured
with the set load phase shift and by measur-
ing the current the compensating value that power source. The relay communicates with
higher-level data acquisition and control sys-
affects the regulator control voltage, can be
tems over the SPA bus.
calculated. The negative reactance principle
can be used for controlling power transform-
When several voltage regulators are to be
ers with different ratings and step voltage val-
operated in parallel, bus connection modules
ues. Since, in this principle, no connection is
required between the regulators, even trans- type SPA-ZC 100 are used.
formers located in different substations can
be operated in parallel.
2
Voltage regulator SPAU 341 C
1MRS 750400-MBG
7DEOH(QHUJL]LQJLQSXWVFXUUHQWPHDVXULQJLQSXWV
Rated current In 1A 5A
Terminal numbers X0/1-3, 4-6, 7-9 X0/1-2, 4-5, 7-8
Thermal current continuously 4A 20 A
withstand for 10 s 25 A 100 A
for 1 s 100 A 500 A
Dynamic withstand half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
7DEOH2XWSXWFRQWDFWUDWLQJV
Type of contact Tap-changer control Signalling
Terminal numbers X2/1-2, 3-4 X2/5-6, 7-8, 9-10-11,
14-15-16
Nominal voltage 250 V ac/dc
Thermal withstand Carry continuously 5A 5A
capability Make and carry for 0.5 s 30 A 10 A
Make and carry for 3 s 15 A 8A
Breaking capacity for dc, 220 V dc 1A 0.15 A
when the control circuit 110 V dc 3A 0.25 A
time constant
48 V dc 5A 1A
L/R ≤ 40 ms, at the
control voltage levels
Contact material AgCdO2
7DEOH([WHUQDOFRQWUROLQSXWV
Terminal numbers X1/1-2, 3-4, 5-6, 7-8, 9-10, 11-12, 13-14
External control voltage 18…250 V dc or 80…250 V ac
Typical control current of input circuit 2…20 mA
7DEOH([WHUQDOP$LQSXW
Terminal numbers X1/15-16
3
Voltage regulator SPAU 341 C
1MRS 750400-MBG
7DEOH$X[LOLDU\VXSSO\PRGXOHV
Power module rated voltages Un 110/120/230/240 V ac
SPGU 240A1 110/125/220 V dc
operative voltage range 80…265 V ac/dc
Power module rated voltages Un 24/48/60 V dc
SPGU 48B2 operative voltage range 18…80 V dc
Power consumption, quiescent/operation conditions ~10 W/~15W
7DEOH$XWRPDWLFYROWDJHUHJXODWLQJPRGXOH63&8'
Operate time setting range 0.0…300 s
Operate time accuracy at definite time characteristic ±1% of set value or ±250 ms
Operate time accuracy at inverse time characteristic ±250 ms and the inaccuracy appearing
when the measured voltage varies ±0.3%
Minimum operate time at inverse time characteristic 1s
7DEOH0DQXDOYROWDJHUHJXODWLQJPRGXOH63&1'
Accuracy, mA input signal ±1% of FSR
Output pulse duration, selectable 0.50…10 s in 0.1 s steps
7DEOH'DWDFRPPXQLFDWLRQ
Transmission mode Fibre-optic serial bus
Data code ASCII
Data transfer rate, selectable 4800 or 9600 Bd
Optical bus connection module for plastic core cables SPA-ZC 21BB
for glass fibre cables SPA-ZC 21MM
Optical bus connection module powered from the for plastic core cables SPA-ZC 17BB
internal power source for glass fibre cables SPA-ZC 17MM
Optical bus connection module for parallel operation for plastic core cables SPA-ZC 100BB
for glass fibre cables SPA-ZC 100MM
4
Voltage regulator SPAU 341 C
1MRS 750400-MBG
7DEOH7HVWVDQGVWDQGDUGV
Test voltages Insulation resistance voltage >100 MΩ, 500 V dc
(IEC 60255-5)
Impulse test voltage (IEC 60255-5) 5 kV, 1.2/50 µs, 0.5 J
Dielectric test voltage (IEC 60255-5) 2 kV, 50 Hz, 1 min
Interference tests High-frequency (1 MHz) disturbance test 2.5 kV
(IEC 60255-22-1), common mode
High-frequency (1 MHz) disturbance test 1.0 kV
(IEC 60255-22-1), differential mode
Fast transients (IEC 60255-22-4, class III 4 kV, 5/50 ns
and IEC 60801-4, level 4), power supply
inputs
Fast transients (IEC 60255-22-4, class III 2 kV, 5/50 ns
and IEC 60801-4, level 4), other inputs
Electrostatic discharge 8 kV
(IEC 60255-22-2 and IEC 60801-2, class
III), air discharge
Electrostatic discharge 6 kV
(IEC 60255-22-2 and IEC 60801-2, class
III), contact discharge
Environmental conditions Service temperature range -10…+55°C
Transport and storage temperature range -40…+70°C
(IEC 60068-2-8)
Temperature influence – voltage <0.025%/°C
measurement
Temperature influence – tap-changer <0.025%/°C
position measurement
Temperature influence – current <0.1%/°C
measurements
Damp heat test (IEC 60068-2-30) 93…95%, +55°C, 6 cycles
Degree of protection by enclosure of flush IP 54
mounting regulator case according to
IEC 60529
Weight of fully equipped regulator ~5.5 kg
5
Voltage regulator SPAU 341 C
1MRS 750400-MBG
Block diagram
L1
L2
L3
Rx
Tx
+ (~)
Uaux
SPA-ZC
- (~)
X0 63 1 2 3 4 5 6 7 8 9 13 14 X1 11 12 X0 62 61 X1 13 14 X2 10 9 11 14 15 16 1 2 3 4 7 8 5 6 Serial port
5A 1A 5A 1A 5A 1A 100/110/120V
~ + + + + + +
U5 + -
U6 SGF2/1
I> SGF2/2
U>
U<
Parallel
RSV
TAP POS
Raise
&
15 16
+
U
Lower
10
SGF1/3
1 &
TCO
&
8
RAISE'
&
LOWER'
S
5
AUTO
R/S &
AUTO'
R Raise
3
2
&
MAN'
Lower
XXX
X1 1
U5 U1 U2
6
Voltage regulator SPAU 341 C
1MRS 750400-MBG
139 ±1
Panel
162
136
cut-out
dim300
Semi-flush mounting
a b
Raising frame a b
SPA-ZX 301 219 74
SPA-ZX 302 179 114
SPA-ZX 303 139 154
SFM300_1
Fig. 3 Semi-flush mounting relay case (dimensions in mm)
SPA-ZX304 SPA-ZX306
SPA-ZX305 SPA-ZX307
SPA-ZX201 SPA-ZX317
SPA-ZX318
+0,4 242 306
482,6 –0 (19")
197
ø6
177 –0 (4U)
101,6
7
+0,4
312
292
6
197 98
21,5
304_5_6
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
7
Voltage regulator SPAU 341 C
1MRS 750400-MBG
Ordering :KHQRUGHULQJSOHDVHVSHFLI\
Ordering information Ordering example
1. Type designation and quantity SPAU 341 C1, 5 pieces
2. Order number RS 488 003-AA
3. Rated frequency In=5 A, Un=110 V, fn=50 Hz
4. Auxiliary voltage Uaux=110 V dc
5. Accessories -
6. Special requirements -
2UGHUQXPEHUV
Voltage regulator SPAU 341 C_ without test adapter
SPAU 341 C1, incl. modules SPCU 1D50 and RS 488 003-AA, CA, DA, FA
SPCN 1D56
SPAU 341 C3, incl. module SPCU 1D50 RS 488 005-AA, CA, DA, FA
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/d
rated frequency fn and the auxiliary voltage Uaux of CA equals fn = 50 Hz and Uaux = 18…80 V dc
the relay as follows:
DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc
References $GGLWLRQDOLQIRUPDWLRQ
Colour brochure “Voltage regulator SPAU 341 C” 1MRS 750013-MDS EN
User’s manual and technical description “Voltage 1MRS 750110-MUM EN
regulator SPAU 341 C”
ABB Oy
P.O. Box 699
FIN-65101 Vaasa, Finland
Tel +358 10 224 000
Fax +358 10 224 1094
www.abb.com/substationautomation