Professional Documents
Culture Documents
Line Differential Protection IED RED 670: Buyer's Guide
Line Differential Protection IED RED 670: Buyer's Guide
Page 1
Features • Four configuration alternatives for single- or - All types of scheme communication including
multi-breaker arrangements available – ready to phase segregated communication for secure
connect phase selection at simultaneous faults
• A protection, control and monitoring IED with - Load encroachment feature
extensive functional library and configuration • Power swing detection including additional logic
possibilities and expandable hardware design to
meet specific user requirements • Pole slip protection
• For overhead lines and cables - Detection of slips in power systems from 0.2
to 8 Hz
• For transformer feeders
- Trip after a set number of slips
• For single and/or three phase tripping
• Directional power protection
• High impedance differential protection for
tee-feeders - Reverse-, low forward-, active-, reactive
power protection
• Phase-segregated line differential protection
- Phase angle compensation
with up to six stabilized inputs for up to five line
terminals with: - Two steps (alarm/trip)
- Charging current compensation • Synchronizing, synchrocheck and dead-line
check function for single- or multi-breaker
- Separate inputs for each CT in double
arrangements:
breaker, ring and one and a half breaker
installations for improved through fault stabil- - Selectable energizing direction
ity
- Two functions with built-in voltage selection
- Suitable for multiplexed, route switched, as - For automatic and manual synchronizing and
well as dedicated fibre, communication net- synchrocheck with different settings
works using C37.94 protocol
- Synchronizing of asynchronous networks
- Power transformers can be included in the
with settable breaker closing time
protected zone
• Auto-reclosing function for single- two-, and/or
- Transfer of up to eight binary signals
three-phase reclosing:
- Time synchronization with the echo-method
- Two functions with priority circuits for
or built-in GPS
multi-breaker arrangements
• Full scheme phase-to-phase and phase-to-earth
distance protection with up to three zones: - Co-operation with synchronizing, synchro-
check function
- Alternative choice of series compen- - Can be switched On-Off from remote through
sated/advanced application quadrilateral communication, from medium size LHMI or
function, quadrilateral function or mho func- with local switches through binary inputs
tion
• Selectable additional software functions such as
- Special quadrilateral version with phase pref-
distance protection, control and monitoring
erence logic and sensitive directional earth
fault function for high ohmic earthed system. • Data communication modules for station bus
IEC 61850-8-1
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 2
• Data communication modules for station bus • Time synchronization over IEC 61850-8-1, LON,
IEC 60870-5-103, TCP/IP or EIA-485 DNP 3.0, SPA, binary input or with optional GPS module
LON and SPA (GSM) or IRIG-B module
• Integrated disturbance and event recorder for up • Analog measurements accuracy up to below
to 40 analog and 96 binary signals 0.5% for power and 0.25% for current and volt-
age and with site calibration to optimize total
• Function for energy calculation and demand
accuracy
handling
• Versatile local human-machine interface
- Outputs from measurement function (MMXU)
can be used to calculate energy. Active as • Extensive self-supervision with internal event
well as reactive values are calculated in recorder
import respectively export direction. Values
• Six independent groups of complete setting
can be read or generated as pulses. Maxi-
parameters with password protection
mum demand power values are also calcu-
lated by the function. • Powerful software PC tool for configuration, set-
ting and disturbance evaluation
Application The RED 670 IED is used for the protection, con- cial applications such as automatic opening of dis-
trol and monitoring of overhead lines and cables in connectors in multi-breaker arrangements, closing
all types of networks. The IED can be used up to of breaker rings, load transfer logics etc. The
the highest voltage levels. It is suitable for the pro- graphical configuration tool ensures simple and
tection of heavily loaded lines and multi-terminal fast testing and commissioning.
lines where the requirement for tripping is one-,
two-, and/or three pole. The IED is also suitable Serial data communication is via optical connec-
for protection of cable feeders to generator block tions to ensure immunity against disturbances.
transformers.
The wide application flexibility makes this product
The phase segregated current differential protec- an excellent choice for both new installations and
tion provides an excellent sensitivity for high the refurbishment of existing installations.
resistive faults and gives a secure phase selection.
The availability of six stabilized current inputs Four packages has been defined for following
allows use on multi-breaker arrangements in three applications:
terminal applications or up to five terminal appli- • Single-breaker (double or single bus) with
cations with single breaker arrangements. Remote
three phase tripping (A31)
communication based on the IEEE C37.94 stan-
dard can be redundant when required for important • Single-breaker (double or single bus) with sin-
installations. Charging current compensation gle phase tripping (A32)
allows high sensitivity also on long overhead lines • Multi-breaker (one-and a half or ring) with
and cables. A full scheme distance protection is
three phase tripping (B31)
included as independent protection or as back-up
at remote end communication failures. Eight chan- • Multi-breaker (one-and a half or ring) with sin-
nels for intertrip and binary signals are available in gle phase tripping (B32)
the communication between the IEDs.
The packages are configured and set with basic
The auto-reclose for single-, two- and/or three functions active to allow direct use. Optional func-
phase reclosing includes priority circuits for tions are not configured but a maximum configura-
multi-breaker arrangements. It co-operates with tion with all optional functions are available as
the synchronism check function with high-speed template in the graphical configuration tool. Inter-
or delayed reclosing. face to analog and binary IO are configurable from
High set instantaneous phase and earth overcur- the Signal matrix tool without need of configura-
rent, four step directional or un-directional delayed tion changes. Analogue and tripping IO has been
phase and earth overcurrent, thermal overload and pre-defined for basic use on the, as standard sup-
two step under and overvoltage functions are plied one binary input module and one binary out-
examples of the available functions allowing the put module.
user to fulfill any application requirement. For details on included basic functions refer to sec-
The IED can also be provided with a full control tion "Available functions".
and interlocking functionality including co-opera- The applications are shown in figures 1 and 2 for
tion with the synchronism check function to allow single resp. multi-breaker arrangement.
integration of the main or back-up control.
Refer to the Application manual for pre-config-
The advanced logic capability, where the user ured analog and binary IO.
logic is prepared with a graphical tool, allows spe-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 3
BUS B
BUS A
79 25
CLOSE
O->I SC/VC
94/86
TRIP
I->O
50BF
3I>
87L
3Id/I>
50/51
3I>
59
3U>
27
3U<
Figure 1: The single breaker packages for single- and three phase tripping typical arrangement for one
protection sub-system is shown here. The differential function is more sensitive than any earth
fault or directional earth fault function and these functions are thus an option.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 4
BUS A
TRIP BUSBAR
&CB2
79 25
CLOSE
O->I SC/VC
94/86 CB1
TRIP
I->O
79 25
O->I SC/VC
50BF
50/51
3I>
3I> Σ TRIP
50BF
CB1/3
3I>
94/86
87L
I->O
CLOSE
59
3Id/I>
TRIP
3U>
27
3U< CB2
en05000303.vsd
TO REMOTE END:
FIBRE OPTIC OR TO MUX
Figure 2: The multi breaker packages for single- and three phase tripping typical arrangement for one pro-
tection sub-system is shown here. The differential function is more sensitive than any earth fault
or directional earth fault function and these functions are thus an option. Auto-reclose, Synchro-
check and Breaker failure functions are included for each of the two breakers.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 5
Available
functions
ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
Differential protection
(Only one alternative can be selected)
87 1 phase High impedance differential protection (PDIF) - 3/A02 - 3/A02 - 3/A02 - 3/A02
87L Line differential protection, 3 CT sets, 2-3 line ends (PDIF) 1 - - - 1 - - -
87L Line differential protection, 6 CT sets, 3-5 line ends (PDIF) - 1/A04 1 - - 1/A04 1 -
87LT Line differential protection 3 CT sets, with in-zone transformers, - 1/A05 - - - 1/A05 - -
2-3 line ends (PDIF)
87LT Line differential protection 6 CT sets, with in-zone transformers, - 1/A06 - 1/A06 - 1/A06 - 1/A06
3-5 line ends (PDIF)
Impedance protection
21 Distance protection zones, quadrilateral characteristic (PDIS) - 3/B01 - 3/B01 - 3/B01 - 3/B01
21 Directional impedance quadrilateral, including series compensa- - 1/B06 - 1/B06 - 1/B06 - 1/B06
tion (RDIR)
21 Full-scheme distance protection, mho characteristic (PDIS) - 3/B07 - 3/B07 - 3/B07 - 3/B07
78 Power swing detection (RPSB) - 1/B01/B06 - 1/B01/B06 - 1/B01/B06 - 1/B01/B06
/B07 /B07 /B07 /B07
Power swing logic (RPSL) - 1/B03 - 1/B03 - 1/B03 - 1/B03
78 Pole slip protection (PPAM) - 1/B21 - 1/B21 - 1/B21 - 1/B21
Automatic switch onto fault logic, voltage and current based - 1/B01/B06 - 1/B01/B06 - 1/B01/B06 - 1/B01/B06
(PSOF) /B07 /B07 /B07 /B07
Current protection
50 Instantaneous phase overcurrent protection (PIOC) 1 - 1 - 1 - 1 -
51/67 Four step phase overcurrent protection (PTOC) 1 - 1 - 1 - 1 -
50N Instantaneous residual overcurrent protection (PIOC) - 1/C04 - 1/C04 - 1/C04 - 1/C04
51N/67N Four step residual overcurrent protection (PTOC) - 1/C04 - 1/C04 - 1/C04 - 1/C04
67N Sensitive directinal residual overcurrent and power protection - 1/C16 - 1/C16 - 1/C16 - 1/C16
(PSDE)
26 Thermal overload protection, one time constant (PTTR) 1 - 1 - 1 - 1 -
50BF Breaker failure protection (RBRF) 1 - 2 - 1 - 2 -
50STB Stub protection (PTOC) - 1/B01 1 1/B01 - 1/B01 1 1/B01
52PD Pole discordance protection (RPLD) 1 - 2 - 1 - 2 -
Directional underpower protection (PDUP) - 1/C17 - 1/C17 - 1/C17 - 1/C17
Directional overpower protection (PDOP) - 1/C17 - 1/C17 - 1/C17 - 1/C17
46 Broken conductor check 1 - 1 - 1 - 1 -
Voltage protection
27 Two step undervoltage protection (PTUV) 1 - 1 - 1 - 1 -
59 Two step overvoltage protection (PTOV) 1 - 1 - 1 - 1 -
59N Two step residual overvoltage protection (PTOV) 1 - 1 - 1 - 1 -
24 Overexcitation protection (PVPH) - 1/D03 - 1/D03 - 1/D03 - 1/D03
60 Voltage differential protection (PTOV) 2 - 2 - 2 - 2 -
27 Loss of voltage check 1 - 1 - 1 - 1 -
Frequency protection
81 Underfrequency protection (PTUF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Overfrequency protection (PTOF) - 2/E02 - 2/E02 - 2/E02 - 2/E02
81 Rate-of-change frequency protection (PFRC) - 2/E02 - 2/E02 - 2/E02 - 2/E02
Multipurpose protection
General current and voltage protection (GAPC) - 4/F01 - 4/F01 - 4/F01 - 4/F01
ANSI Function description Single breaker, Multi breaker, Singel breaker, Multi breaker,
3-phase tripping 3-phase tripping 1-phase tripping 1-phase tripping
(A31) (B31) (A32) (B32)
Basic Option Basic Option Basic Option Basic Option
(Qty/ (Qty/ (Qty/ (Qty/
option option option option
design) design) design) design)
Control
25 Synchrocheck, energizing check and synchronizing (RSYN) 1 - 2 - 1 - 2 -
79 Autorecloser (RREC) 1 1/H04 2 2/H05 1 1/H04 2 2/H05
Apparatus control for single bay, - 1/H07 - - - 1/H07 - -
max 8 apparatuses (1CB) incl. interlocking (APC8)
Apparatus control for single bay, - - - 1/H08 - - - 1/H08
max 15 apparatuses (2CBs) incl. interlocking (APC15)
Logic rotating switch for function selection and LHMI presenta- 15 - 15 - 15 - 15 -
tion (GGIO)
Selector mini switch (GGIO) 20 - 20 - 20 - 20 -
Scheme communication
85 Scheme communication logic for distance or overcurrent protec- - 1/B01/B06 - 1/B01/B06 - 1/B01/B06 - 1/B01/B06
tion (PSCH) /B07 /B07 /B07 /B07
85 Phase segregated scheme communication logic for distance - - - - - 1/B05 - 1/B05
protection (PSCH)
85 Current reversal and weak-end infeed logic for - 1/B01/B06 - 1/B01/B06 - 1/B01/B06 - 1/B01/B06
distance protection (ZCAL) /B07 /B07 /B07 /B07
Current reversal and weak-end infeed logic for phase segre- - - - - - 1/B05 - 1/B05
gated communication (PSCH)
Local acceleration logic (ZCLC) - 1/B01 - 1/B01 - 1/B01 - 1/B01
85 Scheme communication logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)
85 Current reversal and weak-end infeed logic for - 1/C04 - 1/C04 - 1/C04 - 1/C04
residual overcurrent protection (PSCH)
Logic
94 Tripping logic (PTRC) 1 - 2 - 1 - 2 -
Trip matrix logic (GGIO) 12 - 12 - 12 - 12 -
Monitoring
Measurements (MMXU) 6/10/6 - 6/10/6 - 6/10/6 - 6/10/6 -
Event counter (GGIO) 5 - 5 - 5 - 5 -
Disturbance report (RDRE) 1 - 1 - 1 - 1 -
IEC61850 generic communication I/O functions (GGIO) 16 - 16 - 16 - 16 -
Fault locator (RFLO) 1 - 1 - 1 - 1 -
Measured value calculation and demand handling 66 - 66 - 66 - 66 -
Metering
Pulse counter logic (GGIO) 16 - 16 - 16 - 16 -
Function for energy calculation and demand handling (MMTR) 6 - 6 - 6 - 6 -
Station communication
IEC61850-8-1 Communication *) 1 - 1 - 1 - 1 -
LON communication protocol *) 1 - 1 - 1 - 1 -
SPA communication protocol *) 1 - 1 - 1 - 1 -
IEC60870-5-103 communication protocol *) 1 - 1 - 1 - 1 -
DNP3.0 for TCP/IP and EiA-485 communication protocol 1 - 1 - 1 - 1 -
Single command, 16 signals 4 - 4 - 4 - 4 -
Multiple command and transmit 60/10 - 60/10 - 60/10 - 60/10 -
Remote communication
Binary signal transfer 6 - 6 - 6 - 6 -
*) In order to utilize it, an appropriate optional hardware port must be ordered.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 7
Protected zone
en05000039.vsd
The six terminal version is used for conventional arrangements in both ends, as well as multi termi-
two-terminal lines with 1 1/2 circuit breaker nal lines with up to five terminals.
Protected zone
RED RED
670 Comm. Channel 670
en05000040.vsd
The current differential algorithm in RED 670 pro- A special feature with RED 670 is that applica-
vides high sensitivity for internal faults, at the tions with small power transformers (rated current
same time as it has excellent stability for external less than 50 % of the differential current setting)
faults. Current samples from all CTs are connected as line taps (i.e. as "shunt" power trans-
exchanged between the IEDs in the line ends (mas- formers), without measurements of currents in the
ter-master mode) or sent to one IED (master-slave tap, can be handled. The normal load current is
mode) for evaluation. here considered to be negligible, and special mea-
sures need only to be taken in the event of a short
A restrained dual biased slope evaluation is made circuit on the LV side of the transformer. In this
where the bias current is the highest phase current application, the tripping of the differential protec-
in any line end giving a secure through fault stabil- tion can be time delayed for low differential cur-
ity even with heavily saturated CTs. In addition to rents in order to achieve coordination with down
the restrained evaluation, an unrestrained high dif- stream over current relays.
ferential current setting can be used for fast trip-
ping of internal faults with very high currents. A line charging current compensation provides
increased sensitivity of the differential function.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 8
Protected zone
Figure 5: Example of application on a three-terminal line with a power transformer in the protection zone
Analog signal transfer for needed between every IED included in the same
line differential protection (MDIF) line differential protection zone. In the latter, cur-
The line differential communication can be rent samples are sent from all slave IEDs to one
arranged as a master-master system or a mas- master IED where the evaluation is made, and trip
ter-slave system alternatively. In the former, cur- signals are sent to the remote ends when needed. In
rent samples are exchanged between all terminals, this system, a 64 kbit/s communication channel is
and an evaluation is made in each terminal. This only needed between the master, and each one of
means that a 64 kbit/s communication channel is the slave terminals.
Protected zone
RED RED
670 670
Comm.
Channels
en05000043.vsd
Protected zone
RED RED
670 670
Comm.
Channels
en05000044.vsd
Current samples from IEDs located geographically Phase selection with load encroachment
apart from each other, must be time coordinated so (PDIS, 21)
that the current differential algorithm can be exe- The operation of transmission networks today is in
cuted correctly. In RED 670 it is possible to make many cases close to the stability limit. Due to envi-
this coordination in two different ways. The echo ronmental considerations the rate of expansion and
method of time synchronizing is normally used reinforcement of the power system is reduced e.g.
whereas for applications where transmit and difficulties to get permission to build new power
receive times can differ, the optional built in GPS lines. The ability to accurately and reliable classify
receivers shall be used. the different types of fault so that single pole trip-
ping and auto-reclosing can be used plays an
The communication link is continuously moni- important roll in this matter. The phase selection
tored, and an automatic switchover to a standby function is designed to accurately select the proper
link is possible after a preset time. fault loop in the distance function dependent on
the fault type.
Impedance protection The heavy load transfer that is common in many
transmission networks may make fault resistance
Distance measuring zones, coverage difficult to achieve. Therefore the func-
quadrilateral characteristic (PDIS, 21) tion has a built in algorithm for load encroach-
The line distance protection is a zone full scheme ment, which gives the possibility to enlarge the
protection with three fault loops for phase to phase resistive setting of both the phase selection and the
faults and three fault loops for phase to earth fault measuring zones without interfering with the load.
for each of the independent zones. Individual set-
tings for each zone in resistive and reactive reach The extensive output signals from the phase selec-
gives flexibility for use on overhead lines and tion gives also important information about faulty
cables. phase(s) which can be used for fault analysis.
Mho alternative Quad characteristic is available. Power swing detection (RPSB, 78)
Power swings may occur after disconnection of
The function has a functionality for load encroach- heavy loads or trip of big generation plants.
ment which increases the possibility to detect high
resistive faults on heavily loaded lines (see Power swing detection function is used to detect
figure 8). power swings and initiate block of selected dis-
tance protection zones. Occurrence of earth fault
currents during a power swing can block the power
X swing detection function to allow fault clearance.
The distance protection zones can operate, inde- Automatic switch onto fault logic, voltage
pendent of each other, in directional (forward or and current based (PSOF)
reverse) or non-directional mode. Automatic switch onto fault logic is a function that
gives an instantaneous trip at closing of breaker
onto a fault. A dead line detection check is pro-
vided to activate the function when the line is
dead.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 10
The stub protection covers the zone between the Two step overvoltage
current transformers and the open disconnector. protection (PTOV, 59)
The three phase instantaneous overcurrent function Overvoltages will occur in the power system dur-
is released from a NO (b) auxiliary contact on the ing abnormal conditions such as sudden power
line disconnector. loss, tap changer regulating failures, open line
ends on long lines.
Pole discordance protection (RPLD, 52PD)
Single pole operated circuit breakers can due to The function can be used as open line end detector,
electrical or mechanical failures end up with the normally then combined with directional reactive
different poles in different positions (close-open). over-power function or as system voltage supervi-
This can cause negative and zero sequence cur- sion, normally then giving alarm only or switching
rents which gives thermal stress on rotating in reactors or switch out capacitor banks to control
machines and can cause unwanted operation of the voltage.
zero sequence or negative sequence current func-
The function has two voltage steps, each of them
tions.
with inverse or definite time delayed.
Normally the own breaker is tripped to correct the
The overvoltage function has an extremely high
positions. If the situation consists the remote end
reset ratio to allow setting close to system service
can be intertripped to clear the unsymmetrical load
voltage.
situation.
The pole discordance function operates based on Two step residual overvoltage
information from auxiliary contacts of the circuit protection (PTOV, 59N)
breaker for the three phases with additional criteria Residual voltages will occur in the power system
from unsymmetrical phase current when required. during earth faults.
Frequency protection tion with the detection of the earth fault from the
directional earth fault protection function.
Underfrequency protection (PTUF, 81)
Underfrequency occurs as a result of lack of gener- Secondary system supervision
ation in the network.
The function can be used for load shedding sys- Current circuit supervision (RDIF)
tems, remedial action schemes, gas turbine start-up Open or short circuited current transformer cores
etc. can cause unwanted operation of many protection
functions such as differential, earth fault current
The function is provided with an undervoltage and negative sequence current functions.
blocking. The operation may be based on single
phase, phase-to-phase or positive sequence voltage It must be remembered that a blocking of protec-
measurement. tion functions at an occurring open CT circuit will
mean that the situation will remain and extremely
Overfrequency protection (PTOF, 81) high voltages will stress the secondary circuit.
Overfrequency will occur at sudden load drops or The current circuit supervision function compares
shunt faults in the power network. In some cases the residual current from a three phase set of cur-
close to generating part governor problems can rent transformer cores with the neutral point cur-
also cause overfrequency. rent on a separate input taken from another set of
The function can be used for generation shedding, cores on the current transformer.
remedial action schemes etc. It can also be used as A detection of a difference indicates a fault in the
a sub-nominal frequency stage initiating load circuit and is used as alarm or to block protection
restoring. functions expected to give unwanted tripping.
The function is provided with an undervoltage
blocking. The operation may be based on single Fuse failure supervision (RFUF)
phase, phase-to-phase or positive sequence voltage Failures in the secondary circuits of the voltage
measurement. transformer can cause unwanted operation of dis-
tance protection, undervoltage protection, neutral
Rate-of-change frequency point voltage protection, energizing function (syn-
protection (PFRC, 81) chronism check) etc. The fuse failure supervision
Rate of change of frequency function gives an function prevents such unwanted operations.
early indication of a main disturbance in the sys- There are three methods to detect fuse failures.
tem.
The method based on detection of zero sequence
The function can be used for generation shedding, voltage without any zero sequence current. This is
load shedding, remedial action schemes etc. a useful principle in a directly earthed system and
The function is provided with an undervoltage can detect one or two phase fuse failures.
blocking. The operation may be based on single The method based on detection of negative
phase, phase-to-phase or positive sequence voltage sequence voltage without any negative sequence
measurement. current. This is a useful principle in a non-directly
Each step can discriminate between positive or earthed system and can detect one or two phase
negative change of frequency. fuse failures.
The synchrocheck function checks that the volt- For easy and safe implementation of the interlock-
ages on both sides of the circuit breaker are in syn- ing function, the IED is delivered with standard-
chronism, or with at least one side dead to ensure ized and tested software interlocking modules
that closing can be done safely. containing logic for the interlocking conditions.
The interlocking conditions can be altered, to meet
The function includes a built-in voltage selection the customer’s specific requirements, by adding
scheme for double bus and one- and a half or ring configurable logic by means of the graphical con-
busbar arrangements. figuration tool.
Manual closing as well as automatic reclosing can
Logic rotating switch for function selection
be checked by the function and can have different
and LHMI presentation (SLGGIO)
settings.
The SLGGIO function block (or the selector
For systems which are running asynchronous a switch function block) is used within the CAP tool
synchronizing function is provided. The main pur- in order to get a selector switch functionality simi-
pose of the synchronizing function is to provide lar with the one provided by a hardware selector
controlled closing of circuit breakers when two switch. Hardware selector switches are used exten-
asynchronous systems are going to be connected. sively by utilities, in order to have different func-
It is used for slip frequencies that are larger than tions operating on pre-set values. Hardware
those for synchrocheck and lower than a set maxi- switches are however sources for maintenance
mum level for the synchronizing function. issues, lower system reliability and extended pur-
chase portfolio. The virtual selector switches elim-
Autorecloser (RREC, 79) inate all these problems.
The autoreclosing function provides high-speed
and/or delayed auto-reclosing for single or Selector mini switch (VSGGIO)
multi-breaker applications. The VSGGIO function block (or the versatile
switch function block) is a multipurpose function
Up to five reclosing attempts can be programmed. used within the CAP tool for a variety of applica-
The first attempt can be single-, two and/or three tions, as a general – purpose switch.
phase for single phase or multi-phase faults
respectively. The switch can be controlled from the menu or
from a symbol on the SLD of the LHMI.
Multiple autoreclosing functions are provided for
multi-breaker arrangements. A priority circuit Single point generic control 8 signals
allows one circuit breaker to close first and the (SPC8GGIO)
second will only close if the fault proved to be The SC function block is a collection of 8 single
transient. point commands, designed to bring in commands
from REMOTE (SCADA) or LOCAL (HMI) to
Each autoreclosing function can be configured to those parts of the logic configuration that do not
co-operate with a synchrocheck function. need complicated function blocks that have the
capability to receive commands (for example
Apparatus control (APC) SCSWI). In this way, simple commands can be
The apparatus control is a function for control and sent directly to the IED outputs, without confirma-
supervision of circuit breakers, disconnectors and tion. Confirmation (status) of the result of the com-
earthing switches within a bay. Permission to oper- mands is supposed to be achieved by other means,
ate is given after evaluation of conditions from such as binary inputs and SPGGIO function
other functions such as interlocking, synchro- blocks.
check, operator place selection and external or
internal blockings.
Scheme communication
Interlocking
The interlocking function blocks the possibility to Scheme communication logic for
operate primary switching devices, for instance distance protection and directional
when a disconnector is under load, in order to pre- residual overcurrent protection (PSCH, 85)
vent material damage and/or accidental human To achieve instantaneous fault clearance for all
injury. line faults, a scheme communication logic is pro-
vided. All types of communication schemes e.g.
Each apparatus control function has interlocking permissive underreach, permissive overreach,
modules included for different switchyard arrange- blocking, intertrip etc. are available. The built-in
ments, where each function handles interlocking of communication module (LDCM) can be used for
one bay. The interlocking function is distributed to scheme communication signalling when included.
each IED and is not dependent on any central func-
tion. For the station-wide interlocking, the IEDs Phase segregated communication is also available
communicate via the system-wide interbay bus for correct operation at simultaneous faults when
(IEC 61850-8-1) or by using hard wired binary three distance protection communication channels
inputs/outputs. The interlocking conditions depend are available between the line ends
on the circuit configuration and apparatus position
status at any given time.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 14
Current reversal and weak-end infeed logic tion can be supported with logic, that uses commu-
for distance protection and directional nication channels. REx 670 terminals have for this
residual overcurrent protection (PSCH, 85) reason available additions to scheme communica-
The current reversal function is used to prevent tion logic.
unwanted operations due to current reversal when
using permissive overreach protection schemes in If parallel lines are connected to common busbars
application with parallel lines when the overreach at both terminals, overreaching permissive com-
from the two ends overlaps on the parallel line. munication schemes can trip unselectively due to
fault current reversal. This unwanted tripping
The weak-end infeed logic is used in cases where affects the healthy line when a fault is cleared on
the apparent power behind the protection can be the other line. This lack of security can result in a
too low to activate the distance protection func- total loss of interconnection between the two
tion. When activated, received carrier signal buses. To avoid this type of disturbance, a fault
together with local under voltage criteria and no current-reversal logic (transient blocking logic)
reverse zone operation gives an instantaneous trip. can be used.
The received signal is also echoed back to acceler-
ate the sending end. Permissive communication schemes for residual
overcurrent protection, can basically operate only
Three phase or phase segregated scheme logic is when the protection in the remote terminal can
available. detect the fault. The detection requires a sufficient
minimum residual fault current, out from this ter-
Local acceleration logic (PLAL) minal. The fault current can be too low due to an
To achieve fast clearing of faults on the whole line, opened breaker or high positive and/or zero
when no communication channel is available, local sequence source impedance behind this terminal.
acceleration logic (ZCLC) can be used. This logic To overcome these conditions, weak end infeed
enables fast fault clearing during certain condi- (WEI) echo logic is used.
tions, but naturally, it can not fully replace a com-
munication channel.
Logic
The logic can be controlled either by the auto
re-closer (zone extension) or by the loss of load Tripping logic (PTRC, 94)
current (loss-of-load acceleration). A function block for protection tripping is pro-
vided for each circuit breaker involved in the trip-
Scheme communication logic ping of the fault. It provides the pulse prolongation
for residual overcurrent protection to ensure a trip pulse of sufficient length, as well as
(PSCH, 85) all functionality necessary for correct co-operation
To achieve fast fault clearance of earth faults on with autoreclosing functions.
the part of the line not covered by the instanta-
neous step of the residual overcurrent protection, The trip function block includes functionality for
the directional residual overcurrent protection can evolving faults and breaker lock-out.
be supported with a logic that uses communication
channels. Trip matrix logic (GGIO)
Twelve trip matrix logic blocks are included in the
In the directional scheme, information of the fault IED. The function blocks are used in the configu-
current direction must be transmitted to the other ration of the IED to route trip signals and/or other
line end. With directional comparison, an operate logical output signals to the different output relays.
time of the protection of 50 – 60 ms including a
channel transmission time of 20 ms, can be The matrix and the physical outputs will be seen in
achieved. This short operate time enables rapid the PCM 600 engineering tool and this allows the
autoreclosing function after the fault clearance. user to adapt the signals to the physical tripping
outputs according to the specific application needs.
The communication logic module for directional
residual current protection enables blocking as Configurable logic blocks
well as permissive under/overreach schemes. A number of logic blocks and timers are available
for user to adapt the configuration to the specific
Current reversal and weak-end infeed logic application needs.
for residual overcurrent protection
(PSCH, 85) Fixed signal function block
The EFCA additional communication logic is a The fixed signals function block generates a num-
supplement to the EFC scheme communication ber of pre-set (fixed) signals that can be used in the
logic for the residual overcurrent protection. configuration of an IED, either for forcing the
unused inputs in the other function blocks to a cer-
To achieve fast fault clearing for all earth faults on tain level/value, or for creating a certain logic.
the line, the directional earth-fault protection func-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 15
• measured voltages, currents, frequency, active, The function is characterized by great flexibility
reactive and apparent power and power factor, regarding configuration, starting conditions,
recording times and large storage capacity.
• the primary and secondary phasors,
• differential currents, bias currents, A disturbance is defined as an activation of an
input in the DRAx or DRBy function blocks which
• positive, negative and zero sequence currents
is set to trigger the disturbance recorder. All sig-
and voltages, nals from start of pre-fault time to the end of
• mA, input currents post-fault time, will be included in the recording.
• pulse counters, Every disturbance report recording is saved in the
• event counters IED in the standard Comtrade format. The same
• measured values and other information of the applies to all events, which are continuously saved
in a ring-buffer. The Local Human Machine Inter-
different parameters for included functions,
face (LHMI) is used to get information about the
• logical values of all binary in- and outputs and recordings, but the disturbance report files may be
• general IED information. uploaded to the PCM 600 (Protection and Control
IED Manager) and further analysis using the dis-
turbance handling tool.
Supervision of mA input signals (MVGGIO)
The main purpose of the function is to measure
and process signals from different measuring Event list (RDRE)
transducers. Many devices used in process control Continuous event-logging is useful for monitoring
represent various parameters such as frequency, of the system from an overview perspective and is
temperature and DC battery voltage as low current a complement to specific disturbance recorder
values, usually in the range 4-20 mA or 0-20 mA. functions.
Alarm limits can be set and used as triggers, e.g. to The event list logs all binary input signals con-
generate trip or alarm signals. nected to the Disturbance report function. The list
may contain of up to 1000 time-tagged events
The function requires that the IED is equipped stored in a ring-buffer.
with the mA input module.
Indications (RDRE)
Event counter (GGIO) To get fast, condensed and reliable information
The function consists of six counters which are about disturbances in the primary and/or in the
used for storing the number of times each counter secondary system it is important to know e.g.
input has been activated. binary signals that have changed status during a
disturbance. This information is used in the short
Disturbance report (RDRE) perspective to get information via the LHMI in a
Complete and reliable information about distur- straightforward way.
bances in the primary and/or in the secondary sys-
There are three LEDs on the LHMI (green, yellow
tem together with continuous event-logging is
and red), which will display status information
accomplished by the disturbance report functional-
about the IED and the Disturbance Report function
ity.
(trigged).
The disturbance report, always included in the
The Indication list function shows all selected
IED, acquires sampled data of all selected analog
binary input signals connected to the Disturbance
input and binary signals connected to the function
Report function that have changed status during a
block i.e. maximum 40 analog and 96 binary sig-
disturbance.
nals.
actions) and in the long term (e.g. Functional Event function block. The event function block is
Analysis). used for LON and SPA communication.
The event recorder logs all selected binary input Analog and double indication values are also
signals connected to the Disturbance Report func- transferred through the event block.
tion. Each recording can contain up to 150
time-tagged events. Fault locator (RFLO)
The accurate fault locator is an essential compo-
The event recorder information is available for the nent to minimize the outages after a persistent fault
disturbances locally in the IED. and/or to pin-point a weak spot on the line.
The event recording information is an integrated The built-in fault locator is an impedance measur-
part of the disturbance record (Comtrade file). ing function giving the distance to the fault in per-
cent, km or miles. The main advantage is the high
Trip value recorder (RDRE) accuracy achieved by compensating for load cur-
Information about the pre-fault and fault values for rent and for the mutual zero sequence effect on
currents and voltages are vital for the disturbance double circuit lines.
evaluation.
The compensation includes setting of the remote
The Trip value recorder calculates the values of all and local sources and calculation of the distribu-
selected analog input signals connected to the Dis- tion of fault currents from each side. This distribu-
turbance report function. The result is magnitude tion of fault current, together with recorded load
and phase angle before and during the fault for (pre-fault) currents, is used to exactly calculate the
each analog input signal. fault position. The fault can be recalculated with
new source data at the actual fault to further
The trip value recorder information is available for increase the accuracy.
the disturbances locally in the IED.
Specially on heavily loaded long lines (where the
The trip value recorder information is an inte- fault locator is most important) where the source
grated part of the disturbance record (Comtrade voltage angles can be up to 35-40 degrees apart the
file). accuracy can be still maintained with the advanced
compensation included in fault locator.
Disturbance recorder (RDRE)
The Disturbance Recorder function supplies fast, Measured value expander block
complete and reliable information about distur- The functions MMXU (SVR, CP and VP), MSQI
bances in the power system. It facilitates under- (CSQ and VSQ) and MVGGIO (MV) are provided
standing system behavior and related primary and with measurement supervision functionality. All
secondary equipment during and after a distur- measured values can be supervised with four setta-
bance. Recorded information is used for different ble limits, i.e. low-low limit, low limit, high limit
purposes in the short perspective (e.g. corrective and high-high limit. The measure value expander
actions) and long perspective (e.g. Functional block (XP) has been introduced to be able to trans-
Analysis). late the integer output signal from the measuring
The Disturbance Recorder acquires sampled data functions to 5 binary signals i.e. below low-low
from all selected analog input and binary signals limit, below low limit, normal, above high-high
connected to the Disturbance Report function limit or above high limit. The output signals can be
(maximum 40 analog and 96 binary signals). The used as conditions in the configurable logic.
binary signals are the same signals as available
under the event recorder function. Metering
The function is characterized by great flexibility
and is not dependent on the operation of protection Pulse counter logic (GGIO)
functions. It can record disturbances not detected The pulse counter logic function counts externally
by protection functions. generated binary pulses, for instance pulses com-
ing from an external energy meter, for calculation
The disturbance recorder information for the last of energy consumption values. The pulses are cap-
100 disturbances are saved in the IED and the tured by the binary input module and then read by
Local Human Machine Interface (LHMI) is used the pulse counter function. A scaled service value
to view the list of recordings. is available over the station bus. The special
Binary input module with enhanced pulse counting
Event function (EV) capabilities must be ordered to achieve this func-
When using a Substation Automation system with tionality.
LON or SPA communication, time-tagged events
can be sent at change or cyclically from the IED to Energy metering and demand handling
the station level. These events are created from any (MMTR)
available signal in the IED that is connected to the Outputs from measurement function (MMXU) can
be used to calculate energy. Active as well as reac-
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 17
be exchanged between two IEDs. For example, from another LDCM module. The IEEE/ANSI
this functionality can be used to send information C37.94 standard format is used.
such as status of primary switchgear apparatus or
intertripping signals to the remote IED. An IED A module with built-in galvanic X.21 converter
can communicate with up to 4 remote IEDs. which e.g. can be connected to modems for pilot
wires is also available.
Line data communication module, short,
medium and long range (LDCM) Galvanic interface G.703 resp G.703E1
The line data communication module (LDCM) is The external galvanic data communication con-
used for communication between the IEDs situated verter G.703/G.703E1 makes an optical-to-gal-
at distances <150 km or from the IED to optical to vanic conversion for connection to a multiplexer.
electrical converter with G.703 or G.703E1 inter- These units are designed for 64 kbit/s resp 2Mbit/s
face located on a distances <3 km away. The operation. The converter is delivered with 19” rack
LDCM module sends and receives data, to and mounting accessories.
Binary output modules (BOM) Alternative cards for Long range (1550 nm single
The binary output module has 24 independent out- mode), Medium range (1310 nm single mode) and
put relays and is used for trip output or any signal- Short range (900 nm multi mode) are available.
ling purpose.
Galvanic RS485 serial communication
Static binary output module (SOM) module
The static binary output module has six fast static The galvanic RS485 serial communication module
outputs and six change over output relays for use is used as an alternative for DNP3.0 communica-
in applications with high speed requirements. tion.
transformers. The module has twelve inputs in dif- High impedance resistor unit
ferent combinations of currents and voltage inputs. The high impedance resistor unit, with resistors for
pick-up value setting and a voltage dependent
Alternative connectors of Ring lug or Compres- resistor, is available in a single phase unit and a
sion type can be ordered. three phase unit. Both are mounted on a 1/1 19
inch apparatus plate with compression type term-
nals.
B C
D
xx05000003.vsd
xx05000004.vsd
Figure 12: 1/2 x 19” case with rear cover Figure 13: Side-by-side mounting
Case size A B C D E F
6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7
6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0
6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3
(mm)
Connection Table 1: Designations for 1/2 x 19” casing with 1 TRM slot
diagrams
Module Rear Positions
PSM X11
BIM, BOM, SOM or IOM X31 and X32 etc. to X51 and X52
BIM, BOM, SOM, IOM or GSM X51, X52
SLM X301:A, B, C, D
IRIG-B 1) X302
OEM X311:A, B, C, D
RS485 or LDCM 2) 3) X312
LDCM 2) X313
TRM X401
Figure 20: Binary output module (BOM). Output contacts named XA corresponds to rear position X31,
X41, etc. and output contacts named XB to rear position X32, X42, etc.
Figure 22: Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41,
etc. and output contacts named XB to rear position X32, X42, etc.
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 27
Reference value:
The specified value of an influencing factor to which are referred the characteristics of the equipment.
Nominal range:
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements.
Operative range:
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform
its intended functions according to the specified requirements.
Auxiliary DC voltage
Table 7: PSM - Power supply module
Quantity Rated value Nominal range
Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20%
EL = (90 - 250) V EL ± 20%
Power consumption 50 W typically -
Auxiliary DC power in-rush < 5 A during 0.1 s -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 28
Table 9: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/40 V RL ± 20%
48/60 V RL ± 20%
110/125 V RL ± 20%
220/250 V RL ± 20%
Power consumption
24/40 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
Table 11: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load with
L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 29
Function or quantity Trip and signal relays Fast signal relays (parallel reed relay)
Breaking capacity for AC, cos ϕ > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 48 V/1 A 48 V/1 A
ms 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Table 12: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Making capacity at inductive load with L/R>10 ms
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos ϕ>0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Influencing factors
Table 13: Temperature and humidity influence
Parameter Reference value Nominal range Influence
Ambient temperature, oper- +20 °C -10 °C to +55 °C 0.02% /°C
ate value
Relative humidity 10%-90% 10%-90% -
Operative range 0%-95%
Storage temperature -40 °C to +70 °C - -
Differential protection
Table 21: High impedance differential protection (PDIF, 87)
Function Range or value Accuracy
Operate voltage (20-400) V ± 1.0% of Ur for U < Ur
± 1.0% of U for U > Ur
Reset ratio >95% -
Maximum continuous voltage U>TripPickup2/series resistor ≤200 W -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 31
Impedance protection
Table 23: Distance measuring zone, Quad (PDIS, 21)
Function Range or value Accuracy
Number of zones 3 with selectable direction -
Minimum operate current (10-30)% of Ibase -
Positive sequence reactance (0.50-3000.00) Ω/phase ± 2.0% static accuracy
Positive sequence resistance (0.10-1000.00) Ω/phase ± 2.0 degrees static angular accuracy
Zero sequence reactance (0.50-9000.00) Ω/phase Conditions:
Zero sequence resistance (0.50-3000.00) Ω/phase Voltage range: (0.1-1.1) x Ur
Fault resistance, Ph-E (1.00-9000.00) Ω/loop Current range: (0.5-30) x Ir
Fault resistance, Ph-Ph (1.00-3000.00) Ω/loop Angle: at 0 degrees and 85 degrees
Dynamic overreach <5% at 85 degrees measured with -
CCVT’s and 0.5<SIR<30
Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -
Table 24: Phase selection with load encroachment, quadrilateral characteristic (PDIS, 21)
Function Range or value Accuracy
Minimum operate current (5-30)% of Ibase ± 1.0% of Ir
Reactive reach, positive sequence, for- (0.50–3000.00) Ω/phase ± 2.0% static accuracy
ward and reverse ± 2.0 degrees static angular accuracy
Resistive reach, positive sequence (0.10–1000.00) Ω/phase
Conditions:
Reactive reach, zero sequence, forward (0.50–9000.00) Ω/phase
Voltage range: (0.1-1.1) x Ur
and reverse
Current range: (0.5-30) x Ir
Resistive reach, zero sequence (0.50–3000.00) Ω/phase
Fault resistance, phase-earth faults, for- (1.00–9000.00) Ω/loop Angle: at 0 degrees and 85 degrees
ward and reverse
Fault resistance, phase-phase faults, (0.50–3000.00) Ω/loop
forward and reverse
Load encroachment criteria:
Load resistance, forward and reverse (1.00–3000.00) Ω/phase
Safety load impedance angle (5-70) degrees
Reset ratio 105% typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 32
Table 27: Automatic switch onto fault logic, voltage and current based (PSOF)
Parameter Range or value Accuracy
Operate voltage, detection of dead line (1–100)% of Ubase ± 1.0% of Ur
Operate current, detection of dead line (1–100)% of Ibase ± 1.0% of Ir
Delay following dead line detection input before SOTF function (0.000–60.000) s ± 0.5% ± 10 ms
is automatically enabled
Time period after circuit breaker closure in which SOTF func- (0.000–60.000) s ± 0.5% ± 10 ms
tion is active
Current protection
Table 28: Instantaneous phase overcurrent protection (PIOC, 50)
Function Range or value Accuracy
Operate current (1-2500)% of lbase ± 1.0% of Ir at I ≤ Ir
± 1.0% of I at I > Ir
Reset ratio > 95% -
Operate time 25 ms typically at 0 to 2 x Iset -
Reset time 25 ms typically at 2 to 0 x Iset -
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time 10 ms typically at 0 to 10 x Iset -
Reset time 35 ms typically at 10 to 0 x Iset -
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at τ = 100 ms -
Table 32: Sensitive directional residual overcurrent and power protection (PSDE, 67N)
Function Range or value Accuracy
Operate level for 3I0 cosϕ (0.25-200.00)% of lbase ± 1.0% of Ir at I ≤ Ir
directional residual overcurrent ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ± 1.0 mA
(10-50) mA ± 0.5 mA
Operate level for 3I03U0 cosϕ direc- (0.25-200.00)% of Sbase ± 1.0% of Sr at S ≤ Sr
tional residual power ± 1.0% of S at S > Sr
At low setting:
(0.25-5.00)% of Sbase ± 10% of set value
Operate level for 3I0 and ϕ (0.25-200.00)% of Ibase ± 1.0% of Ir at ≤ Ir
residual overcurrent ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ± 1.0 mA
(10-50) mA ± 0.5 mA
Operate level for non directional over- (1.00-400.00)% of Ibase ± 1.0% of Ir at I ≤ Ir
current ± 1.0% of I at I > Ir
At low setting:
(10-50) mA ± 1.0 mA
Operate level for non directional resid- (1.00-200.00)% of Ubase ± 0.5% of Ur at U ≤ Ur
ual overvoltage ± 0.5% of U at U > Ur
Residual release current for all direc- (0.25-200.00)% of Ibase ± 1.0% of Ir at I ≤ Ir
tional modes ± 1.0% of I at I > Ir
At low setting:
(2.5-10) mA ± 1.0 mA
(10-50) mA ± 0.5 mA
Residual release voltage for all direc- (0.01-200.00)% of Ubase ± 0.5% of Ur at U ≤ Ur
tional modes ± 0.5% of U at > Ur
Reset ratio > 95% -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Inverse characteristics, see table 92 19 curve types See table 92 and table 93
and table 93
Relay characteristic angle RCA (-179 to 180) degrees ± 2.0 degrees
Relay open angle ROA (0-90) degrees ± 2.0 degrees
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 34
Table 33: Thermal overload protection, one time constant (PTTR, 26)
Function Range or value Accuracy
Reference current (0-400)% of Ibase ± 1.0% of Ir
Start temperature reference (0-400)°C ± 1.0°C
Operate time: Ip = load current before overload occurs IEC 60255-8, class 5 + 200 ms
Time constant τ = (0–1000) minutes
⎛ I 2 − I p2 ⎞
t = τ ⋅ ln ⎜ 2 ⎟
⎜ I − Ib 2 ⎟
⎝ ⎠
I = Imeasured
Alarm temperature (0-200)°C ± 2.0% of heat content trip
Trip temperature (0-400)°C ± 2.0% of heat content trip
Reset level temperature (0-400)°C ± 2.0% of heat content trip
Voltage protection
Table 40: Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Operate voltage, low and high step (1–100)% of Ubase ± 1.0% of Ur
Absolute hysteresis (0–100)% of Ubase ± 1.0% of Ur
Internal blocking level, low and high (1–100)% of Ubase ± 1.0% of Ur
step
Inverse time characteristics for low - See table 94
and high step, see table 94
Definite time delays (0.000-60.000) s ± 0.5% ±10 ms
Minimum operate time, inverse char- (0.000–60.000) s ± 0.5% ± 10 ms
acteristics
Operate time, start function 25 ms typically at 2 to 0 x Uset -
Reset time, start function 25 ms typically at 0 to 2 x Uset -
Critical impulse time 10 ms typically at 2 to 0 x Uset -
Impulse margin time 15 ms typically -
(0.18 ⋅ k )
IEEE : t =
( M − 1) 2
where M = relative (V/Hz) = (E/f)/(Ur/fr)
Minimum time delay for inverse function (0.000–60.000) s ± 0.5% ± 10 ms
Maximum time delay for inverse func- (0.00–9000.00) s ± 0.5% ± 10 ms
tion
Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms
Frequency protection
Table 46: Underfrequency protection (PTUF, 81)
Function Range or value Accuracy
Operate value, start function (35.00-75.00) Hz ± 2.0 mHz
Operate time, start function 100 ms typically -
Reset time, start function 100 ms typically -
Operate time, definite time function (0.000-60.000)s ± 0.5% + 10 ms
Reset time, definite time function (0.000-60.000)s ± 0.5% + 10 ms
Voltage dependent time delay Settings: Class 5 + 200 ms
UNom=(50-150)% of Ubase
Exponent UMin=(50-150)% of Ubase
⎡ U − UMin ⎤
t=⎢ ⋅ ( tMax − tMin ) + tMin
⎣ UNom − UMin ⎥⎦
Exponent=0.0-5.0
tMax=(0.000-60.000)s
U=Umeasured
tMin=(0.000-60.000)s
Multipurpose protection
Table 49: General current and voltage protection (GAPC)
Function Range or value Accuracy
Measuring current input phase1, phase2, phase3, PosSeq, -
NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base current (1 - 99999) A -
Measuring voltage input phase1, phase2, phase3, PosSeq, -
-NegSeq, -3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2,
phase2-phase3, phase3-phase1,
MaxPh-Ph, MinPh-Ph, Unbalan-
cePh-Ph
Base voltage (0.05 - 2000.00) kV -
Start overcurrent, step 1 and 2 (2 - 5000)% of Ibase ± 1.0% of Ir for I<Ir
± 1.0% of I for I>Ir
Start undercurrent, step 1 and 2 (2 - 150)% of Ibase ± 1.0% of Ir for I<Ir
± 1.0% of I for I>Ir
Definite time delay (0.00 - 6000.00) s ± 0.5% ± 10 ms
Operate time start overcurrent 25 ms typically at 0 to 2 x Iset -
Reset time start overcurrent 25 ms typically at 2 to 0 x Iset -
Operate time start undercurrent 25 ms typically at 2 to 0 x Iset -
Reset time start undercurrent 25 ms typically at 0 to 2 x Iset -
See table 92 and table 93 Parameter ranges for customer See table 92 and table 93
defined characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory (0.0 - 5.0)% of Ubase ± 1.0% of Ur
takes over
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of Ubase ± 1.0% of Ur for U<Ur
± 1.0% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of Ubase ± 1.0% of Ur for U<Ur
± 1.0% of U for U>Ur
Operate time, start overvoltage 25 ms typically at 0 to 2 x Uset -
Reset time, start overvoltage 25 ms typically at 2 to 0 x Uset -
Operate time start undervoltage 25 ms typically 2 to 0 x Uset -
Reset time start undervoltage 25 ms typically at 0 to 2 x Uset -
High and low voltage limit, voltage (1.0 - 200.0)% of Ubase ± 1.0% of Ur for U<Ur
dependent operation ± 1.0% of U for U>Ur
Directional function Settable: NonDir, forward and reverse -
Relay characteristic angle (-180 to +180) degrees ± 2.0 degrees
Relay operate angle (1 to 90) degrees ± 2.0 degrees
Reset ratio, overcurrent > 95% -
Reset ratio, undercurrent < 105% -
Reset ratio, overvoltage > 95% -
Reset ratio, undervoltage < 105% -
Overcurrent:
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Undercurrent:
Critical impulse time 10 ms typically at 2 to 0 x Iset -
Impulse margin time 15 ms typically -
Overvoltage:
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 38
Control
Table 52: Synchronizing, synchrocheck check and energizing check (RSYN, 25)
Function Range or value Accuracy
Phase shift, ϕline - ϕbus (-180 to 180) degrees -
Voltage ratio, Ubus/Uline (0.20-5.00)% of Ubase -
Voltage high limit for synchrocheck (50.0-120.0)% of Ubase ± 1.0% of Ur at U ≤ Ur
± 1.0% of U at U >Ur
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus (0.003-1.000) Hz ± 2.0 mHz
and line
Phase angle difference limit between (5.0-90.0) degrees ± 2.0 degrees
bus and line
Voltage difference limit between bus (2.0-50.0)% of Ubase ± 1.0% of Ur
and line
Time delay output for synchrocheck (0.000-60.000) s ± 0.5% ± 10 ms
Voltage high limit for energizing check (50.0-120.0)% of Ubase ± 1.0% of Ur at U ≤ Ur
± 1.0% of U at U >Ur
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of Ubase ± 1.0% of Ur
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (80.0-140.0)% of Ubase ± 1.0% of Ur at U ≤ Ur
± 1.0% of U at U >Ur
Time delay for energizing check (0.000-60.000) s ± 0.5% ± 10 ms
Operate time for synchrocheck function 160 ms typically -
Operate time for energizing function 80 ms typically -
Scheme communication
Table 54: Scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking communica- (0.000-60.000) s ± 0.5% ± 10 ms
tion scheme
Minimum duration of a carrier send signal (0.000-60.000) s ± 0.5% ± 10 ms
Security timer for loss of carrier guard (0.000-60.000) s ± 0.5% ± 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart
Table 55: Phase segregated scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking communica- (0.000-60.000) s ± 0.5% ± 10 ms
tion scheme
Minimum duration of a carrier send signal (0.000-60.000) s ± 0.5% ± 10 ms
Security timer for loss of carrier guard (0.000-60.000) s ± 0.5% ± 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart
Table 56: Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral voltage (10-90)% of Ubase ± 1.0% of Ur
Detection level phase to phase voltage (10-90)% of Ubase ± 1.0% of Ur
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end infeed (0.000-60.000) s ± 0.5% ± 10 ms
logic
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 40
Table 57: Scheme communication logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Communication scheme coordination (0.000-60.000) s ± 0.5% ± 10 ms
time
Scheme type Permissive UR -
Permissive OR
Blocking
Table 58: Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Operate voltage 3Uo for WEI trip (5-70)% of Ubase ± 1.0% of Ur
Reset ratio >95% -
Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end infeed (0.000–60.000) s ± 0.5% ± 10 ms
logic
Table 59: Current reversal and weak-end infeed logic for phase segregated communication (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral voltage (10-90)% of Ubase ± 1.0% of Ur
Detection level phase to phase voltage (10-90)% of Ubase ± 1.0% of Ur
Reset ratio <105% -
Operate time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Delay time for current reversal (0.000-60.000) s ± 0.5% ± 10 ms
Coordination time for weak-end infeed (0.000-60.000) s ± 0.5% ± 10 ms
logic
Logic
Table 60: Tripping logic (PTRC, 94)
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Monitoring
Table 62: Measurements (MMXU)
Function Range or value Accuracy
Frequency (0.95-1.05) × fr ± 2.0 mHz
Voltage (0.1-1.5) × Ur ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur
Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I ≤ Ir
± 0.5% of I at I > Ir
Active power, P 0.1 x Ur < U < 1.5 x Ur ± 1.0% of Sr at S ≤ Sr
0.2 x Ir < I < 4.0 x Ir ± 1.0% of S at S > Sr
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 41
Metering
Table 72: Pulse counter logic (GGIO)
Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of counter value (0–3600) s -
Station communication
Table 74: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Remote communication
Table 81: Line data communication modules (LDCM)
Characteristic Range or value
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Type of fibre Graded-index multi- Singlemode 8/125 μm Singlemode 8/125 μm
mode 62.5/125 μm or
50/125 μm
Wave length 820 nm 1310 nm 1550 nm
Optical budget 20 dB (typical distance 26 dB (typical distance
Graded-index multimode 62.5/125 μm, 11 dB (typical dis- 80 km *) 120 km *)
tance about 3 km *)
7 dB (typical distance
about 2 km *)
Graded-index multimode 50/125 μm
Hardware
IED
Table 82: Case
Material Steel sheet
Front plate Steel sheet profile with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)
Table 83: Water and dust protection level according to IEC 60529
Front IP40 (IP54 with sealing strip)
Rear, sides, top and bottom IP20
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 44
Connection system
Table 85: CT and VT circuit connectors
Connector type Rated voltage and current Maximum conductor area
Terminal blocks of feed through type 250 V AC, 20 A 4mm2
Terminal blocks suitable for ring lug ter- 250 V AC, 20 A 4 mm2
minals
Inverse characteristics
Table 92: Inverse time characteristics ANSI
Function Range or value Accuracy
Operate characteristic: k = 0.05-999 in steps of 0.01 -
unless otherwise stated
⎛ A ⎞
t = ⎜ P + B⎟ ⋅ k
⎜ ( I − 1) ⎟
⎝ ⎠
Reset characteristic:
tr
t = ⋅k
(I 2
−1 )
I = Imeasured/Iset
ANSI Extremely Inverse no 1 A=28.2, B=0.1217, P=2.0, ANSI/IEEE C37.112, class 5 + 30 ms
tr=29.1
ANSI Very inverse no 2 A=19.61, B=0.491, P=2.0,
tr=21.6
ANSI Normal Inverse no 3 A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse no 4 A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse no 6 A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse no 7 A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse no 8 k=(0.01-1.20) in steps of 0.01
A=0.086, B=0.185, P=0.02,
tr=4.6
⎛ A ⎞
t = ⎜ P ⎟⋅k
⎜ ( I − 1) ⎟
⎝ ⎠
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
IEC Normal Inverse no 9 A=0.14, P=0.02 IEC 60255-3, class 5 + 40 ms
IEC Very inverse no 10 A=13.5, P=1.0
IEC Inverse no 11 A=0.14, P=0.02
IEC Extremely inverse no 12 A=80.0, P=2.0
IEC Short-time inverse no 13 A=0.05, P=0.04
IEC Long-time inverse no 14 A=120, P=1.0
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 46
I = Imeasured/Iset
RI inverse characteristic no 18 k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms
1
t = ⋅k
0.236
0.339 −
I
I = Imeasured/Iset
Logarithmic inverse characteristic no 19 k=(0.05-1.10) in steps of 0.01 IEC 60255-3, class 5 + 40 ms
⎛
t = 5.8 − ⎜ 1.35 ⋅ In
I ⎞
⎟
⎝ k ⎠
I = Imeasured/Iset
Table 94: Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
⎛ U < −U ⎞
⎜ ⎟
⎝ U< ⎠
U< = Uset
U = UVmeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k ⋅ 480
t = + 0.055
⎛ 32 ⋅ U < −U − 0.5 ⎞
2.0
⎜ ⎟
⎝ U < ⎠
U< = Uset
U = Umeasured
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
⎡ ⎤ B = (0.50-100.00) in steps of
⎢ k⋅A
⎥ 0.01
t =⎢ ⎥+D C = (0.0-1.0) in steps of 0.1
⎢ ⎛ U < −U ⎞
P
⎥
⎢⎜B ⋅ −C⎟ ⎥ D = (0.000-60.000) in steps of
⎣⎝ U < ⎠ ⎦ 0.001
U< = Uset P = (0.000-3.000) in steps of
U = Umeasured 0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 47
Table 95: Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
⎛U −U >⎞
⎜ ⎟
⎝ U> ⎠
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k ⋅ 480
t =
⎛ 32 ⋅ U − U > − 0.5 ⎞
2.0
⎜ ⎟ − 0.035
⎝ U > ⎠
Type C curve: k = (0.05-1.10) in steps of 0.01
k ⋅ 480
t =
⎛ 32 ⋅ U − U > − 0.5 ⎞
3.0
⎜ ⎟ − 0.035
⎝ U > ⎠
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
k⋅A
t = +D B = (0.50-100.00) in steps of
⎛B ⋅ U − U > ⎞
P 0.01
⎜ −C⎟ C = (0.0-1.0) in steps of 0.1
⎝ U > ⎠
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 48
Table 96: Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 Class 5 +40 ms
k
t =
⎛U −U >⎞
⎜ ⎟
⎝ U> ⎠
U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01
k ⋅ 480
t =
⎛ 32 ⋅ U − U > − 0.5 ⎞
2.0
⎜ ⎟ − 0.035
⎝ U > ⎠
Type C curve: k = (0.05-1.10) in steps of 0.01
k ⋅ 480
t =
⎛ 32 ⋅ U − U > − 0.5 ⎞
3.0
⎜ ⎟ − 0.035
⎝ U > ⎠
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of
0.001
k⋅A
t = +D B = (0.50-100.00) in steps of
⎛B ⋅ U − U > ⎞
P 0.01
⎜ −C⎟ C = (0.0-1.0) in steps of 0.1
⎝ U > ⎠
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 49
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the function matrix for included software functions given in each software option package.
Please observe that the character length of the software option section varies depending on the included options.
Enter option codes in the shaded spaces to complete the ordering number. To obtain the complete ordering code, please combined code from sheet 1 and sheet 2, as given in the example
below. 1 BIM and 1 BOM is basic. Order futher I/O as required.
Sheet 1 Sheet 2
RED 670* - - - - - - -
Binary input and output, mA and time synchronizating boards. Note! Basic 1 BIM and 1 BOM included.
Slot position (rear view) Note! Max 3 positions in 1/2 rack, 5 in 3/4 - - -
X101
X121
X131
X111
X31
X41
X51
X61
X71
X81
X91
rack with 2 TRM and 11 in 1/1 rack with 2
TRM (=grey fields)
Available slots in 1/2 Case with 1 TRM
Available slots in 3/4 Case with 2 TRM slots
Available slots in 1/1 Case with 2 TRM
No board in this slot X X X X X X X X X
Binary output module 24 output relays (BOM) Note! Maximum 4 (BOM+SOM+MIM) A A A A A A A A A A
boards
BIM 16 inputs, 24-30 VDC B B B B B B B B B B
BIM 16 inputs, 48-60 VDC C C C C C C C C C C
BIM 16 inputs, 110-125 VDC D D D D D D D D D D
BIM 16 inputs, 220-250 VDC E E E E E E E E E E
BIMp 16 inputs, 24-30 VDC for pulse counting F F F F F F F F F
BIMp 16 inputs, 48-60 VDC for pulse counting G G G G G G G G G
BIMp 16 inputs, 110-125 VDC for pulse counting H H H H H H H H H
BIMp 16 inputs, 220-250 VDC for pulse counting K K K K K K K K K
IOM 8 inputs, 10+2 output, 24-30 VDC L L L L L L L L L
IOM 8 inputs, 10+2 output, 48-60 VDC M M M M M M M M M
IOM 8 inputs, 10+2 output, 110-125 VDC N N N N N N N N N
IOM 8 inputs, 10+2 output, 220-250 VDC P P P P P P P P P
IOM with MOV 8 inputs, 10+2 output, 24-30 VDC U U U U U U U U U
IOM with MOV 8 inputs, 10+2 output, 48-60 VDC V V V V V V V V V
IOM with MOV 8 inputs, 10+2 output, 110-125 VDC W W W W W W W W W
IOM with MOV 8 inputs, 10+2 output, 220-250 VDC Y Y Y Y Y Y Y Y Y
mA input module MIM, 6 channels Note! Max 4 (BOM+SOM+MIM) board in R R R R R R R R
1/1 case. Max 1 MIM + 3 BOM in 3/4 case.
No MIM board in 1/2 case
GPS time synchronization module (GSM) (in last slot) S S S
SOM Static output module Note! Max 4 (BOM+SOM+MIM) T T T T T T T T T
Remote end communication, DNP serial comm. and Time synchronization modules
X312
X313
X302
X303
X322
X323
Available slots in 1/2 case with 1 TRM Note: 1 LDCM in A31 and A32, Max 1 LDCM
Available slots in 3/4 & 1/1 case with 2 TRM slots Note: 1 LDCM in B31 and B32, Max 4 LDCM
No remote communication board included X X X X X
Optical short range LDCM A A A A A A
Optical medium range LDCM, 1310 nm B B B B B B
Optical long range LDCM, 1550 nm C C C C C C
Galvanic X21 line data communication module E E E E E E
IRIG-B Time synchronization module F
Galvanic RS485 communication module G
Serial communication unit for station communication
X301
X311
Example:
RED 670*1.1-A31-A03B01C04F01-X0-A-A-B-A-A6X0-DAS-AA-XD
Line differential protection IED RED 670 Buyer's Guide
Pre-configured
1MRK 505 188-BEN
Revision: A, Page 51
Accessories
GPS antenna and mounting details
GPS antenna, including mounting kits
1 2 3 4
External interface converter from C37.94 to G703.E1 Quantity: 1MRK 002 245-BA
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19”
Combiflex
Key switch for lock-out of settings via LCD-HMI
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference manual, Installa-
tion and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label tem-
plate is always included for each IED.
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
Documents related to RED 670 Identity number
Operator’s manual 1MRK 505 184-UEN
Installation and comminssioning manual 1MRK 505 185-UEN
Technical reference manual 1MRK 505 183-UEN
Application manual 1MRK 505 186-UEN
Buyer’s guide 1MRK 505 188-BEN
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbars 1MRK 004 500-82
Configuration diagram B, Single breakers with single or double busbars 1MRK 004 500-83
Configuration diagram C, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-84
Configuration diagram D, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-85
Setting example 1, 230 kV Short cable line with 1 1/2 CB arr. 1MRK 505 175-WEN
Manufacturer
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation