Industrial: For Bay Control Solutions BCS 590 / BCS 593
Industrial: For Bay Control Solutions BCS 590 / BCS 593
............. ...
..............
. ......... .. ...........
... . . ......
...... .. .......
The essential first improvement step
2 ABB ABB 3
Bay control solution concept for BCS590 and BCS593 Modern and conventional control versions
of BCS590 and BCS593
The bay Control Solution Concept is a For both of the applications, two control Single busbar Double busbar
GIS >170 kV GIS >170 kV
standardized comprehensive solution for control cubicle executions are defined:
cubicles for all the types of switchgear that can ■ Modern control Modern BCS590 BCS593
occur in transmission and subtransmission and ■ Conventional control
Conventional BCS590 BCS593
busbar configurations.
Features
Common Features Specific features The modern control cubicle BCS590 modern control BCS593 modern control
is equipped with a microprocessor based Bay
BCS590 and BCS593 are two versions of ■ The BCS590 is designed for a
Controller REC316*4 and a BCM800 mimic.
the Bay Control Solution concept comprising single busbar configuration
The performance characteristics of this solution are:
control cubicles for high voltage gas isolated
■ The BCS593 is designed for a ■ high functionality
switchgear (GIS) for voltage levels higher than ■ simple integration in the ABB SA system via the
double busbar configuration.
170kV. LON bus
■ The main functional differences are in the ■ maximum reliability and availability.
The layout of the control cubicles and the
complexity of the interlocking logic and in
configuration of the devices as well as the main
the quantity of the high-voltage switchgear.
functionality are identical for both solutions.
The conventional control cubicle BCS590 conventional control BCS593 conventional control
mainly differs from the modern by the replacement
of the plant,
■ local operation from the BCM800 mimic,
4 ABB ABB 5
Technical concept of the modern control Technical concept of the conventional control
The diagram shows the structure of the control In LOCAL Mimic HMI mode the BCM800 The diagram shows the structure of the
cubicle in the modern control. The data mimic is used as an input device for the conventional control. The main difference to the
exchange between the components is shown REC316*4. Operator actions are first transmitted modern control is the lack of the REC316*4 bay
diagrammatically. The arrows represent the data to the REC316*4, and are checked there for controller. In place of the REC316*4 a parallel
flow. The beginning and end of an arrow plausibility and for interlocking conditions. The terminal block is available that is used for the
represent an interface. Interfaces can be logical control command then goes from the REC316*4 remote connection to an RTU or station mimic.
or terminal blocks. The "Primary Interface via BCM800 to the Primary Interface Solution. The parallel interface uses exactly the same
Solution" also comprises electromechanical The Primary Interface Solution comprises the terminals on the BCM800 as the REC316*4 bay
relays and the marshalling of the cables. The output contactors for the control of the high controller. The switching dialogs correspond to
concept is very flexibly and modularly designed voltage switching devices. the dialogs of the EMERGENCY Mimic HMI
and permits customer specific adaptations to be mode for the modern control. Because of the
integrated very easily. In EMERGENCY Mimic HMI mode, the lack of the REC316*4 bay controller, all the
switching commands go directly to the Primary functions, with the exception of the alarm
Interface Solution. The REC316*4 is bypassed. handling and the Synchrocheck function are
The operator's comfort is therefore limited. conventionally implemented in the primary
In this mode, the interlocking logic is made interface solution block.
conventionally in the Primary Interface Solution
with cabling.
6 ABB ABB 7
Function packaging for BCS590 and BCS593 The modern control version for BCS590 and BCS593
functionality, solutions can be made that fulfil ■ LOCAL Mimic HMI Mode
the highest requirements. In LOCAL Mode the BCM800 mimic serves as the
input device for the REC313*4 controller. Inputs
are monitored by the REC316*4 controller and
checked for plausibility. Incorrect operation that
could lead to damage to the primary elements is Mimic BCM800
prevented both in own bay itself and also between
different bays by an interlocking and blocking
logic, that is implemented in the REC316*4.
RIO580 (option)
To extend the number of the inputs and outputs
of the REC316*4 controller, a separate RIO580
device is used. This can be equipped with both
digital or analog inputs and outputs. This
concept enables any number of inputs and RIO580
8 ABB ABB 9
The modern control version for BCS590 and BCS593
■ High functionality
Touchscreen integration concept
The modern REC316*4 controller is provided with
a comprehensive library of functions. The
synchrocheck, the programming possibilities, and
various protection functions offer special
potential for applications.
Touchscreen
10 ABB ABB 11
The conventional control version for BCS 590 and BCS 593 Functional description of the base package
BCM800 Mimic Terminal block for the protection recorded with mechanical counters. A total of 6
The BCM800 mimic is the key component of In the control cubicle, there is a terminal block counters are available. For the modern control,
the conventional control. In the basic execution for the connection of Trip Main1, Trip Main2, the switching operations and pump starts are
up to 7 high voltage switching devices can be and Autoreclosure (AR). This simplifies the additionally acquired in the REC316*4 controller
monitored and controlled. As an option, up to protection cubicle. and are transmitted via the LON interface.
8 high voltage switching devices can be
monitored and controlled. Operations counters for circuit Pump control
breakers and pumps Automatic control of the hydraulic pump or
Characteristics The single or three pole switching operations of compressor for maintaining the necessary
■ Local control
the power switches and the start-up of the operating pressure.
is identical with the EMERGENCY Mimic mode
pump in the case of a hydraulic drive are
of the modern controls.
■ Remote control
■ The functionality
Benefits of the BCS590 and BCS593 concept Pump control Yes Yes
Anti-pumping Yes Yes
Pump start cascading Yes Yes
■ Proven packages ■ Seamless integration in the ABB station controls
Pump supervision Yes Yes
there are proven packages that can be assembled (modern control only)
Operating pressure supervision Yes Yes
to form a solution based on modular principles. and in the ABB advanced power system
Pole discrepancy monitoring and trip function Yes Yes
This reduces the commissioning time to a minimum. management higher level systems enable unlimited
Alarm annunciation Yes Yes
access to process data and its processing into
■ Clear scope of supply
Interlocking and blocking Yes Yes
information that is of vital significance for the
already at the offer stage, the exact scope of the Mechanics RESP 97 series Yes Yes
efficient operation of a power network.
functionality is defined and documented. Measurand display Yes Yes
The bay control solutions (BCS) are integrated via
This saves the customer time and resoures for LOCAL mimic HMI mode Yes No
a LON BUS in one of the ABB SAS systems from
project management. EMERGENCY mimic HMI mode Yes Yes*
SAS510 to SAS570.
SA integration Yes No**.
■ Standardized interfaces Interlocking and blocking display Yes No
■ Modifications are possible later
enable the integration of application specific Synchrocheck Yes No***
(modern control only)
extensions without the need to make corresponding Event list Yes No
if for operational reasons, e.g. a manned station
modifications to the standard packages. Breaker position indication per phase Yes No
is to be converted to a remote controlled station,
this does not require any modifications to the Transmission of measurands
■ Scalable solutions from conventional to modern
control cubicle configuration. to the higher station level (SA system) Yes No
support a very wide range of applications.
A later upgrade of the functionality is very easily
■ High quality standards *) The local mimic HMI of the conventional control is the same as the EMERGENY mimic HMI mode
possible. In this way, a conventional control can be
every component used such as auxiliary relays of the modern control.
upgraded to a modern one later.
and intelligent electronic devices IEDs are proved **) A parallel terminal interface is available.
and fulfil the high ABB quality requirements. ***) The synchrocheck is implemented with a synchrocheck relay. This is available as an add-on package.
12 ABB ABB 13
Functional description of the base package
operating mechanism. It is a basic safety rule, For this, both the positions of the high-voltage (other colors are available by selecting the
that a CB operating mechanism must have switching devices in its own bay (bay customized package)
sufficient operating pressure for opening if it interlocking) and also the positions of the other
was accidentally closed onto a fault. In the case bays (interbay interlocking) are taken into BCS 593 modern bay control solution
of low pressure, first the AUTO-RECLOSURE account. An example of interbay interlocking is:
operation is blocked, and then the closing a busbar disconnector must not be closed if the
operation and finally the opening operation are corresponding busbar earthing switch is closed.
blocked. In order that the interlocking is also provided in
emergency operation if the Bay Controller has
failed, the blocking logic and the interlocking
logic are made conventionally with relay logic
and cabling.
14 ABB ABB 15
Functional description of the base package Functional description of the add-on packages
Event list
The REC316*4 maintains an event list where all List of the add-on packages for BCS590 and BCS593
the events are stored with millisecond accuracy.
The event list can be presented on the
Name Available for the modern Available for the conventional
REC316*4 display. control control
Plug connection Yes Yes
Breaker position indication perphase SF6 alarm Yes Yes
The REC316*4 receives the circuit breaker Tap changer Yes Yes*
position signals separately for each phase. Not integrated in the SA system
Touchscreen Yes No
Changes of position are stored with millisecond
Comfort Yes No
accuracy in the internal event list and are also Protection and recording Yes No
sent to the LON interface. They are therefore
available to the higher level SA applications.
16 ABB ABB 17
Functional description of the add-on packages
Tap changer Functions: Protection and Recording Scope of the Protection Functions
The tap changer package is designed for ■ Regulation of tap-changer transformers This package uses the different possibilities of ■ Definite time over/ undervoltage protection
■ Integrated statistical function of all tap-changer ■ High set over/ undervoltage protection
transformer regulation. The kernel of this the REC316*4 bay controller. This function
TM movements (total number of changes, number of ■ Definite time overcurrent protection with inrush
package is the REGSys tapchanger controller package comprises various protection and
changes under load / per tap) detection
that is equipped with a LON interface and that ■ Recording of voltage and visualization via the
monitoring functions. ■ High set overcurrent protection
can be easily integrated in the higher level SA regulator display or PC ■ Inverse time overcurrent protection
System with the modern control. ■ Dynamic transformer group assignment according ■ Thermal overload protection
■ 1 bus coupler, 2 section couplers library of the RE.316 is available for customer
■ Current inputs (-20mA...0…+20mA) for specific solutions
transformer monitoring (J, P, ...) ■ Four independent, user-selectable setting groups
■ Current output (-20mA...0…+20mA) for set point ■ Multi-activation facility for the available functions
Comfort Functions:
This package comprises a complete range of ■ 8 BCM800 mimic LEDs
Position indication
and alarm LEDs
Earthing Switch.
In the Base Package the position of the fast
earthing switch is acquired for each fast earthing
switch. With this option the position signal is
acquired for each pole and is made available to
the SA interface (LON interface).
18 ABB ABB 19