Professional Documents
Culture Documents
1.1.1 Technical Requirements & Specifications (Foundation Field Bus Based)
1.1.1 Technical Requirements & Specifications (Foundation Field Bus Based)
Technical Specifications
1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):
2 All Field bus transmitters shall satisfy, as minimum, the requirement of the Field bus
registration laboratory and in case of Field bus Foundation, shall have FF "tick mark".
All FF transmitters shall be registered with Field bus Foundation having passed the
interoperability tests as per ITK 4.01 as minimum.
2 Field bus electronic transmitters shall be Foundation Field bus H1 compliant bus
powered device having output as FF compliant digital communication and shall have
LAS (Link Active Scheduler) capability to ensure communication during primary LAS
failure (LAS backup).
4 Foundation Field bus transmitters shall comply with ISA S50.02 and IEC-61158
standard.
5 Foundation Field bus transmitter shall be compatible to use along with Foundation
Field bus accessories such as FISCO power supply, spur connector, short circuit
protectors, bus terminator etc. for Intrinsically safe H-1 field bus implemented using
Field bus Intrinsically Safe Concept (FISCO).
6 Foundation Field bus transmitters shall have intrinsically safe/ FISCO (Field bus
Intrinsic Safety Concept) approval from statutory body and shall be suitable for use in
Class I, Division 1, Group B, C, D, temperature class T3 hazardous area.
8 Field bus transmitter shall work with voltages of 9-32 VDC. Transmitters shall be
compatible with FISCO power supply module and should function satisfactorily with
such power supply modules.
10 Field bus transmitter shall have standard function blocks including AI (Analog Input) as
minimum.
11 DD and CFF files for field bus transmitter according to foundation field bus FF-524 and
FF-103 respectively shall be provided.
Project: Neelam Redevelopment Project
Technical Specifications
1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):
13 Transmitter shall run complete diagnostic routine. In the event of detection of failure,
the output shall be driven to predefined value.
14 Transmitter shall be configured to store its tag number, calibration range & other
specifications / data which will be useful for history record purpose.
17 Transmitter shall be provided with external zero adjustment and shall have integral
vent/drain.
20 The material of elastomers used in instruments shall be suitable for the specified
service. Use of asbestos or asbestos-bearing materials shall not be used.
21 For all instruments, all materials of construction shall meet the requirements specified
in nace mr-01-75 latest edition wherever applicable.
22 Transmitter’s meter body and electronics housing material shall be SS-316 and it shall
resist shock, vibration, corrosion and moisture.
Technical Specifications
1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):
37 Integral, Intrinsically Safe Output Required, LCD, 4 1/2 digit display in engg. Units
Meter selectable by user and diagnostics message for
local troubleshooting.
Project: Neelam Redevelopment Project
Technical Specifications
1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):
1 Offered Transmitters shall be Foundation field bus type and shall be used at
unmanned.
2 All Field bus transmitters shall satisfy, as minimum, the requirement of the Field bus
registration laboratory and in case of Field bus Foundation, shall have FF "tick mark".
All FF transmitters shall be registered with Field bus Foundation having passed the
interoperability tests as per ITK 4.01 as minimum. Documentary evidence to this effect
shall have to be submitted.
3 Field bus electronic transmitters shall be Foundation Field bus H1 compliant bus
powered device having output as FF compliant digital communication and shall have
LAS (Link Active Scheduler) capability to ensure communication during primary LAS
failure (LAS backup).
4 Foundation Field bus transmitters shall comply to ISA S50.02 and IEC-61158
standard.
5 Foundation Field bus transmitter shall be compatible to use along with Foundation
Field bus accessories such as FISCO power supply, spur connector, short circuit
protectors, bus terminator etc. for Intrinsically safe H-1 field bus implemented using
Field bus Intrinsically Safe Concept (FISCO).
6 Foundation Field bus transmitters shall have intrinsically safe/FISCO (Field bus
Intrinsic Safety Concept) approval from statutory body and shall be suitable for use in
Class I, Division 1, Group D, temperature class T3 hazardous area.
8 Field bus transmitter shall work with voltages of 9-32 VDC. Transmitters shall be
compatible with FISCO power supply module and should function satisfactory with
such power supply module.
10 Field bus transmitter shall have standard function blocks including AI (Analog Input) as
minimum.
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1
11 DD and CFFf files for field bus transmitter according with foundation field bus FF-524
and FF-103 respectively shall be provided.
13 Transmitter shall run complete diagnostic routine. In the event of detection of failure,
the output shall be driven to predefined value.
14 Transmitter shall be configured to store its tag number, calibration range & other
specifications / data which will be useful for history record purpose.
18 The material of elastomers used in instruments shall be suitable for the specified
service. Use of asbestos or asbestos-bearing materials shall not be used.
19 Transmitter’s meter body and electronics housing material shall be SS-316 and it shall
resist shock, vibration, corrosion and moisture.
23 Accuracy
+ 0.25 Degree c or better
24 Stability Of Calibration 0.15% of URL for 36 months
35 Integral, Intrinsically Safe Output Required, LCD, 4 1/2 digit display in engg units
Meter selectable by user and diagnostics message for
local troubleshooting.
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1