Professional Documents
Culture Documents
Oil-Flooded Rotary Screw Air Compressor: Instruction Manual
Oil-Flooded Rotary Screw Air Compressor: Instruction Manual
Oil-Flooded Rotary Screw Air Compressor: Instruction Manual
OIL-FLOODED
ROTARY SCREW AIR COMPRESSOR
OSP-55VAN2
OSP-75VAN2
OSP-55M5AN2
OSP-75M5AN2
GRAPHIC DESCRIPTIONS:
WARNING
Never remove a protective device from the air compressor or
modify the air compressor.
It is imperative to install an earth leakage (ground) circuit breaker
on the power cable. This prevents a ground fault accident.
Never use the SCREW as a respiratory appliance by which a
person breathes the compressed air directly.
WARNING
The motor rotor contains a powerful magnetic field. This field can effect the operation of digital devices such
as watches, mobile phones etc. Assembly or handling of the rotor should not be attempted by personnel with
cardiac pacemakers, defibrillators or other implanted electronic medical device.
■ Model Code O S P - 55 V 5 A N2
Oil Flooded Type
Screw air compressor
Cooing method (A: air-cooled)
Packaged
Frequency (5: 50 Hz)
V: V type ( ),
M: fixed-speed type ( )
Nominal output (kW)
● For improvement of the product, contents in this manual are subject to change without notice. Please be forewarned.
● The product drawing in this manual shows OSP-55VAN2 as a typical example.
RESIDUAL RISKS
Refer to the table indicated in the next page for the detail of each number indicated in the drawing.
DANGER - DANGER -
Part C
Part B
I
RESIDUAL RISKS
Refer to the table indicated in the next page for the detail of each number indicated in the drawing.
DANGER - DANGER -
Part C
Part B
II
RESIDUAL RISKS
Residual risk list where the operators and maintenance personnel shall
be required protection measures. (Abbreviation: Residual risk list)
*1 The “Seriousness level of the harm” are classified into DANGER, WARNING and CAUTION by the
hazard seriousness levels.
・ DANGER: Indicates the presence of a hazard which will cause serious injury or death, if handled
improperly.
・ WARNING: Indicates the presence of a hazard which can cause serious injury or death, if handled
improperly.
・ CAUTION: Indicates the presence of a hazard which will or can cause injury, if handled improperly.
*2 Alphabet in the “Part” line is the same meaning in the residual risk map.
*3 Required license and education shall be followed each local law, code and regulation.
Required Seriousness
license and Part level of the Required protection measures by operators and
No. Stage When Detail of the harm
education *2 harm maintenance personnel
*3 *1
1 Installation ← B WARNING Electrical shock Before the maintenance or opening the control panel for
Operation servicing or wiring, stop the air compressor and
Maintenance disconnect the power.
Before the maintenance, verify that inverter charge light is
off. (only for the )
During the operation, don’t open the enclosure without the
case indicated in this manual. Never remove the
protective covers or protective devices.
2 Operation ← B WARNING Injury when hands During the operation, don’t open the enclosure without the
Maintenance and maintenance case indicated in this manual.
tools closer to the Never remove the protective covers or protective devices.
rotating fan During the greasing, don't bring the hand or clothes close
to the rotating parts. (only for the model required greasing)
3 Operation ← B WARNING Injury when hands During the operation, don’t open the enclosure without the
Maintenance and maintenance case indicated in this manual.
tools closer to the Never remove the protective covers or protective devices.
rotating part, such as During the greasing, don't bring the hand or clothes close
belt, pulley, coupling. to the rotating parts. (only for the model required greasing)
4 Operation ← B, C WARNING Injury by high During the operation, don’t open the enclosure without the
Maintenance pressure air or the case indicated in this manual.
part flying by Never remove the protective covers or protective devices.
compressed air During the greasing, don't move the face close to the air
relief valve. (only for the model required greasing)
Don't change the alarm or shutdown settings.
Before servicing, close the stop valve located on the
downstream side of the air compressor, and verify that air
compressor internal pressure is released.
5 Operation ← C WARNING Burn injury During the operation, don’t open the enclosure without the
Maintenance case indicated in this manual.
Never remove the protective covers or protective devices.
During the greasing, don't bring the hand or clothes close
to the hot surface. (only for the model required greasing)
Before servicing, verify that the hot surface temperature
fall down enough.
6 Operation ← A WARNING Breathing difficulty Don't use the air compressor for the breathing air
by direct aspirate of application.
the compressed air
III
RESIDUAL RISKS
Required Seriousness
license and Part level of the Required protection measures by operators and maintenance
No. Stage When Detail of the harm
education *2 harm personnel
*3 *1
7 Installation ← Not Caution Injury by getting Pay attention not to drop the air compressor when lifted
specified caught in or being and moved.
pressed under the air Use proper wires for the weight.
compressor
8 Operation ← Not Caution Hearing difficulty by During the operation, don’t open the enclosure without the
Maintenance specified the sound case indicated in this manual.
Never remove the protective cover or device.
Wear earplugs as necessary.
9 Operation ← B Caution Injury by sucking During the operation, don’t open the enclosure without the
Maintenance hand, body, or clothes case indicated in this manual.
Never remove the protective covers or protective devices.
During the greasing, don't bring the hand or clothes close
to the air intake filter. (only for the model required
greasing)
10 Operation ← B, C Caution Burn injury by the hot During the operation, don’t open the enclosure without the
Maintenance surface case indicated in this manual.
Never remove the protective covers or protective devices.
During the greasing, don't bring the hand close to the
parts without greasing port. (only for the model required
greasing)
Before servicing, verify that the hot surface temperature
fall down enough.
11 Maintenance ← B Caution Injury by fin of the Wear the gloves when servicing.
cooler, and inverter
12 Maintenance ← Not Caution Fall by slipping by Wipe the oil spilled on the floor.
specified the scattering oil
13 Maintenance ← B Caution Malfunction of A person having implanted electronic medical devices
medical electronic shall not approrch permanent magnet motor disassembly
device work or a magnetic rotor (only for the with a DCBL
(Permanent magnetic) motor.
14 Maintenance ← B, C Caution Injury by the edge of Wear the gloves when servicing.
the enclosure or
sheet metal
IV
CONTENTS
1. SAFETY PRECAUTIONS‥ ‥‥‥‥‥‥ 2 9. MAINTENANCE‥‥‥‥‥‥‥‥‥‥‥75
1.1 SAFETY PRECAUTIONS‥‥‥‥‥‥‥‥‥2 9.1 Periodical maintenance of air compressor‥‥ 75
1.2 Caution for the DCBL (main) motor ‥‥6 9.2 Standard maintenance schedule A‥ ‥‥ 76
9.3 Standard maintenance schedule B‥ ‥‥ 78
2. PARTS DESCRIPTION AND THEIR FUNCTIONS‥‥ 7 9.4 Operation check of air relief valve‥‥‥‥ 80
2.1 Appearance ‥‥‥‥‥‥‥‥‥‥‥‥‥‥ 7 9.5 Performance check of capacity control
2.2 Components‥‥‥‥‥‥‥‥‥‥‥‥‥‥9 system‥ ‥‥‥‥‥‥‥‥‥‥‥‥‥‥‥ 80
9.6 Replacement of oil filter element‥ ‥‥‥ 81
PERIODIC MAINTENANCE
3. OPERATION PANEL‥‥‥‥‥‥‥‥‥11 9.7 Cleaning and replacement of air intake
3.1 Before operation‥‥‥‥‥‥‥‥‥‥‥‥ 11 filter element‥ ‥‥‥‥‥‥‥‥‥‥‥‥ 82
3.2 Operation panel details‥‥‥‥‥‥‥‥‥ 12 9.8 Cleaning of Oil Coolers‥‥‥‥‥‥‥‥‥ 83
3.3 Initial and monitor displays‥‥‥‥‥‥‥ 14 9.9 Adjustment of minimum pressure /
3.4 Menu display‥ ‥‥‥‥‥‥‥‥‥‥‥‥ 16 check valve‥ ‥‥‥‥‥‥‥‥‥‥‥‥‥ 84
3.5 Message display‥‥‥‥‥‥‥‥‥‥‥‥ 41 9.10 Replacement of oil separator element‥‥ 85
DAILY CHECK
8.2 Conveying the air compressor‥ ‥‥‥‥ 63 13. PARTS LIST‥ ‥‥‥‥‥‥‥‥‥‥‥95
8.3 Location for the air compressor‥‥‥‥‥ 64
8.4 Piping the air compressor‥ ‥‥‥‥‥‥ 65 14. OPERATION RECORD LOGBOOK‥‥108
8.5 Ventilation of air compressor room‥‥‥ 66
8.6 Wiring‥‥‥‥‥‥‥‥‥‥‥‥‥‥‥‥‥ 68 15. STANDARD SPECIFICATION‥ ‥‥110
8.7 Wiring diagram‥ ‥‥‥‥‥‥‥‥‥‥‥ 71
1
1. SAFETY PRECAUTIONS
OSP-55/75VAN2
WARNING
WARNING ● Keep hands androds, away
from the air inlet port of air
Explosion and Burst!
intalke filter.
● Replace the oil and oil separator element periodically as shown
in the instruction manual. Oil separator defect or oil deterioration
can cause explosion or fire.
● Replace the oil separator housing if there is any defect,such as
scratch, crack, deformation or crrosion. This can cause severe
accident, such as damage, oil spout or burst.
WARNING
High Pressure and Hot Oil/Air!
● Do not loose the housing during operation or before internal
pressure is released. High pressure and hot oil/air can cause
severe injury or death.
CAUTION
Other caution!
● Prior to the inspection or replacement of the oil separator, read
and understand the instruction manual.
● Before servicing,stop the air compressor,disconnect the power,
verify that the internal pressure is released.
● Do not directly touch the housing when immediately the air
compressor has stopped, as its surface is extremely hot.
● Use special arranged filter wrench to remove the housing. Using
general one can cause the filter deformation,crack or burst.
● Replace the housing and square ring as well as the element.
WARNING
High Pressure and Hot Oil/Air!
● High pressure and hot oil/air can cause severe injury
or death. Do not open the oil drain valve when the
power is ON.
WARNING
Hot Surface!
● Do not directly touch any component inside the air
compressor enclosure when the air compressor is
operating or immidiately it has stopped, as the
components are extremely hot and can cause severe
injury.
CAUTION
USE THE GENUINE SYNTHETIC OIL ONLY.
● Always use the "NEW SCREW OIL NEXT"
(Hitachi's genuine synthetic oil)for the air
compressor.
● DO not mix it with any other brands of oil.
Replace the oil regularly as scheduled by the
Instruction Manual.
WARNING
High Pressure and Hot Oil/Air!
● Before servicing the air compressor,stop it,close the
discharge stop valve,release the internal pressure,
disconnect the power and verify both the pressure in 2000 NEXT
the operation panel and the oil separator tank
pressure gauge indicate 0MPa.
● Use caution at all times,when the air compressor is
powered. The air compressor may be capable of
restarting without hitting the START button.
2000 NEXT
49D23066XA
2
1. SAFETY PRECAUTIONS
WARNING WARNING
Rotating Parts! Do Not Breathe Air!
● Keep hands and rods, etc. away from, the
● Discharge air can contain Carbon Monoxide and other
ro t a t i n g p a r t s , s u c h a s p u l l e y s , b e l t s ,
couplings, cooling fans etc..
contaminants. Breathing the air can cause severe injury or
● Use caution at all times, when air compressor death.
is powered. The air compressor may be ● Using compressed air insufficient ventilating area, such as in
capable of restarting without hitting the START tunnel, also can cause severe injury or death.
button.
● DO NOT operate the air compressor without
enclosures. WARNING
High Pressure and Hot Oil/Air!
● High pressure and hot oil/air can cause severe injury or death.
Pressurized oil/air can blow out of air relief valve or oil filling
port etc. at incredibly high velocities.
● Before servicing the air compressor, stop it, disconnect the
power, and release the internal pressure before removing the
parts, such as filter, plug, fitting or cover.
WARNING
STRONG MAGNETIC FIELD
The motor rotor contains a powerful
WARNING
magnetic field. Flamable and Burst!
This field can affect the operation of ● Keep a container of the flammable hazards,such as solvents,
digital devices such as watches, mobile away from the air compressor. It can cause explosion.
phones etc. ● DO NOT use any oil other than “NEW SCREW OIL NEXT”.
Assembly or handling of the rotor should Replace the oil and oil separator element periodically as
not be attempted by personnel with shown in the instruction manual. Oil separator defect or oil
cardiac pacemakers, defibrillators or deterioration can cause explosion or fire.
other implanted electronic medical
devices.
WARNING
Rotating Parts!
● Keep hands and rods, etc. away from, the rotating parts, such
as pulleys, belts, couplings, cooling fans etc..
● Use caution at all times, when air compressor is powered.
CAUTION The air compressor may be capable of restarting without
hitting the START button.
Replenishment main motor grease
MOTOR GREASE notice appears on the touch panel
and count-down starts 200 hours before shutdown. WARNING
Before shutdown, apply grease and press the Cancel
button on the touch panel for more than seven (7) Electric Shock Hazard!
second. The time until shutdown is reset and monitor ● 10 minutes before servicing or wiring the air compressor,
display appears. disconnect the power to prevent an electric shock that can
lead severe injury or death. Show the notice stating “Keep
switch off” etc. around the power supply.
● Do not allow any unlicensed person to wire the air
compressor.
Always use a licensed electrician.
● Ground the air compressor.
CAUTION
Precaution against Fire!
● Do not use fire nearby it, otherwise a spark may enter the air
WARNING compressor and burn it internally.
Electric Shock Hazard! ● Do not remove any compressor protective relays. Also do
● 10 minutes before servicing or wiring the air not make a modification of the control circuit that may result
compressor. disconnect the power to prevent an in impairing the protective relay's function. Remember that
electric shock that can lead severe injury or death. the loss of the protective relay's function may cause serious
Show the notice stating “Keep switch off” etc. damage.
around the power supply. ● Install an earth leakage circuit breaker.
● Do not allow any unlicensed person to wire the air
● Ground the air compressor.
compressor. Always use a licensed electrician.
● Ground the air compressor.
CAUTION
Hot Surface!
● Do not directly touch any component inside the air
compressor enclosure when the air compressor is operating
or immediately it has stopped,as the components are
extremely hot and can cause severe injury.
WARNING
Rotating Parts!
● Keep hands and rods, etc. away
from the coupling. The air
compressor is capable of
restarting without hitting the
START button.
3
1. SAFETY PRECAUTIONS
OSP-55/75MAN2
WARNING WARNING
Explosion and Burst!
● Replace the oil and oil separator element periodically as shown ● Keep hands androds, away
in the instruction manual. Oil separator defect or oil deterioration from the air inlet port of air
can cause explosion or fire. intalke filter.
● Replace the oil separator housing if there is any defect,such as
scratch, crack, deformation or crrosion. This can cause severe
accident, such as damage, oil spout or burst.
WARNING
High Pressure and Hot Oil/Air!
● Do not loose the housing during operation or before internal
pressure is released. High pressure and hot oil/air can cause
severe injury or death.
CAUTION
Other caution!
● Prior to the inspection or replacement of the oil separator, read
and understand the instruction manual.
● Before servicing,stop the air compressor,disconnect the power,
verify that the internal pressure is released.
● Do not directly touch the housing when immediately the air
compressor has stopped, as its surface is extremely hot.
● Use special arranged filter wrench to remove the housing. Using
general one can cause the filter deformation,crack or burst.
● Replace the housing and square ring as well as the element.
WARNING
High Pressure and Hot Oil/Air!
● High pressure and hot oil/air can cause severe injury
or death. Do not open the oil drain valve when the
power is ON.
WARNING
Hot Surface!
● Do not directly touch any component inside the air
compressor enclosure when the air compressor is
operating or immidiately it has stopped, as the
components are extremely hot and can cause severe
injury.
CAUTION
USE THE GENUINE SYNTHETIC OIL ONLY.
● Always use the "NEW SCREW OIL NEXT"
(Hitachi's genuine synthetic oil)for the air
compressor.
● DO not mix it with any other brands of oil.
Replace the oil regularly as scheduled by the
Instruction Manual.
WARNING
High Pressure and Hot Oil/Air!
● Before servicing the air compressor,stop it,close the
discharge stop valve,release the internal pressure,
disconnect the power and verify both the pressure in 2000 NEXT
the operation panel and the oil separator tank
pressure gauge indicate 0MPa.
● Use caution at all times,when the air compressor is
powered. The air compressor may be capable of
restarting without hitting the START button. 2000 NEXT
49D23066XA
4
1. SAFETY PRECAUTIONS
WARNING WARNING
Rotating Parts! Do Not Breathe Air!
● Keep hands and rods, etc. away from, the
● Discharge air can contain Carbon Monoxide and other
ro t a t i n g p a r t s , s u c h a s p u l l e y s , b e l t s ,
couplings, cooling fans etc..
contaminants. Breathing the air can cause severe injury or
● Use caution at all times, when air compressor death.
is powered. The air compressor may be ● Using compressed air insufficient ventilating area, such as in
capable of restarting without hitting the START tunnel, also can cause severe injury or death.
button.
● DO NOT operate the air compressor without
enclosures. WARNING
High Pressure and Hot Oil/Air!
● High pressure and hot oil/air can cause severe injury or death.
Pressurized oil/air can blow out of air relief valve or oil filling
port etc. at incredibly high velocities.
● Before servicing the air compressor, stop it, disconnect the
power, and release the internal pressure before removing the
parts, such as filter, plug, fitting or cover.
WARNING
Flamable and Burst!
● Keep a container of the flammable hazards,such as solvents,
away from the air compressor. It can cause explosion.
● DO NOT use any oil other than “NEW SCREW OIL NEXT”.
CAUTION Replace the oil and oil separator element periodically as
shown in the instruction manual. Oil separator defect or oil
Replenishment main motor grease deterioration can cause explosion or fire.
MOTOR GREASE notice appears on the touch panel
and count-down starts 200 hours before shutdown.
Before shutdown, apply grease and press the Cancel
WARNING
button on the touch panel for more than seven (7) Rotating Parts!
second. The time until shutdown is reset and monitor ● Keep hands and rods, etc. away from, the rotating parts, such
display appears. as pulleys, belts, couplings, cooling fans etc..
● Use caution at all times, when air compressor is powered.
The air compressor may be capable of restarting without
hitting the START button.
WARNING
Electric Shock Hazard!
● 10 minutes before servicing or wiring the air compressor,
disconnect the power to prevent an electric shock that can
lead severe injury or death. Show the notice stating “Keep
switch off” etc. around the power supply.
● Do not allow any unlicensed person to wire the air
compressor.
Always use a licensed electrician.
● Ground the air compressor.
CAUTION
Precaution against Fire!
● Do not use fire nearby it, otherwise a spark may enter the air
compressor and burn it internally.
WARNING ● Do not remove any compressor protective relays. Also do
not make a modification of the control circuit that may result
Electric Shock Hazard! in impairing the protective relay's function. Remember that
● 10 minutes before servicing or wiring the air
the loss of the protective relay's function may cause serious
compressor. disconnect the power to prevent an
electric shock that can lead severe injury or death.
damage.
Show the notice stating “Keep switch off” etc. ● Install an earth leakage circuit breaker.
around the power supply. ● Ground the air compressor.
● Do not allow any unlicensed person to wire the air
compressor. Always use a licensed electrician.
● Ground the air compressor.
CAUTION
Hot Surface!
● Do not directly touch any component inside the air
compressor enclosure when the air compressor is operating
or immediately it has stopped,as the components are
extremely hot and can cause severe injury.
5
1. SAFETY PRECAUTIONS
WARNING
Contact the local HITACHI distributor/master dealer or representative office for the repair or disassembly.
Repair and disassembly work must be performed by licensed technician to avoid the electric shock,
injury and/or fire.
Keep the magnetic rotor from a person with electronic medical equipment, such as a cardiac pacemaker.
The medical equipment may malfunction, which may lead to a fatal danger to the person.
Do not connect the motor with anything other than a dedicated controller to avoid the electric shock,
injury and/or fire.
CAUTION
A very strong magnetic force of attraction or repelling is generated between the magnetic rotor and the
other magnet rotors, magnets, iron pieces or iron tools.
Be careful extremely when handling the magnetic rotor. You may get your hand caught in during
rotor assembly work or lose a balance because of attraction or repelling force, which may cause
an accident and/or injury.
Magnets attract iron chips or other metal particles easily. Be very careful for handling.
Using the magnetic rotor with particles may cause a failure.
Do not bring the magnetic rotor close to an electronic device, such as PC board, LCD monitor.
It may cause a failure of electric device.
Do not bring the magnetic rotor to a magnetic tape, computer diskette, prepaid card, ticket, electronic
clock, cathode-ray tube, etc. Electronic record may be damaged or become unusable due to
magnetization.
■ Disposal
Dispose of DCBL (main) motor as general industrial waste. Before disposing
of the magnetic rotor, heat the rotor to 500°C or higher with a gas burner or
heating furnace for thermal demagnetization.
6
2. PARTS DESCRIPTION AND THEIR FUNCTIONS
2.1 Appearance
It is necessary to understand and manage the parts descriptions and their functions related to daily use.
OSP-55/75VAN2
Air exhaust Enclosure
(Air compressor package) Enclosure panels
lower the sound level
Compressed air discharge of the air compressor
(On back side) package.
Air
exhaust
Operation panel
For details, refer to “3.
OPERATION PANEL”
Oil separator
pressure gauge
Air intake
Oil level gauge Oil drain port Fork slot Control panel Power supply port
This indicates the oil (Oil separator tank) After installation, plug Check the
quantity in the oil the fork slots with the specifications, power
separator tank. fork slot covers supply and voltage
See 5.3 to check. (Standard accessories). before connecting the
power supply.
Contact your
OSP-55VAN2
distributor and declare 10.1
the information on the 0.7/0.93
0.7
plate. 55
2700
6.9
1230
2000 1200 1800
7
2. PARTS DESCRIPTION AND THEIR FUNCTIONS [Appearance]
OSP-55/75MAN2
Air exhaust Enclosure
(Air compressor package) Enclosure panels
lower the sound level
Compressed air discharge of the air compressor
(On back side) package.
Air
exhaust
Operation panel
For details, refer to “3.
OPERATION PANEL”
Oil separator
pressure gauge
Air intake
Oil level gauge Oil drain port Fork slot Control panel Power supply port
This indicates the oil (Oil separator tank) After installation, plug Check the
quantity in the oil the fork slots with the specifications, power
separator tank. fork slot covers supply and voltage
See 5.3 to check. (Standard accessories). before connecting the
power supply.
Contact your
OSP-55MAN2
distributor and declare 10.1
the information on the 0.7/0.85
0.7
plate. 55
2650
6.9
1520
2000 1200 1800
8
2. PARTS DESCRIPTION AND THEIR FUNCTIONS [Components]
2.2 Components
OSP-55/75VAN2
Oil cooler and
aftercooler
Two coolers are
combined.
Cooling fan
Turbo fan.
Control panel
Fan motor
6P totally enclosed
type.
DCBL controller
Pressure gauge Oil separator tank Oil level gauge Oil temperature Oil filter
(Oil separator) This separates the oil control valve
from the compressed This keeps the oil
air (Primary separation) temperature to proper
and separated oil value.
drops the oil sump.
Minimum pressure
/ Check valve
This keeps the
minimum pressure to
prevent the oil carry
over.
9
2. PARTS DESCRIPTION AND THEIR FUNCTIONS [Components]
OSP-55/75MAN2
Control panel
Fan motor
6P totally enclosed
type.
Main motor
Oil separator
This separates the oil 2P TEFC motor
from the compressed
air. (Secondary separation)
Pressure gauge Oil separator tank Oil level gauge Oil temperature Oil filter
(Oil separator) This separates the oil control valve
from the compressed This keeps the oil
air (Primary separation) temperature to proper
and separated oil value.
drops the oil sump.
Minimum pressure
/ Check valve
This keeps the
minimum pressure to
prevent the oil carry
over.
10
3. OPERATION PANEL
Connect the power. After 4 seconds, initial display After 12 seconds, home display
The POWER light turns ON. appears. appears.
Power supply
Request:
See 7.1 if the reversal phase or
phase-lacking appears.
Press the “MENU” button on the operation panel to check the menu display.
Press the “CHECK” button on the menu display.
Press the “SPEC” button on the check screen to confirm the air compressor specification.
⇨ ⇨ ⇨
9HU
START STOP
11
3. OPERATION PANEL [Operation panel details]
Touch Panel MENU Button RESET Button Running mode light area
E R G E NC
M
E
SCREW COMPRESSOR
STOP 9HU
START STOP
USB Cover
EMERGENCY STOP button START Button STOP Button Power light E-MODE Button
(Yellow)
How to open the USB cover How to close the USB cover
Touch Panel To see the operating information and to change the setting
( See 3.4.3 (3) for the automatic screen light-out.)
12
3. OPERATION PANEL [Operation panel details]
STOP
The compressor can not be restarted until the switch is manually reset.
Turn the switch knob clockwise and press the RESET button
to reset.
USB Cover To protect the battery and USB connector ( See 3.4.5 for the USB.)
○ Glowing,
Light Color Status ● Blinking
Power light
Yellow The power is turned ON. ○
13
3. OPERATION PANEL [Initial and monitor displays]
RUN HOUR: Total running hours LD/ULD: P revious load period / Previous unload
period in one cycle (Indicated “***”,
DIS TEMP 1: Discharge temperature 1 ( See 6.1)
when the variable speed range for )
AMB TEMP: Ambient temperature ( See 6.1)
LOAD HOUR: Total load hours
Because the sensor is in the package,
indicated temperature can be higher than LOAD TIMES: Total number of load
actual ambient temperature, especially
START: The number of start (including auto restart)
just after air compressor stopping.
FAN FREQ: O perating frequency of the fan motor
FREQ: Operating frequency of the main motor ( )
(only for the model that have the fan
DIS TEMP 2: Discharge temperature 2 ( See 6.1) inverter)
LOAD RATIO: Air consumption ratio CURRENT: Input current of the main motor
Calculated by LD / (LD+ULD) at the
HR TO MAINT: Hours until the next maintenance
point of load to unload for
Calculated by the FREQ for the variable LAST MT: Previous maintenance date
speed range for
Calculated by FREQ and LD/ULD at the
point of load to unload NOT for variable
speed range for
14
3. OPERATION PANEL [Initial and monitor displays]
3.3.2 Icon ① to ⑪
①② ③④⑤⑥⑦⑧⑨⑩
Lead-lag, Slave
③ Alarm/Shutdown No alarm and shutdown
[3.5] [7]
Need to remove the cause of alarm or shutdown
④ Message No message
[3.5]
Need to check the message (Maintenance notice is not included)
⑤ Schedule operation (Start/stop) No scheduled
15
3. OPERATION PANEL [Menu display]
Home display
See 3.3.
Button SW
Button SW
SET PRESSURE PART MAINTENANCE SETTING OPERATION DATA AUTO SAVE SETTING
OTHER
IMPORTANT
16
3. OPERATION PANEL [Menu display]
(1) CAPACITY CONTROL Refer to 6.2 for the detail of capacity control.
Setting other than MAX P shall be set during air compressor is stopped.
How to set ?
■
1 MODE (Capacity control mode)
: “V-mode”, not changeable
: “I-mode”, not changeable
3 AUTO
ON : Auto stop/restart function is effective (default setting)
OFF : Auto stop/restart function is ineffective
4 MAX P : (Maximum cut-out pressure for )
It is possible to set the enforced cut-out pressure.
OFF : invalid (Default)
ON : Valid and can set the value
This function is useful when REF P is set EXT or COM . Set the
minimum rated pressure of controlled air compressors.
17
3. OPERATION PANEL [Menu display]
Control pressure 2
(= Cut-in pressure 2) 3 Press to save.
Restart pressure 1
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
■
Energy Saving Effects
Cut-out pressure 1
Cut-out pressure 2
Cutin Pressure 1
Loading Unloading
Cutin Pressure 2
Time
18
3. OPERATION PANEL [Menu display]
E-MODE default setting is OFF. (a) IPC (Intelligent Pressure Control) mode
The applicable E-MODE functions are as followings. ( , )
When the air consumption ratio is low, the pressure
① PQ wide mode loss of secondary side of the air receiver tank is lower
② IPC mode than it at full load condition. Therefore when the low
air consumption ratio with using IPC mode, air
compressor automatically reduces the discharge
① ECOMODE
pressure with maintaining the air use point pressure
② IPC mode to achieve the energy saving.
Only one mode can be used at once for both
■ IPC mode OFF
and .
High Air consumption ratio Low
Cut-in pressure
■ IPC mode ON
High Air consumption ratio Low
(C)
(A)
Line pressure
(B)
Air compressor
discharge
pressure range
Cut-in pressure
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
19
3. OPERATION PANEL [Menu display]
How to set ?
1 Press IPC in E-MODE display.
2 Input the value for P LOSS (pressure loss)
Set the value after measuring pressure loss from air compressor
to air use point at the full load condition.
3 Press AUTO or MANUAL for PIPE VOL (Total pipe volume).
is not required to input PIPE VOL .
AUTO : The PIPE VOL value is calculated automatically when
first load/unload action after power on. This load ratio
is not equal to the value indicated in touch panel.
Calculation is effective only if the load ratio is higher
than 50% and continued until the load ratio become
higher than 50%. Until confirmation of this value, IPC
mode is ineffective. The value is calculated every time
when power on.
MANU : Input the total pipe volume manually.
IMPORTANT
IPC mode can be used for the case that one air compressor operated for one application. If 2 or more air compressors is used
for one application, it may cause the pressure drop.
IPC mode can’t be set with PQ wide mode or ECOMODE.
1 Press E-MODE button for more than 7 seconds to activate with E-MODE IPC .
CAUTION
● It needs the detail setting depending on the customer’s system to use IPC mode effectively.
Contact the local HITACHI distributor/master dealer or representative office if the desired energy saving
effect is not appeared.
● IPC mode is the predicted control. This does not guarantee to keep the pressure of air use point. If the
pressure prediction does not work well in the case, such as wide and rapid load fluctuation, cancel the
function.
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
20
3. OPERATION PANEL [Menu display]
IMPORTANT
●
}
Pa
Pa PQ wide mode ON
M
90 6 M
0.
0.
Pa
0.
7M 2 Input the value for INTERVAL .
Pa
5M Setting range is 5 to 60 seconds. Default and
80 0.4
recommended value is 30 seconds.
3 Input the pressure differential
Setting range is 0 to 0.10MPa. P DIF 1 to 3 is for
80 90 100 105
Air consumption (%) each P SELECT 1 to 3. Refer to page 18 for
the P SELECT
4 Press to set.
IMPORTANT
How to activate or cancel ?
PQ wide mode can’t be set with IPC mode.
1 Press E-MODE button for more than 7 seconds
If the PQ-MODE is set A , the capacity (airend rotating
to activate with E-MODE ECO .
speed) is controlled by the CONTROL pressure.
( See 3.4.2 (2) for the CONTROL pressure.
2 ECO is appeared in monitoring display.
3 Press E-MODE button more than 7 seconds
to cancel.
4 ECO is disappeared.
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
21
3. OPERATION PANEL [Menu display]
(4) IPI Restart from IPI (Instantaneous Power Interruption) is the standard
function. Instantaneous power interruption means that the power voltage
drops instantaneously. The air compressor can restart automatically, if the
power recovers within the time set in IPI TIME .
Press to save.
Example of the action when IPI is ON.
1 If the IPI is more than IPI TIME (default : 5 seconds), the air compressor
automatically stops and light turns OFF. .
2 After the power recovers, light turns on (blinking),
light turns on (glowing), and AUTO RESTART display appears on the
touch panel. ( See 3.5 for the AUTO RESTART display.)
3 The countdown started from the value in WAITING (default: 20 second).
The value shall be longer than 20 seconds for standard model, to
release the internal pressure.
4 After time is up, the air compressor automatically restarts.
5 The history of IPI auto restart is recorded in ERROR HISTORY
display. ( See 3.4.3 for the ERROR HISTORY .)
IMPORTANT
● Date and time is not recorded in error history for IPI (code3).
● There is the possibility to record the communication error as well for IPI in error
history.
● Error history is recorded in both SET is ON and OFF .
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
22
3. OPERATION PANEL [Menu display]
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
23
3. OPERATION PANEL [Menu display]
CAUTION
Caution for LEVEL setting
● Starting signal is effective regardless of the air compressor shutdown.
So when the air compressor shutdowns, following procedure is necessary to restart the air compressor.
1) Remote start signal shall be OFF. 2) Press . 3) Send the start signal.
● If the external start signal is ON when LOCAL is set, air compressor starts just after pressing REMOTE .
● Air compressor can’t start by operation panel when remote start signal is OFF.
● In the REMOTE setting, STOP is effective only while it is pressed. If you release the STOP, air
compressor restarts.
IMPORTANT
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
24
3. OPERATION PANEL [Menu display]
(6) SCHEDULE
₀ Press in
SCHEDULED 1/6
1 Press at No.1
(No.2) in
SCHEDULED 1/6.
2 Select ON at No.1
Up to 7 items Touch the right arrows
(No.2) in
hereafter can on the schedule 1 Press at No.1
be set. operation setting screen SCHEDULED 2/6
for setting details. (No.2) in PRESSURE
3 Select MON to FRI SCHEDULED 4/6.
at EFFECTIVE DAY . 2 Select ON at No.1
4 Input the time at (No.2) in PRESSURE
START and STOP . SCHEDULED 5/6
◦ If 24:00 is input, the air 3 Select No. at P SELECT
compressor keeps the
same status (operating 4 Select MON to FRI
or stopping). at EFFECTIVE DAY .
◦ If is pressed
5 Input the time to
setting value change
change the pressure
to initial value.
combination at TIME.
5 Press . ◦ If is pressed
setting value change
to initial value.
6 Press .
6 Press in
SCHEDULED 1/6.
₇ Press in
PRESSURE SCHEDULED
4/6.
GRAPH screen
Press to confirm GRAPH screen
the time schedule for
Press to confirm
each day.
the time schedule for each
day.
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
25
3. OPERATION PANEL [Menu display]
(7) OTHER
When the power consumption is required to reduce, the air compressor
can reduce the power consumption by reducing the rotating speed by
peak-cut function.
How to set ?
1 Input the required maximum rotating speed ratio against rated
maximum rotating speed at RATIO in OTHER .
2 Press .
To use peak-cut function, set ON at PEAK-CUT .
To cancel peak-cut function, set OFF at PEAK-CUT .
Setting change is acceptable while the air compressor is operating as
well as stopping.
[EX1] PQ OFF, maximum frequency 60Hz, PEAK-CUT ON, RATIO 70%
Maximum frequency become 42Hz
[EX2] PQ ON, maximum frequency 60Hz @0.7MPa, 70Hz @0.85MPa
Maximum frequency becomes 42Hz @0.7MPa, 49Hz@0.85MPa
IMPORTANT
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
26
3. OPERATION PANEL [Menu display]
27
3. OPERATION PANEL [Menu display]
How to set ?
1 Brightness
Select brightness at the BRIGHT .
1 Dark ⇔ 6 Bright (initial value: 4)
is not required.
2 Time until sleep
Set the time at SCRN OFF .
Setting range: 0 to 60 minutes (initial value: 10 minutes)
If set “0”, display always appears. However this shortens the life of the
monitor.
is not required.
3 Display calibration
Use this function if the touch panel response becomes worse.
Press .
Press the center of mark for one second in order.
is not required.
1 Press COM.
(b) Specification
Protocol Modbus RTU
Interface RS-485
Character format Data length: 8, Stop bit:1, Parity bit: Even
Transmission speed 19,200bps
Communication system Half-duplex (Asynchronous, Transmission code: Binary)
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
28
3. OPERATION PANEL [Menu display]
Terminating
resistance (120Ω, SN SP SN SP SN SP
10 9 10 9 10 9 Air Compressor
1/2W) shall be set TB2 TB2 TB2
on the external NEXTII
device. OFF OFF ON
JP7 JP7 JP7
1 1 1
Terminating resistance
● Terminating air compressor from external device : ON CN31
● Other than above : OFF
OFF ON
JP7 1
1
② Response: The frame returned from the air compressor to the external device after air compressor receives
③ Function code
Code Function Remarks
01h Read coil status
03h Read holding resisters
05h Force coil
11h Response message See 3.4.3 (4) (h)
29
3. OPERATION PANEL [Menu display]
30
3. OPERATION PANEL [Menu display]
Refer to 3.4.4 (2) (3) for the detail of OPERATION DATA and ERROR
HISTORY .
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
31
3. OPERATION PANEL [Menu display]
(1) SPECIFICATION
IMPORTANT
● Maximum 20 error histories can be confirmed. Press to check the operating data when the error occurred.
●P
ress to save the error history (MAX. 20 histories). Refer to 3.2 and 3.4.5 for the location of USB
port. USB flash memory is out of scope of supply.
Refer to 7.1 for the error detail.
32
3. OPERATION PANEL [Menu display]
● The latest controller and fan inverter error history are confirmed.
Refer to 7.1.2 How to identify the failure cause of “13 (controller error)”
and “57 (fan inverter error)” and check the history for the error detail.
(5) GRAPH
The time until the next maintenance is in the left. The maintenance cycle
time is in the right. When the time in left become zero, maintenance
message appears ( See 3.5.6). See 3.4.3 (2) for time setting.
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
33
3. OPERATION PANEL [Menu display]
This function is the same function as OPERATION Operating data can be saved 1 time per 1 day
DATA → in 3.4.4 (2). automatically.
Data is saved until 0:00 on 2 days before. The one day before (from 0:00 to 23:59) operating
data is saved.
How to save ?
How to save ?
1 Press MAN SAVE to save the data.
1 Connect the USB flash memory to USB port.
2 Pop up menu appears. Press .
Refer to the next page for the connection.
3 Data is saving. 2 Press AUTO SAVE.
4 Pop-up message “COMMUNICATE” appears and 3 Input the time when the data is saved.
SAVING blinks during data saving. 4 Select ON at AUTO SAVE .
It takes 6 minutes to save the all data. 5 Pop-up message “A-SAVING” appears and
5 Pop-up message “COMMUNICATION COMPLETED” SAVING blinks during data saving.
appears. It takes 2 minutes to save the data.
6 “A-SAVING CMPL” appears.
IMPORTANT
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
34
3. OPERATION PANEL [Menu display]
35
3. OPERATION PANEL [Menu display]
36
3. OPERATION PANEL [Menu display]
(4) PAIRING
It is possible to see the air compressor operation data by the web server function on the tablet through the
Bluetooth.
IMPORTANT
A USB flash memory and Bluetooth dongle can’t be connect at once to the USB port. USB hub also can’t be used.
The Bluetooth dongle and tablet are out of scope of supply.
IMPORTANT
● Bluetooth is a global wireless communication standard that connects devices together over a certain distance. (Transmit
frequency 2.4GHz, Allowable distance 10m)
● Bluetooth dongle is a device to provide additional forms of wireless connectivity to Bluetooth support, often over USB
connection.
Refer to 3.4.6 “Setting list” for the detail, such as range, initial value.
37
3. OPERATION PANEL [Menu display]
38
3. OPERATION PANEL [Menu display]
39
3. OPERATION PANEL [Menu display]
MULTI
MODE REMOTE - SNGL SNGL SNGL MULTI DUAL - □ MULTI and DUAL is option
3.4.3 (1)
COMP NO.
- NO. 1 1 1 - 99 □
(MULTI)
PART PACKAGE
hr 500 500 0-1,000h -
MAINTENANCE FILTER CLEAN
3.4.3 (2) AIR INTAKE FILTER
hr 6000 6000 0-6,000h -
ELEMENT REPLACE
OIL FILTER
hr 6000 6000 0-6,000h -
REPLACE
OIL SEPARATOR - hr 6000 6000 0-6,000h -
REPLACE
COOLER CLEAN hr 6000 6000 0-6,000h -
OIL TOP UP hr 0 0 0-12,000h -
BELT CHECK hr - 6000 0-6,000h -
MOTOR GREASE hr 3000 3000 0-3,000h -
TOUCH PANEL BRIGHT - 4 4 1-6 -
FUNCTION SETTING
(including clock) SCRN OFF min 10 10 0 - 60 -
3.4.3 (3) - Year: 2000-9999, Month: 1-12,
Date/Time - Remarks Remarks - Set in the factory.
Day: 1-31, Hour 0-23, Minute: 0-59
CAL - - - -
COMMUNICATION SLAVE NO. NO. 1 1 1 - 99 - Set Modbus RTU SLAVE No.
3.4.3 (4)
COMP NO. Use for the file name (3.4.5 (3)), and
3.4.5 (3) (4) NO. 1 1 1 - 99 -
(ID) - the device name (3.4.5 (4))
IP For Modbus/TCP communication, enter the
- Remarks Remarks 0 - 255 0 - 255 0 - 255 0 - 255 -
ADDRESS IP address 192: 168: 000: 001 (Option).
CLEAR DATA CPU Ver. - - - -
3.4.3 (5)
IT Ver. - - - -
TP Ver. - - - - -
ERROR HISTORY - - - - Clear ALARM/Shutdown history.
OPERATION DATA - - - - Clear operation data.
AUTO USB
AUTO SAVE - OFF OFF OFF ON - - -
3.4.5 (2)
-
USB SAVE TIME - 00:00 00:00 Hour : 0 - 23, Minute : 0 - 59 -
40
3. OPERATION PANEL [Message display]
Page/Total page
Message appear Use arrow to move the page
(*1) Press
for LOAD COUNT OVER.
SETting/CONNECT ERR
SHUTDOWN
Message menu
See 3.5.2
DEVICE ERRor
See 3.5.2
Press the blinking
menu to see the
message again.
Stand by status
See 3.5.4
Operation status
See 3.5.5
41
3. OPERATION PANEL [Message display]
(1) SHUTDOWN
How to reset ?
1
W hen the air compressor shutdowns, alarm light blinks and
SHUTDOWN or DEVICE ERR message appears in touch panel.
2 Remove the cause. Refer to 7.1 to know how to remove the cause.
3 Press RESET Button.
(1) ALARM
1 When the air compressor raise alarms, alarm light glows and ALARM
or SET & CONNECT ERR message appears in touch panel.
2 Remove the cause. Refer to 7.1 to know how to remove the cause.
3 Press RESET Button.
IMPORTANT
● SET & CONNECT ERR includes both alarm and shutdown. See 7.1 for the
detail.
● The multiple alarms may appear because the air compressor continues to
operate in case of alarm.
Use key to see other pages.
42
3. OPERATION PANEL [Message display]
AUTO RESTART message appears and auto light glows or blinks when the air compressor can restart
automatically, AUTO RESTART message appears and auto light glows or blinks. After restarting, Monitor display
appears.
RUN STATUS appears when the operation status changes as following table.
43
3. OPERATION PANEL [Message display]
When the operating hours reaches the maintenance term, MAINTENANCE notice appears.
There are three types of maintenance notice. (a) is for the annual maintenance term, (b) is for each parts
replacement or cleaning and (c) is for the greasing to main motor.
Replace the consumable parts of the suction throttle valve whichever faster, annual maintenance notice or alarm
display of LOAD COUNT OVER (the number of the load/unload cycle).
(a) ANNUAL MAINTENANCE notice
ANNUAL MAINTENANCE appears whichever faster, every 6000 hours or
one year (Maintenance schedule A). Maintenance schedule B (every 3000
hours) is not indicated.
After completing the maintenance, press the button on the touch
panel for more than seven (7) seconds. Remaining time is reset and
monitor display appears.
Part name and required action appears when the time is up. Refer to
3.4.3 (2) and 3.4.4 (6) for the period or remaining time.
After completing the maintenance, press the button on the touch
panel for more than seven (7) seconds. Remaining time is reset and
monitor display appears.
(c) MOTOR GREASE notice (only for the model required the greasing for main motor bearing)
After 200
hours
MOTOR GREASE appears and count-down starts 200 hours before shutdown. Before shutdown, apply grease,
and press the button on the touch panel for more than seven (7) seconds. Remaining time is reset and
monitor display appears.
■ Trademarks
CAUTION ・iPad is a registered trademark of Apple Inc.
・Android is the registered trademark of Google Inc.
Maintenance action shall be done as
・Bluetooth is a registered trademark of Bluetooth SIG, Inc.
possible when maintenance display
・Modbus is a registered trademark of Schneider Automation Inc.
appears. Refer to 9 Maintenance how
・Windows is a registered trademark of Microsoft Corporation USA.
to do the maintenance.
・USB: Universal Serial Bus is abbreviated.
・CSV: Comma-Separated Values are abbreviated.
・Safari is a registered trademark of Apple Inc.
・Nexus 7 is a registered trademark of Google Inc.
・Chrome is a registered trademark of Google Inc.
44
4. DAILY OPERATION
CAUTION
● Before connecting the power, verify that the air compressor is correctly installed, piped and wired.
● If the air compressor is not operated for more than 7 days, do the startup operation.
● Close the enclosures when operating.
● Oil is filled for the startup operation.
● See the WARNING, CAUTION and IMPORTANT described in 4.2 daily operation.
4.1.2 Starting
Refer to 3.1 how to do.
Oil filing port
₁ Connect the power and check the POWER
Oil level gauge
light is ON (glowing).
45
4. DAILY OPERATION [Startup operation]
4.1.3 Operation
Oil separator Discharge Power ₁ Press the START button.
pressure stop valve supply
gauge 2 Air compressor starts with START light glows.
₃ G radually close the discharge stop valve, and
keep the air compressor running for an hour with
the pressure gauge (oil separator) indicating 0.5-
0.6MPa.
₄ Verify that the oil level is kept between two red
lines at loading. Refer to 5.3.1 for confirming
the oil level.
5 Verify that the discharge air temperature is stable
between 65 to 100℃ on the touch panel.
IMPORTANT
4.1.4 Stop
Refer to 3.1 how to do.
IMPORTANT
46
4. DAILY OPERATION [Daily operation]
CAUTION
● When using the air compressor, do not raise the discharge pressure excessively. Operating the air
compressor over the rated pressure can result in main motor overload, shutdown of the airend and/or
damage of parts.
● If the air relief valve has blown or a protective device has shutdown the air compressor, investigate the
cause of and take corrective action. If there are any questions or comments in taking these actions,
contact the local HITACHI distributor/master dealer or representative office.
●W
hen the air compressor stops and restarts frequently or continuously occurs under the hot and humid
environment, water condenses in the oil separator tank. Open the oil separator tank drain valve to check
the condensate five hour after stopping the air compressor. If there is condensate, drain it. If the air
compressor operates with accumulated condensate, rotor, bearing and other apparatus may rust and
cause a failure. It also results in the lubricant deterioration.
Operation
panel
4.2.2 Power ON
1 Connect the power.
2 POWER light turns on the operation panel.
3 Fully open the discharge stop valve.
IMPORTANT
Oil level gauge
(1) F or the safety reason, START button is not
Upper
effective for 5 seconds after power turns ON. red line
(2) If the START button is pressed 5 to 10 seconds Lower
after power turns ON, air compressor starts 0 to 5 red line
seconds after with the AUTO light blinking.
( type).
(3) START, STOP, RESET needs to be
pressed more than 0.3 seconds.
47
4. DAILY OPERATION [Daily operation]
IMPORTANT
48
5. DAILY INSPECTION
WARNING
1. Before conduct the maintenance of the air compressor, carefully read “RESIDUAL RISK” and “1.
SAFETY PRECAUTIONS”.
2. Be sure to disconnect the POWER when conduct the maintenance. As for type, make sure that
the charge lamp of the inverter turns off 10 minutes after the power off.
4. The air compressor unloads and loads frequently. If the condensate and lubricant oil is not distinguishable,
check its viscosity by your finger tips while draining.
Be sure the condensate is well cooled before touching it.
If the condensate sticks to your fingers, the lubricant is
CAUTION coming out.
Oil pan
(Customer supply)
49
5. DAILY INSPECTION [Lubricant management]
WARNING
1. When deteriorated lubricant is used without replacement, some of it adheres on the oil separator element
and accumulates heat caused by its oxidization. This may bring even fire in the worst separator tank.
2. Change lubricant and oil separator element constantly according to the standard maintenance
schedule ( 9.2 and 9.3). Deteriorated Lubricant may result fire to the oil separator element. If the
fire breaks out, immediately disconnect the power.
3. Use genuine synthetic oil (NEW SCREW OIL NEXT) for lubricant. Avoid use of other brand or mix
use with it.
CAUTION
● Top up the lubricant periodically to maintain the proper oil level. Improper oil level may cause the
abnormal oil carry over. Long time operation at low oil level may cause the shorter oil life or oil
deterioration.
● Lubricant shall be topped up every 1,000 to 1,500 operating hours. The normal amount is 1.8 liters for
55kW, 2.4 liters for 75kW.
(Actual replenish amount shall be determined by its oil level, as it is varied by the operating condition.)
● Sampling analysis of the oil at every 3000 hours interval is recommended. Early lubricant replacement
may be necessary depending on the result of the analysis.
Contact the local HITACHI distributor/master dealer or representative office for the sampling analysis.
50
5. DAILY INSPECTION [Lubricant management]
Draining
tank
and place an oil pan as the picture below.
After making sure the oil has been completely
Oil level gauge Oil separator tank drain port drained, close the valve and plug.
③ Drain oil from the oil cooler as follows:
Place the oil pan, remove the oil drain plug and
Oil cooler drain port
open the oil drain valve. After making sure the
(in the exhaust duct
on the rear side oil has been completely drained, close the
valve and plug the oil drain port.
④ Drain oil from the airend as follows:
Place the oil pan, remove the oil drain plug.
After making sure the oil has been completely
drained, close plug the oil drain port.
⑤ Fill the lubricant into the oil separator tank as
follows:
Remove the oil filling plug. Fill the specified
amount of (NEW SCREW OIL NEXT), and
Filling
START
button, and stop 7, 8 second after. Refill the
oil until the oil level becomes between two red
lines on the oil level gauge at the loading
operation. Any time the oil is filled, power
Airend oil drain port 2
(Bottom of airend, front side) shall be disconnected and oil separator tank
internal pressure shall be 0MPa.
CAUTION
● Replace the whole lubricant every two years.
● Be sure to drain whole oil and condensate before the lubricant replacement.
● Be sure to use HITACHI genuine synthetic oil NEW SCREW OIL NEXT).
● Make sure the oil separator pressure gauge shows 0 MPa.
● Do not judge the internal pressure by the pressure gauge indicated in digital monitor. (The pressure
shown in the digital monitor can be lower than the oil separator tank internal pressure.)
● Overhauling is required when the lubricant is deteriorated such as sludge or to be green. (Cleaning the
oil cooler, oil separator tank and oil piping is not enough to recover the air compressor condition.)
51
6. FLOW DIAGRAM AND CAPACITY CONTROL
Air exhaust
Cooling fan
Compressed air flow
Minimum
pressure/ Air intake filter Lubricant flow
check valve 63
Oil SV
separator Air intake for
compressed air
TH2
63E
P
TH1 : Thermistor (Discharge temperature 1)
Unloader
Oil filter
MOHR
Air intake for
airend
TH2 : Thermistor (Discharge temperature 2)
Oil separator THX
tank THX : Thermistor (Ambient temperature sensor)
THM : Thermistor (Motor) ( )
Oil temperature control valve
TH1
Airend PS : Pressure sensor (for capacity control)
Oil discharge Main motor P : Pressure gauge (For displaying oil separator
tank internal pressure)
63E : Pressure switch
63SV : Pressure differential sensor of air intake filter
MOHR : Thermostat (Temperature of bearing for main
motor) ( )
Only 75kW-0.85/1.0MPa ( )
52
6. FLOW DIAGRAM AND CAPACITY CONTROL [Capacity control]
PS
From
air intake COM
filter NC
NO Orifice
20US
To the
airend
Orifice To discharge
air piping
20P
20P : Blowoff solenoid valve 20US : Control solenoid valve PS : Pressure sensor
20VS : Unload solenoid valve (M type 55kW : 0.85/1.0MPa, and M type 75kW : 0.7MPa)
Refer to 3.4.1 for the capacity control mode and each pressure setting change
53
6. FLOW DIAGRAM AND CAPACITY CONTROL [Capacity control]
I: integral
Pressure sensor
D: differential
Cut-out pressure 1
IMPORTANT
Control pressure
If the V-mode continues for more than one hour, capacity (=Cut-in pressure)
control change to I-mode for 2 seconds to scavenge the
Motor restart pressure
mechanical seal drain oil.
Time
IMPORTANT
seconds.
100
①
Q (%)
54
6. FLOW DIAGRAM AND CAPACITY CONTROL [Capacity control]
■ For changing the capacity control mode setting and each pressure value setting, refer to pages 3.4.2 (1) and
3.4.2 (2).
55
6. FLOW DIAGRAM AND CAPACITY CONTROL [Capacity control]
■ AUTO ON flow
t (s): Load/unload one cycle in I-mode
This controls the capacity as a flow chart in Q (%): Load ratio Pressure t =1 Cycle time
figure (A).
0.75MPa
● I+P mode : Initial setting of standard model
(1) Q ≧ 30 : I-mode 0.65MPa
(2) Continuous unload time in I-mode ≧ 3 minutes: Time
Suction t≧3 minutes
P-mode throttling
time
NO t<3 minutes
IMPORTANT
YES Flowchart of
P-mode capacity
control
①
②
NO
I-mode
control P-mode control
100
Load factor %.
① ①
0
② ② Time
[Figure A]
100
Load factor %.
0
Time
[Figure B]
56
7. TROUBLESHOOTING
CAUTION
If a shutdown, alarm, problem or failure occurs, investigate the cause and take proper corrective action
before restarting. If there are any questions or comments, Contact the local HITACHI distributor/master
dealer or representative office.
57
7. TROUBLESHOOTING [Alarm and shutdown]
(3) Others
Touch panel Indication Shut Condition and Type How to History
Cause What actions to take
Heading Trouble description down light (*8) timing V M reset (*4) code
Communication Wiring or setting Check the wiring, setting and Communication Automatically
No Option 68
(CPU-MR) failure noise. error reset (*7)
Communication
Lead-lag Check the wiring, setting and Communication
error between No Option 61
communication noise. Glows error
lead-lag
Setting error
Schedule
SET & for schedule No Check the setting See 3.4.2 (6) ○ ○ 62
operation
CONNECT operation
ERR ②
Communication
Controller Communication button
error in the Yes Check the wiring and noise. ○ - 65
communication error
controller
Communication Blinks
Fan inverter error between Communication
Yes Check the wiring and noise. ○ - 66
communication CPU PCB and error
fan inverter
Controller (*2) See 7.1.2 Yes See 7.1.2 Controller failure ○ - 13
Fan inverter See 7.1.2 Yes See 7.1.2 Controller failure ○ - 57
DEVICE
ERR Check the controller,airend and button
Retry Controller failure Yes Blinks After retrying ○ - 44
other rotating parts.
ROM error Yes Disconnect and restore the power. ○ ○ Power 47
CPU PCB If failure occurs again, replace the Power ON
FRAM error Yes ○ ○ restored 43
CPU PCB.
58
7. TROUBLESHOOTING [Alarm and shutdown]
(3) Others
Touch panel Indication Shut Condition and Type How to History
Cause What actions to take
Heading Trouble description down light (*8) timing V M reset (*4) code
Thermistor 1
TH1 disconnect TH1 disconnect Yes ○ ○ 31
Check the connector and replace disconnect (*10)
the thermistor if required Thermistor 2
DEVICE TH2 disconnect TH2 disconnect Yes ○ ○ 32
disconnect (*10) button
ERR
Check the connector and replace Blinks Pressure sensor 2
PS2 disconnect PS2 disconnect Yes ○ ○ 34
the sensor if required disconnect (*10)
Less applying 200 hours no
Motor grease
the grease, Yes Apply the grease action after the ○ ○ Press for B1
(Shutdown)
Shutdown message appears. seven seconds
A1,
IT PCB 1, 2 IT PCB defect No Replace the IT PCB IT PCB error ○ ○ (*3)
A2
Replace the battery with a new Battery voltage
Battery out Battery life No ○ ○ A3
one. See 9.16. low
SET & Communication Wiring or device Check the wiring and noise, Glows Communication 69,
CONNECT error No ○ ○
failure replace the PCB if required error A4
ERR ③ (IT-CPU), (TP-IP)
Communication Check the wiring and noise, Automatically 63,
Wiring or device Communication
error (Modbus/ No replace the PCB or repair the ○ ○ reset (*7) 68,
failure error
RTU), (LAN) external device if required. A6
Malfunction or
Communication setting error Check the setting of connected Communication
No ○ ○ A7
error (Bluetooth) of connected equipment, replace it if required error
equipment
2V or less
ALARM Check the CT and replace the
CT disconnect CT disconnect No when power is ○ ○ 3A
② thermistor if required
Glows connected (0A).
Check the connector and replace Indicate -30℃ or button
THX disconnect THX disconnect No ○ ○ 3B
the thermistor if required lower
(*1) The air compressor with control transformer, such as 380-480V, indicates a phase-lacking connection as reversal phase.
(*2) Air compressor doesn't start for ten seconds with AUTO light blinking after RESET action.
(*3) This depends on the model, type and manufacturing date.
(*4) Before pressing the RESET button, remove the cause of failure.
When overload occurs on , thermal relay reset action is required.
(*5) When main motor overloading occurs, reset the thermal relay.
When main motor overloading occurs, reset and restore the power.
(*6) When fan motor overloading occurs, reset the thermal relay.
(*7) After the failure recovering, automatically reset
(*8) Alarm light blinking means "ALARM" and shutdown relay Y3 is ON.
Alarm light blinking means "CAUTION" and caution relay Y2 is ON.
(*9) If MAINTENANCE notice is appeared on touch panel, follow the procedure in 9. Maintenance.
For the maintenance alarm, there is no history code.
(*10) When disconnect error occures, minimum value is indicated in the touch panel and history.
(*11)
Because the sensor is in the package, indicated temperature can be higher than actual ambient temperature, especially just after air
compressor stopping.
59
7. TROUBLESHOOTING [Alarm and shutdown]
ow to identify the failure cause of “13 (controller error)” and “57 (fan inverter
7.1.2 H
error)” and check the history
When the controller or inverter error appears on touch panel, press MENU button, “ ” and “ ”, then
confirm the detail.
History code
● Controller error ● Check ● Controller error history
Shutdown contents
● Fan inverter error
60
7. TROUBLESHOOTING [A list of failure not displayed on the touch panel]
61
7. TROUBLESHOOTING [A list of failure not displayed on the touch panel]
WARNING
1. R
unning the air compressor with deteriorated lubricant or in a hot environment will bring the lubricant to
a blink point and may cause a serious accident. Be sure to check the lubricant regularly ( see. 50 - 51)
2. Do not operate the air compressor without the protective equipment. In case of a SHUTDOWN, read
section “7 TROUBLESHOOTING” to correct the issue. If the issue is unknown, contact your local
authorized distributor
CAUTION
If the unit stops due to the function of temperature relay, check leakage in the mechanical seal and replace
it if lubricant leak is found there.
62
8. INSTALLATION
63
8. INSTALLATION [Location for the air compressor]
■ Install the air compressor in a bright, wide, and airy room as follows:
Ventilating fan
Piping and
If you install the air maintenance space C ※K
eep spaces of indicated in the
compressor in a small room,
provide a ventilating fan to table below, or more for daily
keep the room temperature operation and periodical
at 45℃ or lower. Foundation maintenance and for keeping the
Provide a vibration-absorbing
mat if the foundation is
enough cooling air for coolers.
Maintenance space D vibrative.
If it is too vibrative, look for Maintenance space
another dequate location. Item mm
A Front 600
B Right side 500
C Rear 1000
Air intake and
D Left side 500
Plug the fork slots with the fork maintenance space B
Maintenance space A
slot covers (standard accessory).
■ Install the air compressor in a dry and dust-free room, and avoid the following.
Raindrops, basements, steam Metals, sand, other hard materials Harmful gases
( )
Toxic gases such as chlorine gas, hydrogen
sulfide gas, sulfurous acid gas, high consistency
ozone, ammonia gas
Causes electric leak, generation of Causes motor insulation failure, bearing Causes deterioration of oil, wear of cooler,
drain/rust, microcomputer malfunction. damage, microcomputer malfunction. detachment of coating from rotor surface.
CAUTION
● Install the air compressor indoors. Installing it outdoors may lead to damage of the airend due to water
vapor, dust, etc.
● The air compressor installation room should have an air intake opening, an air exhaust opening and have
good ventilation. If the room is poorly ventilated, hot air exhausted by the air compressor may cause the
room temperature to rise excessively and lead to damage of the air compressor.
64
8. INSTALLATION [Piping the air compressor]
8.4 Piping the air compressor (5) If the compressed air piping near the air compressor
is to be elevated, keep a space of 500mm (20inches)
8.4.1 Air receiver tank between the elevated piping and the enclosure for
Install the air receiver tank to maximize the energy ease of maintenance (see figure below)
saving feature. The minimum size of the air receiver
500mm or more
tank is indicated in the table blow.
Model Minimum capacity of air receiver (m3)
1.24
OSP-55MAN2 1.24 (Using ECOMODE)
2.26 (V-M combination)
1.24
OSP-75MAN2 2.26 (Using ECOMODE) Drain valve
4.21 (V-M combination)
(6) If the air compressors discharge pipe is connected
0.7
OSP-55VAN2 to the main compressed air piping, run the
2.26 (V-M combination)
1.24 discharge up above the main compressed air piping
OSP-75VAN2
4.21 (V-M combination) and then down into the top of the main compressed
Do not install a check valve between this air air piping (see figure below). This prevents the
compressor and the air receiver tank. This may result backflow of condensate.
in short cycling (frequent loading and unloading) or
excessive high pressure in the system.
Install a dryer and line filters after air receiver tank to
Discharge Main Pipe
prevent short cycling (frequent loading and unloading)
by pressure loss, especially when the filter clogging.
CAUTION
When connecting discharge air piping, connect Drain valve
with the flange or union joint at least 150 mm
from the left panel. Piping to air receiver
tank outlet
(3) If the plant compressed air piping installation is
extensive in length, using a larger diameter pipe assists
in lowering pressure drop throughout the piping system.
(4) If there is an area in the compressed air piping that
is concaved or vertical (see figure below), provide a
condensate drain valve at its bottom as a drip leg.
65
8. INSTALLATION [Ventilation of air compressor room]
CAUTION
Provide a ventilating system to the air compressor room in the event that the room temperature exceeds
the allowable ambient operating temperature of 45℃. Operating the air compressor at an ambient
operating temperature above 45℃ may cause a serious problem.
IMPORTANT
● Stop the ventilating fan when the air compressor has stopped.
● The ventilating fan should be running while the air compressor is operating. If the ventilating fan is not running, the loss of air
flow may reduce the performance of the cooler.
● The duct should be detachable for ease of maintenance on the air compressor.
ventilating fan ②
on the table above.
20 Pa, a ventilating fan is not required on the duct.
Air intake
Install the duct with its detachable end directly in opening
66
8. INSTALLATION [Ventilation of air compressor room]
67
8. INSTALLATION [Wiring]
8.6 Wiring
WARNING
1. A
lways use a licensed electrician. Do not allow an unlicensed person to wire the compressor. An
unlicensed person may wire the air compressor wrongly, and a wrong wiring may cause an electric shock.
2. D
o not remove any protective relays on the air compressor. Also, do not make a modification of the
control circuit that may result in impairing the protective relay's function. Remember that the loss of
the protective relay's function may cause serious damage to the air compressor such as a burning of
the airend. In the event that you need to modify the control circuit, consult your distributor.
3. B
efore opening the control panel to service or wire the air compressor, disconnect the power;
otherwise you may receive an electric shock. In case that the air compressor has the variable speed
drive, such as controller or fan inverter, the variable speed drive are still charged when the power is
disconnected. Be sure to wait approximately 10 minutes after power-off so that each variable speed
drive discharges electricity before starting the procedure. In addition, attach a notice on the power
supply stating “Under the maintenance work. Keep the switch off.” to prevent someone from
carelessly turning the switch on.
68
8. INSTALLATION [Wiring]
Terminal block
Terminal block
Control panel cover Front panel
69
8. INSTALLATION [Wiring]
failure.
controller rated capacity and more than Below Schaffner EMI filter is also acceptable.
500kVA. Model Type
③ The voltage imbalance between the phases is 55kW 380-480V FS25108 - 149 - 07
more than 1%. 75kW 380-480V FS25108 - 400 - 99
Recommended HITACHI AC reactor
for fan inverter
Model Type
Model Type
55kW 380-480V ALI-75H2
55kW 380-480V NF-CEH7
75kW 380-480V ALI-120H2
75kW 380-480V NF-CEH7
(5) E lectrical equipment design temperature at
・HITACHI Zero phase reactor ZCL-A
transportation and storage : - 25℃ to + 55℃ and
: Quantity 4, number of penetration 1
for short periods not exceeding 24 hours at up to
for fan motor: Quantity 1, number of penetration 4
+ 70℃.
For non-CE applications, capacitive filter is usable
(6) Electrical equipment shall be capable of operating
to reduce the radiation noise.
correctly at altitudes up to 1000 m above mean
HITACHI CFI-H for 380-480V
sea level. If operating above 1000 m, contact the
local HITACHI distributor/master dealer or
representative office.
(7) SCCR : 5kA
70
8. INSTALLATION [Wiring diagram]
71
8. INSTALLATION [Wiring diagram]
72
8. INSTALLATION [Wiring diagram]
73
8. INSTALLATION [Wiring diagram]
74
9. MAINTENANCE
CAUTION
● Before servicing the air compressor, carefully read “1. SAFETY PRECAUTIONS”.
● Before servicing, disconnect the power to prevent an electric shock.
●T he inverter is still live immediately after disconnecting the power. Before servicing the instrument/control panel,
verify that the inverter’s charge indicators are off or wait 10 minutes after disconnecting the power.
● Before removing or disassembling any parts on the air compressor, stop it, disconnect the power and
make sure that the internal pressure of the air compressor has dropped to atmospheric pressure to
prevent high pressure air from blowing off and causing injury. Special attention must be paid to the
piping between the compressor check valve and stop valve located in the air discharge piping.
WARNING
The motor rotor contains a powerful magnetic field. This field can effect the operation of digital devices such as
watches, mobile phones etc. Assembly or handling of the rotor should not be attempted by personnel with cardiac
pacemakers, defibrillators or other implanted electronic medical device.
IMPORTANT
(1) If the annual operating hour is longer than 6,000h, follow the hours indicated in “Maintenance schedule A”.
(2) Unless otherwise specified, conduct the maintenance as it shows repeatedly.
75
9. MAINTENANCE [Standard maintenance schedule A]
76
9. MAINTENANCE [Standard maintenance schedule A]
4 Maintenance every 4 years (When annual operating hours are 6,000 hours or less)
Inspection Type
Maintenance part and item Action Remarks
time V M
DCBL controller cooling fan Replacement ● ○ ー The cooling fan on the panel is included.
Fan inverter cooling fan Replacement ● ー ○
Check valve (1/4 inch) (*2) Replacement ● ○ ○ Locate it on the oil-scavenging pipe from the shaft seal.
Oil temperature control valve Replacement ● ○ ○
Thermistor Inspection ● ○ ○
Coupling elastic body Replacement ● ○ ー It can be used further if appropriate.
(*2) 55kW only.
5 Maintenance every 8 years (When annual operating hours are 6,000 hours or less)
Inspection Type
Maintenance part and item Action Remarks
time V M
DCBL motor Inspection ● ○ ー Magnetic force
Main motor bearing (*3) Replacement ● ー ○
Mechanical seal Replacement ● ○ ○
Compressor airend bearing (*3) Replacement ● ○ ○
O-ring, airend Replacement ● ○ ○
Flange gasket, O-ring Replacement ● ○ ○
Oil separator tank O-ring Replacement ● ○ ○ Replace 1/2 stop valve O-ring at the same time
Smoothing capacitor, controller Replacement ● ○ ー
Each PCB for controller, Thyristor module ● ○ ー
Check/Clean/ Check for contamination and discoloration.
Control PCB, power supply PCB, Replace Replace as required. It can be used further if appropriate.
● ○ ○
communication PCB, touch panel
Electromagnetic contactor Inspection ● ○ ○ Replace as required
Check for contamination and discoloration.
Cooling fan inverter Check/Clean/Replace ● ○ ○
Replace as required. It can be used further if appropriate.
Battery Replacement ● ○ ○
(*3) For 1MPa specification, replace every 4 years.
(*4) Electric parts not described in the table are recommended to replace every 8 years.
77
9. MAINTENANCE [Standard maintenance schedule B]
78
9. MAINTENANCE [Standard maintenance schedule B]
5 Maintenance every 8 years (When annual operation hours are 3,000 hours or less)
Inspection Type
Maintenance part and item Action Remarks
time V M
DCBL motor bearing Inspection ● ○ ー Magnetic force
Main motor bearing Replacement ● ー ○
Compressor airend bearing Replacement ● ○ ○
O-ring, air end Replacement ● ○ ○
Flange gasket, O-ring Replacement ● ○ ○
Oil separator tank O-ring Replacement ● ○ ○ Replace 1/2 stop valve O-ring at the same time
Mechanical seal Replacement ● ○ ○
Smoothing capacitor, controller Replacement ● ○ ー
Each PCB for controller, Thyristor module ● ○ ー
Check/Clean/ Check for contamination and discoloration.
Control PCB, power supply PCB, Replace Replace as required. It can be used further if appropriate.
● ○ ○
communication PCB, touch panel
Electromagnetic contactor Inspection ● ○ ○ Replace as required
Check for contamination and discoloration.
Cooling fan inverter Check/Clean/Replace ● ○ ○
Replace as required. It can be used further if appropriate.
Battery Replacement ● ○ ○
(*3) Electric parts not described in the table are recommended to replace every 8 years.
79
9. MAINTENANCE [Air relief valve, Capacity control system]
IMPORTANT
● If the proper size air receiver tank is not installed, the
capacity control changes unloading to loading before
the oil separator pressure gauge indicates 0.3MPa.
● D o not operate the stop valve immediately after
stopping the air compressor. Otherwise the motor’s
operating frequency may fluctuate and/or the air relief
valve may operate.
1 Maintain the rated maximum discharge pressure
(ex. 0.7MPa). 4 Fully open the stop valve within 3 minutes. Verify
that the capacity control changes unloading to
2 Remove the front door and pull the ring connected
loading.
to air relief valve.
3 Verify that the air relief valve operates properly and 9.5.2 P-mode and I-mode
get a hand off of the ring. 1 Gradually close the stop valve installed on the
downstream side of the air receiver tank.
When the discharge pressure goes up to cut-out
CAUTION pressure, suction throttle valve is fully closed
(unloading). During the unloading, oil separator
During inspection of the operation of the air tank internal pressure is released.
relief valve, use the appropriate facial
2 During the unloading, fully close the stop valve.
protection. High pressure air containing dust
particles can cause severe injury. 3 Make sure the pressure in the oil separator tank is
stable within the range given in the following table.
Model 55kW 75kW
0.15 - 0.25
Unloading (0.7/0.85MPa)
MPa 0.09 - 0.15
pressure 0.25 - 0.3
(1.0MPa)
IMPORTANT
80
9. MAINTENANCE [Oil filter element]
Oil pan
CAUTION
● Don’t use the tightening tool, such as filter
wrench because the scratch and crack cause
the oil leak or burst.
● If the oil filter element clogs, circulating oil
quantity is reduced. This causes discharge
air temperature increasing and worse bearing
lubrication. As a result, this leads the air
compressor malfunction.
Replace 2 elements at the same time.
● Just after the air compressor is stopped, the
oil and surface of parts, such as oil filter
element, pipings, etc., are hot.
81
9. MAINTENANCE [Air intake filter element]
Air intake
Pull out. filter cover
Air intake filter
element
Snap-on fitting CAUTION
If atmospheric air contains car exhaust and
soot from incinerators and boilers, the air
intake filter element shall clog earlier than
usual. In this case, investigate the environment
where the air compressor is installed, and take
effective measures to intake the clean air such
as making the duct or changing the installation
location.
82
9. MAINTENANCE [Oil coolers]
IMPORTANT
Rear cover
If the cooler is heavily dirtied, a steam cleaning is
required. Contact the local HITACHI distributor/master
Fan duct (5) dealer or representative office for more information.
83
9. MAINTENANCE [Minimum pressure/check valve]
Adjustment screw
Check valve
spring
Check valve
body
Element
Head
84
9. MAINTENANCE [Oil separator element]
CAUTION
● P arts surface is hot after air compressor
stopped. Be careful not to get burned.
● Replace the two elements at the same time.
IMPORTANT
Square ring
[Figure B]
85
9. MAINTENANCE [Oil separator element]
9.10.2 R
eplacement of oil separator
Housing element
Replace the housing and square ring with the
element. The gasket comes with the element.
Element head
1 Verify that there is no damage, crack and scratch
Element on the surface of thread and square ring slot of the
element head. They may be potential of leaking.
Element Grind by fine abrasive paper and clean the surface
Square if required.
ring
2 Verify that there is no damage, crack and scratch
on the new housing.
End
plate 3 Apply the new oil of NEW SCREW OIL NEXT
Gasket onto the parts indicated in Figure A. Verify that the
Spread lubricant
gasket is set to the end plate properly. (Figure A)
[Figure A] 4 Silicon grease is applied on the surface of square
ring. Do not wipe the grease. Set the square ring
to the slot of the element head.
Housing
5 Set the element to the element head. Be careful
Gasket
Element
so that the gasket does not protrude. (Figure B)
End
plate 6 Set the housing to the element head. Be careful
Element so that the square ring does not protrude.
head
7 At first, tighten the housing with both hands. When
Square
ring Gasket hand tightening is hard to turn, tighten by the
Element special tools until housing contact to the element
head. (Figure C)
End
plate
8 Put the caution sticker on the housing front side.
Element
head
(Figure D)
[Figure B]
Caution
sticker
Clamp
Turn.
[Figure C] [Figure D]
86
9. MAINTENANCE [Replenishment of motor grease]
CAUTION
● M OTOR GREASE notice appears on the
touch panel and count-down starts 200
hours before shutdown.
Before shutdown, apply grease and press the Opposite side
button on the touch panel for more The bearing on the opposite side is shield type, so
than seven (7) seconds. greasing is not necessary.
The time until shutdown is reset, and monitor Replace the bearing according to 9.1, 9.2 and
display appears. 9.3.
● Be aware that greasing over the specified
amount may cause bearing overheat and/or
grease leakage, etc.
87
9. MAINTENANCE [Replenishment of motor grease]
9.11.2
The main motor bearings must be greased as ● Example of grease gun
following table. Grease following amount of RMS Lever-type grease gun (CH-400), Micro-Hose (pin
grease (Ref. No. 131) (Raremax Super by Kyodo Yushi). type SPK-1C) by Yamada Corporation
2 Draw the grease pan out, and if the used grease 2 Remove the rear cover and draw the grease pan
has been discharge, clean the grease pan as out, and if the used grease has been discharge,
required. clean the grease pan as required.
3 Close the front door. 3 Close the front cover and rear cover.
Greasing port for Greasing port for
main motor load side main motor opposite side
Grease pan
[Rear view]
Grease pan
[Front view]
CAUTION
●M OTOR GREASE notice appears on the touch panel and count-down starts 200 hours before shutdown.
Before shutdown, apply grease and press the button on the touch panel for more than seven (7)
seconds.
T
he time until shutdown is reset, and monitor display appears.
● Be aware that greasing over the specified amount may cause bearing overheat and/or grease leakage,
etc.
88
9. MAINTENANCE [DCBL motor, controller and fan inverter]
₂C
heck that the charge lamp of the controller and
fan inverter off. Check for abnormal overheat,
discoloration, abnormal odor, and contamination.
₃ Blow off the dust by dry air.
₄ D uring periodical maintenance, re-tighten the
terminals, check the fin dirt, conductor and
insulator for corrosion, and inspect/replace the
cooling fan and smoothing capacitor.
89
9. MAINTENANCE [Controller and fan inverter]
2S
ince fin cover and duct behind the control panel
are very hot soon after the air compressor is
stopped, wait until they are cooled down properly
Fin cover (1) before starting the work. Remove fin cover (1) and
the duct behind the control panel as shown in the
figure.
90
9. MAINTENANCE [Controller and fan inverter, Battery]
Fixing band
WARNING
Screw
A discharged battery may explode. Do not set
fire to it. Do not recharge it.
USB cover
CAUTION
The used battery shall be disposed of properly
in accordance with your local government
disposal regulations.
91
10. CAUTIONS FOR A LONG TERM OPERATION SUSPENSION
Make sure to proceed as following for the long term storage or suspension.
If the air compressor is not operated for 3 to 6 months, take actions indicated in below table. If the
air compressor is not operated for 6 to 12 months, special rust proof treatment is required. Contact
the local HITACHI distributor or master dealer or representative office for the detail.
If the air compressor is not operated for more than 12 months, special rust proof treatment is
required again.
Rotate the airend by hand Rotate the airend by hand Airend overhauling
(*1) Contact the local HITACHI distributor or master dealer or representative office for the detail.
CAUTION
● If the rust preventive actions (dry or/and seal) are not performed, it may cause the airend or bearing
trouble when the air compressor is restarted.
● If the actions “before operation” indicated in the table are not performed, it may cause the airend or
bearing drive unit, and motor trouble.
● If lubricant is not replaced or the lubricant is not flushed properly, it may cause earlier lubricant
deterioration, moreover this may result airend trouble or oil cooler earlier clogging.
92
11. RELOCATION AND DISPOSAL
11.1 Relocation
To relocate the product, contact the local HITACHI distributor/master dealer or representative office. Note in
particular that you need to replace the parts to relocate the air compressor ( ) from a 50 Hz area to a 60 Hz
area, and vice versa. Otherwise, the air compressor cannot be operated at the relocation site. Operating the air
compressor without parts replacement may cause failure of the air compressor.
11.2 Disposal
To dispose of the air compressor after long use, be sure to drain lubricating oil. It is dangerous if lubricating oil
leaks to the outside for some reason from a disposed air compressor. Contact the local HITACHI distributor/
master dealer or representative office.
● Disposal procedure of the DCBL motor
Before disposing the DCBL motor, magnetic rotor shall be heated to higher than 500℃ to demagnetize by the
equipment, such as gas burner or heating furnace.
Dispose the DCBL motor properly in accordance with your local government disposal regulations.
WARNING
The motor rotor contains a powerful magnetic field. This field can effect the operation of digital devices
such as watches, mobile phones etc. Assembly or handling of the rotor should not be attempted by
personnel with cardiac pacemakers, defibrillators or other implanted electronic medical device.
93
12. LIMITED WARRANTY AND AFTER-SALES SERVICE
12.1 Warranty
This limited warranty applies to products manufactured by Hitachi Industrial Equipment (Nanjing) Co., Ltd.
Warranty period
The warranty period is 12 (twelve) calendar months after the date of the product delivery or 18 (eighteen)
calendar months after the date of the product shipping (as indicated by the bill of lading), whichever passes
earlier.
HITACHI shall not liable for any indirect or consequential damages caused by the failed product, including any
lost production or sales.
Contact your distributor to obtain warranty services if necessary.
94
13. PARTS LIST
Airend
Ref.
No.
Description
003 028 004 002 009 001 Airend assembly
002 Casing
003 D-Casing
011 004 Male rotor
006 Female rotor
008 D-Cover
022
023
009 65 Roller bearing
011 50-3 Angular ball bearing (55kW)
011 60-3 Angular ball bearing (75kW)
016 038 012 50 Roller bearing
014 Bolt (75kW)
016 Cover
017 Cover
018 Bolt (55kW)
118 019 Bolt
008 018
020 Gasket
017 021 Gasket
022 Gasket
023 Retaining ring (1)
018 (55kW)
014 (75kW)
024 Retaining ring (2)
019 028 Knock pin
016 038 Spacer
118 Key
024
022
Ref.
No.
Description
003 028 004 002 009
001 Airend assembly
011
002 Casing
003 D-Casing
004 Male rotor
006 Female rotor
022 008 D-Cover
023
009 65 Roller bearing
011 50-3 Angular ball bearing (55kW)
016 038 011 60-3 Angular ball bearing (75kW)
012 25 Roller bearing
014 Bolt (75kW)
016 Cover
017 Cover
018 Bolt (55kW)
008 118
018 019 Bolt
017 020 O-ring
021 O-ring
022 O-ring
018 (55kW) 023 Retaining ring (1)
014 (75kW)
019 024 Retaining ring (2)
028 Knock pin
016
038 Spacer
118 Key
024
022
95
13. PARTS LIST
Motor
Ref.
No.
Description
007 C-casing
015 Mechanical seal
029 025 O-ring
121 015 007 126
026 O-ring
029 Knock pin
112 DCBL Motor
143 112
144 115 DCBL Motor thermistor
149 121 Spring fixture (3)
115 145 125 Safety cover (1)
026 126 Safety cover (2)
029 ※ 131 RMS grease (400g)
025
141 132 Vibration suppression rubber
125 141 Coupling
143 Rubber, coupling
144 Motor bearing (DE)
132 146 145 Motor bearing (ODE)
148
146 Motor fan
147 147 Motor base
148 Grease reservoir
149 Felt
132 ※Does not come with the product.
Ref.
No.
Description
007 G-casing
025 015 Mechanical seal
025 O-ring
029 142 127 026 O-ring
143 029 Knock pin
122
112 Motor
007 700 121 Spring fixture (3)
122 Gear stop plate
123 L-bolt
123
026 144 112 127 Guard
029
※ 131 RMS grease (400g)
123 132 Vibration proof rubber
122 141 145
140 121 015 140 Gear spacer (1)
141 Bull gear
142 Pinion gear
143 Gear spacer (2)
144 Motor bearing (DE)
145 Motor bearing (ODE)
148 148 Grease reservoir
148 700 Thermostat
132
132 ※Does not come with the product.
96
13. PARTS LIST
Fan • Cooler
391
55kW 75kW
391
390
163
151 390
164
155 Ref.
No.
Description
151 Fan motor
152 Mount, fan motor
152
153 Turbo fan
154 Bell-mouth
155 Fan shaft key
156 L nut
157 Spring washer
158 Flat washer
163 Bearing (ODE)
153
164 Bearing (DE)
390 Aftercooler
158
391 Oil cooler
157
156
154
Control valves
Ref.
No.
Description
203 Minimum pressure/check valve
204 O-ring
205 Minimum pressure valve piston
206 Check valve piston
204
205
206
97
13. PARTS LIST
099
074
104
083
104
Ref.
094 Description
075 No.
071 Suction throttle valve
092 098 107 (only 55kW)
072 Unloader case
076 074 Cover
075 Piston
071 076 Spring (1)
105 077 Valve seat
078 Shaft
079 Spring (2)
072
083 O-ring
090 Bush metal
090
092 Cap seal
077 097 094 O-ring
079 097 Air intake filter
098 Air intake filter element
099 Indicator
103 Band (1)
078 104 Pipe
105 Band (2)
107 Joint
Oil separator
Ref.
No.
Description
031 Vibration suppression rubber
032 Oil separator tank
056 034 Plug
035 O-ring
061 040 O-ring
046 Skirt
※063 051 Oil level gauge assembly
※064 052 Oil level gauge (single item)
201
054 O-ring
057
055 Bolt
056 Oil separator
057 Square ring
061 Air relief valve
※065 046 ※ 063 NEW SCREW OIL NEXT 4L
※ 064 NEW SCREW OIL NEXT 20L
※ 065 Special tool
040
066 Oil filter body
034 035 067 O-ring
192 1/2 Stop valve
196 O-ring
201 Element head
051 ※Does not come with the product.
067 066
055 054
052 032
192
031
98
13. PARTS LIST
Control piping
Ref.
No.
Description
227
55kW , 058 Thermistor (2)
059 Thermistor (1)
75kW 193 Check valve
203 Minimum pressure/Check valve
225 Pressure gauge
226 Pressure switch
227 Pressure sensor
240 229 Piping
244 240 Solenoid valve (20P)
P02 P03 244 Solenoid valve (20US)
203 P01
251 Orifice (1)
193 254 Orifice (2)
254 P04
225
251
058
226
229
059
75kW
227 Ref.
No.
Description
058 Thermistor (2)
059 Thermistor (1)
193 Check valve
203 Minimum pressure/Check valve
225 Pressure gauge
226 Pressure switch
227 Pressure sensor
240
229 Piping
240 Solenoid valve (20P)
244 P03
244 Solenoid valve (20US)
P02 193
203 P01 245 Solenoid valve (20VS)
251 Orifice (1)
P04 254 Orifice (2)
254
225
229
251
058
226
059
245
193
P06
P05
99
13. PARTS LIST
184
Oil piping 189
190
194 195 Ref.
No.
Description
033 Nipple
55kW 190
039 O-ring
186 184 042 Cover
P08 060 Oil temperature C.V
173 Check valve
194 195 179 Oil filter element
254 181 O-ring
184 O-ring
173 186 Oil piping (1)
187 Oil piping (2)
188 Oil piping (3)
189 Joint (1), elbow
190 Magnet rubber
194 O-ring
195 Plug
195 194 254 Orifice
179 181
P07
181
033
187
181
181 188
060
039 042
191
75kW 184
Ref.
No.
Description
190 033 Nipple
189
184 039 O-ring
194 195 042 Cover
P08
060 Oil temperature C.V
197
179 Oil filter element
254 181 O-ring
184 O-ring
194 195 186 Oil piping (1)
187 Oil piping (2)
188 Oil piping (3)
187 193
189 Joint (1), elbow
190 190 Magnet rubber
191 Joint (2), elbow
179 186
193 Check valve
194 O-ring
195 Plug
033 194 197 Check valve
181 181 195
P07 254 Orifice
181
188
181
060 039 042
100
13. PARTS LIST
184
Oil piping 189
190
194 195 Ref.
No.
Description
033 Nipple
039 O-ring
55kW 190
186 184 042 Cover
189 060 Oil temperature C.V
P08
173 Check valve
195 179 Oil filter element
194
254 181 O-ring
184 O-ring
173 186 Oil piping (1)
187 Oil piping (2)
188 Oil piping (3)
181 189 Joint (1), elbow
190 Magnet rubber
194 O-ring
195 Plug
195
179 194 200 Oil piping (4)
P07
254 Orifice
181 200
033
181
181 187
188
181
060
039 042
75kW
Ref.
Only 0.85/1.0MPa No.
Description
191
033 Nipple
039 O-ring
199
198 042 Cover
060 Oil temperature C.V
179 Oil filter element
191 181 O-ring
184 184 O-ring
189 186 Oil piping (1)
184
190 194 195 187 Oil piping (2)
197 188 Oil piping (3)
189 Joint (1), elbow
190 Magnet rubber
191 Joint (2), elbow
194 195 193 Check valve
187
194 O-ring
195 Plug
179 186 193 197 Check valve
190 198 Stop solenoid valve
200 Oil piping (4)
254 Orifice
033
194
181 195
P07
181 181 200
101
13. PARTS LIST
214
062
062
202
75kW
223
215
223
215
207
Ref.
214 510 No.
Description
062 O-ring
202 Discharge pipe (1)
207 Discharge pipe (2)
214 O-ring
215 Gasket
223 Magnet rubber
510 Discharge pipe (4)
062
062
202
102
13. PARTS LIST
408
096
407
400
417
75kW Ref.
No.
Description
096 Air intake cover
415 399 Maintenance cover (1)
400 Motor duct
414
405 Cover (4), cooler
412 406 Fan duct (6)
418
407 Mount (1), cooler
399 408 Mount (2), cooler
406 405
409 Mount (3), cooler
410 Fan duct (1)
411 Fan duct (2)
412 Fan duct (3)
416 413 Fan duct (4)
419 414 Fan duct (5)
410
415 Cover (1), cooler
413 416 Cover (2), cooler
399
411 417 Cover (3), cooler
418 Base, cooler
419 Rubber bush
096
408
409
407
400
400
103
13. PARTS LIST
Operation panel
269
266
262
276
280
274
277
264
265
275
278 279
264 Ref.
No.
Description
263
262 Operation panel
263 USB cover
264 Panel sheet
265 Operation circuit board
266 Cord tube, OPE
267 Cover
269 Rubber bush
270 OPE code
271 OPE code
272 OPE code
273 OPE code
274 OPE code
275 Connector
276 Touch panel
277 IT board
278 Band
279 Battery
280 E-Stop
104
13. PARTS LIST
Enclosure
437
432
438
455
430
433
427
429
453
479
449
447
451
449 426
441
450
442 448
452
445 431
434 425
477
420 443
475 444
423
421
Ref. Ref.
No.
Description No.
Description
436 420 Common base 438 Top panel (3)
435
421 Center front frame 441 Rear-center cover
428
422 Corner frame FL 442 Left-upper front panel
423 Corner frame FR 443 Rubber bush
424 Corner frame BL 444 Rubber bush
425 Corner frame BR 445 Exterior screw
426 Right panel 447 Model sticker
427 Left panel 448 NEXTⅡ name plate
428 Front door (1) 449 Color sticker
429 Rear panel 450 Fixing bracket (1)
430 Top panel (1) 451 Fixing bracket (2)
431 Operation panel 452 Fixing bracket (3)
432 Corner cap (1) 453 Piping bracket
433 Corner cap (2) 454 Cover, discharge pipe
434 Chain 455 Rubber bush
435 Door (2) 475 Fork slot cover
436 Magnet 477 Filter holder
437 Top panel (2) 479 Air intake filter
105
13. PARTS LIST
286
460
462 335
289
333
291
336
466
307 293
465 309 290
290
288
332 292 294
305 306
295
75kW 385 334
292
460
461
285 323
326
298
287
335
308 289
282
284 291
307
336
286 296
336
290 288
463 464
Ref. Ref.
No.
Description No.
Description
333
282 Control panel 308 Rubber bush
284 Fin cover (1) 309 Rubber bush
285 DCBL controller 323 Cooling fan, starter
466 286 Fin cover (2) 326 Guard, starter
106
13. PARTS LIST
55kW
300
461
385
460
332
306
299
301 335
333
345
334 336
288
291
462
466
465
308
309
307 461
300 385
460
306
299
308
301 335
293 288
462
291
466
465
309
309
332 463 464 Ref.
No.
Description
Ref.
Description
No. 323 Cooling Fan, starter
282 Control panel 326 Guard, cooling fan
288 Fan inverter 332 Cover, starter
291 Fan inverter cooling fan 333 Rubber bush
293 Terminal block 334 Reveral Phase Protector
295 Relay 335 Transformer
298 Control PCB 336 Relay
299 Electromagnetic contactor 385 Transformer
300 Electromagnetic contactor 460 Line filter
301 Electromagnetic contactor 461 AVR
305 Earth Leakage Breaker 462 AC Reactor
306 Support clasp 463 Current transformer
307 Rubber bush 464 Bus bar
308 Rubber bush 465 Ground bolt
309 Rubber bush 466 Handle
107
14. OPERATION RECORD LOGBOOK
Operation hour Inlet air Discharge Remarks
Total Discharge temperature temperature Lubricant
operation air ℃ ℃ replenish
Date hour pressure amount
Start Stop Control value Parts replacement, other special notes
Control value
h MPa 100℃ L
0 - 45
or lower
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
108
14. OPERATION RECORD LOGBOOK
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
. . : :
109
15. STANDARD SPECIFICATION
■ Air compressor specification
Model
Unit OSP-55VAN2 OSP-75VAN2
Item
Type of compressed gas - Air
Intake air pressure - Atmospheric pressure
Intake air temperature ℃ 0 - 45
Rated Discharge pressure MPa 0.7
specification Discharge air capacity m3/min 10.1 13.3
PQ WIDEMODE Discharge pressure MPa 0.6 0.85 0.6 0.85
ON Discharge air capacity m3/min 10.6 9.1 14.0 12.0
Working range of PQ wide mode function MPa 0.60 to 0.85
Discharge temperature ℃ Ambient temperature +15 or lower
Main motor nominal shaft power kW 55 75
Main motor type - 6-pole totally enclosed permanent magnet motor
Main motor insulation class - F class
Fan motor output
kW 1.5 2.2
(Specification plate value)
Fan motor type - 3-phase squirrel-cage induction, totally enclosed type
Fan motor insulation class - E class
Starting method - Soft starting
Voltage・Frequency - 3 phase 380/415V 50Hz
Motor turn down % About 30 to 105
Lubricating oil - NEW SCREW OIL NEXT (genuine synthetic oil)
Lubricating oil filling amount L 26 36
Total weight kg 1,230 1,405
Size (Width × Depth × Height) mm 2,000 × 1,200 × 1,800
NOTE
(1) Capacity is measured according to ISO 1217, 4th Edition, Annex C.
(2) Pressures are indicated as the gauge pressure.
(3) Earth leakage circuit breaker is out of scope of supply from Hitachi.
(4) Do not use the any lubricant other than the oil indicated above table.
(5) Hitachi may make improvements and/or changes in the appearance and/or specifications described in this publication at any time
without notice.
■ Controller specification
Main Motor Specification Fan Motor Specification
Output kW 55 75 1.5 2.2
Controller capacity kVA 78 107 2.8 4.1
400V
Rated output current A 120 165 3.7 5.5
class
Rated input current A 110 150 ー ー
110
15. STANDARD SPECIFICATION
111
Note the Air Compressor’s Specifications below for future reference.
Model OSP- kW Hz
HIA-745 2018.4
Printed in Japan