Comments Resolution Sheet

Contract No. 4400004078 SEC letter No: SEC/AT/HAIL-2CC/10632 Date: 30/09/2021


Al Toukhi Ref. No: H-AT-SEC-E10415 Date: 10/10/2021
CONVERSION OF HAIL-2 PP SIMPLE
Project Title CYCLE EXTENSION III TO COMBINED Doc/Dwg Code: HAIL2CC-00-BF-EDC-AT-0104 Rev: 01
CYCLE
Doc Name: Warranty Inspection Procedures for Transformers Doc status: NA
Item SEC Comments AT Response
No. SEC/AT/HAIL-2CC/10632
As per Contract, contractor shall submit the warranty inspection procedure Noted as applicable
which should include the proposed work, method statement, risk assessment
and proforma inspection templates but AT submitted only the suggestions for
the proposed work.
Following the contract item 4.6.3 (Electrical), inspection for transformer Noted
should be done according to the supplier recommended procedure (only for
routine tests).
Below missing tests & inspections shall also be added to the submitted
documents.
1 Oil sample should be taken to check (Di electric breakdown, color, Noted, one sample can be tested
neutralization number, power factor, water content, interfacial tension)
2 Gas analysis test in oil by taking sample for checking combustible dissolved Noted, one sample can be tested
gases in oil.
This was done during commissioning work and it is Not related to warranty inspection
Measurement of insulating resistance & polarization index of winding.
3
4 Capacitance and loss angle (Tan&) measurement of winding & bushings. This was done during commissioning work and it is Not related to warranty inspection
5 Voltage ratio measurement on each tapping position. This was done during commissioning work and it is Not related to warranty inspection
6 Measurement of winding resistance. This was done during commissioning work and it is Not related to warranty inspection
7 Impedance Voltage and load loss measurement This was done during commissioning work and it is Not related to warranty inspection

SEC

Page 1 of 2
Comments Resolution Sheet
Contract No. 4400004078 SEC letter No: SEC/AT/HAIL-2CC/10632 Date: 30/09/2021
Al Toukhi Ref. No: H-AT-SEC-E10415 Date: 10/10/2021
CONVERSION OF HAIL-2 PP SIMPLE
Project Title CYCLE EXTENSION III TO COMBINED Doc/Dwg Code: HAIL2CC-00-BF-EDC-AT-0104 Rev: 01
CYCLE
Doc Name: Warranty Inspection Procedures for Transformers Doc status: NA
Item SEC Comments AT Response
No. SEC/AT/HAIL-2CC/10632
8 No load loss and No load Current measurement. This was done during commissioning work and it is Not related to warranty inspection
9 Line Terminal ac withstand test with PD measurement. This was done during commissioning work and it is Not related to warranty inspection

10 Temperature test. This was done during commissioning work and it is Not related to warranty inspection
11 Induced voltage with stand test &Induced voltage test with PD measurement. This was done during commissioning work and it is Not related to warranty inspection
12 Measurement of single phase short circuit impedance with 60Hz, 380v This was done during commissioning work and it is Not related to warranty inspection
13 Measurement of single phase excitation current with 60 Hz, 380v This was done during commissioning work and it is Not related to warranty inspection
14 Magnetic Balance Test with 60 Hz, 380v This was done during commissioning work and it is Not related to warranty inspection
15 Frequency Response Test. This was done during commissioning work and it is Not related to warranty inspection
16 Testing all Mechanical protection devices and control circuits This was done during commissioning work and it is Not related to warranty inspection
17 Oil Leakage Test This was done during commissioning work and it is Visual inspection

SEC

Page 2 of 2