Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Materials System Specification

27-SAMSS-011 23 February 2013


Fire, Smoke, and Combination Fire-Smoke Dampers
Document Responsibility: HVAC Standards Committee

Saudi Aramco DeskTop Standards


Table of Contents

1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 Terminology.................................................... 4
5 Basic Requirements....................................... 8
6 Inspection and Testing................................. 14
7 Delivery, Storage and Handling................... 15

Appendix A – Damper Data Table...................... 17


Appendix B – Form 175-270500......................... 18
Appendix C – UL Marking................................... 19

Previous Issue: 10 November 2012 Next Planned Update: 14 May 2016 Page 1 of 20
Revised paragraphs are indicated in the right margin
Primary contact: Hamid, Adel Sulaiman on +966-3-8809593

Copyright©Saudi Aramco 2013. All rights reserved.


Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

1 Scope

1.1 This Specification covers the minimum mandatory requirements of Fire, Smoke
and Combination Fire-Smoke Dampers for HVAC System.

1.2 This specification is applicable for the following 9COMs:

1.2.1 6000013336 – Combination Fire-Smoke Damper

1.2.2 6000001863 – Fire Damper

1.2.3 6000014320 – Smoke Damper

2 Conflicts and Deviations

2.1 Any conflicts between this specification and other applicable Saudi Aramco
Materials System Specifications (SAMSSs), Engineering Standards (SAESs),
Standard Drawings (SASDs), or industry standards, codes and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Consulting Services Department, Saudi Aramco, Dhahran.

2.2 Direct all requests to deviate from this specification in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Consulting Services Department of
Saudi Aramco, Dhahran.

2.3 All deviations from this specification shall be separately listed by the Vendor in
his quotation and shall refer to the relevant paragraph numbers.

3 References

Material or equipment supplied to this specification shall comply with the latest edition
of the references listed below, unless noted otherwise.

3.1 Saudi Aramco References

Saudi Aramco Engineering Procedure


SAEP-302 Instructions for Obtaining a Waiver of a Mandatory
Saudi Aramco Engineering Requirement

Saudi Aramco Engineering Standards


SAES-K-001 Heating, Ventilating and Air Conditioning (HVAC)
SAES-K-100 Saudi Aramco Mechanical (HVAC) Code

Page 2 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

SAES-K-101 Regulated Vendor List (RVL) for HVAC Equipment

Saudi Aramco Inspection Requirements


Form 175-270500 Fire, Smoke and Combination Fire-Smoke Dampers

3.2 Industry Codes and Standards

Sheet Metals and Air Conditioning Contractors National Association


SMACNA Ducts Construction Standards Metal & Flexible,
3rd Edition 2005
SMACNA Fire, Smoke and Radiation Damper Installation
Guide

National Fire Protection Association


NFPA 80 Standard for Fire Doors and Other Opening
Protectives
NFPA 90A Standard for the Installation of Air Conditioning
and Ventilation System
NFPA 92A Recommended Practice for Smoke-Control System
NFPA 92B Smoke Management Systems in Malls, Atria and
Large Areas
NFPA 101 Life Safety Code
NFPA 105 Standard for the Installation Smoke Door Assemblies

Underwriters Laboratory Standards


UL 555 Standard for Fire Dampers
UL 555S Standard for Fire-Smoke Dampers
UL 33 Standard for Heat Responsive links for Fire-
Protection Service

International Codes
IBC International Building Code
IMC International Mechanical Code
ASHRAE ASHRAE Handbooks

Page 3 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

4 Terminology

Actuator: An electric or pneumatic device which drives the damper open or closed.
It is often referred to as a damper operator or damper motor and is integral to the proper
operation of the damper. Actuators used with Smoke, Fire-Smoke dampers are spring
return type which returns to their normal position when power is removed. The actuator
shall be UL listed.

Area Separation Wall: A wall of fire-rated construction (expressed in hours) which


serves to divide the floor area of a building into acceptable area limits as set forth in the
applicable code.

Blade Axle: Is the shaft that supports the blade and extends through the frame.

Blade Edge Seal: A strip of material applied to the edge of the blade to minimize air
leakage between blades. Blade edge seals are typically made of flexible silicone rubber
or stainless steel. This seal shall be mechanically attached to blade edge. Glue or grip
type seals are not acceptable.

Blade Stop: It is a metal strip attached to the top and bottom parts of the frame that
provides a surface for the blades to stop against in the closed position. They also
minimize air leakage at the top and bottom of the frame.

Breakaway Connection: A joint connecting a damper sleeve / collar and attached


ductwork which will allow collapse of the ductwork during a fire without disturbing the
integrity of the damper.

Ceiling Radiation Damper: Is a device used to protect HVAC openings in fire rated
horizontal ceiling assemblies. A ceiling damper closes automatically to restrict the
passage of flame and heat.

Collar: is a transitional connector between the damper sleeve and HVAC system.
Collars can be round, oval or square/rectangular.

Combination Fire-Smoke Damper: Is a device that functions as both fire damper and
smoke damper.

Corridor Damper: Is a fire-smoke damper intended for use where air ducts penetrate
or terminate at horizontal openings in the ceilings of interior (tunnel) corridors.

Damper: used in this specification to mean either of the following, Fire Damper;
Smoke damper or Combination Fire-smoke Damper.

Draft Stop: A continuous membrane used to subdivide a concealed space to restrict the
passage of Smoke, Heat and Flames.

Page 4 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

Drive Blade: Is a blade connected to the jackshaft and is the source of actuation for the
other blades. Actuation force is transmitted through the jackshaft to the drive blade and
through the linkage to the other blades.

Electric Fuse Link (EFL): Is an electric, resettable, quick release device which allows
the damper to close upon a rise in temperature. The EFL replaces “old fashioned”
fusible rods and is used in conjunction with an electric actuator.

Electro-Pneumatic (EP) Switch: Is a device which allows electricity to control a


pneumatic actuator. EP’s are required when utilizing pneumatic actuators with ELFs.

Fire Damper: A normally open damper installed in an air distribution system designed
to close automatically upon detection of heat, to interrupt migratory air flow and to
restrict the passage of flames.

Fire dampers are evaluated for use in either of the following conditions:
a) Static Application – For HVAC Systems that are automatically shut down in
the event of a fire or for air transfer openings in walls or partitions.
b) Dynamic Application – For HVAC Systems that are operational during a fire.

Damper Sleeve: A steel enclosure surrounding a fire damper, in an air passage


penetrating a fire rated barrier mounted in such a manner that disruption of attached
ductwork, if any will not impair operation of the fire damper sleeve.

Fire Rated Ceiling: A ceiling tested for fire resistance as part of a floor-ceiling, roof-
ceiling or floor-ceiling-roof assembly.

Fire Rated Partition: A partition having an assembly of materials that will afford a
given fire resistance rating (expressed in HOURS) to impede the spread of fire from one
area to another.

Fire Separation Wall: A fire resistance rated wall, having protective openings that
restrict the spread of fire and extend continuously from the foundation to or through the
roof, with sufficient structural stability under fire conditions, to allow collapse of
construction on either side without collapse of the wall.

Floor-Ceiling or Roof-Ceiling Assembly: A form of construction comprised of floor-


ceiling or roof-ceiling as an assembly which when fire tested as a unit, has been
assigned a fire endurance rating expressed in hours. It is commonly termed as floor-
ceiling assembly.

Heat Responsive Link: A device that holds a fire damper or fire door in an open
position until a designated ambient temperature is reached, wherein the fire damper or
door is released to close. The device may be a soldered type, strut type, glass bulb type

Page 5 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

or bi-metallic metal as designed by UL 33, Standard for Heat Responsive links for Fire-
Protection Service.

Heat Stop: A method by which temperature rise is retarded for ceiling openings in a
fire rated floor-ceiling or roof-ceiling assembly. (Commonly used methods are ceiling
dampers, hinged damper at duct collar inlet, UL Fire Resistance Directory Protection
Systems A and B and duct outlet protection covers.)

Jackshaft: Is a (12 mm) ½” solid steel rod or 1” hollow steel tube used to connect the
actuator to the drive blade on fire-smoke dampers. The jackshaft is mechanically
attached to the drive blade. A jackshaft is also used to connect multiple section
dampers together so they work as a single unit.

Jamb Seal: Is a strip of material applied to the gap between the damper frame and the
end of the blade which minimizes air leakage through that area. Jamb seals shall be
made of compressible stainless steel.

Linkage Assembly: Stainless steel linkage bar, galvanized steel linkage brackets, axles
and knee lock used to interconnect all the blades of a damper. The linkage is either
concealed within the damper frame or exposed in the airstream.

Mullion Damper: A separate steel member or members used to join dampers in a


multiple damper opening, either horizontally or vertically.

Occupancy Separation: it is a wall, partition, floor-ceiling assembly or roof ceiling


assembly of fire-rated construction, so located as to separate or partition off portions of
a building having different fire potentials or safety requirements based on the use or
occupancy of such areas.

Plenums: A compartment or chamber to which one or more air ducts are connected
and that forms part of the air distribution system.

Air-Handling Unit Room Plenum - An individual room containing an air-handling


unit(s) used to gather air from various sources and combine the air within the room
for returning to the air-handling unit.

Apparatus Casing Plenum - A sheet metal construction attached directly to a fan


enclosure, fan coil unit, air handling unit, or furnace bonnet for the purpose of
connecting distribution ducts.

Ceiling Cavity Plenum - The space between the top of the finished ceiling and the
underside of the floor or roof above where used to supply air to the occupied area,
or to return or exhaust air from the occupied area.

Raised Floor Plenum -The space between the top of the finished floor and the
underside of a raised floor where used to supply air to the occupied area, or to return

Page 6 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

or exhaust air from the occupied area.

Pneumatic Fuse Link (PFL): A pneumatic quick release device which allows the
damper to close upon achieving the set point temperature. The PFL is used in
conjunction with a pneumatic actuator.

Position Indication Switch: A device that provides the ability to check the damper
blade position from a remote location.

Retaining Angle: Framed retaining angles attach to the sleeve on both sides of the fire
rated floor, wall or partition to secure it in place. The framed retaining angle must also
cover the openings between the outside of the sleeve and the inside of the hole in the
fire rated barrier. Framed retaining angles do not attach to the fire rated barrier.

Sleeve: A steel box, open on both ends, which encloses a fire; smoke or combination fire-
smoke damper. It shall be an integral part of the damper assembled by the manufacturer.
It is required in order to install the dampers properly on the fire separation wall.

Smoke Barrier: A continuous membrane, either vertical or horizontal such as a wall,


floor or ceiling assembly that is designed and constructed to restrict the movement of
smoke. A smoke barrier may or may not have a fire resistance rating. Such barriers
may have protected openings.

Smoke Control Zone: A space within a building enclosed by smoke barriers on all
sides, including the top and bottom that is part of a zoned smoke-control system.

Smoke Damper: Is a device to resist the passage of smoke which is arranged to operate
automatically, controlled by a smoke detection device, may be required to be positioned
manually from a remote command station, is rated for leakage at specific static pressure
ranges and may have a temperature rating in such case it shall be so marked.

A smoke damper may be a fire damper or a damper serving other functions, if its
location lends itself to be multiple functions. A combination fire and smoke damper
shall meet the requirements of both test standards (UL 555 and UL 555S).

Some smoke dampers are rated for use as volume control dampers, they shall be so marked.

Smokeproof Enclosure: as defined by the NFPA 101, Life safety code, a stair
enclosure is designed to limit the movement of products of combustion produced by a
fire. The smokeproof enclosure must be a continuous stair enclosed from the highest
point to the lowest point, enclosed by two-hour rated fire barriers.

Transition: Is a connection which allows a rectangular damper to be fastened to a


round or oval duct.

Page 7 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

Zoned Smoke Control: Is a smoke-control system that includes smoke exhaust for the
smoke zone and pressurization for all contiguous smoke-control zones. The remaining
smoke-control zones in the building also may be pressurized.

5 Basic Requirements

5.1 General

5.1.1 All dampers shall comply with the requirements of the project
specification / Issued for Construction (IFC) Drawings, Damper
Schedule and latest revision of Fire, Smoke and Radiation Damper
Installation Guide of SMACNA.

5.1.2 All dampers shall be supplied / delivered at the project site complete
with all required accessories for installation by the manufacturer but
not limited to the following: duct sleeve, actuators, retaining angles,
fusible links, etc.

5.1.3 All dampers shall be installed in accordance with the latest revision of
Fire, Smoke and Radiation Damper Installation Guide of SMACNA or
manufacturer’s recommendation, whichever is most stringent.

5.1.4 Vendor / Manufacturer for dampers shall be an approved Saudi


Aramco source.

5.1.5 Vendor / Manufacturer and record number shall be listed on the online
UL Directory.

5.1.6 Model number, type, mounting, fire rating, and single or multiple
sections shall be as listed on the online UL Directory.

5.1.7 Smoke and Combination Fire-Smoke damper shall bear UL Classified


label indicating leakage class rating.

5.1.8 Damper size shall not exceed the listed size (H x W) on the online
UL Certification Directory.

5.1.9 All damper accessories shall be UL compliant.

5.1.10 Multiple section dampers shall be factory / manufacturer assembled.

5.1.11 Approved damper shall be either curtain or multi blade type.

5.1.12 Blade material for approved damper shall either be galvanized or


stainless steel.

Page 8 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

5.1.13 All dampers shall not be modified in the field / project site or at the
contractor’s workshops. All required modification shall be done by the
manufacturer with UL prior consent and approval.

5.1.14 Dampers used for the protection of openings in walls, partitions, or


floors with fire resistance ratings of less than 3 hours shall have a
minimum of 1-½ hour fire protection rating.

5.1.15 Dampers used for the protection of openings in walls, partitions, or


floors with fire resistance ratings of 3 hours or more shall have no less
than 3 hour fire protection rating.

5.1.16 Designers shall consider the following when selecting and applying
smoke or fire-smoke dampers:

5.1.16.1 Leakage Rating


a) Class I (Lowest Leakage)
b) Class II
c) Class III (Highest Leakage)

5.1.16.2 Elevated Temperature Rating


a) 250°F
b) 350°F

5.1.16.3 Operational Rating


a) Fire dampers shall be classified for dynamic closure
with an approved actuator at a minimum air velocity
of 2000 fpm and against a minimum static pressure of
4 ” wg. (1 kPa).
b) Dampers shall be rated based on the conditions they
will be exposed to in their application.

5.1.16.4 Blade Design


a) Triple vee-groove blades shall be used in HVAC
systems with velocities up to 2,000 fpm.
b) Airfoil blades shall be used in HVAC systems with
velocity greater than 2,000 fpm.
c) Smoke damper blades shall be designed as follows:
1. Airfoil profile, single piece and double skin.

Page 9 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

2. Action shall be either opposed or parallel.


3. Orientation shall be either vertical or horizontal.
4. Material shall be minimum of 14 gauge
galvanized steel.
5. Blade width maximum shall be 6 inches (152 mm).

5.1.17 Damper shall bear the official “UL Classified” sticker with the
following data / information as a minimum:
a) Record / File Number
b) Fire Resistance Rating
c) Type of System (Dynamic or Static)
d) Company (Manufacturer) Name / Logo (optional)

5.1.18 Smoke Damper


Smoke damper specific requirements are as follows:
a) Linkage shall be concealed in frame.
b) Mounting is either in the vertical or horizontal.
c) Provision of two position indicator switches linked directly to
damper blades. This position switch shall remotely provide
indication of damper blade position.

5.1.19 Combination Fire-smoke damper

Combination fire-smoke damper specific requirements are as follows:


a) Maximum allowable static pressure drop across a combination
fire-smoke damper shall not exceed 0.1” wg at a face velocity of
1,000 fpm on a 24” x 24” section.
b) Combination fire-smoke damper and actuators shall have a
UL 555S elevated temperature rating of either 250°F (121°C) or
350°F (177°C) depending on application.
c) Actuator shall be an integral part of the CFSD assembly and shall be
same as used in obtaining UL Classification by the manufacturer.
d) Provision of UL compliant controlled closure quick detect heat
activated release device. Use of instantaneous damper fusible
link release device is not allowed.

Page 10 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

e) Combination fire-smoke damper shall be provided with factory


mounted sleeves.
f) Sleeves shall have factory mounted access doors.

5.2 Components

5.2.1 Construction

5.2.1.1 The frame shall be made not less than rolled formed
ASTM A653/A653M, Grade 90 galvanized sheet or 316L
stainless steel sheet.

5.2.1.2 Blades shall be not less than the interlocking type either
ASTM A653/A653M, Grade 90 galvanized steel or 316L
stainless steel.

5.2.2 Fusible Link

5.2.2.1 Shall meet requirements of UL 33, Standard for Heat


Responsive links for Fire-Protection Service.

5.2.2.2 Shall have a minimum set point of 165°F (74°C) for


standard applications.

5.2.2.3 Shall have a minimum set point of 212°F for generator


exhaust.

5.2.3 Mounting

5.2.3.1 Dampers shall be mountable either vertical, horizontal or


both vertical & horizontal positions.

5.2.3.2 Damper mounting signs shall be provided on curtain type


dampers.

5.2.4 Closure Springs

5.2.4.1 Fire damper closure springs shall be made of not less than
304 stainless steel.

5.2.4.2 Closure springs shall be either constant force type or spring


clip type.

Page 11 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

5.2.5 Actuators

5.2.5.1 All electric or pneumatic dampers shall be supplied with a


factory mounted actuator.

5.2.5.2 Actuators shall be UL compliant as an assembly of the


damper.

5.2.5.3 All actuators shall be mounted on an easily accessible


location for testing and maintenance.

5.2.5.4 Actuators shall be listed for dedicated use in fire-smoke


application.

5.2.5.5 Actuators shall comply with the requirements of UL 555S.

5.2.6 Duct Sleeve

5.2.6.1 Dampers shall be supplied with factory mounted sleeves.

5.2.6.2 Sleeves shall extend from the face of the fire separation
wall to the breakaway joints as follows:
a) Not to exceed 6 inches (152 mm) on sleeve side
having no factory installed access door nor a factory
installed actuator.
b) Not to exceed 16 inches (406 mm) on sleeve side
having factory installed access door or a factory
installed actuator.

5.2.6.3 Steel sleeve shall be constructed in accordance with


Table 5-2 “Recommended Minimum Sleeve Thickness for
Fire Dampers” of the latest edition of SMACNA’s “FIRE,
SMOKE and RADIATION DAMPER INSTALLATION
GUIDE FOR HVAC SYSTEM”.

5.2.6.4 Steel sleeve shall extend far enough beyond the wall to be
able to properly install the necessary retaining angles, duct-
to-sleeve connection, access doors, actuators and any other
required options.

5.2.6.5 For curtain type fire dampers the damper sleeve shall
extend a minimum of 4” on both sides of the wall.

Page 12 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

5.2.6.6 Damper sleeve shall have an expansion clearance minimum


⅛ inch per linear foot (10 mm per linear meter) of damper -
both dimensions (¼” (6 mm) minimum) not to exceed 1”
(25.4 mm).

5.2.6.7 Secure damper to sleeves on 8” centers (203 mm) with:


a) ½” (12 mm) long welds
b) ¼” (6 mm) bolts and nuts
c) No. 10 sheet metal screws
d) Minimum 3/16” (5 mm) steel rivets.
e) The size and spacing requirements may differ by
damper manufacturer. (Consult Manufacturer’s
installation instruction for specifics.)

5.2.6.8 Sleeves shall be provided integral with dampers.


These sleeves shall be factory installed as a single assembly
with the corresponding damper.

5.2.7 Retaining Angle

5.2.7.1 Retaining angle shall be minimum 1-½” x 1-½” x 16 ga


(40 mm x 40 mm x 1.6 mm).
a) Dampers shall be provided with factory retaining
angles.
b) Retaining angles shall overlap structure opening
minimum 1 inch and cover corners of openings in
accordance with manufacturer’s UL listing.
c) 16 ga shall be the minimum thickness for retaining
angles. For larger dampers heavier gage may be
required as recommended by the manufacturer.

5.2.7.2 Retaining angles shall be secured to the sleeves only on 8”


centers with:
a) ½” (12 mm) long welds
b) ¼” (6 mm) bolts and nuts
c) No. 10 sheet metal screws
d) Minimum 3/16” (5 mm) steel rivets

Page 13 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

e) The size and spacing requirements may differ by


damper manufacturer. (Consult Manufacturer’s
installation instruction for specifics).

5.2.8 Transition Options

5.2.8.1 Rectangular dampers are constructed 2” larger than the duct


dimensions and provided with a factory sleeve.

5.2.8.2 The sleeve is transitioned at each end.

5.2.8.3 Approved and appropriate collar depending on duct size


and shape shall be used.

5.2.8.4 Rectangular dampers are transitioned with rectangular


collars to achieve a higher damper net free area.

5.2.9 Bearings

5.2.9.1 Bearings shall be of the self-lubricating type.

5.2.9.2 Bearings shall be of 304 stainless steel or better.

5.2.9.3 Bearings shall rotate in extruded hole in the frame.

5.2.10 Seal

5.2.10.1 Seal material shall be made of either approved flexible


silicone rubber or approved stainless steel or of better material.

5.2.10.2 Seal shall be mechanically attached to blade edge.

5.2.10.3 Use of glue or grip type seals is not allowed.

6 Inspection and Testing

6.1 Inspection

Inspection of manufactured products shall include the following:

6.1.1 Ensure all shipping documents including Installation; Operation and


Maintenance manuals are provided.

6.1.2 Inspect for shipping damage.

6.1.3 Inspect compliance with required size, type and model.

Page 14 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

6.1.4 Inspect orientation of installed damper as stated in damper label.

6.1.5 Inspect for obstruction that could interfere with operation of damper
and complete closure.

6.1.6 Dampers with actuators shall be inspected for loose linkage and
tightened accordingly.

6.1.7 Clean damper blades as per manufacturers’ recommendations.


Petroleum based cleaners shall not be used.

6.1.8 Inspect damper and actuator via repetitive (not less than three times)
opening and closing fully.

6.1.9 Ensure dampers are delivered complete with the accessories as


required above. This includes but is not limited to the damper sleeves,
retaining angles, actuators, fusible links, access doors, etc.

6.1.10 Ensure that the official UL Classified and manufacturer’s labels are
affixed on the damper.

6.2 Testing

Perform functional test for complete opening and closure of the damper blades.

7 Delivery, Storage and Handling

7.1 Delivery

Deliver materials to site in manufacturer’s original, unopened containers and


packaging, with labels clearly indicating manufacturer, material, and location of
installation.

7.2 Storage

Store materials in a dry area indoors, protected from damage, and in accordance
with manufacturer’s instructions.

7.3 Handling

7.3.1 Handle dampers using the frame or sleeve.

7.3.2 Do not lift or move dampers using blades, actuator or jackshaft.

7.3.3 Handle and lift dampers in accordance with manufacturer’s instructions.

Page 15 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

7.3.4 Protect materials and finishes during handling and installation to prevent
damage.

Revision Summary
14 May 2011 New Saudi Aramco Materials System Specification.
10 November 2012 Editorial revision to change FD, SD & CFSD from max 17 inches to min 16 inches.
23 February 2013 Editorial revision due to typo in internal static pressure drop in CFSD of incorrect value of
0.03"wg instead of correct value of 0.1" wg.

Page 16 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

Appendix A - Damper Data Table


MM, DD, YYYY
BI / JO Number: Project Name / Description:
Project Location:
Contractor: Transmittal Reference No.:

Damper Blade
Required Size

Leakage Class
Damper Type

Application

Number of
PROPOSAL
Fire Rating

Mounting

Location
Damper

Damper
(Length x Height)

Section
Bldg
QTY
Location
mm inches Manufacturer Model

Legend:
Damper Type: Damper Mounting: Leakage Class: Damper Blade Location:
A. Fire Damper A. Horizontal A. Class I A. In Air Stream
B. Smoke Damper B. Vertical B. Class II B. Out of Air Stream
C. Fire-Smoke Damper C. Class III
Fire Rating: Damper Application: Number of Sections:
A. 1-½
A. Dynamic A. Single Section
Hr
B. 3 Hr. B. Static B. Multiple Section

Page 17 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

Appendix B - Form 175-270500

REVISION: 05/11 CODE NUMBER: PAGE:


INSPECTION & TESTING REPLACES: New IR270500
REQUIREMENTS
SAUDI ARAMCO FORM-175
SCOPE: Fire, Smoke, and Combination Fire-Smoke Dampers PURCHASE ORDER NUMBER:

TEST and INSPECTION PER: 27-SAMSS-011 and ITEM NUMBER(s):


Specifications As Noted Below.

(1) VISUAL INSPECTION / WITNESSING BY BUYER REPRESENTATIVE (Note 1 )

(2) CERTIFICATES / RECORDS TO BE CHECKED BY BUYER REPRESENTATIVE


LINE
NO (3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
Pre-Fabrication / Pre-Production Requirements Specification Details / Notes:

01 X Material Test Report Per 27-SAMSS-011


02 X Design and Drawing Per 27-SAMSS-011
03 X Manufacturer for Dampers Manufacturer shall be listed on the online UL directory.
In-Process Inspection & Testing Requirements

UL classified Model Number, outing position, size


04 X X limitation, Number of sections, Fire rating(hours), Leakage Per 27-SAMSS-011 / UL555 /UL555S
Class rating
05 X Damper Blade location Per 27-SAMSS-011 and approved drawing.
06 X Components/Accessories Per 27-SAMSS-011 and PO requirement
07 X Damper data table Per 27-SAMSS-011 Appendix-A
08 X Size , type and Model Per 27-SAMSS-011

Final Inspection & Testing Requirements

09 X X Workmanship, Components, and Dimensions Per 27-SAMSS-011 and PO requirement


10 X Marking , UL sticker Per 27-SAMSS-011 Appendix-C
11 X Painting, Tagging and shipment Per 27-SAMSS-011
12 X Storage, Handling and delivery Per 27-SAMSS-011
13 X Functional test Per 27-SAMSS-011. Verify opening and closure of damper blades.

Additional / Supplementary Requirements

14 X Installation, Operation and Maintenance manual Per 27-SAMSS-011 and PO requirement

Notes:
(1) May only be waived by the responsible Saudi Aramco, ASC, or AOC Inspection Offices.
(2) See form IR000003 for instructions on using this form.

Page 18 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

Appendix C - UL Marking

UL Classification Mark

This Mark appears on representative samples of products that UL has evaluated but only
with respect to specific properties, a limited range of hazards, or suitability for use under
limited or special conditions. Typically, products Classified by UL fall into the general
categories of building materials and industrial equipment. Examples of types of
equipment Classified by UL include immersion suits, fire doors, protective gear for fire
fighters and industrial trucks.

Just like the UL Listing Mark, there are also three variations of UL's Classification
Mark: one used only in the United States, one used only in Canada and one for both the
United States and Canada. The C-UL Classification Mark is applied to products for the
Canadian market. The products with this type of Mark have been evaluated to Canadian
standards for a specific hazard or property. The optional C-UL-US Classification Mark
indicates compliance with both Canadian and U.S. requirements. UL encourages
manufacturers distributing UL Classified products evaluated for both countries to use
this combined Mark, but they may continue using separate UL Classification Marks for
the United States and Canada.

In the Classification service, UL determines that a manufacturer has demonstrated the


ability to produce a product complying with UL's requirements with respect to one or
more of the following:
 Specific risk, e.g., casualty, fire, etc.
 Performance under specific conditions
 Compliance with regulatory codes
 Compliance with specific standards such as international standards
 Other condition, as determined by UL

All of the products carrying a UL Classification Mark are covered by UL's Follow-Up
Services program to verify that products carrying the UL Classification Mark continue to
be manufactured in compliance with UL's safety requirements. A UL Classification
Marking that appears on a product typically consists of four required elements:

Page 19 of 20
Document Responsibility: HVAC Standards Committee 27-SAMSS-011
Issue Date: 23 February 2013
Next Planned Update: 14 May 2016 Fire, Smoke, and Combination Fire-Smoke Dampers

 “UL in a circle” symbol


 Word "Classified"
 Product name or company name/file number
 Issue/serial number or alphanumeric control number

Without Manufacturer’s Name and Logo

Page 20 of 20

You might also like