DIESEL GENERATOR SET

PRIME
1600 ekW 2000 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT 3516B TA DIESEL ENGINE
• Low fuel consumption • Reliable, rugged, durable design
• Field-proven in thousands of applications
FULL RANGE OF ATTACHMENTS worldwide
• Wide range of bolt-on system expansion • Four-stroke-cycle diesel engine combines
attachments, factory designed and tested consistent performance and excellent fuel
• Flexible packaging options for easy and cost economy with minimum weight
effective installation
CAT SR4B GENERATOR
SINGLE-SOURCE SUPPLIER • Designed to match the performance and output
• Fully prototype tested with certified torsional characteristics of Caterpillar diesel engines
vibration analysis available • Single point access to accessory connections
• UL 1446 recognized Class H insulation
WORLDWIDE PRODUCT SUPPORT
• Caterpillar® dealers provide extensive post sale CAT EMCP 3 SERIES CONTROL PANELS
support including maintenance and repair • Simple user friendly interface and navigation
agreements • Scalable system to meet a wide range of
• Caterpillar dealers have over 1,600 dealer branch customer needs
stores operating in 200 countries • Integrated Control System and Communications
• The Cat® S•O•SSM program cost effectively detects Gateway
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products
®

PRIME 1600 ekW 2000 kVA


50 Hz 1500 rpm 400 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet • Single element canister type air cleaner • Dual element & heavy duty air cleaners (with
• Service indicator pre-cleaners)
• Air inlet adapters & shutoff
Exhaust • Dry exhaust manifold • Mufflers and Silencers
• Flanged faced outlets • Stainless steel exhaust flex fittings
• Elbows, flanges, expanders & Y adapters
Fuel • Secondary fuel filters • Water separator
• Fuel priming pump • Duplex fuel filter
• Flexible fuel lines
• Fuel cooler*
*Not included with packages without radiators
Generator • Class H insulation • Oversize & premium generators
• Class F temperature (105ºC prime/130ºC standby)
• Winding temperature detectors(select models)
• Anti-condensation space heaters
Power Termination • Bus bar (NEMA and IEC meachanicallug holes) • Circuit breakers, UL listed, 3 pole with shunt trip, 80%
-right side standard or 100% rated, choice of trip units, manual or
• Top and bottom cable entry electrically operated (low voltage only)
• Circuit breakers, IEC compliant, 3 or 4 pole with shunt
trip (low voltage only), choice of trip units, manual or
electrically operated
• Shroud cover for bottom cable entry
• Power terminations can be located on the left and/or
rear as an option. Also, multiple circuit breakers can
be ordered (up to 3)
Governor • ADEM™ 3 • Load share module

Control Panels • User Interface panel (UIP) - rear mount • EMCP3.3


• EMCP3.1 Genset Controller • Option for right or left mount UIP
• Voltage and Speed adjust • Local & remote annunciator modules
• AC&DC customer wiring area (right side) • Load share module
• CAT digital voltage regulator (CDVR) with KVAR/PF • Discrete I/O module
control, 3-phase sensing • Generator temperature monitoring & protection
• Reactive droop
• Emergency Stop Pushbuttom
Lube • Lubricating oil and filter • Oil level regulator
• Oil drain line with valves • Deep sump oil pan
• Fumes disposal • Electric & air prelube pumps
• Gear type lube oil pump • Manual prelube with sump pump
• Duplex oil filter
Mounting • Structual steel tube • Isolator removal
• Anti-vibration mounts (shipped loose) Spring-type isolator, zone 4
Starting/Charging • 24 volt starting motor(s) • Battery chargers (10&20AMP)
• Batteries with rack and cables •45 amp charging alternator
• Battery disconnect switch • Oversize batteries
• Ether starting aid
• Heavy duty starting motors
• Barring device (manual)
• Air starting motor with control & silencer

2 March 24 2008 08:06 AM


®

PRIME 1600 ekW 2000 kVA


50 Hz 1500 rpm 400 Volts

SPECIFICATIONS

CAT GENERATOR CAT EMCP CONTROL PANELS


SR4B Generator • EMCP 3.1 (standard)
Frame size......................................................................... 828 • EMCP3.3 (additional features)
Excitation................................................ Permanent Magnet • Generator mounted rear-facing control panel
Pitch.............................................................................. 0.7777 • Emergency Stop button
Number of poles...................................................................4 • 24 Volt DC Control
Number of bearings............................................................. 2 • Environmental sealed front face
Number of leads................................................................... 6 • Text alarm / event descriptions
Insulation....................... UL 1446 Recognized Class H with • Warning / Shutdowns with indicating lights for:
tropicalization and antiabrasion - Low oil pressure
IP rating..........................................................Drip Proof IP22 - High coolant temperature
Alignment.....................................................Closed Coupled - Overspeed
Overspeed capability - % of rated................................... 180 - Emergency stop
Wave form....................................................................003.00 - Failure to start (overcrank)
Paralleling kit/Droop transformer.......................... Standard - Low coolant level
Voltage regulator.3 Phase sensing with selectible volts/Hz • Controls:
Voltage regulation............Less than +/- 1/2% (steady state) - Speed adjust
Less than +/- 1% (no load to full load) - Auto start/stop control
Telephone Influence Factor.............................. Less than 50
- Engine cool-down timer
Harmonic Distortion.........................................Less than 5%
- Alarm acknowledge
CAT DIESEL ENGINE - Lamp test
3516B TA, V-16, 4-stroke-cycle watercooled diesel • True RMS AC metering, 3-phase
Bore - mm.............................................. 170.00 mm (6.69 in) • Digital indications for:
Stroke - mm........................................... 190.00 mm (7.48 in) - RPM
Displacement - L................................... 69.00 L (4210.64 in3) - Operating hours
Compression ratio........................................................ 14.0:1 - Oil pressure (psi, kPa or bar)
Aspiration........................................................................... TA - Coolant temperature
Fuel system..................................... Electronic unit injection - System DC volts
Governor type............................................................ ADEM3 - L-L volts, L-N volts, Phase amps, Hz
- ekW, kVA, kVAR, kWhr, %kW, PF
• Programmable digital (4) inputs and (4) outputs
• MODBUS islolated data link (RS-485 half-duplex)
supports 3.3 serial communication at data rate up to
115.2 kbaud (*)
*Consult your Caterpillar Dealer for Details

3 March 24 2008 08:06 AM


®

PRIME 1600 ekW 2000 kVA


50 Hz 1500 rpm 400 Volts

TECHNICAL DATA

Open Generator Set - - 1500 rpm/50 Hz/400 Volts DM7938


Low Fuel Consumption

Coolant to aftercooler
Coolant to aftercooler temp max 60 º C
Generator Set Package Performance
Genset Power rating @ 0.8 pf 2000 kVA
Genset Power rating with fan 1600 ekW
Fuel Consumption
100% load with fan 400.2 L/hr
75% load with fan 303.9 L/hr
50% load with fan 214.5 L/hr
Cooling System1
Engine coolant capacity 233.0 L
Inlet Air
Combustion air inlet flow rate 123.0 m³/min
Exhaust System
Exhaust stack gas temperature 477.1 º C
Exhaust gas flow rate 323.4 m³/min
Exhaust flange size (internal diameter) 203.2 mm
Exhaust system backpressure (maximum allowable) 6.7 kPa
Heat Rejection
Heat rejection to coolant (total) 628 kW
Heat rejection to exhaust (total) 1458 kW
Heat rejection to aftercooler 304 kW
Heat rejection to atmosphere from engine 139 kW
Heat rejection to atmosphere from generator 51.2 kW
Alternator2
Motor starting capability @ 30% voltage dip 4557 skVA
Frame 828
Temperature Rise 80 º C
Lube System
Sump refill with filter 401.3 L
Emissions (Nominal)3
NOx mg/nm3 4257.6 mg/nm³
CO mg/nm3 208.4 mg/nm³
HC mg/nm3 58.1 mg/nm³
PM mg/nm3 22.7 mg/nm³
1
For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from
factory.
2
Generator temperature rise is based on a 40º C (104º F) ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

4 March 24 2008 08:06 AM


®

PRIME 1600 ekW 2000 kVA


50 Hz 1500 rpm 400 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034, ISO 3046, ISO 8528, NEMA MG 1-33, These ratings also apply at ISO 3046 standard conditions.
UL508A, 98/37/EC
Prime - Output available with varying load for an Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
unlimited time. Average power output is 70% of the gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
prime power rating. Typical peak demand is 100% of when used at 29º C (85º F) and weighing 838.9 g/liter
prime rated ekW with 10% overload capability for (7.001 lbs/U.S. gal.). Additional ratings may be available
emergency use for a maximum of 1 hour in 12. Overload for specific customer requirements, contact your
operation cannot exceed 25 hours per year. Prime power Caterpillar representative for details. For information
in accordance with ISO 3046. Prime ambients shown regarding Low Sulfur fuel and Biodiesel capability,
indicate ambient temperature at 100% load which results please consult your Caterpillar dealer.
in a coolant top tank temperature just below the alarm
temperature.

5 March 24 2008 08:06 AM


®

PRIME 1600 ekW 2000 kVA


50 Hz 1500 rpm 400 Volts

DIMENSIONS

Package Dimensions
NOTE: For reference only - do not use for
Length 6554.6 mm installation design. Please contact
Width 2587.6 mm your local dealer for exact weight
and dimensions. (General
Height 3015.1 mm Dimension Drawing #2748723).
Weight 16 960 kg

www.CAT-ElectricPower.com
Performance No.: DM7938
© 2008 Caterpillar
Feature Code: 516DE3N All rights reserved.
Materials and specifications are subject to change without notice.
Gen. Arr. Number: 2628140 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, SAFETY.CAT.COM their respective logos, "Caterpillar
Source: U.S. Sourced Yellow," and the POWER EDGE trade dress, as well as corporate and
product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
March 24 2008 10193232