Professional Documents
Culture Documents
SPLN T5 008 2015 - English (Quick Translation)
SPLN T5 008 2015 - English (Quick Translation)
com
PT PLN (Persero)
Jl. Trunojoyo Blok M - 1/135 Kebayoran Baru
South Jakarta 12160
i
STANDARD SPLN T5.008: 2015
Attachment to the Decision of the Board of Directors
PT PLN (Persero)
Jl. Trunojoyo Blok M - 1/135 Kebayoran Baru
South Jakarta 12160
TOWER FRAME FOUNDATION DESIGN GUIDE
ELECTRICAL AIR LINE
BASED ON
CONUS / SONDIR PENETRATION TEST RESULTS
(Cone Penetration Test)
Arranged by :
Published by:
PT PLN (Persero)
Jl. Trunojoyo Blok M - 1/135, Kebayoran Baru
South Jakarta 12160
Sk sahdir
Sk sahdir
Standardization Transmission Field Group
Decree of the Head of PT PLN (Persero) PUSLITBANG for Electricity
(Research Institute)
No. 0103.K/LIT.03/KAPUSLITBANG/2015
list of contents
i
SPLN T5.008: 2015
ii
SPLN T5.008: 2015
List of Tables
Table 1. Level of Suitability of Field Test Methods for Geotechnical Parameters & Soil
Types ................................................ ................................................................. ..............................................1
Table 2. Correlation qc with N (after Schmertmann, 1970)* ................................................. ...10
Table 3. Value of Nkt for Cohesive and Non-Cohesive Soils ............................................... ...10
Table 4. Correlation of M with qc (after Mitchell and Gardner, 1975) ..................................16
Table 5. Foundation class .......................................................... ................................................................. ....19
iii
SPLN T5.008: 2015
list of picture
Figure 1. Graph of soil behavior type for mechanical type cone penetration test ................ 8
Figure 2. Graph of estimated total soil unit weight (after Robertson, 2010)................... 9
Figure 3. q . correlationc with N based on grain size (after Robertson, 1983)......... 9
Figure 4. Estimated Ko as correlation with su, OCR and Ip................................... 12
Figure 5. D . Correlationr with conical end resistance qc and❤ vo ................................................. 13
Figure 6. Correlation❤ with qc and❤ vo for sandy soils (Robertson & Campanella,
1983)................................................................ ................................................................. ................................ 13
Figure 8. Classification of Foundations on the Graph of Soil Behavior Types from the Schmertmann
Graph. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 10. The bearing capacity factor of the foundation on the slope................................................................. ......... 22
Figure 11. Bearing capacity factor of the foundation on the slope ............................................... ......... 24
Figure 15. Bearing capacity factor of deep foundation (Meyerhof, 1976) ................................ 31
Figure 16. Kulhawy adhesion factor, 1991 .......................................... ............................ 31
Figure 17. Pile blanket friction correction factor (source: Nottingham, 1975) ............. 33
Figure 18. Distribution of frictional resistance................................................................. ................................ 35
Figure 27. Soil reaction and cohesive earth pile moment plane ............................... 43
Figure 28. The ultimate lateral bearing capacity of short piles in cohesive soils ................................ 44
iv
SPLN T5.008: 2015
Figure 31. Deflection, soil reaction diagram and bending moment in cohesive soil ........47
Figure 32. The ultimate lateral bearing capacity of long piles in cohesive soils ..................48
Figure 33. Deflection, soil reaction diagram and bending moment in non-cohesive soil49
Figure 34. Ultimate lateral bearing capacity of long piles in non-cohesive soil. ............50
Figure 35. Diagram of earth pressure & internal forces in pile ................................................................ ........51
Figure 57. Flowchart of the calculation stages of the foundation block and anchor in rock ...78
Figure 58. Sketch of the installation of testing equipment with hydraulic jacks ...........81
Figure 59. Comparison of test times (Fellenius, 1975) ............................................... .84
Figure 60. Pile settlement behavior due to loading (Fellenius, 1975) .................84
v
SPLN T5.008: 2015
Hoy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 69. Typical loading equipment with one hydraulic jack ............... 92
Figure 70. Example of determining the ultimate pile tensile load (Sharma et. al., 1984) .............. 93
vi
SPLN T5.008: 2015
Foreword
In determining the design criteria of the tower foundation for High Voltage Air Ducts,
Extra High Voltage Air Ducts and Distributions, SPLN standards are needed to provide a
directional and uniform grip on the detailed design of Tower foundations.
The design of this tower foundation in the planning and construction implementation uses
the tower foundation design method based on the results of the sondir cone penetration test
(Cone PenetrationTest), this is done considering that this method is more practical and the
implementation time is relatively short.
With the stipulation of SPLN T5.008:2015, the preparation of design criteria and the design of
transmission and distribution tower foundations must follow this standard.
viii
SPLN T5.008: 2015
1 Scope
This standard is intended to establish design criteria and design methods for
transmission and distribution frame tower foundations with standard spans based on
cone/sondir penetration test data.
Conus/sondir penetration test data are used to estimate soil types and parameters,
including:
a. Soil layer and soil type;
b. Characteristics of the strength or bearing capacity of the soil;
c. Characteristics of deformation or subsidence of the soil.
Soil parameters determined based on test results in the field have different levels of
accuracy from each other or even some parameters cannot be determined, so it is
necessary to know that there are limitations in the design of foundations that use soil
parameters from the results of the konus / sondir penetration test in particular and the
test method other fields in general.
The limitations of each test method can be seen in Table 1 which states the level of
suitability for the type of soil and soil parameters under investigation.
Table 1. Level of Suitability of Field Test Methods for Geotechnical Parameters & Types
Land
1
SPLN T5.008: 2015
d. The required soil data is beyond the capabilities of the test equipment;
e. Changes in the position of the ground water level need to be known with certainty;
f. The design of the transmission structure foundation with a very high level of risk
for;
g. Foundations of special transmission structures such as crossing towers or large span
transmissions and others;
h. The foundation is a layer of rock.
the foundation design using cone penetration test data cannot be carried out with this
standard unless accompanied by test data from other soil/rock investigation methods.
2 Aim
This standard is used as a guideline in equating the design method of the truss tower
foundation using the sondir cone penetration test data.
3 Normative Reference
Unless otherwise specified in this standard, the provisions follow the following standards
and references. In the event of a change, the provisions follow the latest edition.
1) ASTM D 1143M-07 (2013), Standard Test Methods for Deep Foundations Under Static
Axial Compressive Load, 2013;
2) ASTM D 3689M-07 (2013) e1, Standard Test Methods for Deep Foundations Under
Static Axial Tensile Load, 2013;
3) ASTM D 3966M-07 (2013) e1, Standard Test Methods for Deep Foundations Under
Lateral Load, 2013;
4) ASTM D 3441-98, Standard Test Methods for Mechanical Cone Penetration Tests of
Soils, 1999;
5) G, Sanglerat, The Penetrometer and Soil Exploration, Elsevier Publishing Company,
Amsterdam, London, New York, 1972;
6) J, E, Bowles, Foundation Analysis and Design, 3rd edition, McGraw-Hill, 1982;
7) NAVFAC DM-7, Design Manual Soil Mechanics, Foundations, and Earth Structures,
Department of The Navy Naval Facilities Engineering Command, 200 Stovall Street,
Alexandria, VA. 22332, 1971;
8) J, M, Duncan, A., L., Buchignani, Geotechnical Engineering An Engineering Manual for
Settlement Studies, Department of Civil Engineering, University of California,
Berkeley, 1976;
2
SPLN T5.008: 2015
9) H, G, Poulos, E, H, Davis, Pile Foundation Analysis and Design, John Wiley & Sons, New
York, 1980;
10) IEEE ISBN 0471-01076-8, IEEE Trial-Use Guide for Transmission Structure Foundation
Design – Draft American National Standard, The Institute of Electrical and Electronics
Engineers, Inc. – Wiley-Interscience of John Wiley & Sons, Inc., 1986;
11) P, P, Rahardjo, Pillar Foundation Manual, Postgraduate Masters in Civil Engineering,
Parahyangan Catholic University, ISBN 979-95267-0-1;
12) EPRI EL-6800, Manual on Estimating Soil Properties for Foundation Design, Final
Report, Electric Power Research Institute, 1990;
13) EPRI EL-2870, Transmission Line Structures Foundation for Uplift Compression
Loading, Final Report, Electric Power Research Institute, 1983;
14) EPRI EL-3777, Load Transfer Mechanisms in Rock Sockets and Anchors, Final Report,
Electric Power Research Institute, 1984;
15) EPRI EL-5918, Analysis and Design of Drilled Shaft Foundations Socketed Into
Rocks”, Final Report, Electric Power Research Institute, 1988;
16) P, K, Robertson, K, L, Cabal (Robertson), Guide to Cone Penetration Testing for
Geotechnical Engineering, Gregg Drilling & Testing Inc., 5th edition, 2012;
17) B, H, Fellenius, A, Eslami, Soil Profile Interpreted from CPTu Data, Year 2000
Geotechnics, Geotechnical Engineering Conference, Asian Institute of Technology,
Bangkok, Thailand, November 27 - 30, 2000, 18p;
18) J, H, Schertmann, Guide Lines for Cone Penetration Test, Performance and Design”,
US Department of Transportation, Federal Highway Administration, Washington DC,
1978;
19) P, W, Mayne, Cone Penetration Testing State of Practice, Transportation Research Board
Synthesis Study, Washington, 2007;
20) D, L, Presti, C, Meisina, Use of Cone Penetration Tests for Soil Profiling and Design of
Shallow and Deep Foundations, CPT Handbook, Pagani Geotechnical Equipment.
4.1 Towers
Frame structure to support High Voltage Air Line (SUTT), Extra High Voltage Air Line
(SUTET) and Distribution.
4.2 Foundation
Substructure building that functions to distribute the tower load into the surrounding soil
layer.
Foundations that have a depth of not more than the width of the foundation include grades 1, 2, 3, 4A,
5, and 7 foundations.
3
SPLN T5.008: 2015
Foundations that have a depth of more than the width of the foundation and use support
poles with the type of drill pile (bored pile) or piles (driven pile), all deep foundations are
classified into class 6 foundations.
Shallow foundation consisting of a plate (foot/pad) and a column part (chimney) at each leg of
the tower separately from each other with the material in the form of reinforced concrete.
Foundations on rock consisting of concrete blocks with or without anchors at each foot of the
tower separately from each other with materials in the form of reinforced concrete for blocks
and steel reinforcement with grout for anchors (foundation class 4B).
4.7 Grout
Gap filling material between anchor steel and rock on block and anchor foundations.
Shallow foundations consisting of slabs (palms/pad) which unites all tower legs and column
sections (chimney) at each leg of the tower separately from each other with the material in
the form of reinforced concrete.
The deep foundation is in the form of reinforced concrete piles, the installation of which
is done by drilling the ground first and then casting the reinforced concrete piles.
Deep foundations in the form of reinforced concrete poles or steel poles or wooden poles
whose installation is done by pounding the pole into the ground.
Tests to obtain the parameters of the resistance to penetration of the soil layer in the
field with the conus sondir penetration tool. The parameter is in the form of cone
resistance (qc), shear resistance (fs), shear ratio (Rf), and the total soil shear (Tf), which can
be used for the interpretation of soil layers and the physical and mechanical parameters
of the soil that are part of the foundation design.
4
SPLN T5.008: 2015
The ability of the foundation to bear axial compression loads, axial tensions, laterals and
overturning moments without collapsing and not causing excessive soil deformation or
settlement.
The ability of the soil/foundation to withstand compressive axial loads, tensile axial loads,
laterals, and overturning moments expressed in units of pressure or stress without
experiencing excessive failure or settlement.
The ability of the foundation to bear the load until there is a complete shear failure of the
soil (general shear failure).
The ability of the foundation to bear the load without experiencing soil collapse whose
magnitude is the ultimate bearing capacity divided by the safety factor.
Vertical deformation of the subgrade layer of the foundation by the load caused by the elastic properties
of the soil.
Vertical deformation of the cohesive soil layer of the foundation base by the load in the form of soil
compression caused by the release of water from the soil pores (consolidation).
Vertical deformation of the cohesive soil layer of the foundation base by the load in the form
of soil compression caused by a decrease in the pore ratio (void ratio) soil at constant earth
pressure and over a long period of time.
-
5
SPLN T5.008: 2015
The value of the frictional resistance of the soil against the pile foundation is expressed in kg/cm.
The test is carried out to determine the value of soil density expressed in the value of N.
Is N-SPT with 60% energy efficiency. The standard value for energy efficiency ranges from
35-85% when a donut or safe beater is used. In America and England an average of 60%
energy efficiency is used for drill rod lengths of more than 10 meters.
Fine-grained soil material consisting of silt or clay that contains or does not contain
organic material.
Coarse-grained soil material with visible grain size visually and has no cohesion or
adhesion between grains, for example sandy soils.
The angle between the vertical axis and the line on the failure plane due to tensile loads
uplift which can be either a prism or a truncated cone.
4.27 Concrete
Loads that work perpendicular to the foundation plane consisting of compression and tension.
6
SPLN T5.008: 2015
The load caused by the eccentricity of the vertical load and the lateral load to the center of gravity of the
foundation base.
Comparison between the ultimate capability of the foundation to the permit/workability of the foundation on
the permit design method.
Comparison between the total length of intact rock test samples with a length equal to or
more than 10 cm to the total length of the test samples in one test tube.
The design of the foundation must meet the design criteria, including the foundation must be stable,
strong and not experiencing excessive settlement, namely:
a. The stability and strength of the foundation consists of the bearing capacity of the foundation in carrying axial
compressive, tensile, lateral and overturning loads;
b. The settlement of the foundation must be limited so that it does not cause damage to the superstructure
and does not interfere with the aesthetics or comfort of the surrounding environment.
Stratigraphy or soil layers and soil types need to be known in designing the foundation to
determine the calculation method according to the type of soil. This can be estimated by
using the sondir cone penetration test data in the form of sondir cone tip resistance (qc)
and the friction ratio, which is the ratio between the frictional resistance of the sondir
blanket (fs) with conus sondir end resistance (Rf = fs/qc).
Interpretation of soil type from mechanical sondir cone penetration test data using
graphs from Schmertmann (1978) as in Figure 1.
7
SPLN T5.008: 2015
Figure 1. Graph of soil behavior for mechanical type cone penetration test
The unit weight of soil is determined using the equation from Robertson, 2010 as follows:
With:
= total unit weight of soil;
w = unit weight of water;
qt = cone resistance with pore water pressure correction, taken equal to qc;
Rf = The ratio of the frictional ground of the blanket to the resistance of the cone tip = fs/qt x 100%; Pa =
atmospheric pressure.
8
SPLN T5.008: 2015
Figure 2. Graph of total soil unit weight estimation (after Robertson, 2010)
Correlation between sondir cone penetration test data and N60 The SPT uses the graph of
Robertson & Campanella, 1983 as the graph in Figure 3. below:
9
SPLN T5.008: 2015
For non-cohesive soils, the Schmertmann, 1970 correlation table can be used for mechanical
penetration test equipment as shown in table 2.
The empirical formula used to estimate the shear strength of the soil under undrained
conditions is as follows (Prandtl, 1921):
……………………………………………………………………………………………….… (2)
With:
su = undrained shear strength;
qt = resistance of the corrected sondir cone tip, taken equal to qc for test equipment
without pore water;
v = earth pressure above the studied soil elevation (overburden pressure); = conus
Nkt sondir factor according to table 3.
Undrained shear strength is used in foundation soil analysis as undrained cohesion Cu.
The sensitivity of the clay soil is the ratio of the undrained peak shear strength of the
undisturbed test soil sample to the undrained shear strength of the disturbed test soil
sample (“remolded”) su(brake). Undrained shear strength su(brake) assumed to be equal to the
frictional resistance of the conical blanket (“sleeve”) fs so that the sensitivity of clay can be
estimated as follows (after Robertson, 2100):
10
SPLN T5.008: 2015
For very sensitive clay soils (St > 10) f values which is measured is relatively low with a low
level of accuracy so that the value of St it is used for instructions only.
This parameter is used to estimate the plasticity index of clay Ip in looking for a
correlation with the modulus of elasticity of clay in undrained conditions Eu which is
expressed by the empirical formula as follows (after Robertson, 2010):
With :
Qt =
Excessive consolidation ratio (“overconsolidation ratio”) is the ratio between the past
effective earth pressure and the present effective earth pressure
which is expressed by the equation:
…………………………………………………….…………..……… (6)
Empirical correlation between with qt from Kulwahy and Mayne, 1990 are:
= k(qt –vo) …………………………………………………………………………. (7)
The value of k ranges from 0.2 to 0.5 and an average value of 0.33 is often used, a larger
value of k is recommended for highly consolidated clays.
11
SPLN T5.008: 2015
Ko determined using the correlation between undrained shear strength, OCR and
plasticity index for fine-grained soils as shown in Figure 4.
For non-cohesive soils, relative density or density index is an intermediate soil parameter
that is used to obtain other soil parameters and to determine its density.
Correlation between the tip resistance of the sondir cone and relative density, as shown
in Figure 5. quoted from Wesley, 2009. This graph is the average curve of the curves of
Lunne and Christofferson (1983), Baldi et al. (1989), and Jamiolkowski et al. (1988).
12
SPLN T5.008: 2015
(Lunne and Christofferson, 1983, Baldi et al., 1989) and Jamiolkowski et al., 1988)
The correlation between the effective internal shear angle and the tip resistance of cone
penetration for uncemented light quartz sand soils with medium compressibility is shown
in Figure 6.
Figure 6. Correlation' with qc and' vo for sandy soils (Robertson & Campanella,
1983)
13
SPLN T5.008: 2015
For fine-grained or cohesive soils, the shear angle in effective The most precise is
determined by triaxial test of the sample of consolidated test soil in the laboratory. As an
estimate for the purposes of initial foundation design, the assumed value of 28° for clay
soils and 30° for silt soils is considered adequate (Robertson, 2012).
The main soil parameter needed to estimate the deformation or settlement of the soil on
the foundation is the modulus of elasticity or Young's modulus (E) and constrained
modulus (M).
The correlation between qc where E is very sensitive to stress-strain history, age and soil
mineralogy. One of the guidelines for estimating the modulus of elasticity of incohesive
soils under drained conditions is the correlation proposed by Robertson, 2010 as follows:
With:
E❤ = Young's modulus equivalent under drained conditions;
E = function of load degree, unit weight, pressure history, age, grain shape and
soil mineralogy = 0.015 [10(0.55 Ic + 1.68)];
qt = qc for penetration testing of mechanical and electrical types.
Ic = Soil behavior type index = [(3.47 – log Qt)2 + (log Fr +1.22)2]0.5 ……………….. (9)
Soil parameters for cohesive soil deformation analysis are modulus of elasticity for
instantaneous settlement and constrained modulus for consolidation decline. The
correlation between the shear strength of cohesive soils under undrained conditions (su)
with the modulus of elasticity (Eu) proposed by Ladd et al, 1977, is as shown in Figure 7.
14
SPLN T5.008: 2015
Constrained modulus To analyze the consolidation of the cohesive soil, the correlation of
the electric cone penetration test data by Robertson, 2010 is used as follows:
With:
mv = soil compressibility coefficient;
If Ic > 2.2 thenM = Qt for Qt < 14 orM = 14 for Qt > 14; If Ic < 2.2 thenM =
0.0188 [10(0.55 Ic + 1.68)];
qt = resistance of the tip of the cone corrected for pore water pressure;
Qt = .
For the interpretation of the results of the mechanical type cone penetration test, it is more
appropriate to use the correlation from Mitchell and Gardner, 1975, as shown in Table 4. taken
from Sanglerat, 1972.
15
SPLN T5.008: 2015
To estimate the settlement time of a cohesive soil at a certain degree of consolidation (U),
a soil permeability parameter (k) is needed. Soil permeability is most precisely
determined from the results of the permeability test of undisturbed soil samples in the
laboratory, but for estimates, the correlation from Robertson, 2010 can be used which is
expressed by the following equation:
k = 10(-4.52 – 1.37 Ic) (m/s) for 3.7 < Ic < 4.0 ......................................................................................... (12)
This correlation cannot be used on sensitive soils or fine-grained hard soils and very
dense coarse-grained soils.
Coefficient of vertical consolidation (cv) is estimated from its correlation with the soil
compressibility coefficient (mv) that is:
With:
w = unit weight of water.
For the electric cone penetration test with pore water pressure measurements, the vertical
consolidation coefficient (cv) is estimated by measuring the drop in pore water pressure when
penetration is stopped.
16
SPLN T5.008: 2015
With:
T50 = theoretical time factor;
t50 = time required for 50% degree of consolidation; Ro =
cone radius.
For the mechanical type cone penetration test without measuring the pore water pressure when
the soil subsides at a certain degree of consolidation, it is expressed by the equation:
With:
tU = time of decline in the degree of consolidation U; =
TU theoretical time factor in degree of consolidation U; =
H thickness of compressible soil.
The type of foundation used for the frame tower foundation in the PLN environment is
one of the following types of foundation:
The grouping of foundations is based on grading the bearing capacity of the foundation soil
according to the table and identifying the types and properties of the soil according to point 6
as shown in Figure 8 and used as an initial estimate of the type and depth of the foundation.
17
SPLN T5.008: 2015
In designing the foundation, the bearing capacity used for calculating the size of the
foundation in the same class is the smallest soil bearing capacity based on the method in
item 9.
Soil with conical pressure less than 2 kg/cm2 additional testing of other types of soil and
testing of undisturbed soil samples must be carried out in the laboratory to determine
the technical feasibility of the soil layer.
Investigation of rock layers for class 4b foundations was carried out to determine the physical and
mechanical properties of the rock.
18
SPLN T5.008: 2015
Foundation Class 1 2 3 4a 4b 5 6 7
19
SPLN T5.008: 2015
Figure 8. Classification of Foundations on the Graph of Soil Behavior Types from the Schmertmann . Graph
The naming of the transmission tower foundation legs is determined based on the serial number
of the transmission tower from the small number to the large number, with the position facing the
large tower number in clockwise order, then the positions A and D are in the right position while B
and C are in the left position. , according to Figure 9 in the illustration below.
B C
A D
20
SPLN T5.008: 2015
This standard is used to calculate the bearing capacity of the soil using the direct method,
namely using the empirical formulation of the test parameters in the field.
The location or position of the ground water level will affect the bearing capacity of the foundation, namely
through the unit weight of the soil which is determined based on the location of the ground water level
mentioned above, namely as follows:
a. Dry unit weight in all terms of the bearing capacity equation if the water table is at a
depth below the base of the foundation;
b. The effective unit weight for all terms of the bearing capacity equation if the water level is
the soil is at a depth above the base of the foundation.
The bearing capacity of the foundation can be reduced if it is located around the slope, this is
due to the reduced layer of soil around the foundation to withstand the load, namely the
reduced volume of soil in the collapse area. The bearing capacity of the foundation at the
location around the slope can be estimated using the Terzaghi method with the corrected
Meyerhof bearing capacity factor as shown in the graphs of Figure 10 and Figure 11.
The correction factor for the bearing capacity of the foundation around the slope using the direct
method can be approached by comparing the bearing capacity factors of the foundation at
position around the slope (Ncq or N q) to the bearing capacity factors of the foundation in a position
without slopes, namely:
a. For cohesive soil, foundation bearing capacity correction factor = Ncq(β>0)/ Ncq(β=0);
b. For non-cohesive soil, correction factor for foundation bearing capacity = Nq(β>0)/ N q(β=0).
The placement of the foundation around the slope affects the stability of the slope so that a
slope stability analysis needs to be carried out.
The bearing capacity of the foundation located on the slope with a distance b from the edge of the slope
as shown in Figure 10(a) can be estimated by using a comparison of the bearing capacity factor of the
foundation on the slope (β> 0) with the bearing capacity factor of the foundation on flat ground (β=0 ).
For cohesive soils, the foundation bearing capacity factor on the slope is Ncq obtained
from Figure 10(b) using a curve with a value of > 0, while the bearing capacity factor of a
foundation without a slope is Ncq with a value of =0.
21
SPLN T5.008: 2015
In Figure 10(b), Ns is the slope stability value calculated by the following equation:
With:
Ns = slope stability value;
= unit weight of soil; H
s = slope height; C = soil
cohesion.
Equation (16) above is used when the width of the foundation Bf Hs, when Bf < Hs
then the price Ns = 0.
(a) Geometry (b) Cohesive soil ( =0) (c) Soil is not cohesive (c=0)
When Bf Hs then for the value 0<Df/Bf<1 price Ncq interpolated from both D . curvesf/Bf=0 and D
f/Bf=1 with a value of Ns=0.
When Bf < Hs then the price Ncq for the value of Ns>0 can be interpolated from the two N . curvess
between the value of Df/Bf=0.
As an example:
If b = 4 m, then b/Bf =1 then Ncq = 5.5 so that the carrying capacity factor increases to
6/7 or 0.86. The bearing capacity is not affected by slope geometry if b/ Bf 3 or
foundation edge b is equal to or greater than 12 meters.
For = 60°, b/Hs=0.5, Df/Bf=0 and Ns=2, from the graph of Figure 10(a) we get Ncq= 2.6
So for = 60°, b/Hs=0.5, Df/Bf=0 and Ns=0.8, inter [placing the two prices above and
getting Ncq= 3.44.
While the cohesive soil bearing capacity factor on flat land (β = 0°) for Ns=0.8 obtained
from the interpolation of the two graphs above is Ncq= 4.4
So that the bearing capacity of the foundation above the slope must be corrected to
3.44/4.4 or 0.78 of the bearing capacity on flat ground.
23
SPLN T5.008: 2015
(a) Geometry (b) Cohesive soil ( =0) (c) Soil is not cohesive (c=0)
Example:
24
SPLN T5.008: 2015
Df/Bf=1;
The empirical correlation for the bearing capacity of the foundation in cohesive soils is:
By ignoringv , value Nkt of 15 and the safety factor of the soil bearing capacity is 3, then the bearing
capacity of the foundation permit on cohesive soil can be taken as follows:
A direct method that directly correlates the bearing capacity of a non-cohesive soil as a
linear function of the end resistance of the cone qc which is expressed by the equation by
Eslaamizaad and Robertson, 1996 as follows:
With:
qult = ultimate bearing capacity of the soil;
K = factor depends on B/D in Figure 12;
qc(ave) = average cone tip resistance at depth B below the base of the foundation.
In general K the minimum price can be taken of 0.16 and with a safety factor of 3, the
bearing capacity of the foundation soil permit becomes:
25
SPLN T5.008: 2015
The ultimate tensile axial bearing capacity of the shallow foundation is as shown in Figure 13. The
Axial Tensile Bearing Capacity using the Prism/Truncated Cone Method is as follows:
Tu = Wf + Ws ……………………………….………………..…….……………… (22)
With:
Tu = ultimate tensile axial bearing capacity (tons or kN); Wf =
Foundation weight (tonnes or kN);
Ws = Weight of soil in the failure chamber (tonnes or kN).
With:
t = unit weight of soil (ton/m3 or kN/m3);
Vo = Volume of foundation below ground level (m3); V1 =
Base area of foundation x depth of foundation (m3); D =
depth of foundation (m);
B = Width of foundation base (m);
= prism/cone angle or frustum angle (°) according to table 6.
The allowable bearing capacity of the axial tensile load of the foundation is obtained from the ultimate bearing
capacity divided by the value of the safety factor of 2.
26
SPLN T5.008: 2015
Figure 13. Tensile axial bearing capacity using the prismatic method
(Source: Guide for Transmission Structure Foundation Design, IEEE Std 691, 1986)
27
SPLN T5.008: 2015
The shear strength of the foundation comes from the difference between passive soil pressure and
active soil pressure and from the shear resistance at the soil surface at the base of the foundation as
shown in Figure 14 Shallow Foundation Shear Stability.
The minimum value of the factor of safety against shear is set at 1.5.
Ws Ws
W
D Te
Tf
4 Cu
B
(a)Cohesive Soil
Ws Ws
W
D
Te
Tf
A
t D (Kp – Ka)
B
28
SPLN T5.008: 2015
The overturning safety factor must not be less than 2, where the magnitude of the
foundation overturning moment at point A in Figure 14 is the sum of the multiplications
between the forces and each arm of the moment, while the overturning moment due to
the load at point A is the product of the force H with the arm. moment about point A.
The soil bearing capacity for pile foundations consists of compressive axial, tensile and lateral axial bearing
capacity. The pile foundation analysis method is carried out in two ways, namely:
With:
Qult = ultimate bearing capacity of the pile;
Qb = ultimate bearing capacity of pile end resistance;
Qs = ultimate bearing capacity of pile blanket friction resistance;
Ap = cross-sectional area of the ends of the pile;
As = area of the pile end
qp blanket; = pile end resistance;
fp = pile friction resistance.
29
SPLN T5.008: 2015
The safety factor used to calculate the bearing capacity of the axial compression permit is
2.5 to 3.
tensile bearing capacity (uplift) The single pile is produced by the frictional resistance of the pile blanket and the pile
weight, namely:
With:
Wp = pile weight.
The safety factor used to calculate the axial tensile permit bearing capacity is 2.
With:
Then the ultimate bearing capacity of the axial concrete drill pile is:
30
SPLN T5.008: 2015
With:
qp =❤ p Nq;
❤p = effective earth pressure at pile tip depth;
Nq = bearing capacity factor of deep foundation from Meyerhof, 1976;
fp = Ko ❤ z tan ;
Ko = earth pressure coefficient at rest at depth z;
❤z = effective earth pressure at depth z;
= effective internal shear angle of the soil.
With:
qp = 0.5(qc1 + qc2);
qc1 = qc averaged at 0.7 D above the tip of the pile to 4 D below the tip
pole;
qc2 = qc averaged at 8 D above the pole tip;
fp =c ;
c = clay reduction factor according to Figure 17.
32
Translated from Indonesian to English - www.onlinedoctranslator.com
With:
qp =❤ p Nq;
❤p = effective earth pressure at pile tip depth;
Nq = bearing capacity factor of deep foundation from Meyerhof, 1976;
fp = Ko ❤ z tan ;
Ko = earth pressure coefficient at rest at depth z;
❤z = effective earth pressure at depth z;
= effective internal shear angle of the soil.
With:
qp = 0.5(qc1 + qc2);
qc1 = qc averaged at 0.7 D above the tip of the pile to 4 D below the tip
pole;
qc2 = qc averaged at 8 D above the pole tip;
fp =c ;
c = clay reduction factor according to Figure 17.
32
SPLN T5.008: 2015
Figure 17. Pile blanket friction correction factor (source: Nottingham, 1975)
The procedure is the same as for cohesive soils but with the following limitations:
The tensile axial bearing capacity of a single pile foundation is expressed as:
With:
Tult = tensile axial ultimate bearing capacity;
33
SPLN T5.008: 2015
The ultimate frictional resistance of a single pile in a cohesive soil is estimated by the formula (Das and
Seeley, 1982):
With:
L = length of the pole; P =
Perimeter of the pile;
= adhesion factor for tensile capacity according to Table 7 Capacity Adhesion Factor
Pull;
Cu = Cohesion of undrained soil.
= 0.9 – 0.00625 Cu
Bore pile
(Cu 80 kPa)
= 0.4 (Cu > 80 kPa)
= 0.715 – 0.0191 Cu
Pipe Pole
(Cu 27 kPa)
= 0.2 (Cu > 27 kPa)
The ultimate frictional resistance of a single pile in a cohesive soil is estimated by the equation:
With:
fu = The blanket-pull friction resistance = Ku ❤ v tan according to Figure 18 Distribution
Friction Resistance;
Ku = Tensile coefficient from Figure 19 Tensile
❤v = coefficient; Effective vertical stress;
= Shear angle between the pile and the ground from Figure 20 Angle of Shear
Pole-Earth & Lcr;
= inner shear angle;
34
SPLN T5.008: 2015
Lcr = Critical depth according to Figure 20 Pile-Ground Shear Angle & Lcr.
Dr = Degree of relative density
35
SPLN T5.008: 2015
When L Lcr and the groundwater level is above the base of the pile, then:
When L Lcr and the groundwater level is below the base of the pile, then:
36
SPLN T5.008: 2015
Pile foundations that are in embankment soil (compressible clay/silt or loose sand) or
there is a large decrease in groundwater level, the subsidence of the soil layer that occurs
can cause the pile to be dragged down. The downward friction on the pile is called
negative friction (negative skin friction). The negative friction force based on the Beta
Garlenger method is:
With:
= Coefficient of friction between pile and soil according to Table 8 Value of for Types
Land;
❤vi = effective soil stress layer i; =
hi layer thickness i;
p = circumference of the pole;
Type of soil
Clay 0.20 – 0.25
Silt 0.25 – 0.35
Sand 0.35 – 0.50
The axial bearing capacity of the pile group is influenced by the distance between the piles, for that
a minimum distance between the piles is required between 2 D to 3 D where D is the diameter of
the pile.
The bearing capacity of the pile group on cohesive soil is determined by the lowest value
between the sum of the single pile bearing capacity calculated at 9.5.1 or 9.5.2 and the
bearing capacity based on the collapse of the pile group as the block foundation as
shown in Figure 21 Pile Group as Block Foundation.
37
SPLN T5.008: 2015
The axial bearing capacity of the pile group block with length L, width B and depth D is
(Tomlinson, 1994):
With:
Cur = mean soil cohesion along L; Cub =
soil cohesion at depth L;
S = Block foundation form factor according to Figure 22 Block Foundation Form Factor; Nc =
Bearing capacity factor of block foundation according to Figure 23 Bearing Capacity Factor
Block Foundation.
38
SPLN T5.008: 2015
Figure 23. Bearing capacity factor of block foundation (Meyerhof, Source: Tomlinson, 1994)
The comparison between the bearing capacity of the pile group and the sum of the carrying
capacity of the single pile is referred to as the pile group efficiency factor. The efficiency of this pile
group is only used for sandy soils with frictional resistance as the main component of carrying
capacity.
The pile group efficiency was estimated using Bowles' (1982) equation:
Eg = ………………………………………………………………………….. (42)
With:
Eg = Pile group efficiency factor; D =
Diameter or width of single pile; P =
Perimeter of single pile;
m = Number of piles on the wide side of the pile group; n =
Number of piles on the long side of the pile group.
Compressive axial bearing capacity of pile group = Eg x Total bearing capacity of single pile.
39
SPLN T5.008: 2015
The tensile axial bearing capacity of pile group for cohesive soil is shown in Figure 24.
Tensile failure of pile group block on cohesive soil whose magnitude is:
……………………………………………………………..…….. (43)
For non-cohesive soils, the same principle is used as for cohesive soils, but the form of
block failure is shown in Figure 25. Tensile Collapse of Pile Group Blocks in Non-Cohesive
Soils.
The methods that can be used in the analysis of pile foundations against lateral loads are:
a Broms . Method
Used to calculate the ultimate lateral load on homogeneous (uniform) cohesive
undrained or homogeneous (uniform) incohesive soil layers;
40
SPLN T5.008: 2015
Pile foundations are divided into short (rigid) and long (rigid) piles.elastic) which is
determined by the ratio of the length of the pile to its stiffness.
Pile stiffness for overconsolidated clay/cohesive soils (overconsolidated) is:
…………………………………………………………………………………….. (44)
With:
R = Pile stiffness factor (m); E = Modulus of
elasticity of the pile (kN/m2); I = moment of
inertia of the pile (m4); B = Diameter or
width of the pile (m);
k = k1 = Reaction modulus subgrade soil (kN/m3) according to Table 9 Relationship k1
with Cu.
Undrained shear strength (Cu) kN/m2 50 - 100 100 - 200 > 200
T= ……………………………………………………………………………..….………… (45)
With:
T = Pile stiffness factor (m);
41
SPLN T5.008: 2015
Figure 26. The relationship between modulus of variation (ηh) with the degree of soil density (Dr)
Pile classification criteria are stated in the ratio of pile length to stiffness factor (soil
modulus) as shown in Table 11 Pile Classification below:
Short (stiff) L 2T L 2R
42
SPLN T5.008: 2015
Broms (1965) developed a simple method for calculating the ultimate lateral load bearing
capacity of piles using the following assumptions:
1. In short piles, failure occurs in the soil in the form of shear failure;
2. In long piles, the passive resistance of the soil is so large that failure occurs
in pile bending which is determined by the plastic yield resistance of the
pile section;
3. Cohesive or non-cohesive homogeneous soil properties.
In undrained cohesive soils or with short term loading, the soil pressure and pile bending
moment diagrams are depicted as in Figure 27 Soil Reaction and Cohesive Pile Moment
Fields where the soil reaction is considered not to occur in the shrinkage area as deep as
1.5 B.
From the figure above for the free pile head condition, the pile shear force is equal to
zero if Hu equal to 9 Cu Bf or:
with:
f = zero shear depth; Hu = ultimate
lateral bearing capacity; Cu =
Cohesion of undrained soil.
43
SPLN T5.008: 2015
The maximum moment on the pile occurs at zero shear force, then by taking the moment
at the zero shear point, we get:
The horizontal forces in the system of Figure 27(a) are in equilibrium, then the reaction or
soil pressure below the zero shear force point has a resultant force equal to zero or the
earth pressure on the left of the pile is the same as the soil pressure on the right of the
pile. So that the maximum pile moment can be expressed in the equation:
With the same analogy as above, for a short pile of pinched heads, zero shear force and
zero moment lie at the base of the pile, so Mmax obtained:
To simplify the calculation, the lateral ultimate bearing capacity of single short piles in
cohesive soils is calculated using the curve in Figure 28. Lateral ultimate bearing capacity
of short piles in cohesive soils.
Figure 28.. The ultimate lateral bearing capacity of short piles in cohesive soils
44
SPLN T5.008: 2015
Meanwhile, the ultimate lateral bearing capacity of a single short pile on a non-cohesive soil is
calculated based on the soil reaction diagram and the bending moment of the pile as shown
in Figure 29. Soil Reaction and Non-Cohesive Soil Moment Plane.
At depth z, the soil reaction is calculated based on its passive pressure, namely:
………………………………………………………………………………. (50)
The passive pressure at the base of the pile is expressed in terms of the concentrated
force P by using equation (50) and by using the moment and horizontal force equilibrium
equation, the ultimate lateral bearing capacity of the free head pile is;
………………………………………………………………(52)
………………………………………………………………………… (53)
45
SPLN T5.008: 2015
In order to simplify the calculation, the lateral bearing capacity can be calculated using
the curve in Figure 30. Lateral ultimate bearing capacity of short piles in non-cohesive
soils.
30 image. The ultimate lateral bearing capacity of short piles on non-cohesive soil
The maximum bending moment in the pile is calculated using the equation:
……………………………………………………………….. (54)
Passive soil resistance in long piles as shown in Figure 31 Deflection, Soil Reaction Diagram
and Bending Moment in Cohesive Soils is considered very large, then the ultimate lateral
bearing capacity of the pile is determined by the strength or bending capacity of the pile Mu
not by the strength of the foundation soil.
By using equation (55), the ultimate lateral bearing capacity of long piles with free head
on cohesive soil is:
46
SPLN T5.008: 2015
………………………………..……………… (55)
As for the condition of the head of the pile being pinched, the ultimate lateral bearing capacity on the
cohesive soil is:
…………………………………………………….. (56)
Figure 31. Deflection, soil reaction diagram and bending moment in cohesive soil
To simplify the calculation, the lateral ultimate bearing capacity of a single long pile on a
cohesive soil is calculated using the curve in Figure 32. Lateral ultimate bearing capacity
of a long pile on a cohesive soil.
47
SPLN T5.008: 2015
Image 32. Ultimate lateral bearing capacity of long piles on cohesive soil
Source: Tomlinson, 1994
The ultimate lateral bearing capacity of long piles on non-cohesive soils is based on
Figure 33 Deflection, Soil Reaction Diagram and Bending Moments in Non-Cohesive Soils,
where the maximum moment occurs at zero shear forces.
48
SPLN T5.008: 2015
Figure 33. Deflection, soil reaction diagram and bending moment in non-cohesive soil
For the free pile head condition the location of the zero shear force is:
…………………………………………………….. (57)
…………………….……………………………….. (58)
So that the ultimate lateral bearing capacity of free piles on non-cohesive soils is obtained
by equating Mmax with Mu in equation (55) and substitute f from equation (57):
………………………………..………………………………………… (59)
For long piles where the pile head is wedged into a non-cohesive soil, the bearing
capacity is:
49
SPLN T5.008: 2015
……………………………………………………..…….............. (60 )
The lateral ultimate bearing capacity of a single long pile on non-cohesive soils can also
be calculated using the curve in Figure 34. Lateral ultimate bearing capacity of long piles
on non-cohesive soils.
Figure 34. The ultimate lateral bearing capacity of long piles on non-cohesive soil.
50
SPLN T5.008: 2015
7. If it is necessary to design the cross section of the pile in detail, draw the plane of the
shear force and bending moment according to the force system in Figures 27, 29, 31
and Figure 33;
8. Detailed cross-sectional design drawings in accordance with applicable regulations or
standards.
This method assumes that the short pile will rotate at point X at a depth x from the
ground surface and the soil will resist the movement of the pile with passive pressure as
shown in Figure 35 Diagram of Earth Pressure & Internal Pile Force.
Figure 35(a) shows a pressure or soil reaction diagram, Figure 35(b) shows a diagram of
the forces in pile shear and Figure 35(c) shows a diagram of the forces in pile moments.
Passive earth pressure at depth z which consists of internal shear angle and cohesion
parameters is expressed in:
with:
pz = passive earth pressure at depth z;
poz = effective vertical soil pressure at depth z; = soil
C cohesion at depth z;
Kqz = Coefficient of internal shear passive pressure at depth z according to Figure 36 Kq and
Kc;
Kcz = Cohesive passive pressure coefficient at depth z according to Figure 36 Kq and Kc.
51
SPLN T5.008: 2015
The cohesion parameter C is adjusted to the loading stage conditions or the soil
conditions under review, Cu, =0 is used for short term loading conditions or undrained
conditions and C❤,❤ used for long term loading conditions or drained soil conditions.
In calculating z for cohesive soils (clay), then the z value is taken starting from the top of
each layer as shown in Figure 37. Determination of z for cohesive soils.
The total passive resistance for an element with height L/n and pile width B at depth z is
pz L/n B.
The sum of the moments at the point of the lateral force H is:
52
SPLN T5.008: 2015
……………(62)
The number of moments at the point of lateral force for the free head pile is equal to
zero, so by trial and error, the value of x is obtained from equation (62) above. If the load
is a moment, then the moment can be replaced by a force H which is a distance e from
the ground. Meanwhile, if the condition of the pile head is pinched, it can be analogous to
the condition of the free pile head with a lateral force distance of e1 from the virtual pinch
point at depth zf . The buckling length of the pile that is pinched at both ends is half the
length of the pile, it can be analogous to a pile that is pinched only at one end, so that the
condition of the pinched pile head can be replaced by a free pile head condition with
length:
The ultimate lateral bearing capacity of the free head pile can be calculated by taking the moment at the point
of rotation X, namely:
. . . . . . . . . . . . . . . . . . . . . . (64)
By obtaining the value of Hu, then the internal force fields in the form of shear forces and bending
moments can be calculated and described as shown in Figure 35 Diagram of Earth Pressure & Internal
Pile Force.
6. Calculate pz according to equation (61) with the value of Kq and Kz according to Figure 36;
7. Calculate the number of moments about the capture point Hu;
8. If the number of moments is not close to zero, then try another value of x until the
number of moments = 0;
9. Calculate Hu according to equation (64) and check the Safety Factor, if it has not
reached 2 or more, return to stage 2) by changing the dimensions of the pile;
53
SPLN T5.008: 2015
10. Calculate and draw the field of shear force and bending moment of the pile based on the values of
the forces in steps 6) and 9);
11. Calculate and check the pile deflection according to item 9.9.5, if it does not meet the
requirements, return to step 2) by changing the pile dimensions;
12. Design and cross-sectional drawings of piles in accordance with applicable regulations or
standards.
With the Broms and Brinch-Hansen methods the lateral load bearing capacity, maximum
bending moment, maximum shear force and maximum pile deflection can be calculated
quite simply, but if it is necessary to know the magnitude along the pile depth, both
methods require a calculation process that is not simple.
The Reese-Matlock method can be used for this purpose by using the curves that have
been analyzed for normally consolidated cohesive soils and non-cohesive soils based on
elastic deformation analysis. In the elastic analysis, the load used is the workload, not the
ultimate load. Soil elasticity modulus Es considered to increase linearly as a function of
depth with a value of Es= 0 at ground level.
The shape of the deformation, the angle of inclination, the bending moment, the shear/transverse force
of the pile and the soil reaction along the depth of the pile are shown in Figure 38. Deformation,
Moment, Pile Shear and Soil Reaction.
The calculation of deformation, slope angle, bending moment, pile shear force and soil
reaction is carried out using the following equations;
…………………………… (65)
………….……………… (66)
54
SPLN T5.008: 2015
……………………….… (67)
......................................................... (68)
…………………….… (69)
With:
Y = Pile deflection;
S = Pile deformation tilt angle; M = Pile
bending moment;
V = Pile shear/latitude; P =
Soil reaction;
Index A, B = Index that expresses load H (lateral) or load M (moment) Index y, s,
m, v, p = Index that represents Y, S, M, V, P;
H = Lateral working load at pile end; Mt =
moment working load at pile end; E =
Modulus of elasticity of the pile;
I = moment of inertia of the
pile; T = Pile stiffness factor;
Ay, By = Coefficient of deflection due to load H and Mt;
As, Bs = Coefficient of slope angle due to load H and Mt
Am, Bm = Coefficient of bending moment due to load H and Mt
Av, Bv = Coefficient of shear force due to load H and Mt
Ap, Bp = Coefficient of soil reaction due to loads H and Mt.
The coefficients for A and B are obtained from the curves in Figure 39. Reese-Matlock
Coefficient Load H Free Head Mast with Increasing Modulus.
55
SPLN T5.008: 2015
Figure 39. Reese-Matlock coefficient of load H free head pile with modulus
increase.
As for the pile with free head condition due to moment load, the coefficients are taken
from Figure 40 Reese-Matlock Coefficient Load Mt Free Head Mast with Increasing
Modulus.
56
SPLN T5.008: 2015
Z is the depth coefficient, i.e. the ratio of the depth variable x to the stiffness factor of the
pile T with the maximum value on the curve being 5. Since piles with a length of more
than 5T have the same deflection as shown in the pictures above, these curves can be
used. also for poles having a length greater than 5T.
In piles with a pinched head condition, the angle of inclination at the pile head is zero and
the load Mt entirely supported by the pile cap, so the diagrams that need to be calculated
are the deformation, bending moment of the pile and the reaction of the soil.
………………………………………………………………… (70)
57
SPLN T5.008: 2015
………………………………………………………… (71 )
With:
Fy, Fm, Fp = Coefficient of deflection, bending moment and soil reaction due to load H
according to Figure 41 Reese-Matlock Coefficient of Load H Squeezed Head Pile with
Increased Modulus.
Figure 41. Reese-Matlock coefficient of load H of wedged head pile with modulus
increase
58
SPLN T5.008: 2015
4. Check that the maximum deflection does not exceed the allowable, if it exceeds return
to stage 1) with a larger pile dimension;
5. The design of the pile cross-section is in accordance with the maximum internal
strength of the pile with the allowable strength design method according to
applicable standards, if the cross section is inadequate, return to stage 1) with a
larger cross section.
For the calculation of the ultimate lateral load bearing capacity using the Broms method and the
Brinch-Hansen method, the estimated pile deflection is carried out using the Broms method based
on the reaction modulus. subgrade from the foundation soil.
Pile deflection properties in cohesive soils are mainly influenced by the length coefficient
L which has no units, with:
With:
k = Soil subgrade reaction coefficient that can be taken is equal to k1 according to Table 9;
The pile is considered short/stiff if the value of L is less than 1.5 for free head piles or less
than 0.5 for clamped head piles. The deflections occurring at the ground surface for the
free head pile and the clamped head are as follows:
Free Head Mast;
……………………………………………………………… .........(73)
59
SPLN T5.008: 2015
The pile is considered long/flexible if the value of L is more than 2.5 and the deflection
that occurs at the ground surface for the free head pile and the stuck head is as follows:
Where:
e = Distance H to the ground;
k = Ko/B = Soil subgrade reaction coefficient for long piles; = n1 n2
KO = 0.305 k1
n1 and n2 determined from Table 12 Coefficient n1 and n2 below this:
Calculations can also be done using the curve in Figure 42 Pile Deflection in Cohesive Soil.
60
SPLN T5.008: 2015
Broms correlates the pile deflection with the factor into the pile L (without units) with the
following equation:
………………………………………………………..…….……..……….. (77)
With:
h= Coefficient of modulus of soil variation according to Figure 26; E =
Modulus of elasticity of the pile;
I = moment of inertia of the pile.
……………………………………………………………… ..........(79)
61
SPLN T5.008: 2015
Equation (78) and equation (79) do not apply to very short piles, namely piles with a
length of less than 4 times the diameter.
Besides using the above equations, the calculation of pile deflection can also be
calculated using the curve in Figure 43 Pile Deflection in Non-Cohesive Soil as follows;
The lateral bearing capacity of the pile group is affected by the distance between the single
piles (pile spacing), Prakash (1962) concluded that the lateral pile bearing capacity is the sum
of the lateral bearing capacity of a single pile if the pile spacing is more than 3B in the
direction perpendicular to H and more than (6 – 8)B in the direction parallel to H. Pile spacing
less than these values is treated as a single pile unit equivalent to the pile width B❤ = width of
the pile group in the direction perpendicular to H as shown in Figure 44. Lateral bearing
capacity of the pile group.
62
SPLN T5.008: 2015
The bearing capacity of the raft foundation is the same as the bearing capacity of the shallow
foundation according to items 9.1 to 9.4.
The foundation of the steel frame transmission tower in the rock layer can be in the form of a
block foundation with or without anchors with an example of a block foundation as shown in
Figures 45 and 46.
63
SPLN T5.008: 2015
The compressive axial load bearing capacity of rock with conditions in the field is lower than the
strength of massive or intact rock (intact) which consists of end/base resistance and frictional
resistance which is expressed by the equation:
With:
Qult = ultimate bearing capacity of rock foundation layers;
qb = End resistance/strength i.e. qallowed in Figure 47; fs = Resistance/
friction strength according to Equation (83); Ab = Base area of
foundation; As = Area of the foundation wall.
End resistance or bearing capacity is taken based on empirical equations or curves from Peck et.al
(1974) as shown in Figure 47 End/Base bearing capacity which is influenced by the RQD value with
the maximum value not exceeding the compressive strength of the massive rock (qu).
64
SPLN T5.008: 2015
While the frictional resistance fs used the equation from Kulhawy et.al (2005) as follows:
With:
pa = atmospheric pressure
With the safety factor for the axial compression load bearing capacity of 3, the allowable
compressive axial load bearing capacity is:
The ultimate bearing capacity of the axial tensile load consists of frictional resistance and the weight of the block
foundation, namely:
Qutricle = fs As + W ……………………………………………………………… .......... (85)
With:
W = Weight of block foundation and soil on it if any
If the safety factor for the tensile axial load is the same as the compressive axial load,
then the allowable bearing capacity is:
The shear stability of block foundations in rock is analyzed by the same analogy as
shallow foundations on soil, but by using the parameters of the foundation layer in the
form of rocks, namely:
65
SPLN T5.008: 2015
Rock passive earth pressure Kp calculated based on the value of the shear angle in rock , obtained
from triaxial experiments or with an approximate value of 30°. The factor of safety for shear
stability is determined to be a minimum of 1.5 if the internal shear angle is obtained from
laboratory experiments or 2.0 if an approximate value is used.
The overturning stability is analyzed on the same principles as shallow foundations on
soil and using the same factor of safety as the shear stability factor of safety mentioned
above.
The vertical and horizontal/lateral compressive loads on the block foundation with anchors are considered to
be borne only by the concrete block foundation with the condition that the concrete block foundation must be
embedded in a layer of rock, while the vertical tensile/uplift loads are supported by the anchors and the
weight of the concrete block foundation. The moment load is equivalent to the vertical compressive and
tensile loads and the compressive load is only held by the concrete block.
The bearing capacity of the concrete block foundation section against the vertical compressive load is
calculated using equation (82) above.
The bearing capacity of the anchor foundation is determined by the lowest strength of the
components/materials in the foundation system, namely:
- Strength of steel material or steel anchor connection with concrete block;
- Material strength grout;
- Frictional strength between anchor steel and grout/concrete;
- Friction strength between grout with rocks;
- The strength of the foundation rock mass in carrying the tensile load (uplift),
where the failure occurred in the bedrock layer.
The ultimate tensile bearing capacity of steel anchor materials can be calculated as follows:
With:
Tb = ultimate tensile bearing capacity; Ab =
cross-sectional area of steel anchors;
fy = yield stress of steel anchor material.
Shear strength between anchor steel and grout can be estimated using several formula
recommendations, including:
66
SPLN T5.008: 2015
……………………..………………………………………….…… (90)
With:
b = Shear strength/bond of screw steel reinforcement with concrete/grout (psi);
fc ❤
= compressive strength of concrete/grout (psi);
db = Diameter of steel reinforcement (inch).
American Petroleum Institute, API RP2A, 1984 for plain steel pipe/reinforcement:
With:
fba = Shear strength of plain steel pipe/reinforcement; fcu =
compressive strength of grout characteristics; h = Length
of sliding connector;
s = Sliding connector spacing.
The shear bearing capacity of the anchor steel with grout is as follows;
With:
Tbg = ultimate bearing capacity of steel shear with grout; Pb
= circumference of anchor steel; Lb = length of anchor
steel; FK = Safety factor.
The shear strength of anchor steel with grout (σb or fba) is restricted, some examples of
the value of the restriction include:
Table 13. Ultimate Shear Bearing Capacity of Anchor Steel with Grout (BS 8081)
67
SPLN T5.008: 2015
Table 14. The ultimate shear bearing capacity of steel anchors with Grout (IS: 456-2000)
Limit bond stress between concrete and reinforcement steel deformed in tension of
grade Fe.415 (conforming to IS : 1786-1985 and 1139-1165)
1 (a) With M 15 Mix = 16.0 kg/cm2
(b) With M 20 Mix = 19.5 kg/cm2
Note : For bars in compression the above values shall be increased by 25%
Limit bond stress between concrete and stubs in tension with (a)
M 15 Mix = 10.0 kg/cm2
2
(b) M 20 Mix = 12.0 kg/cm2
For compression above values will be increased by 25%
4 Limit bond stress between hard rock and grout = 2.0 kg/cm2
Shear strength between grout with rocks according to Adam et. al (1976) is a function of
the rock compressive strength orgrout. One of the formulations that can be used is the
one recommended by Horvath – Kenney (1979), namely:
For large diameter (≥ 16 inch):
With:
Sr = ultimate shear strength of grout with rock (psi);
fw = The lowest characteristic compressive strength between grout with concrete (psi).
So that the ultimate shear bearing capacity grout with rocks are:
With:
Tgr = ultimate shear bearing capacity of grout with rock (psi); pg =
Circumference grout (inches); Lg = Length grout;
68
SPLN T5.008: 2015
The failure may occur in the bedrock mass layer, the single anchor failure mechanism is
shown in Figure 48. Single Anchor Failure Mechanism.
The maximum stress in the rock first occurs at the top of the anchor so that local failure
will occur as shown in Figure 48(a). Progressive failure then occurs to the lower end of the
anchor. In partially grouted anchors, local failure at the top does not occur becausegrout
compressed. Failure then occurs up to the lower end of the anchor as shown in Figure
48(b).
The actual shape of the collapse space is very complex influenced by the leveljoint and
fissuring as well as the slope of the bedding plane (bedding plane), the shape of the
conical failure model with an angle of 30° is considered quite conservative for design
calculations. Wyllie (1991) recommends that the top of the cone is in the middle of the
length of the grouted anchor, but this does not apply if the lower end of the anchor is
attached to a plate or bolt retainer.
Because the shear resistance in the rock failure chamber is not taken into account, the
safety factor or rock load factor in calculating the rock weight in the failure chamber is
enough to be taken as 1, so that the ultimate bearing capacity in rock collapse is:
69
SPLN T5.008: 2015
Installation of anchors for tower foundations is usually more than one, so it is necessary
to know the carrying capacity of the anchor group. The failure space of the anchor group
based on the cone failure model is shown in Figure 49. The failure space of the anchor
group is where there is overlapping of the failure space between the anchors.
As an approximation, the ultimate tensile bearing capacity of a block foundation with anchorage is
the sum of the single anchor bearing capacity Ta plus the weight of the concrete block, while the
weight of the soil in the failure chamber is neglected, so:
10 Foundation Drop
Limitation of settlement for truss tower foundations refers to the criteria by Skempton &
Mac Donald (1956), Polskin & Tokar (1957) and NAVFAC DM 7.1 (1971) which are included
in the category of lean buildings/structures with the following limitations:
a) The difference in settlement between the foundation columns with each other 25 mm;
b) Rotation of the foundation, namely the ratio of settlement to the length of the building or the width of the
foundation 0.002.
70
SPLN T5.008: 2015
S = Si + Sc + Ss ………………………………………………………………………………………………..(100)
The instantaneous reduction of the one-dimensional average for cohesive soils uses the
equation from Janbu, 1963 assuming a Poisson ratio of 0.5 for cohesive soils, namely:
With:
o = the influence factor of the depth of the foundation according to Figure 50; 1 =
influence factor of the shape of the foundation according to Figure 50; q = increase
in average soil pressure at the base of the foundation; B = width of the foundation;
71
SPLN T5.008: 2015
Sc = ……………………………………………………………………………………….. (102)
With:
Ss ………………………………………………………………………….. (103 )
With:
Ci = coefficient of secondary consolidation/crawl settlement according to Figure 51;
zi = thickness of compressible soil layer i; t = time.
72
SPLN T5.008: 2015
The largest decrease that occurs is an instantaneous settlement while the creep decrease is
not dominant, the total subsidence of the non-cohesive soil is estimated by the method of
Schmertmann, 1970:
S = C1 C2 p ………………………………………………………………………….……….. (104)
With:
C1 = depth correction factor = 1 - 0.5❤ o / p;
C2 = creep correction factor;
p = increase in effective earth pressure at the base of the foundation = p -❤ o
Izi = strain influence factor according to Figure 52;
E❤I = modulus of elasticity of non-cohesive soil according to equation (8);
Zi = thickness of soil layer i;
n = number of soil layers;
❤o = effective earth pressure above the base of the foundation.
The method of calculating pile foundation settlement on cohesive and non-cohesive soils
is the same as for shallow foundations where pile group foundations are considered as
shallow raft foundations equivalent to a depth of 2/3 pile length with a slope of 1/4 as
shown in Figure 53.
73
SPLN T5.008: 2015
74
SPLN T5.008: 2015
The design of the footing foundation using cone penetration test data consists of several
stages as described in the following flow chart:
Figure 54. Flow chart for the calculation of the footing foundation
75
SPLN T5.008: 2015
The design of the pile foundation consists of several stages as described in the
following flow chart:
76
SPLN T5.008: 2015
77
SPLN T5.008: 2015
The design of the block and anchor foundation consists of several stages as
described in the following flow diagram:
Figure 57. Flowchart of the calculation stages of block foundations and anchors in rock
78
SPLN T5.008: 2015
For steel frame tower foundations, the type of load is in the form of compressive axial static load, tensile axial
and lateral so that the type of load test can be in the form of compressive, tensile and lateral axial load tests.
The planner must determine a test program from several alternative choices as follows:
- Taking one type of load for testing so that the load test results are easier to
evaluate or interpret;
- Taking all types of loads together for testing but load test results are very difficult to
interpret or evaluate;
- Taking all types of loads with a certain loading scenario but the load test results are
difficult to evaluate.
In steel frame tower foundations, in general, the foundation load test is based on giving
only one type of load which is considered critical.
To obtain a safe, reliable and economical foundation design, the foundation load test
must be carried out with the type, location and number of tests determined based on the
analysis taking into account the costs to be incurred and the benefits to be gained (cost-
benefit analysis). One of the criteria or strategies for determining the number of tests
that can be used as a reference that can be considered is as shown in Table 15 taken
fromHandbook on Pile Load Testing by Federation of Piling Specialists, 2006.
79
SPLN T5.008: 2015
Preliminary pile foundation load test (preliminary pile test) is a load test carried out on a
special foundation for testing with a maximum load until the foundation collapses while
the load test on a working pile foundation (working pile) is a load test carried out on a
working foundation with a minimum loading of 100% and a maximum of 200% of the
design load.
Practical foundation load tests can be carried out at two alternative locations, namely:
1) Test Foundation
Foundation load tests are generally carried out on test foundations that are built not
far from the working foundation and the soil conditions are considered the same.
The test is carried out by giving the load gradually until the foundation soil collapses;
2) Work Foundation
If there is sufficient information or experience that the foundation design has been
carried out for the same type of soil elsewhere, the foundation load test can be
carried out at the working foundation location. Loading is usually done in stages up
to a maximum of 100% of the design load.
The procedure for testing at the two locations mentioned above is the same, the only
difference being the maximum load applied to the test foundation.
Test equipment, instrumentation and testing procedures for axial compression loads for steel
frame tower foundations refer to the ASTM D 1143M-07 (2013) standard, “Standard Test Methods
for Deep Foundations Under Static Axial Compressive Load" This standard can also be used for
other types of foundations such as footing foundations, concrete block foundations, raft
foundations and anchor foundations.
80
SPLN T5.008: 2015
The main equipment for loading and measuring tests is shown in Figure 58 which
consists of:
- Hydraulic jack (hydraulic jack);
- load cell (load cell).
Pole deformation measurements are carried out by installing a minimum of 2 different types of measuring
instruments, namely 2 dial gauges which are installed parallel as primary measuring instruments and 1 wire
measuring instrument or survey scale ruler as a secondary measuring instrument which is installed
perpendicular to each other.
The method of testing the load on the pile foundation, can be done with 2 (two) methods
from the 4 (four) methods contained in the ASTM D 1143M-07 (2013) standard, namely: Slow
Maintained Load Test Method (SM Test), Quick Maintained Load Test Method (QM Test), Slow
Maintained Load Test Method (SM Test) used when settlement is an aspect that determines
the design dimensions of the foundation, while Quick Maintained Load Test Method (QM Test)
used if the settlement does not determine the design dimensions of the foundation.
81
SPLN T5.008: 2015
This test method is the recommended method in the ASTM standard with the following
testing stages:
a. The burden is divided into 8 stages with the same increase, for example; 25%, 50%,
75%, 100%, 125%, 150%, 175% and 200% of the design load;
b. The load at each increment is maintained until the deformation rate of reduction
reaches 0.25 mm/hour but does not exceed 2 hours;
c. 200% load is maintained for 24 hours;
d. After that, the load is lowered gradually with the same level of decline, namely 25%
and a lag time of 1 hour for each level of load reduction;
e. After the load has been completely lowered, the test foundation is then given
another load with an increase of 50% to 200% of the design load and the lag time
for each load increase is 20 minutes;
f. Then the load is increased at a rate of 10% every 20 minutes until the foundation
collapses.
The testing time required for this method ranges from 40 hours to 70 hours or even
more. This method is known as the ASTM standard method which is often used before
construction or before carrying out detailed designs.
In the ASTM standard this method is an alternative method (optional) with the following
testing stages:
a. The load is given in 20 stages of increase until it reaches 300% of the design load or
stages of increasing the load by 15%;
b. Loading was maintained for 5 min for each stage with reading intervals every 2.5 min;
c. The loading in point b is carried out until the amount of loading reaches 300% of the
design load;
d. The load is reduced to 0% in the same 4 stages of descent (75% load reduction stage);
e. At each descent, the loading was maintained for 5 minutes with an interval of reading
every 2.5 minutes.
This method is fast and economical with loading completion time between 3 to 5 hours,
this loading condition is close to the condition of undrained soil. This method cannot be
used to estimate the amount of land subsidence.
82
Translated from Indonesian to English - www.onlinedoctranslator.com
This method is an alternative method (optional) in the ASTM standard with the following
main steps:
a. The pile head is loaded so that the rate of increase in pile settlement is 1.25 mm/min;
The advantage of this method is that the test can be completed in a short time, which is
between 2 to 3 hours and is economical. This method is only suitable for pile foundations
with the largest bearing capacity from pile blanket friction, while for foundations with
end bearing capacity it is not suitable because it requires very large hydraulic pressure.
As in the QM Test, this method cannot be used to estimate settlement of pile
foundations.
This method is recommended by the Swedish Pile Commission with the following main
steps:
a. Loading is given up to 1/3 of the design load;
b. The load is reduced to 1/6 of the design load;
c. The loading in point a and point b was repeated 20 times;
d. The loading is increased by 50% of the load in point a and then decreased as in point
b;
e. The loading in point d is repeated as in point c;
f. The loading is continued with the level of increase as in point d until failure occurs.
The time required for this test is very long with many stages, so it is only suitable for
foundation design with cyclic loading such as earthquake loading or engine vibration
loads.
Comparison of the time required for testing of the above test methods is shown in Figure
59 Comparison of Test Time (Fellenius, 1975) below. From the figure, it can be seen that
the SM Test and SC Test require a longer time than other methods, while the CRP Test is a
test method with the fastest completion time.
83
SPLN T5.008: 2015
In Figure 60 the behavior of pile settlement due to loading (Fellenius, 1975) shows the
behavior of pile settlement against loading.
From the figure, it can be seen that the CRP Test curve shows the behavior of the
foundation soil in general when it is given a load until it collapses and the CRP Test curve
is similar to the QM Test curve before the soil collapses.
84
SPLN T5.008: 2015
The method of interpretation of the test results data is carried out using 3 (three) methods
from several of those contained in the ASTM D 1143M-07 (2013) standard as follows:
a. Davisson method (1972);
b. Chin method (1970, 1971);
c. the De Beer Method (1967) or the De Beer & Wallays Method (1972);
d. Brinch Hansen criteria 90% (1963);
e.Brinch Hansen Criteria 80% (1963);
f. Mazur Kiewiecz Method (1972);
g. Fuller & Hoy method (1970);
h. Butler & Hoy Method (1977);
i. The Vander Veen Method (1953).
a. Davisson method
The procedure of this method to determine the failure load of the foundation is as
follows:
1. Draw a graph of the loading and deformation of the test data as shown in Figure 61
Davisson's Method of Interpretation of Test Results;
2. Calculate the change in the elastic length of the pile foundation for a load test data
amount based on Hooke's law so that point A is obtained in Figure 61;
= Qva L / (EA)
With:
Qva = an arbitrary load data magnitude L =
length of the pile foundation
A = cross-sectional area of foundation piles E =
modulus of elasticity of foundation piles
3.Draw a straight line connecting point O with point A; Draw a straight line BC parallel
to line OA so that it intersects the test result curve at point C with the distance
between the two lines equal to;
X = 4 + b/120
With;
X = distance between line OA and BC (mm) b
= pile diameter (mm)
4. The bearing capacity of the pile is the magnitude of the load on the curve at point C.
85
SPLN T5.008: 2015
This method was originally recommended for pile types with a QM Test where the
excess line BC can be drawn (with Qva is the bearing capacity of the design pile) before
the test is carried out so that it can be used as a criterion for the acceptance test or
proof load test.
b. Chinese Method
2. The slope of the regression line from the data in item 1 above is C1;
3. The ultimate load of the pile is 1/C1.
This method can be used for both QM Test and SM Test as long as the load increase and
decrease time is constant.
86
SPLN T5.008: 2015
c. De Beer Method
As shown in Figure 63 Method of Interpretation of Test Results by De Beer, the stages of
this method are as follows:
1. Make a graph between loading and deformation on a logarithmic scale;
2. The resulting graph is in the form of two intersecting straight lines;
3. The ultimate pile load is located at the point of intersection of the two lines above.
This method uses trial and error (trial & error) as shown in Figure 64 Method of
Interpretation of Test Results by Brinch Hansen Criteria 90% with the following
procedure:
1. Make a graph between the load and the deformation of the pile foundation in a normal scale;
2. Take a point on the curve as the ultimate point then read the load magnitude (Qultimate)
and its deformation (Δlimit);
3. Take a point on the curve with the ordinate 90% of Qultimate which is tried in point 1, then read
the magnitude of the deformation;
4. If the amount of deformation for the load is 90% of the ultimate load in point 3, the
amount is 50% oflimit in item 2, then the magnitude of the load taken in item 2 is the
ultimate load of the pile while if it is not the same then return to item 2 with a trial
price for the new ultimate load.
87
SPLN T5.008: 2015
Image 64. The method of interpretation of test results by Brinch Hansen criteria 90%
2. From the results of the data regression in point 1 above, it is found that the slope of the line C1 and
the line constant C2;
3. The magnitude of the load and ultimate deformation of the pile foundation is as follows:
Figure 65. Method of interpretation of test results by Brinch Hansen 80% criteria
This method can be used for QM Test and SM Test and the results are in accordance with the
criteria for collapse of the foundation collapse, but this method is not suitable for testing with
a decrease in load or tests that do not reach collapse with the criteria for falling.
88
SPLN T5.008: 2015
2. Make a division on the axis of the pile deformation with equal intervals and draw a vertical
line so that it intersects the curve. From each of these points of intersection, draw a
horizontal line so that it intersects with the load axis;
3. From each point of intersection between the horizontal line and the load axis, a line is
drawn at an angle of 45° so that it intersects the horizontal line above it;
4. The connecting line between the points of intersection in point 3 above will generally form
an almost straight line that intersects the load axis. This point of intersection is the
ultimate load of the pile foundation.
This method assumes that the curve is a parabolic function, so the results should be close
to the results of the Brinch Hansen Criterion method of 80%. Sometimes the connecting
line generated in point 4 does not approach a straight line, so justification is needed.
Figure 67. Methods of interpretation of test results by Fuller & Hoy and by Butler & Hoy
89
SPLN T5.008: 2015
This method can be used for QM Tests, but it has drawbacks if it is carried out for long
piles because the elastic line from the test results is long enough so that a point with a
slope of 0.05 inch/ton will be obtained long before the actual failure occurs.
As shown in Figure 67 Methods of Interpretation of Test Results by Fuller & Hoy and by
Butler & Hoy, this method has the following stages:
1.Draw the test result curve in a normal scale;
2. The ultimate load and deformation of the pile is the point of intersection between a
line having a slope of 0.05 inch/ton as in the Fuller & Hoy method with one of the
following lines:
a. The slope line at the beginning of the elastic curve or;
b. curve line parallel to the load shedding curve starting from point O (not shown
in the figure).
90
SPLN T5.008: 2015
The study conducted by Joshi and Sharma (1987) on the 9 interpretation methods
mentioned above for 5 data from the SM Test test results on different types of pile
foundations concluded the following:
1. For drilled pile foundations and belled pile piles, the method
Fuller & Hoy estimates the ultimate load well;
2. For Franki piles, the Davisson, Fuller & Hoy and Buttler & Hoy methods predict the
ultimate load well;
3. For H steel piles, the Brinch Hansen Criteria 90% method and the Fuller & Hoy method
predict the ultimate load well.
Meanwhile, the results of a similar study by Fellenius (1980) on concrete piles with the
CRP Test showed that interpretations using the Fuller & Hoy method, Brinch Hansen
Criteria 90% and the Vander Veen method produced more rational predictions than other
methods.
From all cases reviewed, in general, the De Beer method and the Davisson method
produce conservative predictions, while the Chin method gives a value above the failure
load of the actual failure test. The Fuller & Hoy method is the method that produces the
most rational value. As an illustration of the results of the study, it can be seen in Table
16. Collapse Loads of various Interpretation Methods below:
Test equipment, instrumentation and testing procedures for tensile axial loads for steel frame
tower foundations refer to the ASTM D 3689M-07 (2013) e1 standard, “Standard Test Methods for
Deep Foundations Under Static Axial Tensile Load" This standard can also be used for other types
of foundations such as footing foundations, concrete block foundations, raft foundations and
anchor foundations.
91
SPLN T5.008: 2015
The minimum clearance between the test pile and the reaction beam is 5 times the diameter of the test
pile but not less than 2.5 m.
The calibration and strength requirements of the test beam and reaction beam are the same as those for the
tests for axial compression loads.
92
SPLN T5.008: 2015
The type and requirements of movement measuring equipment for tensile axial load
testing are the same as for movement measuring equipment for compressive axial load
testing.
The loading method for the tensile axial load test is the same as for the compressed axial
load, the only difference being the direction of the load.
The method of interpretation of test results to predict the load on pile failure is
influenced by the tolerance of the movement of the test pile at the time of failure. In
general, the failure load in the tensile axial load is easier to distinguish than for the axial
compression test because the decrease in frictional resistance which is quite large before
failure can be measured more clearly. The failure / ultimate load can be considered as the
minimum tensile axial load from the 3 criteria below (Sharma et. al, 1984):
1. The ultimate tensile load is the magnitude of the tensile load that produces a net
movement (net movement) from the top end of the test pile by 6.25 mm (0.25
inch);
2. The ultimate tensile load occurs at the point of intersection of the 2 tangents on
the test curve;
3. The ultimate tensile load at the time of a sudden disproportionate increase in
movement (point on the sharpest curve).
An example of the criteria for determining the ultimate tensile load is shown in Figure 70. An
example of determining the ultimate tensile load for a pile (Sharma et. al., 1984) is below:
Image 70. An example of determining the ultimate pile tensile load (Sharma et. al., 1984)
93
SPLN T5.008: 2015
From the picture above, the ultimate tensile load based on the 3 criteria above is as
follows:
a. Criterion 1: 758 kN;
b. Criterion 2: 779 kN;
c. Criterion 3: 800 kN.
So that the ultimate tensile load from the test pile is the one that has a minimum value of the
3 criteria above, which is 758 kN.
Test equipment, instrumentation and lateral load testing procedures for steel frame tower
foundations refer to the ASTM D 3966M-07 (2013) e1 standard, “Standard Test Methods for Deep
Foundations Under Lateral Load" This standard can also be used for other types of foundations
such as footing foundations, concrete block foundations, raft foundations and anchor foundations.
The loading apparatus for testing pile lateral loads is shown in Figure 71 where the load
is applied by a hydraulic jack placed between the test pile and the support which can be
(a) reaction pile, (b) deadman or (c) platform.
94
SPLN T5.008: 2015
95
SPLN T5.008: 2015
Dial gauges and wire-mirror gauges are used to measure the total movement of the pile
head, while the inclinometer is placed on the axis of the test pile to measure the
distribution of movement or flexural deformation of the pile. We recommend that at least
2 pieces of motion measurement equipment are used in each test.
96
SPLN T5.008: 2015
1.Standard Loading:
a. Give the total load in 10 stages up to 200% of the design load, for example 25%,
50%, 75%, 100%, 125%, 150%, 170%, 180%, 190% and 200%. The loading at
25% and 50% was maintained for 10 minutes, the loading of 75% was
maintained for 15 minutes while the other loading was for 20 minutes;
b. After the load reaches 200%, this load is maintained for 60 minutes then the
load is lowered in stages every 50%, namely for example 150%, 100%, 50% and
0% with loading maintained for 10 minutes for each step of descent;
2. Non-standard loading:
a. After the standard loading test is completed as in point 1, increase the load in
stages by 50% so that it reaches 200% of the design load with a duration of
every 10 minutes for each stage;
b. Then the load is increased in increments of 10% every 15 minutes until the pile
collapses or up to another specified load value;
c. The maximum load in point b is maintained for 30 minutes and then the load is
reduced to levels of 75%, 50%, 25% and 0% with a load holding time of 10
minutes for each stage.
The ultimate lateral load of the test pile is determined based on the lowest value of the 2
criteria below:
1. Load at the time of movement of 6.25 mm (0.25 inch) or,
2. Load at the point of intersection of 2 tangents to the test curve.
97
SPLN T5.008: 2015
The ultimate lateral load based on the 2 criteria above are as follows;
So that the ultimate lateral load of the test pile is 96.5 kN.
98