1. GENERAL:
a. TYPICAL DETAILS AND SECTIONS SHALL APPLY WHERE SPECIFIC DETAILS 7. BAR SUPPORTS:
ARE NOT SHOWN ON THE DRAWINGS, AND ONLY WHERE A REFERENCE TO BAR SUPPORTS SHALL BE PROVIDED IN ACCORDANCE WITH ACI 315 DETAILING MANUAL
THESE DETAILS AND SECTIONS IS MADE. AND AS SPECIFIED.
b. EACH OF THE STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION
c. ANY STOP IN CONCRETE WORK MUST BE MADE NEAR THE QUARTER OF SPAN WITH
2. CONCRETE: VERTICAL BULK HEAD AND SHALL BE APPROVED BY THE ENGINEER.
a. DESIGN COMPRESSIVE STRENGTH OF CONCRETE, f'c SHALL BE AS FOLLOWS: d. SEALANTS SHALL BE PLACED AT LOCATIONS INDICATED ON THE DRAWINGS AND IN
1- CAST-IN-SITU CONCRETE IN REINFORCED CONCRETE MEMBERS THE SPECIFICATIONS AT CONSTRUCTION, CONTROL, ISOLATION AND EXPANSION
FOUNDATIONS CONCRETE CUBE STRENGTH MIN. fcu=35 N/mm² JOINTS IN ACCORDANCE WITH THE STANDARD DETAILS AND SPECIFICATIONS.
COLUMNS CONCRETE CUBE STRENGTH MIN. fcu=35 N/mm² e. REFER TO ARCHITECTURAL DRAWINGS, SPECIFICATIONS AND STANDARD DETAILS
BEAMS AND SLABS CONCRETE CUBE STRENGTH MIN. fcu=30 N/mm². FOR DETAILS OF EXPANSION JOINTS.
2- BLINDING CONCRETE B.S. fcu=15N/mm². f. EXPANSION JOINT ASSEMBLIES AND FILLER MATERIALS SHALL HAVE A FIRE RATING
b. STRENGTH TESTS FOR CONCRETE SHALL BE MADE IN ACCORDANCE WITH CORRESPONDING TO ADJACENT MATERIALS. JOINTS SHALL BE COMPLETELY SEALED
"METHOD OF TEST FOR COMPRESSIVE STRENGTH OF MOLDED CONCRETE CUBE, AGAINST SMOKE PENETRATION.
B.S. 1881-PART116/1983. g. ALL STEEL CONNECTION JOINT TO BE APPROVED BY STRUCTURAL ENGINEER.
c. THE FOLLOWING ADDITIONAL REQUIREMENTS SHALL ALSO APPLY
- MINIMUM CEMENT CONTENT : 380 kg/m3. 9. OPENINGS, PIPES SLEEVES AND FITTINGS EMBEDDED IN CONCRETE:
- MAXIMUM CEMENT CONTENT : 425kg/m3 a. THE CONTRACTOR SHALL REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR
- MAXIMUM WATER/CEMENT RATIO : 0.45 VERIFICATION OF OPENINGS, PIPES, CONDUITS, SLEEVES AND FITTINGS IN REINFORCED
- ADMIXTURES : SUPERPLASTICIZERS AS APPROVED BY THE ENGINEER . CONCRETE COLUMNS, BEAMS AND SLABS.
- MAXIMUM AGGREGATE SIZE : 20mm. b. NO OPENINGS, PIPES OR SLEEVES OTHER THAN THOSE INDICATED ON STRUCTURAL
- MAXIMUM TOTAL CHLORIDE PERCENTAGE BY WEIGHT OF CEMENT FROM ALL DRAWINGS SHALL BE PLACED IN COLUMNS, BEAMS, OR SLABS WITHOUT THE APPROVAL
SOURCES (CEMENT, SAND, AGGREGATES, ADMIXTURES AND WATER) : 0.20%, OF THE STRUCTURAL ENGINEER.
EXPRESSED AS CHLORIDE ION, CI. c. OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS UP TO A MAXIMUM DIMENSION
- MAXIMUM TOTAL SULFATE CONTENT BY WEIGHT OF CEMENT FROM ALL OF 200mm. MAY BE PLACED OR DRILLED IN SOLID SLABS.
SOURCES : 4.0% . d. ADDITIONAL STEEL AROUND THE OPENING TO BE PROVIDED WITH U-BAR FOR THE
b. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A497, A185 OR TO B.S. 4483. 10. CONCRETE PROTECTION:
a. FOUNDATIONS
60mm OVER BLINDING, 75mm EARTH FACE, 75mm ALL OTHER 11. BASE SLABS ON GROUND:
FACE a. FILL UNDER BASE SLABS ON GROUND SHALL BE COMPACTED IN ACCORDANCE WITH
SPECIFICATIONS.
b. GROUND BEAM (IF ANY)
b. CONSTRUCTION, CONTROL AND ISOLATION JOINTS SHALL BE PROVIDED AT PLACES
75mm ALL OTHER FACE 60mm OVER BLINDING, 75mm EARTH FACE,
d. COLUMN AND PEDESTAL INDICATED ON DRAWINGS. ALL JOINTS SHALL BE IN ACCORDANCE WITH THE STANDARD
75mm EARTH FACE, 40mm ALL OTHER FACE DETAILS AND THE SPECIFICATIONS.
b. UNLESS OTHERWISE INDICATED ON DRAWINGS, AT APPROVED SPLICES BARS SHALL 13. DESIGN LOADS:
BE LAPPED A MINIMUM OF A CLASS "B" SPLICE. a. SUPERIMPOSED DEAD LOAD: DEAD LOADS WILL BE BASED ON ACTUAL SELF WEIGHT OF THE
C. SPLICE LENGTHS FOR EACH BAR SIZE ARE 40d STRUCTURE, FINISHES, PARTITIONS, MECHANICAL AND ELECTRICAL SERVICES, ETC. FOR
d. ALL HORIZONTAL BARS IN SLABS AND BEAMS HAVING MORE THAN 300mm OF PARTITION BLOCKS (HOLLOW & SOLID), THE QUALITY SHOULD BE APPROVED BY THE ARCHITECT
CONCRETE BELOW THEM SHALL BE CONSIDERED AS "TOP BARS". & ENGINEER FOR COMPATIBILITY.
e. UNLESS OTHERWISE INDICATED ON DRAWINGS, AT APPROVED SPLICES, NO MORE b. LIVE LOADS:
THAN 1/2 THE BARS MAY BE SPLICED AT A GIVEN SECTION (EACH ALTERNATE BAR). 1- TYPICAL FLOORS (GENERAL) 7 KN/m².
f. UNLESS OTHERWISE INDICATED, BARS DESIGNATED CONTINUOUS (CONT.) MAY BE 2- INACCESSIBLE ROOFS 2 KN/m².
SPLICED CLASS A SPLICE AT CONVENIENT LOCATION WITH NO MORE THAT 1/2 THE BARS c. STATIC LOAD DESIGN CODE ACI 318-19
(EACH ALTERNATE BAR) SPLICED AT A GIVEN SECTION
6. BAR BENDS:
6 BAR DIAMETERS FOR Ø10 TO Ø20 8 BAR DIAMETERS FOR Ø25 TO Ø32
4 BAR DIAMETERS FOR STIRRUPS AND TIES TITLE: Structural Details SCALE: AS.SH.
DWG. NO: 00 00