Service Manual: Models: ASD9U2I DN Asd912Ui DN

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

Service Manual

Models: ASD9U2I DN
ASD912UI DN
Service Manual

Model '2608,'1
Product Code
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50
supply
Phases 1
Cooling capacity(max~min) W 5200(2140~4836)
Heating capacity(max~min) W 5400(2579~5510)
Cooling Power Input(max~min) W 1450
Heating Power Input(max~min) W 1550
Cooling Current Input A 6.88
Heating Current Input A 6.43
Rated Power Input W 1780
Rated Current A 7.90
SEER W/W 6.1
SCOP W/W 4.0
ZHUHAI LANDA COMPRESSOR
Compressor Trademark
CO.,LTD
Compressor Model QXA-B141zF030A
Compressor Refrigerant Oil Type RB68EP
Compressor Type Inverter Rotary
L.R.A A 25
Compressor Rated Load Amp (RLA) A 7.2
Compressor Power Input W 1440
"1NT11L-6233
Compressor Thermal Protector
KSD115OCHPC115/95U1"
Throttling Method Electron expansion valve
O
Cooling Operation Ambient Temperature Range C 18~43
O
Heating Operation Ambient Temperature Range C -15~24
Condenser Material Aluminum Fin-copper Tube
Condenser Pipe Diameter mm ĭ
Rows-Fin Gap(mm) mm 2-1.4
Coil length (l) X height (H) X coil width (L) mm 851X38.1X660
Fan Motor Speed (rpm) (H/M/L) rpm 800
Output of Fan Motor W 60
Outdoor
Fan Motor RLA A /
Unit
Fan Motor Capacitor ȝ) /
Air Flow Volume of Outdoor Unit m3/h 3200
Fan Type-Piece $[LDOÀRZ
Fan Diameter mm ĭ
Defrosting Method Automatic Defrosting
Climate Type T1
Isolation I
Moisture Protection IP24
Permissible Excessive Operating Pressure for the
MPa 4.3
Discharge Side
Permissible Excessive Operating Pressure for the
MPa 2.5
Suction Side
Dimension (WXHXD) mm 963X700X396
Dimension of Package (LXWXH) mm 1026X455X735
Dimension of Package(LXWXH) mm 1029X458X750
Net Weight kg 51
Gross Weight kg 55
efrigerant Charge R410A
Refrigerant Charge kg 1.60

Technical Information
Service Manual

Cross-sectional Area of Power Cable Conductor mm2 / /


Recommended Power Cable(Core) N 3 3
Connection Pipe Connection Method - Flare Connection Flare Connection
Not Additional Gas Connection Pipe Length m 10 10
Connection Pipe Gas Additional Charge g/m 20 20
Outer Diameter of Liquid Pipe(GREE Allocation)
mm ĭ ĭ
(Metric)
Outer Diameter of Gas Pipe(GREE Allocation)
mm ĭ ĭ
Outdoor (Metric)
Unit Outer Diameter of Liquid Pipe(GREE Allocation)
mm ĭ ĭ
(Metric)
Outer Diameter of Gas Pipe(GREE Allocation)
mm ĭ ĭ
(Metric)
Connection Pipe Max. Height Distance(indoor and
m 5 5
indoor)
Max. equivalent connection pipe length(outdoor to
m 10 10
last indoor)
Connection Pipe Max. Length Distance(total lenght) m 20 20
The above data is subject to change without notice; please refer to the nameplate of the unit.

Technical Information
6SHFL¿FDWLRQ6KHHW
'HKXPLGLI\LQJ9ROXPH /K 0.8 1.4
$LU)ORZ9ROXPH 6++0/6/  m3K 550/500/430/300/- 550/480/410/290/-
Cooling Capacity
Model W '6.,'%
2500 3200
'6.,'%
'HKXPLGLI\LQJ9ROXPH /K 0.8 1.4
ServiceService
Service
Service
Manual Manual
ManualManual
Heating Capacity W 2800 3400

6SHFL¿FDWLRQV

6SHFL¿FDWLRQV
6SHFL¿FDWLRQV
6SHFL¿FDWLRQV
$LU)ORZ9ROXPH 6++0/6/  m3K 550/500/430/300/- 550/480/410/290/-
6SHFL¿FDWLRQ6KHHW
6SHFL¿FDWLRQ6KHHW
6SHFL¿FDWLRQ6KHHW
6SHFL¿FDWLRQ6KHHW
'HKXPLGLI\LQJ9ROXPH /K 0.8 1.4
Model of Indoor Unit '6.,'%
'6.,'%
'6.,'%
'6.,'%
'6.,'% '6.,'%
Model
Model
Model
Model '6.,'%
'6.,'%
'6.,'%
'6.,'%
3URGXFW&RGHRI,QGRRU8QLW
Cooling Capacity W 2500 3200
Model of Indoor Unit
)DQ7\SH '6.,'%
&URVVÀRZ '6.,'%
&URVVÀRZ
Heating Capacity W 2800 3400
3URGXFW&RGHRI,QGRRU8QLW
'LDPHWHU/HQJWK ';/  mm Ɏ; ĭ;
$LU)ORZ9ROXPH 6++0/6/  m3K 550/500/430/300/- 550/480/410/290/-
)DQ7\SH
)DQ0RWRU&RROLQJ6SHHG 6++0/6/  r/min &URVVÀRZ
1300/1200/1100/850/- &URVVÀRZ
1350/1200/1100/850/-
'HKXPLGLI\LQJ9ROXPH /K 0.8 1.4
'LDPHWHU/HQJWK ';/  mm Ɏ; ĭ;
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
Model of Indoor Unit r/min 1250/1150/1050/900/-
'6.,'% 1350/1200/1100/900/-
'6.,'%
)DQ0RWRU&RROLQJ6SHHG 6++0/6/  r/min 1300/1200/1100/850/- 1350/1200/1100/850/-
Cooling
Cooling
Cooling
Capacity
Capacity
CoolingCapacity
Capacity
3URGXFW&RGHRI,QGRRU8QLW WW WW 2500 25002500
2500 3200 32003200
3200
Heating
Heating
Heating
Capacity
Capacity
Heating )DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
Capacity
Capacity WW r/min
WW 1250/1150/1050/900/-
2800 2800 2800
2800 1350/1200/1100/900/-
3400 3400 3400
3400
)DQ7\SH &URVVÀRZ &URVVÀRZ
'LDPHWHU/HQJWK ';/  mm Ɏ; ĭ;
3
$LU)ORZ9ROXPH 6++0/6/ 
)DQ0RWRU&RROLQJ6SHHG 6++0/6/ 
(YDSRUDWRU)RUP m K
r/min 550/500/430/300/-
1300/1200/1100/850/-
$OXPLQXP)LQFRSSHU7XEH 550/480/410/290/-
1350/1200/1100/850/-
$OXPLQXP)LQFRSSHU7XEH
Model
'HKXPLGLI\LQJ9ROXPH of Indoor Unit
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/  /K
r/min '6.,'%
0.8
1250/1150/1050/900/- '6.,'%
1.4
1350/1200/1100/900/-
Indoor Unit Pipe Diameter mm ĭ5 ĭ
3URGXFW&RGHRI,QGRRU8QLW
5RZ¿Q*DS
(YDSRUDWRU)RUP mm 2-1.4
$OXPLQXP)LQFRSSHU7XEH 2-1.4
$OXPLQXP)LQFRSSHU7XEH
&RLO/HQJWK /;';: 
)DQ7\SH mm ;;
&URVVÀRZ ;;
&URVVÀRZ
Indoor Unit Pipe Diameter ĭ5 ĭ
5RZ¿Q*DS
Swing Motor Model
'LDPHWHU/HQJWK ';/  mm 2-1.4
MP24AN
Ɏ; 2-1.4
MP24AN
ĭ;
&RLO/HQJWK /;';: 
$LU)ORZ9ROXPH 6++0/6/ 
$LU)ORZ9ROXPH 6++0/6/ 
$LU)ORZ9ROXPH 6++0/6/ 
$LU)ORZ9ROXPH 6++0/6/  m3K
)DQ0RWRU&RROLQJ6SHHG 6++0/6/  mmm
m3K mr/min
3 3
KK 550/500/430/300/- ;;
550/500/430/300/-
550/500/430/300/-
550/500/430/300/-
1300/1200/1100/850/- 550/480/410/290/-;;
550/480/410/290/-
550/480/410/290/-
550/480/410/290/-
1350/1200/1100/850/-
'HKXPLGLI\LQJ9ROXPH
'HKXPLGLI\LQJ9ROXPH(YDSRUDWRU)RUP
Swing
'HKXPLGLI\LQJ9ROXPH
'HKXPLGLI\LQJ9ROXPH Motor Model $OXPLQXP)LQFRSSHU7XEH
MP24AN $OXPLQXP)LQFRSSHU7XEH
1.41.4 MP24AN
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ /K/K /K
/K
r/min 0.80.8 0.8 0.8
1250/1150/1050/900/- 1.4
1.4
1350/1200/1100/900/-
Pipe Diameter
6RXQG3UHVVXUH/HYHO 6++0/6/ 
Indoor Unit Model mm
dB (A) ĭ5
40/37/35/28/- ĭ
42/37/34/28/-
of Indoor Unit '6.,'% '6.,'%
5RZ¿Q*DS
6RXQG3RZHU/HYHO 6++0/6/  mm
dB (A) 2-1.4
55/49/47/40/- 2-1.4
55/49/46/40/-
3URGXFW&RGHRI,QGRRU8QLW
&RLO/HQJWK /;';:  mm ;; ;;
6RXQG3UHVVXUH/HYHO 6++0/6/ 
'LPHQVLRQ :;+;'  dBmm (A) 40/37/35/28/-
;; 42/37/34/28/-
;;
)DQ7\SH
Swing Motor Model &URVVÀRZ
MP24AN &URVVÀRZ
MP24AN
6RXQG3RZHU/HYHO 6++0/6/ 
'LPHQVLRQRI&DUWRQ%R[ /;:;+ dBmm (A) 55/49/47/40/-
;; 55/49/46/40/-
;;
'LDPHWHU/HQJWK ';/  mm Ɏ; ĭ;
'LPHQVLRQ :;+;' 
(YDSRUDWRU)RUP
'LPHQVLRQRI3DFNDJH /;:;+  mm
mm ;;
$OXPLQXP)LQFRSSHU7XEH
;; ;;
$OXPLQXP)LQFRSSHU7XEH
;;
)DQ0RWRU&RROLQJ6SHHG 6++0/6/  r/min 1300/1200/1100/850/- 1350/1200/1100/850/-
'LPHQVLRQRI&DUWRQ%R[ /;:;+
Pipe Diameter
1HW:HLJKW mm
NJ ;;
ĭ5
8.5 ;;
ĭ
8.5
Indoor Unit
Model
Model
ofModel
Model
Indoor
of Indoor
ofof
Unit
Indoor
Indoor
Unit Unit
Unit
6RXQG3UHVVXUH/HYHO 6++0/6/  dB '6.,'%
(A) '6.,'%
'6.,'%
'6.,'%
40/37/35/28/- '6.,'%
'6.,'%
'6.,'%
'6.,'%
42/37/34/28/-
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
5RZ¿Q*DS
*URVV:HLJKW r/min
mm
NJ 1250/1150/1050/900/-
2-1.4
9.5 1350/1200/1100/900/-
2-1.4
9.5
'LPHQVLRQRI3DFNDJH /;:;+  ;; ;;
3URGXFW&RGHRI,QGRRU8QLW
3URGXFW&RGHRI,QGRRU8QLW
3URGXFW&RGHRI,QGRRU8QLW
3URGXFW&RGHRI,QGRRU8QLW
6RXQG3RZHU/HYHO 6++0/6/  dB (A) 55/49/47/40/- 55/49/46/40/-
&RLO/HQJWK /;';: 
1HW:HLJKW mm
NJ ;;
8.5 ;;
8.5
)DQ7\SH
)DQ7\SH
)DQ7\SH
)DQ7\SH
'LPHQVLRQ :;+;'  mm &URVVÀRZ
&URVVÀRZ
&URVVÀRZ
&URVVÀRZ
;; &URVVÀRZ
&URVVÀRZ
&URVVÀRZ
&URVVÀRZ
;;
Swing Motor Model
*URVV:HLJKW NJ MP24AN
9.5 MP24AN
9.5
'LDPHWHU/HQJWK ';/ 
'LDPHWHU/HQJWK ';/ 
'LDPHWHU/HQJWK ';/ 
'LDPHWHU/HQJWK ';/ 
'LPHQVLRQRI&DUWRQ%R[ /;:;+ mmmm mm mm
mm Ɏ;
Ɏ;
Ɏ;
Ɏ;
;; ĭ;
ĭ;ĭ;
ĭ;
;;
)DQ0RWRU&RROLQJ6SHHG 6++0/6/ 
)DQ0RWRU&RROLQJ6SHHG 6++0/6/ 
)DQ0RWRU&RROLQJ6SHHG 6++0/6/ 
)DQ0RWRU&RROLQJ6SHHG 6++0/6/ 
'LPHQVLRQRI3DFNDJH /;:;+  r/min
r/minr/min
r/min
mm1300/1200/1100/850/-
1300/1200/1100/850/-
1300/1200/1100/850/-
1300/1200/1100/850/-
;; 1350/1200/1100/850/-
1350/1200/1100/850/-
1350/1200/1100/850/-
1350/1200/1100/850/-
;;
(YDSRUDWRU)RUP
1HW:HLJKW NJ(A) $OXPLQXP)LQFRSSHU7XEH
8.5 $OXPLQXP)LQFRSSHU7XEH
8.5
6RXQG3UHVVXUH/HYHO 6++0/6/ 
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
)DQ0RWRU+HDWLQJ6SHHG 6++0/6/ 
r/min dB
r/minr/min
r/min 40/37/35/28/-
1250/1150/1050/900/-
1250/1150/1050/900/-
1250/1150/1050/900/-
1250/1150/1050/900/- 42/37/34/28/-
1350/1200/1100/900/-
1350/1200/1100/900/-
1350/1200/1100/900/-
1350/1200/1100/900/-
Pipe Diameter
*URVV:HLJKW
Indoor Unit 6RXQG3RZHU/HYHO 6++0/6/  mm
NJ ĭ5
9.5 ĭ
9.5
dB (A) 55/49/47/40/- 55/49/46/40/-
5RZ¿Q*DS mm 2-1.4 2-1.4
2 'LPHQVLRQ :;+;' 
&RLO/HQJWK /;';:  mm
mm ;;
;; ;;
Technical Information
;;
'LPHQVLRQRI&DUWRQ%R[ /;:;+
Swing Motor Model mm ;;
MP24AN ;;
MP24AN
2 'LPHQVLRQRI3DFNDJH /;:;+  mm ;; Technical Information
;;
(YDSRUDWRU)RUP
(YDSRUDWRU)RUP
(YDSRUDWRU)RUP
(YDSRUDWRU)RUP $OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH$OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH
$OXPLQXP)LQFRSSHU7XEH
1HW:HLJKW NJ 8.5 8.5
Indoor
Indoor
Unit Pipe
Indoor
Indoor Pipe
Diameter
Unit Unit Pipe
Diameter
PipeDiameter
Diameter
Unit *URVV:HLJKW mm mm mmmm ĭ5 ĭ5 ĭ5
ĭ5 ĭĭ ĭ ĭ
6RXQG3UHVVXUH/HYHO 6++0/6/  dB NJ(A) 9.5
40/37/35/28/- 9.5
42/37/34/28/-
5RZ¿Q*DS
5RZ¿Q*DS
5RZ¿Q*DS
5RZ¿Q*DS mmmm mm mm 2-1.4
2-1.42-1.4
2-1.4 2-1.4
2-1.42-1.4
2-1.4
6RXQG3RZHU/HYHO 6++0/6/ 
&RLO/HQJWK /;';: 
&RLO/HQJWK /;';: 
&RLO/HQJWK /;';: 
&RLO/HQJWK /;';:  mmmm mm dBmm (A) ;;
55/49/47/40/-
;;
;;
;; 55/49/46/40/-
;;
;;
;;
;;
2 Technical Information
Swing
Swing 'LPHQVLRQ :;+;' 
Motor
Swing
Swing
Motor
Model
Motor
Motor
ModelModel
Model mm MP24AN ;;
MP24AN
MP24AN
MP24AN MP24AN ;;
MP24AN
MP24AN
MP24AN
'LPHQVLRQRI&DUWRQ%R[ /;:;+ mm ;; ;;
'LPHQVLRQRI3DFNDJH /;:;+  mm ;; ;;
6RXQG3UHVVXUH/HYHO 6++0/6/ 
6RXQG3UHVVXUH/HYHO 6++0/6/ 
6RXQG3UHVVXUH/HYHO 6++0/6/ 
6RXQG3UHVVXUH/HYHO 6++0/6/ 
1HW:HLJKW dB dB
(A)(A)
dBdB(A)
NJ(A) 40/37/35/28/-
40/37/35/28/-
40/37/35/28/-
40/37/35/28/-
8.5 42/37/34/28/-
42/37/34/28/-
42/37/34/28/-
42/37/34/28/-
8.5
*URVV:HLJKW
6RXQG3RZHU/HYHO 6++0/6/ 
6RXQG3RZHU/HYHO 6++0/6/ 
6RXQG3RZHU/HYHO 6++0/6/ 
6RXQG3RZHU/HYHO 6++0/6/  dB dB
(A)(A)
dB NJ(A)
dB(A) 55/49/47/40/- 9.5
55/49/47/40/-
55/49/47/40/-
55/49/47/40/- 55/49/46/40/- 9.5
55/49/46/40/-
55/49/46/40/-
55/49/46/40/-
2 Technical Information
'LPHQVLRQ :;+;' 
'LPHQVLRQ :;+;' 
'LPHQVLRQ :;+;' 
'LPHQVLRQ :;+;'  mmmm mm
mm ;;
;;
;;
;; ;;
;;
;;
;;
'LPHQVLRQRI&DUWRQ%R[ /;:;+
'LPHQVLRQRI&DUWRQ%R[ /;:;+
'LPHQVLRQRI&DUWRQ%R[ /;:;+
'LPHQVLRQRI&DUWRQ%R[ /;:;+ mmmm mm
mm ;;
;;
;;
;; ;;
;;
;;
;;
'LPHQVLRQRI3DFNDJH /;:;+ 
'LPHQVLRQRI3DFNDJH /;:;+ 
'LPHQVLRQRI3DFNDJH /;:;+ 
'LPHQVLRQRI3DFNDJH /;:;+  mmmm mmmm ;;
;;
;;
;; ;;
;;
;;
;;
1HW:HLJKW
1HW:HLJKW
1HW:HLJKW
1HW:HLJKW NJ NJ NJNJ 8.58.5 8.5
8.5 8.58.5 8.5
8.5
*URVV:HLJKW
*URVV:HLJKW
*URVV:HLJKW
*URVV:HLJKW NJ NJ NJNJ 9.59.5 9.5
9.5 9.59.5 9.5
9.5

2 Technical Information

2 22 Technical
Technical
Technical
Technical
Information
Information
Information
Information
Service Manual

Outline Dimension Diagram


Indoor Unit

W D

W1 W2 W3

Φ55
Φ55

35 35

75 75

Unit:mm

Models W H D W1 W2 W3
09/12K 773 250 185 131 462 180

Technical Information
Service
Service ManualManual

3. Outline
3. Outline
Dimension
Dimension
Diagram
Diagram

.

892 341

700
963 396

560

368

Unit:mm

. .
12 Technical Information
892 892 341 341
700

700

963 963 396 396

560 560
368

368

Unit:mm
Unit:mm

12 12 Technical
Technical
Information
Information
Service Manual

Function and Control


Remote Controller Introduction
Buttons on Remote Controller

1 On/Off button
2 Mode button
3 Fan button
4 ▲/ button

1 5 Swing button
2
6 Sleep button
3 4
7 Temp button
5
6 8 Turbo button
7
8 9 I Feel button
9
10 10 Timer button
12
11 11 X-Fan button
12 Light button

Icon Display on Remote Controller


Temp. display type
:Set temp. :Indoor ambient temp.
:Outdoor ambient temp.
Turbo mode
Set fan speed
Send signal
Operation mode Child lock
Auto mode health function
ventilation operation
Cool mode 8ć heating function
Dry mode Set temperature
Fan mode Sleep mode
Light function
Heat mode I feel function
X-fan mode
Set time
TIMER ON /TIMER OFF
Up & down swing
Operation introduction of remote controller
Note: “ ” This is a general remote controller. Some models have this function while some do not. Please refer to the
actual models.
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which
the model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
●After putting through the power, the air conditioner will give out a sound.Operation indictor " " is ON (red indicator). After that,
you can operate the air conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " "on the display of remote controller will
blink once and the air conditioner will give out a “de” sound, which means the signal has been sent to the air conditioner.
● Under off status, set temperature and clock icon will be displayed on the display of remote controller (If timer on, timer off and
light functions are set, the corresponding icons will be displayed on the display of remote controller at the same time); Under on
status, the display will show the corresponding set function icons.

Technical Information
Service Manual

1. ON/OFF button
Press this button to turn on the unit. Press this button again to turn off the unit.

2. MODE button
Each time you press this button,a mode is selected in a sequence that goes from AUTO, COOL, DRY, FAN, and HEAT *,
as the following:
* Note: Only for models with heating function.
AUTO COOL DRY FAN HEAT*

Fan Swing

Fan Swing

Swing

Fan Swing

Fan Swing

3. FAN button
This button is used for setting Fan Speed in the sequence that goes from AUTO, , to , then back to Auto.

Auto

4.▲ / button

Press ▲ / button to increase/decreaseset temperature.In AUTO mode,set temperature is not adjustable.




▲ OFF

5. SWING button
Press this button to set up & down swing angle.

no display
(horizontal louvers
stops at current position)

6. SLEEP button

Technical Information
Service Manual

7. TEMP button
Press this button, you can see indoor set temperature, indoor ambient temperature on indoor unit’s display. The setting
on remote controller is selected circularly as below:
no display

8. TURBO button
Press this button to activate / deactivate the Turbo function.

9. I FEEL button
Press this button to turn on I FEEL function.
10. Timer button
Under ON status, press this button to set timer OFF; Under OFF status, press this button to set timer ON.

11. X-FAN button (NOTE:X-FAN is the alternative expression of BLOW for the purpose of understanding.)

12. LIGHT button


Turn on the display's light and press this button again to turn off the display's light.

NOTICE:
As for the detailed content of remote controller, please refer to QR code on the cover.

Function introduction for combination buttons



Combination of "▲" and " " buttons: About lock
Press "▲" and " " buttons simultaneously 3s to lock or unlock the keypad. If the remote controller is locked, is displayed. In this case,

pressing any button, blinks three times.



Combination of "MODE" and " " buttons: About switch between Fahrenheit and centigrade

At unit OFF, press "MODE" and " " buttons simultaneously to switch between ć and ̧.
Combination of "TEMP" and "TIMER" buttons: About Energy-saving Function
Press "TEMP" and "TIMER" simultaneously in COOL mode to start e nergy-saving function. Nixie tube on the remote controller displays
"SE". Repeat the operation to quit the function.
Combination of "TEMP" and "TIMER" buttons: About 8 ćHeating Function
Press "TEMP" and "TIMER" simultaneously in HEAT mode to start 8ć Heating Function Nixie tube on the remote controller displays " "
and a selected temperature of "8ć". (46̧ if Fahrenheit is adopted). Repeat the operation to quit the function.

Technical Information
Service Manual

WIFI Function
Press this button to turn on the unit. Press this button again to turn off the unit. Press "MODE" and "TURBO" button simultaneously to
turn on or turn off WIFI function. When WIFI function is turned on, the " " icon will be displayed on remote controller; Long press "MODE"
and "TURBO" buttons simultaneously for 10s, remote controller will send WIFI reset code and then the WIFI function will be turned on.
WIFI function is defaulted ON after energization of the remote controller.
● This function is only available for some models.
signal sender battery
Replacement of batteries in remote controller
1. Press the back side of remote controller marked
reinstall
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar remove
are correct.
3. Reinstall the cover of battery box. Cover of battery box

Emergency operation
If remote controller is lost or damaged, please use auxiliary button to turn on or turn off the air conditioner.
The operation in details are as below:
As shown in the fig.Open panel ,press aux.button to turn on or turn off the air conditioner. panel
aux. button
When the air conditioner is turned on, it will operate under auto mode.

WARNING:
Use insulated object to press the auto button

Technical Information
Service Manual

Part ė : Installation and Maintenance


Notes for Installation and Maintenance
Safety Precautions: 10. If the power cord or connection wire is not long enough,
please get the specialized power cord or connection wire
Important! from the manufacture or distributor. Prohibit prolong the wire
by yourself.
Please read the safety precautions carefully before 11. For the air conditioner without plug, an air switch must
installation and maintenance. be installed in the circuit. The air switch should be all-pole
The following contents are very important for installation parting and the contact parting distance should be more than
and maintenance. 3m.
12. Make sure all wires and pipes are connected properly and
Please follow the instructions below. the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes,
Ɣ7KHLQVWDOODWLRQRUPDLQWHQDQFHPXVWDFFRUGZLWKWKH please eliminate the electric leakage.
instructions.  5HSODFHWKHIXVHZLWKDQHZRQHRIWKHVDPHVSHFL¿FDWLRQ
Ɣ&RPSO\ZLWKDOOQDWLRQDOHOHFWULFDOFRGHVDQGORFDO if it is burnt down; don’t replace it with a cooper wire or
electrical codes. conducting wire.
Ɣ3D\DWWHQWLRQWRWKHZDUQLQJVDQGFDXWLRQVLQWKLV 15. If the unit is to be installed in a humid place, the circuit
manual. breaker must be installed.
Ɣ$OOLQVWDOODWLRQDQGPDLQWHQDQFHVKDOOEHSHUIRUPHGE\
GLVWULEXWRURUTXDOL¿HGSHUVRQ
Ɣ$OOHOHFWULFZRUNPXVWEHSHUIRUPHGE\DOLFHQVHG Installation Safety Precautions:
technician according to local regulations and the
instructions given in this manual. 1. Select the installation location according to the require-
Ɣ%HFDXWLRQGXULQJLQVWDOODWLRQDQGPDLQWHQDQFH3URKLELW ment of this manual.(See the requirements in installation
incorrect operation to prevent electric shock, casualty and part)
other accidents. 2. Handle unit transportation with care; the unit should not
be carried by only one person if it is more than 20kg.
 :KHQ LQVWDOOLQJ WKH LQGRRU XQLW DQG RXWGRRU XQLW D VXI¿-
FLHQW¿[LQJEROWPXVWEHLQVWDOOHGPDNHVXUHWKHLQVWDOODWLRQ
Warnings VXSSRUWLV¿UP
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur-
ing installation.
Electrical Safety Precautions:  0DNHVXUHQRIRUHLJQREMHFWVDUHOHIWLQWKHXQLWDIWHU¿Q-
ishing installation.
1. Cut off the power supply of air conditioner before
checking and maintenance. Refrigerant Safety Precautions:
2. The air condition must apply specialized circuit and
prohibit share the same circuit with other appliances.  $YRLGFRQWDFWEHWZHHQUHIULJHUDQWDQG¿UHDVLWJHQHUDWHV
3. The air conditioner should be installed in suitable poisonous gas; Prohibit prolong the connection pipe by
location and ensure the power plug is touchable. welding.
4. Make sure each wiring terminal is connected firmly  $SSO\ VSHFL¿HG UHIULJHUDQW RQO\ 1HYHU KDYH LW PL[HG ZLWK
during installation and maintenance. any other refrigerant. Never have air remain in the refrigerant
5. Have the unit adequately grounded. The grounding line as it may lead to rupture or other hazards.
wire can’t be used for other purposes. 3. Make sure no refrigerant gas is leaking out when
6. Must apply protective accessories such as protective installation is completed.
boards, cable-cross loop and wire clip. 4. If there is refrigerant leakage, please take sufficient
7. The live wire, neutral wire and grounding wire of measure to minimize the density of refrigerant.
power supply must be corresponding to the live wire, 5. Never touch the refrigerant piping or compressor without
neutral wire and grounding wire of the air conditioner. wearing glove to avoid scald or frostbite.
8. The power cord and power connection wires can’t be
pressed by hard objects. ,PSURSHULQVWDOODWLRQPD\OHDGWR¿UHKD]DUGH[SORVLRQ
9. If power cord or connection wire is broken, it must be electric shock or injury.
UHSODFHGE\DTXDOL¿HGSHUVRQ

Installation and Maintenance


Service Manual

Main Tools for Installation and Maintenance


1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill

4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner


hexagon spanner

7. Electronic leakage detector 8. Vacuum pump 9. Pressure meter

10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container

Installation and Maintenance


Service Manual

Installation Manual
Installation procedures

Start installation

Preparation before installation

Read the requirements select installation Prepare tools


for electric connection location

Select indoor unit Select outdoor unit


installation location installation location

Install wall-mounting Install the support of outdoor unit


frame, drill wall holes (select it according to the actual situation)

Connect pipes of indoor Fix outdoor unit


unit and drainage pipe

Connect wires of indoor unit Install drainage joint of outdoor unit


(only for cooling and heating unit)

Bind up pipes and


hang the indoor unit

Make the bound pipes pass


through the wall hole and then
connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this section.

Installation and Maintenance










Space to the ceiling


Space to the ceiling

the ceiling
At least 15cm
to 15cm

At least 15cm
At least
Space
Space
Space
Space
toto
the
the
wall
towall
the wall
AtAt
least
least
At15cm
least
15cm15cm
AtAt
least
least
At15cm
least
15cm15cm
Space
Space
Space
toto
the
the
wall
towall
the wall

mm m

At least 250cm
At least 250cm

At least 250cm
0 00c0c 00c
t 3t 3 t 3 n n n
l e alesas leasucuticotio uctio
AtAt At bsbtrstr bstr
oo o
t hethe the
to to to
a caece ace
SpSp Sp
Space to the obstruction
Space to the obstruction

Space to the obstruction


Service Manual

Installation Parts-Checking Requirements for electric connection


1. Safety Precaution
No. Name No. Name
 0XVW IROORZ WKH HOHFWULF VDIHW\ UHJXODWLRQV ZKHQ LQVWDOOLQJ
1 ,QGRRUXQLW 8 6HDOLQJJXP
WKHXQLW
2 2XWGRRUXQLW 9 Wrapping tape
 $FFRUGLQJ WR WKH ORFDO VDIHW\ UHJXODWLRQV XVH TXDOLILHG
6XSSRUWRIRXWGRRU
3 Connection pipe 10 SRZHUVXSSO\FLUFXLWDQGDLUVZLWFK
XQLW
 0DNHVXUHWKHSRZHUVXSSO\PDWFKHVZLWKWKHUHTXLUHPHQW
4 Drainage pipe 11 )L[LQJVFUHZ
RI DLU FRQGLWLRQHU 8QVWDEOH SRZHU VXSSO\ RU LQFRUUHFW ZLULQJ
:DOOPRXQWLQJ 'UDLQDJHSOXJ FRROLQJ
5 12 PD\UHVXOWLQHOHFWULFVKRFN¿UHKD]DUGRUPDOIXQFWLRQ3OHDVH
frame DQGKHDWLQJXQLW
LQVWDOO SURSHU SRZHU VXSSO\ FDEOHV EHIRUH XVLQJ WKH DLU
Connecting 2ZQHUVPDQXDO
6 13 conditioner.
cable(power cord) remote controller
 3URSHUO\FRQQHFWWKHOLYHZLUHQHXWUDOZLUHDQGJURXQGLQJ
7 Wall pipe
ZLUHRISRZHUVRFNHW
Note:  %HVXUHWRFXWRIIWKHSRZHUVXSSO\EHIRUHSURFHHGLQJDQ\
3OHDVHFRQWDFWWKHORFDODJHQWIRULQVWDOODWLRQ ZRUNUHODWHGWRHOHFWULFLW\DQGVDIHW\
'RQWXVHXQTXDOL¿HGSRZHUFRUG  'RQRWSXWWKURXJKWKHSRZHUEHIRUH¿QLVKLQJLQVWDOODWLRQ
 )RU DSSOLDQFHV ZLWK W\SH < DWWDFKPHQWWKH LQVWUXFWLRQV
VKDOOFRQWDLQWKHVXEVWDQFHRIWKHIROORZLQJ,IWKHVXSSO\FRUGLV
Selection of Installation Location GDPDJHGLWPXVWEHUHSODFHGE\WKHPDQXIDFWXUHULWVVHUYLFH
DJHQWRUVLPLODUO\TXDOL¿HGSHUVRQVLQRUGHUWRDYRLGDKD]DUG
1. Basic Requirement:
,QVWDOOLQJWKHXQLWLQWKHIROORZLQJSODFHVPD\FDXVH  7KH WHPSHUDWXUH RI UHIULJHUDQW FLUFXLW ZLOO EH KLJK SOHDVH
PDOIXQFWLRQ,ILWLVXQDYRLGDEOHSOHDVHFRQVXOWWKHORFDOGHDOHU NHHSWKHLQWHUFRQQHFWLRQFDEOHDZD\IURPWKHFRSSHUWXEH
 7KHSODFHZLWKVWURQJKHDWVRXUFHVYDSRUVÀDPPDEOHRU  7KHDSSOLDQFHVKDOOEHLQVWDOOHGLQDFFRUGDQFHZLWKQDWLRQDO
H[SORVLYHJDVRUYRODWLOHREMHFWVVSUHDGLQWKHDLU ZLULQJUHJXODWLRQV
 7KH SODFH ZLWK KLJKIUHTXHQF\ GHYLFHV VXFK DV ZHOGLQJ
2. Grounding Requirement:
PDFKLQHPHGLFDOHTXLSPHQW 
 7KHDLUFRQGLWLRQHULV¿UVWFODVVHOHFWULFDSSOLDQFH,WPXVW
 7KHSODFHQHDUFRDVWDUHD
EH SURSHUO\ JURXQGLQJ ZLWK VSHFLDOL]HG JURXQGLQJ GHYLFH
 7KHSODFHZLWKRLORUIXPHVLQWKHDLU
E\ D SURIHVVLRQDO 3OHDVH PDNH VXUH LW LV DOZD\V JURXQGHG
 7KHSODFHZLWKVXOIXUHWHGJDV
HIIHFWLYHO\RWKHUZLVHLWPD\FDXVHHOHFWULFVKRFN
 2WKHUSODFHVZLWKVSHFLDOFLUFXPVWDQFHV
 7KH\HOORZJUHHQZLUHLQDLUFRQGLWLRQHULVJURXQGLQJZLUH
 7KHDSSOLDQFHVKDOOQRWEHLQVWDOOHGLQWKHODXQGU\
ZKLFKFDQWEHXVHGIRURWKHUSXUSRVHV
2. Indoor Unit:  7KH JURXQGLQJ UHVLVWDQFH VKRXOG FRPSO\ ZLWK QDWLRQDO
 7KHUHVKRXOGEHQRREVWUXFWLRQQHDUDLULQOHWDQGDLURXWOHW HOHFWULFVDIHW\UHJXODWLRQV
 6HOHFWDORFDWLRQZKHUHWKHFRQGHQVDWLRQZDWHUFDQEH  7KH DSSOLDQFH PXVW EH SRVLWLRQHG VR WKDW WKH SOXJ LV
GLVSHUVHGHDVLO\DQGZRQWDIIHFWRWKHUSHRSOH accessible.
 6HOHFWDORFDWLRQZKLFKLVFRQYHQLHQWWRFRQQHFWWKH  $QDOOSROHGLVFRQQHFWLRQVZLWFKKDYLQJDFRQWDFWVHSDUDWLRQ
RXWGRRUXQLWDQGQHDUWKHSRZHUVRFNHW RIDWOHDVWPPLQDOOSROHVVKRXOGEHFRQQHFWHGLQ¿[HGZLULQJ
 6HOHFWDORFDWLRQZKLFKLVRXWRIUHDFKIRUFKLOGUHQ  ,QFOXGLQJDQDLUVZLWFKZLWKVXLWDEOHFDSDFLW\ SOHDVHQRWH
 7KHORFDWLRQVKRXOGEHDEOHWRZLWKVWDQGWKHZHLJKWRI WKH IROORZLQJ WDEOH$LU VZLWFK VKRXOG EH LQFOXGHG PDJQHW
LQGRRUXQLWDQGZRQWLQFUHDVHQRLVHDQGYLEUDWLRQ EXFNOH DQG KHDWLQJ EXFNOH IXQFWLRQ LW FDQ SURWHFW WKH FLUFXLW
 7KHDSSOLDQFHPXVWEHLQVWDOOHGPDERYHÀRRU VKRUWDQGRYHUORDG &DXWLRQSOHDVHGRQRWXVHWKHIXVHRQO\
 'RQWLQVWDOOWKHLQGRRUXQLWULJKWDERYHWKHHOHFWULF IRUSURWHFWWKHFLUFXLW
appliance. Air-conditioner $LUVZLWFKFDSDFLW\
 3OHDVHWU\\RXUEHVWWRNHHSZD\IURPÀXRUHVFHQWODPS 09K 10A
12K 13A
3. Outdoor Unit:
 6HOHFWDORFDWLRQZKHUHWKHQRLVHDQGRXWÀRZDLUHPLWWHGE\
WKHRXWGRRUXQLWZLOOQRWDIIHFWQHLJKERUKRRG Installation of Indoor Unit
 7KHORFDWLRQVKRXOGEHZHOOYHQWLODWHGDQGGU\LQZKLFK
1. Choosing Installation Iocation
WKHRXWGRRUXQLWZRQWEHH[SRVHGGLUHFWO\WRVXQOLJKWRUVWURQJ
5HFRPPHQG WKH LQVWDOODWLRQ ORFDWLRQ WR WKH FOLHQW DQG WKHQ
wind. FRQ¿UPLWZLWKWKHFOLHQW
 7KHORFDWLRQVKRXOGEHDEOHWRZLWKVWDQGWKHZHLJKWRI
2. Install Wall-mounting Frame
RXWGRRUXQLW
 +DQJ WKH ZDOOPRXQWLQJ IUDPH RQ WKH ZDOO DGMXVW LW LQ
 0DNHVXUHWKDWWKHLQVWDOODWLRQIROORZVWKHUHTXLUHPHQWRI
KRUL]RQWDOSRVLWLRQZLWKWKHOHYHOPHWHUDQGWKHQSRLQWRXWWKH
installation dimension diagram.
VFUHZ¿[LQJKROHVRQWKHZDOO
 6HOHFWDORFDWLRQZKLFKLVRXWRIUHDFKIRUFKLOGUHQDQGIDU
 'ULOOWKHVFUHZ¿[LQJKROHVRQWKHZDOOZLWKLPSDFWGULOO WKH
DZD\IURPDQLPDOVRUSODQWV,ILWLVXQDYRLGDEOHSOHDVHDGG
VSHFLILFDWLRQ RI GULOO KHDG VKRXOG EH WKH VDPH DV WKH SODVWLF
IHQFHIRUVDIHW\SXUSRVH
H[SDQVLRQSDUWLFOH DQGWKHQ¿OOWKHSODVWLFH[SDQVLRQSDUWLFOHV
LQWKHKROHV
Installation and Maintenance
Service Manual

 )L[WKHZDOOPRXQWLQJIUDPHRQWKHZDOOZLWKWDSSLQJVFUHZV 5. Connect the Pipe of Indoor Unit


67;7$ DQGWKHQFKHFNLIWKHIUDPHLV¿UPO\LQVWDOOHGE\  $LPWKHSLSHMRLQWDWWKHFRUUHVSRQGLQJEHOOPRXWK $VVKRZ
SXOOLQJ WKH IUDPH ,I WKH SODVWLF H[SDQVLRQ SDUWLFOH LV ORRVH LQ)LJ
SOHDVHGULOODQRWKHU¿[LQJKROHQHDUE\  3UHWLJKWHQLQJWKHXQLRQQXWZLWKKDQG
 $GMXVWWKHWRUTXHIRUFHE\UHIHUULQJWRWKHIROORZLQJVKHHW
3. Install Wall-mounting Frame 3ODFH WKH RSHQHQG ZUHQFK RQ WKH SLSH MRLQW DQG SODFH WKH
 &KRRVHWKHSRVLWLRQRISLSLQJKROHDFFRUGLQJWRWKHGLUHFWLRQ WRUTXH ZUHQFK RQ WKH XQLRQ QXW7LJKWHQ WKH XQLRQ QXW ZLWK
RI RXWOHW SLSH7KH SRVLWLRQ RI SLSLQJ KROH VKRXOG EH D OLWWOH WRUTXHZUHQFK $VVKRZLQ)LJ
ORZHUWKDQWKHZDOOPRXQWHGIUDPH $VVKRZLQ)LJ  :UDS WKH LQGRRU SLSH DQG MRLQW RI FRQQHFWLRQ SLSH ZLWK
Wall Wall LQVXODWLQJSLSHDQGWKHQZUDSLWZLWKWDSH $VVKRZLQ)LJ
Mark in the middle of it Level meter
Space Space
to the to the
Open-end
wall wall wrench
above above
150mm 150mm Union nut
Pipe joint Union nut Pipe
Torque wrench Pipe
Left Right
Φ55mm )LJ Φ55mm
Rear piping hole Rear piping hole )LJ Indoor pipe )LJ

 2SHQ D SLSLQJ KROH ZLWK WKH GLDPHWHU RI ĭPP RQ WKH
VHOHFWHG RXWOHW SLSH SRVLWLRQ,Q RUGHU WR GUDLQ VPRRWKO\ VODQW
WKH SLSLQJ KROH RQ WKH ZDOO VOLJKWO\ GRZQZDUG WR WKH RXWGRRU
VLGHZLWKWKHJUDGLHQWRIƒ $VVKRZLQ)LJ
Insulating pipe )LJ

Indoor Outdoor
5HIHUWRWKHIROORZLQJWDEOHIRUZUHQFKPRPHQWRIIRUFH
)LJ
+H[QXWGLDPHWHU PP 7LJKWHQLQJWRUTXH 1.m)
ĭ 15~20
Φ55mm ĭ 30~40
e ĭ 45~55
ĭ 60~65
Note: ĭ 70~75
 3D\ DWWHQWLRQ WR GXVW SUHYHQWLRQ DQG WDNH UHOHYDQW VDIHW\
PHDVXUHVZKHQRSHQLQJWKHKROH 6. Install Drain Hose
 7KHSODVWLFH[SDQVLRQSDUWLFOHVDUHQRWSURYLGHGDQGVKRXOG  &RQQHFWWKHGUDLQKRVHWRWKHRXWOHWSLSHRILQGRRUXQLW $V
EHERXJKWORFDOO\ VKRZLQ)LJ
 %LQGWKHMRLQWZLWKWDSH $VVKRZLQ)LJ
4. Outlet Pipe
 7KHSLSHFDQEHOHGRXWLQWKHGLUHFWLRQRIULJKWUHDUULJKW
OHIWRUUHDUOHIW $VVKRZLQ)LJ Drain hose
 :KHQVHOHFWLQJOHDGLQJRXWWKHSLSHIURPOHIWRUULJKWSOHDVH Outlet pipe
FXWRIIWKHFRUUHVSRQGLQJKROHRQWKHERWWRPFDVH $VVKRZLQ
)LJ
Tape
Drain hose
Outlet
pipe )LJ
)LJ

Note:

Left Rear left  $GG LQVXODWLQJ SLSH LQ WKH LQGRRU GUDLQ KRVH LQ RUGHU WR
SUHYHQWFRQGHQVDWLRQ
)LJ Rear right
Right  7KHSODVWLFH[SDQVLRQSDUWLFOHVDUHQRWSURYLGHG
$VVKRZLQ)LJ

Left Right Drain hose

Cut off
the hole )LJ
Insulating pipe
)LJ

Installation and Maintenance


Service Manual

7. Connect Wire of Indoor Unit 8. Bind up Pipe


 2SHQWKHSDQHOUHPRYHWKHVFUHZRQWKHZLULQJFRYHUDQG  %LQGXSWKHFRQQHFWLRQSLSHSRZHUFRUGDQGGUDLQKRVH
WKHQWDNHGRZQWKHFRYHU $VVKRZLQ)LJ ZLWKWKHEDQG $VVKRZLQ)LJ
 5HVHUYHDFHUWDLQOHQJWKRIGUDLQKRVHDQGSRZHUFRUG
Panel Screw IRULQVWDOODWLRQZKHQELQGLQJWKHP:KHQELQGLQJWRDFHUWDLQ
GHJUHHVHSDUDWHWKHLQGRRUSRZHUDQGWKHQVHSDUDWHWKHGUDLQ
KRVH $VVKRZLQ)LJ
 %LQGWKHPHYHQO\
 7KHOLTXLGSLSHDQGJDVSLSHVKRXOGEHERXQGVHSDUDWHO\DW
)LJ
Wiring cover WKHHQG

 0DNHWKHSRZHUFRQQHFWLRQZLUHJRWKURXJKWKHFDEOHFURVV
Indoor and
KROHDWWKHEDFNRILQGRRUXQLWDQGWKHQSXOOLWRXWIURPWKHIURQW outdoor power cord
VLGH $VVKRZLQ)LJ Indoor unit Gas
pipe

Cable-cross Liquid
hole )LJ Band pipe
Drain hose

Power connection
wire )LJ
Connection pipe Drain hose
Band
 5HPRYH WKH ZLUH FOLS FRQQHFW WKH SRZHU FRQQHFWLRQ
ZLUHVLJQDOFRQWUROZLUH RQO\IRUFRROLQJDQGKHDWLQJXQLW WRWKH
ZLULQJ WHUPLQDO DFFRUGLQJ WR WKH FRORU WLJKWHQ WKH VFUHZ DQG
WKHQ IL[ WKH SRZHU FRQQHFWLRQ ZLUH ZLWK ZLUH FOLS $V VKRZ LQ
)LJ )LJ
Indoor power cord

)LJ
N(1) 2 3
Note:
yellow-
blue black brown
green
 7KH SRZHU FRUG DQG FRQWURO ZLUH FDQW EH FURVVHG RU
winding.
 7KHGUDLQKRVHVKRXOGEHERXQGDWWKHERWWRP

Outdoor unit connection 9. Hang the Indoor Unit


 3XWWKHERXQGSLSHVLQWKHZDOOSLSHDQGWKHQPDNHWKHP
1RWH7KHZLULQJFRQQHFWLVIRUUHIHUHQFHRQO\SOHDVHUHIHUWR SDVVWKURXJKWKHZDOOKROH
WKHDFWXDORQH  +DQJWKHLQGRRUXQLWRQWKHZDOOPRXQWLQJIUDPH
 6WXIIWKHJDSEHWZHHQSLSHVDQGZDOOKROHZLWKVHDOLQJJXP
 3XWZLULQJFRYHUEDFNDQGWKHQWLJKWHQWKHVFUHZ
 )L[WKHZDOOSLSH $VVKRZLQ)LJ
 &ORVHWKHSDQHO
 &KHFNLIWKHLQGRRUXQLWLVLQVWDOOHG¿UPO\DQGFORVHGWRWKH
Note: ZDOO $VVKRZLQ)LJ
 $OOZLUHVRILQGRRUXQLWDQGRXWGRRUXQLWVKRXOGEH
connected by a professional. Indoor Outdoor
 ,IWKHOHQJWKRISRZHUFRQQHFWLRQZLUHLVLQVXI¿FLHQWSOHDVH Wall pipe )LJ
Sealing gum
FRQWDFWWKHVXSSOLHUIRUDQHZRQH$YRLGH[WHQGLQJWKHZLUHE\
Upper hook
\RXUVHOI
 )RUWKHDLUFRQGLWLRQHUZLWKSOXJWKHSOXJVKRXOGEH
UHDFKDEOHDIWHU¿QLVKLQJLQVWDOODWLRQ
 )RUWKHDLUFRQGLWLRQHUZLWKRXWSOXJDQDLUVZLWFKPXVWEH
LQVWDOOHGLQWKHOLQH7KHDLUVZLWFKVKRXOGEHDOOSROHSDUWLQJ )LJ
DQGWKHFRQWDFWSDUWLQJGLVWDQFHVKRXOGEHPRUHWKDQPP Lower hook of
wall-mounting frame

Note:
'RQRWEHQGWKHGUDLQKRVHWRRH[FHVVLYHO\LQRUGHUWRSUHYHQW
EORFNLQJ

Installation and Maintenance


Service Manual

Electrical Connections
.
..
1. Remove the handle at the right side plate of the outdoor Handle
unit (one screw).
2. Remove the cable clamp, connect the power connection
cable with the terminal at the row of connection and fix the
FRQQHFWLRQ7KH¿WWLQJOLQHGLVWULEXWLQJPXVWEHFRQVLVWHQWZLWK
the indoor unit. terminal of line bank. Wiring should meet that of Front
side plate
indoor unit.
3. Fix power connection wire by wire clamp. To the power supply To unit A To unit B
 (QVXUHZLUHKDVEHHQ¿[HGZHOO
5. Install the handle. L

Including an air switch with suitable capacity,please note


the following table. Air switch should be included magnet
buckle and heating buckle function, it can protect the Power cord connecting connecting
cable cable
circuit-short and overload. (Caution: please do not use the
fuse only for protect the circuit)

L
Air-conditioner Air switch capacity
. 10A N
L
. 10A

An all-pole disconnection switch having a contact


separation of at least 3mm in all pole should be connected
LQ¿[HGZLULQJ .

Handle
Wrong wire connection may cause malfunction of
VRPHHOHFWULFFRPSRQHQWV$IWHU¿[LQJFDEOHHQVXUH
WKDWOHDGVEHWZHHQFRQQHFWLRQWR¿[HGSRLQWKDYH
some space.

The connection pipes and the connectiong wirings


of the unit A and unit B must be corresponding to
each other respective.
To unit A To unit B

The appliance shall be installed in accordance with


national wiring regulations.

Power cord connecting connecting


cable cable
1RWHWKHDERYH¿JXUHVDUHRQO\LQWHQGHGWREHDVLPSOH
diagram of the appliance and may not correspond to the
To the power supply
appearance of the units that have been purchased.

L
N
L

Installation and Maintenance


Service Manual

Installing the Outdoor


Use bolts Unit
to secure the unit to a flat, solid floor. ,QVWDOOWKHGUDLQ¿WWLQJDQGWKHGUDLQKRVH IRUPRGHOZLWK
When mounting the unit on a wall or the roof, make Install
heat pumpthe drain
only)fitting and the drain hose(for
sure the support is firmly secured so that it cannot
Do not install the outdoor unit in pits or air vents model with heat
Condensation is pump only)and flows from the outdoor unit
produced
When mountingmovethein unit
the event of intense
on a wall vibrations
or the roof, make or a strong
sure the Condensation is produced
when the appliance is operating and inflows
the from themode.
heating outdoorIn unit
order
wind.
VXSSRUWLV¿UPO\VHFXUHGVRWKDWLWFDQQRWPRYHLQWKHHYHQWRI
when the appliance is operating in the heating
not to disturb neighbours and to respect the environment,
mode. In order
Do not install the outdoor unit in pits or air vents not to disturb neighbours and to respect the environment,
intense vibrations or a strong wind.
Installing the pipes install a drain fitting and a drain hose to channel the conden-
install a drain fitting and a drain hose to channel the
FRQGHQVDWHZDWHU,QVWDOOWKHGUDLQ¿WWLQJDQGUXEEHUZDVKHU
Installing the pipes
Use suitable connecting pipes and equipment for the sate water. Install the drain fitting and rubber washer on the
refrigerant R410A.
Use suitable connecting pipes and equipment for outdoor
on unit chassis
the outdoor and connect
unit chassis and connecta drainahose
draintohose
it as toshown
it as
VKRZQLQWKH¿JXUH
in the figure.
the refrigerant R410A.
Models(m) 14/18K GWHD(24)NK3DO 24/28K
Models(m) Max. connection14/18K 21/24K 28K
Max. connection pipepipe length
length 2020 6020 70
70
Max. connection
Max. connection pipe
1010 2010 20
length(Simpleonepipe length(Simple
indoor unit) 20
one indoor unit)
The sum of the capacity codes of the indoor units should be among 50%-
Theoutdoor
150% of that of the refrigerant
unit.pipes must not exceed the maximum
heights 10m.
Wrap all the refrigerant pipes and joints.
The refrigerant pipes must not exceed the maximum heights

Tighten the connections using two wrenches working


m(14K&18K &24Kx2)or 10m(24Kx3&28K).
in opposite directions.
Wrap all the refrigerant pipes and joints.
TightenCaution: Installationusing
the connections Musttwo bewrenches
Performedworking
in Accordance
in opposite
with the NEC/CEC
directions.by Authorized Personnel Only. by Authorized Personnel Only.
Humid air left inside the refrigerant circuit can cause com-
pressor malfunction.
Caution: Installation Must be After havinginconnected
Performed Accordance the indoor
with the NEC/
and outdoorPersonnel
CEC by Authorized units, bleed the air and humidity from the
Only.
refrigerant circuit using a vacuum pump.
Humid air left inside the refrigerant circuit can cause compressor
1.Unscrew and remove the caps from the 2-way and 3-
way valves.
malfunction. After having connected the indoor and outdoor units, bleed
the air and2.Unscrew
humidity from andthe
remove the capcircuit
refrigerant fromusing
the service
a vacuumvalve.
pump.
3.Connect the vacuum pump hose to
(1) Unscrew and remove the caps from the 2-way and 3-way valves.the service valve.
4.Operate the vacuum pump for 10-15 minutes until an
(2) Unscrew and remove the cap from the service valve.
absolute vacuum of 10 mm Hg has been reached.
(3) Connect5.With the vacuum
the vacuum pumppump hose still in operation,
to the close the
service valve.
low-pressure knob on the vacuum pump
(4) Operate the vacuum pump for 10-15 minutes until coupling.
an absoluteStopvacuum
of 10 mm Hgthe hasvacuum pump.
been reached.
6.Open
(5) With the vacuum thepump
2-waystillvalve by 1/4 turnclose
in operation, and the
thenlow-pressure
close it knob Vacuum pump Vacuum pump
on the vacuum afterpump
10 seconds . the
coupling.Check
Stop all the jointspump.
vacuum for leaks using
liquid soap or an electronic leak device.
(6) Open the 2-way valve by 1/4 turn and then close it after 10 seconds.
7.Turn the body of the 2-way and 3-way valves. Discon-
nect the vacuum pump hose.
Check all the joints for leaks using liquid soap or an electronic leak device.
8.Replace
(7) Turn the body of the and2-way
tighten andall3-way
the caps on the
valves. valves.
Disconnect
the vacuum pump hose.
Diameter
(8) Replace and tighten all the(mm) Twisting
caps on moment (N.m)
the valves.
Diameter (mm) Twisting moment (N.m) .
ĭ
36.35(1/4”)
15-20
14-18N m(140-180kgf.cm) Vacuum pump
ĭ 39.52(3/8”)
35-40 34-42N.m(340-420kgf.cm)
ĭ 312.7(1/2”)
60-65 49-61N.m(490-610kgf.cm) INDOOR (8) Secure
ĭ 45-50 UNIT
Refrigerant fluid direction of flow 2-way valve
ĭ 70-75
18K unit need to be installed the indoor unit
 ,IWKHVSHFL¿FDWLRQRIRXWGRRUXQLWJDVYDOYHLVEXWFXUVWRPHUQHHGV 3-way valve
(6) Open by 1/4 turn
to install 1/2"indoor18K
unitModel:
so that it is need to use a “pipe joint subassembly” (7) Turn to open fully
(Code 06643008) to make a conversion joint with outdoor unit gas valve (7) Turn to open fully Valve cap
Service
and connection pipe, as show in following. inlet (2) Turn
(2) Turn (2) Turn (8) Secure
(8) Secure Valve cap Connect to the
conversion joint indoor unit

conversion joint

Installation and Maintenance


Service Manual

Installation Dimension Diagram

Use suitable instruments for the refrigerant R410A.

Ɣ 'RQRWXVHDQ\RWKHUUHIULJHUDQWWKDQ5$

Do not use mineral oils to clean the unit.

7KHLQVWDOODWLRQPXVWEHGRQHE\WUDLQHGDQGTXDOL¿HGVHUYLFHSHUVRQQHOZLWKUHOLDELOLW\DFFRUGLQJWRWKLVPDQXDO

Contact service center before installation to avoid the malfunction due to unprofessional installation.

:KHQSLFNLQJXSDQGPRYLQJWKHXQLWV\RXPXVWEHJXLGHGE\WUDLQHGDQGTXDOL¿HGSHUVRQ

Ensure that the recommende dspace is left around the appliance.

18/21K 24/28K

50cm or more
Space to the cover
50cm or more
Space to the cover
30cm or above
30cm or above (Air inlet side) 30cm or above
Space to the cover 30cm or above
Space to the cover (Air inlet side)
200cm or above 200cm or above
(Air outlet side) (Air outlet side)
50cm or above
Space to the wall
5 0 cm o r
a b o ve
S p a ce to
th e w a ll

14K

50cm or more
Space to the cover

30cm or above
30cm or above (Air inlet side)
Space to the cover

200cm or above
(Air outlet side)
50cm or above
Space to the wall

Installation and Maintenance