Professional Documents
Culture Documents
Qdoc - Tips Dse Ingepac Ef LD Eng (35page)
Qdoc - Tips Dse Ingepac Ef LD Eng (35page)
Line differential
differential pro tection
Data Sheet
A
.
v
e
R
No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam Power
Technology.
One of the main aims of Ingeteam Power Technology lies in the continuous improvement of the company’s equipment and,
therefore, the information contained in this catalogue may be modified without prior notification.
For further information, consult the corresponding manual or contact us directly.
No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam Power
Technology.
One of the main aims of Ingeteam Power Technology lies in the continuous improvement of the company’s equipment and,
therefore, the information contained in this catalogue may be modified without prior notification.
For further information, consult the corresponding manual or contact us directly.
Table of contents
Table of contents
Communication ..........................
.......................................
..........................
...........................
...........................
..........................
...........................
....................
......11
Differential
Diffe rential protection ..............................................................
.............................. ................................................................
.................................................................
..............................................
............. 11
CT error detection
detect ion...............................................................
............................... ................................................................
.................................................................
..............................................
............. 12
Saturation
Saturat ion detector
detecto r.............................................................
............................. ................................................................
.................................................................
..............................................
............. 12
Load compensation
compensatio n ................................................................
................................ ................................................................
................................................................
.........................................
......... 12
87N Restricted
Restrict ed ground differential
differen tial..................................................................
................................. ................................................................
..............................................
............... 12
Function 86 ........................................................................................................................................................ 13
Distance
Distan ce units................................................................
................................ .................................................................
..................................................................
.........................................................
........................ 13
Phase identification
identif ication ................................................................
................................ .................................................................
.................................................................
.........................................
......... 14
Fault detector
detect or.................................................................
................................ .................................................................
................................................................
....................................................
.................... 14
Directional
Direct ional monitoring
monitorin g.................................................................
................................ ..................................................................
................................................................
...................................
.... 14
Directional .......................................................................................................................................................... 15
Undercurrent 37 ................................................................................................................................................ 17
Voltage units............................................................................................................................................................ 17
Overvoltage 59 .................................................................................................................................................. 17
Undervoltage 27 ................................................................................................................................................ 18
Recloser 79 .............................................................................................................................................................. 19
Synchronism 25 ...................................................................................................................................................... 20
Locator ...............................................................................................................................20
CT monitoring.................................................................................................................................................... 20
VT Characteristics ............................................................................................................................................ 21
Logics .................................................................................................................................22
Events.................................................................................................................................................................. 22
Faults ................................................................................................................................................................... 22
Oscillography .................................................................................................................................................... 22
Statistics ............................................................................................................................................................. 22
Measurements ................................................................................................................................................... 22
Communication protocols..............................................................................................23
Tests .................................................................................................................................................................... 25
Measurements ................................................................................................................................................... 29
MODEL
87, 87N, 5th armonic and V /f overexcit ation, SOTF, 68FF, 67, 67N, 50/51, 50N/51N,
50G/51G, 67Q, 46FA, 37, 49, 25, 79, 74TC/CC, 50BF, Stub bus, Fault locator
0
87, 87N, 5th armonic and V/f overexcitati on, 21,POTT (21),POTT (67N/67Q),
SOTF, 68LE,68FF,78, 67, 67N, 50/51, 50N/51N, 50G/51G, 67Q, 46FA, 37, 49, 59,
27, 59N, 47, 81M/m, 81R, 32, 25, 79, 74TC/CC, 50BF, Stub bus, Fault locator
1
HOUSING
1/2 chassis 19" 5U with configurable keyboard A
1/2 chassis 19" 5U with predefined keyboard Note 1 B
Chassis 19" 4U with configurable keyboard C
Chassis 19" 4U with predefined keyboard Note 1 D
TERMINALS
Pin type standard terminals A
Closed terminals Note 2 B
Closed terminals for analog inputs and pin type standard terminals for the rest C
Pag. 7
Model Code Selection
The following figures show the board position acording to model encoding.
Fig. 1.3 Redundant power supply ½ 19” chassis Fig. 1.4 Redundant power supply 19” chassis
Pag. 8
Functions table and functional diagrams
LD0 LD1
Differential functions
87: differential protection (Instantaneous and percentage)
Second harmonic restraint and blocking (Cross blocking)
87N: Restricted earth
V/f Overexcitation
5º harmonic level Overexcitation
Directional supervisión
CT error detector
Saturation detector
Load compensation
86 function
Distance functions
Quadrilateral (5 areas)
MHO (5 areas)
21 High Speed
Zone 1 extension
Double lines
Lines with serial compensation
CVT: Lines with Capacitive Voltage Transformers
Common protection functions
SOTF Switch onto fault
27 Undervoltage
59 Overvoltage
59N Zero sequence overvoltage
47 V2 overvoltage
Frequency (81 M/m)
Frequency rate of change (81R)
3x50/51 (67)
50N/51N (67N)
50G/51G. Earthing overcurrent
46TOC (67Q), 46IOC(67Q)
46BC Broken conductor
50CSC Second harmonic restraint
50CSC Second and fifth harmonic restraint
37 Undercurrent
49 Thermal image
32 Power units
Stub bus
Teleprotection
Teleprotection (21)
Teleprotection (67/67Q)
Monitoring units
68LE Load encroachment
68FF Fuse failure
78 Power swing
Fault locator
Fault locator
Breaker monitoring
kI2 breaker monitoring per pole
Closing and trip circuit monitoring
Excessive number of trips
Open pole/Dead line detector
Breaker status logic
Pole discordance
50BF Breaker failure
Breaker failure with monopolar/tripolar trip
Pag. 9
Functions table and functional diagrams
LD0 LD1
Automatism
Synchronism
Recloser one/three poles
Coupling
Data Acquisition Functions
Phase and neutral current m easurements
Phase and synchronism voltage measurements
Real and reactive power
Real and reactive energy
Historical event, protection event and fault recording
Breaker monitoring
Oscillographs
Historical reports
Pag. 10
Communication
Protection functions
Communication
The functions available in the equipment are shown below: In
The line differential scheme is based on the data exchange order to check if a specific model has a function, refer to the
(measurement and signal) between the devices placed on the model functions table.
sides of the line. It allows two and three terminal lines. Usually, each function has its own general operating settings,
It allows line with intermediate transformer. apart from the functional settings.
The communication uses the serial channels with baud rates Blocking. It allows selecting a signal so that when it is
between 64kbits and 128kbits and port types RS232 and FO on, it blocks the function.
multimode and singlemode (up to 60km). With external General trip. It indicates if it involves the opening of the
converters it can be used in G703 nets. breaker.
In 2 ends configuration for simple communication the port Trip permission following reclosure. It indicates the state
Com-3 is used and for redundant Com-3 and Com-4 ports. In of the function depending on the state of the recloser.
3 ends configuration Com-3 and Com-4 ports are used.
Reclosure permission. It indicates if the reclosure is
The communication can be: permitted following the trip of that function.
Simple. It only has one channel. In case of failure in that Records of events enabled. It enables the generation of
channel, it produces a loss of communication and the events related to the function
differential protection can´t work.
Redundant. It has two channels. In case of failure in one
channel, the communication is made with the other
channel. Differential protection
The configuration type can be selected: Valid for 2 and 3 ends.
Master. All the devices communicate between each Three phase differential unit.
other, receiving the measurements and executing the
Correction of relation and connection group numerically.
differential protection.
Slave. Only one device (master) executes the executing Homopolar component filter, allows to eliminate the zero
the differential protection, sending the trip command to sequence component of the phase currents.
the other devices Adjustable instantaneous differential current tripping.
The type connector can be RS232, multimode fiber optic Restraining and blocking by 2nd, harmonic. Cross blocking
(GFO y PFO), singlemode fiber optic (conector ST o LC), also available.
G.703 or C37.94. The line and end characteristics are adjustable.
Ia TRIP
Ic Ic
End B Vrated (kV) 1 10000 0,1
Ic
Ia
TRIP
C Ib
C
End C Vrated (kV) 1 10000 0,1
End A CT ratio 1 10000 0,1
End B CT ratio 1 10000 0,1
End C CT ratio 1 10000 0,1
End A Irated (A) 1 2 1A / 5A
End B Irated (A) 1 2 1A / 5A
Fig. 1.7 Master/Master Fig. 1.8 Master/Slave End C Irated (A) 1 2 1A / 5A
Intermediate transformer 0 1 NO / SI
The differential protection needs the synchronization of the
Connectiontype - End A 0 2 Y/D/Z
measurement of the line ends, in order to use the
Connectiontype - End B 0 2 Y/D/Z
measurement of the same instant in the algorithm.
Connectiontype - End C 0 2 Y/D/Z
To synchronise the ends without GPS, it is used a Phase-shift code - End A 0 11 1
communication method that allow to calculate the Phase-shift code - End B 0 11 1
propagation time of the messages and synchronise the Phase-shift code - End C 0 11 1
Port 1 0 4 Disabled / COM 3 / COM 4 / COM 5 / COM 6 End A polarity 0 1 Incoming / Outgoing
Baud rate 1 (bauds) 0 1 64Kb / 128Kb End B polarity 0 1 Incoming / Outgoing
Remote end 1 0 2 A/B/ C End C polarity 0 1 Incoming/ Outgoing
Remote ID 1 0 2 1 I0 type:measure/calculated 0 1 Measured / Calculated
Port 2 0 4 Disabled. / COM 3 / COM 4 / COM 5 / COM 6
Neutral Irated (A) 1 2 1A / 5A
Baud rate 2 (bauds) 0 1 64Kb / 128Kb
NeutralCT ratio 1 10000 0,1
Remote end 2 0 2 A/B/ C
Ground Irated (A) 1 2 1A / 5A
Remote ID 2 0 2 1
Max. propagation time (us) 0 250 10 Ground CT ratio 1 10000 0,1
Pag. 11
Protection functions
Saturation detector
Detection of saturation in any of the current transformer. It
analyses each phase independently to detect the instant
when the saturation happens.
Load compensation
Depending on the breaker status, the percentage differential
protection changes the characteristics during a configurable
time.
Fig. 1.9 Percentage and instantaneous differential protection
Ajuste Mínimo Máximo Paso
Setting Minimum Maximum Step
Enabled 0 1 1
Enabled Yes/ NO
Minimunthreshold 0,08 20 0,01
Sensitivity (xTap) 0,15 2 0,01
Delay time (ms) 10 1000 10
Rest.current step 1 (xTap) 0 2 0,01
Pag. 12
Protection functions
Vph-gnd FUND
Vph-ph FUND
Vph-gnd RMS
Vph-ph RMS
Operation type Standard
Function 86
This consists in activating the programmed relays when a
differential trip occurs (instantaneous or percentage) or in
activating a signal to be used to block the circuit breaker
Setting Minimum Maximum Step
closing circuits.
Non-directional
Setting Minimum Maximum Step Forward
Directional Mode
Enabled NO / Yes Following trip
Following pickup
Desactivate Lock Trip 86 Logical input
Characteristic Angle (º) 0 90 1
Activate Trip 86 Logical input
Phase Enabled (Ph) NO / YES
Mho
Phase Characteristic (Ph) Quadrilateral
10
There are 5 independent zones of operation, with the Mho reach (Ph) 0.05 500 0.01
possibility to select mho and/or quadrilateral characteristics in Resistive Reach (Ph) 0.05 500 0.01
Mho
Direction can be selected in each area: forward, reverse or Gnd Characteristic (Gnd) Quadrilateral
non-directional. Mho and quadrilateral
Each of the 5 zones can be set independently. Phase-ground time (ms) 0 600,000 10
Km Angle(º) 0 90 1
R Blinder Angle(Gnd) 0 90 1
Disabled
Tilt Type (Gnd) Timing
Continuous
I0
Quad. Type (Gnd) I2
Max (I0, I2)
Pag. 13
Protection functions
There is a quick operation unit for zone 1 (only forward) and Enabled NO / YES
another one for zone 4 (only backward), based on the CVT type Pasive / Active
medium cycle DFT, both for the Mho and the Quad
characteristic.
Fuse failure 68 FF
Setting Options
Zone 1 enabled NO / YES It detects if a fuse has blown up in the secondary circuit of the
Zone 4 enabled NO / YES voltage transformers. While this situation is detected, the
Zone 1 Blocking input Logical input blocking of the operation of other protection functions is
Zone 4 Blocking input Logical input allowed.
Setting Minimum Maximum Step
10
Phase Reverse threshold (A) 0.05 150 0.01 Minimum I1 threshold (A) 0.05 25 0.01
3I0 Forward threshold (A) 0.05 150 0.01 Z forward (Ohm) 0.01 500 0.01
3I0 Reverse threshold (A) 0.05 150 0.01 Positive angle forward (º) 0 90 1
Fault detector
This function detects the beginning of a fault, checking the
differences among the zero-sequence, direct and inverse
sequences measurements of the present current and the
ones of the two previous cycles.
Directional monitoring
It monitors the direction of a fault, so that it only permits the
faults produced in the direction set f or each area.
Setting Minimum Maximum Step
Pag. 14
Protection functions
Middle zone Right R 0.05 500 0.01 GSL Minimum time (ms) 0 150 10
Middle zone Left R 0.05 500 0.01 GSL Maximum time (ms) 0 200 10
Middlezone Top X 0.05 500 0.01 GSL Drop off time (ms) 0 200 10
Internal zone Right R 0.05 500 0.01 ECHO pulse time (ms) 0 10000 10
Internal zone Left R 0.05 500 0.01 ECHO Blocking time (ms) 0 1000 10
I1 Minimum threshold (A) 0.05 500 0.01 ECHO delay time (ms) 0 200 10
Distance between zones 0.1 5 0.1 Current rev. pickup T (ms) 0 10000 10
Directional unblocking
Inverse sequence directional
Additionally, together with the schemes, the following can
also be selected: Setting Minimum Maximum Step
Z2 offset 0 100 1
Weak infeed 27WI
Minimum I2 / I1 Ph (%) 1 100 1
Inverse directional block Minimum 3I2 / Irated (%) 1 100 1
Depending on the model, the schemes can be 67 NQ S2 Directional inversion Logical input
(employing the neutral overcurrent and unbalance units) and Blocking input Logical input
Pag. 15
Protection functions
Minimum V polarization (V) 1 200 0.1 - Neutral earthing. It´s not directional
Minimum 3I0/Irated gnd (%) 1 100 1 - Unbalance. The measurement type is phasor (rms is not
V allowed)
IPOL
Polarization method IPOL V Setting Minimum Maximum Step
IPOL o V Enabled YES / NO
IPOL o V
TRIP
S0 Operation type:
PICK UP
S2
S2 y S0 Start value (A) 0.02 150.0 0.01
Voltage directional Type S2 y S0 Delay time (ms) 0 600,000* 10
S2 S0
NO
S0 S2
Automatic Torque control Forward
Reverse
Offset Z0 (Ohm) 0 100 1
Nothing
Minimum 3I0/I1 (%) 1 100 1
Inhibit
Behaviour with Fuse fail
Permission with low Vpol YES / NO Block
Minimum Ipol/Irated gnd (%) 1 100 1 Enable
- Unbalance. The measurement type is phasor (rms is not Maximum threshold I0/Irated 0 20 0.1
allowed)
Setting
Enabled
Minimum Maximum Step
YES / NO
Second harmonic restraint
TRIP It allows blocking the 50/51,50N/51N and 67Q protection
PICK UP
Operation type: IOC1 BLOCK
functions when a second harmonic percentage is surpassed.
IOC1, 2 BLOCK Unit 50/51 have restraint per phase or for all of the phases.
IOC1, 2, 3 BLOCK
Setting Minimum Maximum Step
Start value (A) 0.02 150.0 0.01
NO / YES
Extreme ANSI-EI. Inverse Enabled
Only in closure
ANSI-MI Very inverse
Normal inverse I2nd harm. / Ifund. threshold (%) 10 100 1
ANSI-MODI Moderately inverse
Minimum current (A) 0.1 150.0 0.01
IEC-I Normal inverse
IEC-MI Very inverse
IEC-EI Extreme. Inverse
Curve type IEC-IC Short inverse
IEC-IL Long inverse
2nd and 5nd harmonic blocking
IEC-MIEs Very inverse special
User curves 1 It allows the instantaneous and timed grounding overcurrent
User curves 2 units to be blocked (51ES and 50ES).
User curves 3
User curves 4 Ajuste Mínimo Máximo Paso
Definite time Enabled NO/YES
Time dial 0.05 30.0 0.01
I 2nd/fund. Threshold (%) 5 100 1
Definite/Minimum time (ms) 0 600,000* 10
I 5th/fund. Threshold (%) 5 100 1
NO
Minimum current (A) 0,1 150 0,01
Torque control Forward
Reverse Blocking 51ES Unit 1 NO/YES
Nothing Blocking 51ES Unit 2 NO/YES
Inhibit
Behaviour with Fuse fail Blocking 51ES Unit 3 NO/ YES
Block
Enable Blocking 50ES Unit 1 NO/ YES
Instantaneous Blocking 50ES Unit 2 NO/ YES
Reset type
Timed
Blocking 50ES Unit 3 NO/ YES
Phasor
Operating Quantity
Rms
Time delay cancel Input Logical input
Pag. 16
Protection functions
It protects the faults happening between the current Start value (V) 0.5 200 0.01
transformers and the line switch in breaker and a half Delay time (ms) 0 7,200,000 10
Instantaneous
Setting Minimum Maximum Step
Enabled NO / YES
Pag. 17
Protection functions
Instantaneous
Setting Minimum Maximum Step
Start value (V) 0.5 200 0.01 Step 1. Start value (Hz/s) 0.20 5 0.05
Pag. 18
Automatic functions
Reclose number 1 3 1
1
600
600
1
Open pole detection 1 Pole Reclose 1 time (s) 0.05 600 0.01
Three-pole
Operation type
Single-pole
Synchrocheck Supervision
Sealed by current NO / YES
Setting Minimum Maximum Step
Time signal relapse (ms) 0 120000 1
Internal
Supervision by current NO / YES Synchrocheck type:
External
Phase current threshold (A) 0.02 150 0.01
Check 3pole first reclose YES / NO
Gnd current threshold (A) 0.02 150 0.01
Check rest of autorecloses YES / NO
Retrip time delay (ms) 0 60000 0.5
Sync. delay time (s) 0.05 600 0.01
Trip time delay (ms) 0 60000 0.5
External sync. Permission Logical input
Pag. 19
Locator
Synchronism 25 Locator
The synchronism checking function, also called
"synchrocheck", is used in order to set conditions for the The fault locator processes the information gathered in each
closure of the breaker. fault, calculating the estimated distance to the fault. The
The function compares the voltage signals of a phase (in settings are primary values.
module and angle) of the two sides of the breaker, giving Description Minimum Maximum Step
permission to close the breaker when the set conditions are Enabled YES / NO
met. It can be used for both m anual and automatic closure. Line length (Kms or miles) 0.1 5,000 0.1
Sync. Time Autoreclose(ms) 0 100,000 10 Z0M Mutual angle (º) 0 359.9 0.1
B-Side lack of Voltage (V) 10 200 0.1 I Minimum after close (A) 0 200 0.1
Without permission
A not and B yes
A yes and B not
Manual closing condition
A not and B not
A not or B not
Monitoring functions
A xor B
Without permission
A not and B yes
A yes and B not
CT monitoring
Autoreclose condition
A not and B not
A not or B not It allows the detection of a fault in any of the relay's input
A xor B channels (adaptation transformer + internal wiring),
comparing the absolute value of three times the zero-
zequence current 3·I0 (calculated on the basis of the phase
currents) with the current measured in the neutral
transformer, taking into account the phase and neutral
transformation ratio. None of the phases should surpass 1.5
times the rated current.
Setting Options
Enabled YES / NO
Pag. 20
General configuration
Enabled YES / NO
10
280
280
1
1
General configuration
alarm signal when it is not inside the set range. Language Spanish / English
IRIG-B format B002 (without year) / B002 IEEE 1344 (with year)
Breaker monitoring Local/remote selection Logical input
The inactivity days of the breaker are also checked. Select Setting group 3 Logical input
Pag. 21
Logics
It stores up to 20 faults with the description of the fault: Maximum and minimum real, reactive and apparent
powers
Date and time: Day/Month/Year Hour/Min/Sec.msec
Units tripped during the fault
Measurements
Units started during the fault
Fault beginning date and time (first unit started) Depending on the model, the measurements below are
available:
Trip date and time (first unit tripped)
Phase-to-earth, neutral and average currents
Fault end date and time (end of trips)
Direct, inverse sequence and zero-sequence currents
Current opened by breaker upon trip.
Phase-to-earth, neutral and average voltages
Active setting group during the fault.
Phase-to-phase voltages: AB, BC, CA and average
Fault type and trip type (code of up to 3 letters)
Direct, inverse sequence and zero-sequence voltages
Pre-fault and fault measurements of all the channels.
Phase residual current
Calculated measurements (V and I direct, inverse and
zero-sequence sequences, total powers). Phase restraint current
Distance to fault. Frequency (Hz)
Thermal image temperature upon trip. Total real power and real power per phase (MW)
Tripped phases. Total reactive power and reactive power per phase
(MVA)
Maximum phase and neutral currents and voltages
during the fault. Total apparent power and apparent power per phase
(MVA)
Fault end date and time (end of trips).
Positive and negative real power energy counters
Pag. 22
Communication protocols
Positive and negative reactive power energy counters Parallel Redundancy Protocol (PRP)
Average power factor and per phase
The PRP is a redundancy communication protocol defined in
Fi cosine per phase an total the IEC 62439-3 standard and it is one of the redundancy
Current, voltage, real, reactive and apparent power mechanism recommended in IEC 61850 networks.
maximeter In PRP solutions two independent ethernet networks are
External power supply used. Each device is attached to both networks and sends
and receives all the frames over both LANs simultaneously,
Internal battery
consumes the first frame and discards the duplicate. With this
Thermal image (%) mechanism PRP ensures zero-packet loss and zero recovery
Equipment temperature (º C) time upon single network failures.
Distance to fault (km)
Link failover redundancy
With the link failover redundancy the device uses two
Communication protocols ethernet ports for a redundant communication. In this
redundancy mode the device communicates by one of the
ethernet ports and if there is a link failure in that port,
Front Ethernet port (RJ45) switches to the redundant port if the link status of that port is
Configuration and 61850 protocol (without Gooses) active.
Up to 6 serial ports (RS232, RS485, GFO or PFO) and 2 In this redundancy, unlike the case of PRP redundancy, it
Ethernet ports (RJ45 or GFO) in the rear: should not be used two independent ethernet networks. The
two Ethernet ports of the equipment must be connected to
Slave Procome protocol different network switches, but must belong to the same
Slave DNP protocol network, so that the switches should be connected at some
61850 protocol point in the network.
Pag. 23
Technical specifications
Technical specifications
Current circuits
Phases/neutral/polarisation current thermal capacity (Unified Rated Current 1/5A)
Measurement range 0.02 A to 200 A
Permanent 20 A
Thermal current 10 s. 50 A
Short duration 500 A
Very short duration (1/2 cycles) 1,250 A
Burdens at In= 5 A <0.2 VA
Burdens at In= 1A <0.02 VA
Voltage circuits
Thermal capacity
Measurement range 1 to 200 Vac
Rated voltages 63.5 / 120 Vac
Thermal capacity
Permanent 250 Vca
Short duration 300 Vca (1s.)
Burden at 63.5 V <0.015 VA
Burdens at 100 VA <0.03 VA
Mechanical Features:
½ 19” chassis and 5 U models approximate weight (without I/O modules) 3,5 kg.
19” chassis and 4 U models approximate weight (without I/O modules) 4,9 kg.
Approximate additional weight for each I/O module 0,4 kg.
Front IP IP30
Optional Front IP IP54
Pag. 24
Technical specifications
Environmental conditions
Operating temperature -40 to +60 ºC
Storage temperature -40 to +85 ºC
Relative humidity Up to 95% without condensation
Tests
Climatic test Standard
Cold IEC -60068-2-1 -40°C, 16 hours
Dry Heat IEC -60068-2-2 +85°C, 16 hours
Damp heat steady state IEC -60068-2-78 +40°C/93%RH, 96 hours
Damp heat cyclic IEC -60068-2-30 55ºC / 95% HR 6 cycles of 12+12
hours
Rapid change of temperature IEC -60068-2-14 -20ºC/+70ºC 2 cycles of 4+4 hours
External protection level IEC60529 IP30
AC power supply interruptions and dips immunity test IEC 61000-4-11 100% 10 ms, 20 ms, 5 s
60% 200 ms
30% 500 ms
20% 5 s
Ripple immunity test IEC 61000-4-17 15% (50 and 100 Hz)
Measurements of Harmonic current emissions IEC 61000-4-7 / IEC 61000-3-2
Power frequency immunity test IEC 60255-22-7 Class B
Measuremets of radioelectric emissions IEC 61000-6-4 Class A
Radiated radiofrequency electromagnetic field immunity test IEC 61000-4-3 10V/m
Conducted disturbances induced by radiofrequency fields immunity
IEC 61000-4-6 10Vrms
test
50 Hz magnetic fields immunity test IEC 61000-4-8 100 A/m 1000 A/m (2 s)
Pulse magnetic fields immunity test IEC 61000-4-9 1000 A/m
Damped oscillatory magnetic fields immunity test IEC 61000-4-10 100 A/m
Pag. 25
Technical specifications
I/O modules
Available in 24 Vcc/48 Vcc/125 Vcc/250 Vcc. Features:
Digital inputs:
24 Vcc. 48 Vcc. 125 Vcc. 250 Vcc.
Voltage levels 12-72 Vcc 37-72 Vcc 87-300 Vcc 172-300 Vcc
Inactive below: 9 Vcc. 32 Vcc. 82 Vcc. 165 Vcc.
Burden <3 mA
Digital outputs:
Independent standard and trip outputs
Carry (Permanent ) 8 A at 25 ºC
Make (1 s.) 30 A
Connection capacity 2500 W at 250 Vcc
220 Vcc. 125 Vcc. 48 Vcc.
Trip or close capacity (L/R = 40 ms) 0.7 A 1.0 A 1.5 A
With resistive load 1.0 A 1.5 A 2.0 A
Operating time 5 ms ON, 8 ms OFF
3-contact switched, common point signal outputs
Carry (Permanent ) 5 A at 25 ºC
Make (1 s.) 20 A
Make (1/2 s.) 30 A
220 Vcc. 125 Vcc. 48 Vcc.
Trip or close capacity (L/R = 40 ms) 0.1 A 0.2 A 0.5 A
With resistive load 0.2 A 0.4 A 1A
Operating time 8 ms ON/OFF
h.b.c.o outputs (high break contact outputs)
Carry (Permanent) 8 A at 25 ºC
Make (1 s.) 30 A
Connection capacity 2500 W at 250 Vcc
220 Vcc. 125 Vcc. 48 Vcc.
Trip or close capacity (L/R = 40 ms) 10 A (L/R=20 ms) 10 A (L/R=40 ms) 10 A (L/R=40 ms)
With resistive load 10 A 10 A 10 A
Cyclic capacity 4 cycles in 1 second, 2 minutes waiting for thermal dissipation
5 ms ON, 5 ms OFF (Resistive load)
Operating time
6 ms ON, 14 ms OFF (L/R = 40 ms)
Analogue inputs
AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 AI 7 AI 8
Type +/- 5mA +/- 5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 20mA +/- 20mA
Options for each input: ±1mA, ±2.5mA, ±5mA, ±20mA, ±5V, ±10V
Pag. 26
Technical specifications
Module types
Pag. 27
Technical specifications
Communication ports
Front communication port
Ethernet RJ45
RJ45 connector RJ45 female
Cable type Shielded
Cable length 100 m max.
Insulation 500 V
Communication speed 10/100 Mbps
USB
Version Compatible with USB 2.0
Operating mode Master
Speed 480 Mbps (high-speed), 12 mbps (full-speed) or 1.5 Mbps (low-speed)
Insulation 500 V
Rear communication port types
RS232
RS232C connector 9 pin type D female DTE
Cable type Shielded
Cable length 15 m max.
Insulation 500 V
RS485
RS485 connector 9 pin type D female DTE
Cable type Shielded crossed pair
Cable length 1,000 m max.
Insulation 500 V
GFO
GFO connector ST
Wavelength 820 nm
Permitted attenuation 8 db with 62.5/125 µm GFO
Multimode GFO 62.5/125 µm
Maximum distance 1.5 km
PFO
PFO connector HP standard
Wavelength 660 nm
Permitted attenuation 24,7 db with plactic cable of 1mm
22 db with 200/125 µm silica cable
Maximum distance 115 m with 1 mm plastic cable
1.9 km with 200 µm silica cable
FO single-mode 60km (E/F) 20-120km (M/N)
Connector ST or LC ST o LC
Wavelength 1310 nm 1550nm
Permitted attenuation 30 db 35 dB
Singlemode GFO 9 / 125 nm 9 / 125nm
Distance 60 Km Maximum 120km / Minimum 20km
C37.94 glass optical fiber
Connector ST
Wavelength 850 nm
Permitted attenuation 8 db
Multimode GFO 50/125µm and 62.5/125 µm
Distance 2 Km
Ethernet RJ45
RJ45 connector RJ45 female
Cable type Shielded
Cable length 100 m max.
Insulation 500V
Communication speed 10/100 Mbps
Pag. 28
Technical specifications
GFO Ethernet
GFO connector ST
Wavelength 1,300 nm
Permitted attenuation: 8 db with GFO
Multimode GFO 62.5/125 µm
Communication speed 100 Mbps
Maximum distance 1.5 km
LC Ethernet
LC connector LC duplex
Wavelength 1,310 nm
Permitted attenuation: 8 db
Multimode GFO 62.5/125 u m and 50/125um
Communication speed 100 Mbps
Maximum distance 1.5 km
Irig-B input
IRIG-B output
Input Demodulated
Input level TTL
Cable type 2 shielded wires
Insulation 2,000 V
Measurements
Frequency
Frequency of the programmable system 50 or 60 Hz
Operating range Fn ± 5 Hz
Measurement accuracy
Current
Measurement range (0 to 1.2 x In)
At In=1/5A 0.5 % FS
Protection range (0 to 200 A)
Accuracy 1 % over the measurement or 2 mA
Voltage
Measurement range (0 to 1.2 x Vn)
At Vn=63.5/120 Vac 0.5 % FS
Protection range (0 to 200 Vac)
Accuracy 1 % over the measurement or 50 mV
Angle of phase different
Accuracy ± 1º
Power
Measurement range (0 to 1.2 x In x 1.2 x Vn)
At In=1 A Class 1 (1 % of Pn)
At In=5 A Class 0.5 (0.5% of Pn)
Time accuracy
Additional time = 0ms. Currents must be above 100mA, depending on Measurement/start value:
From 1 to 1,5 times: Up to 40ms (typical 35ms)
2 times: Between 30-35ms
From 3 times: Under 30ms
Additional time higher than 50ms.
30ms or 3% of the theorical value (the higher of the two)
Pag. 29
Construction features
Construction features
Pag. 30
Rear views
Rear views
Fig. 1.13 Ingepac EF rear view with half a 19" chassis and 5U
Pag. 31
Keypad/Local display
Keypad/Local display
Pag. 32
Keypad/Local display
1. 5 functional keys.
Pag. 33
Interconnection diagrams
Interconnection diagrams
The following images show the different interconnection options of the analogue inputs, according to t he inputs available.
Pag. 34