Professional Documents
Culture Documents
CIGRE UK October 2021 Technical Webinar
CIGRE UK October 2021 Technical Webinar
• Rafal Zaleski
Rafal Zaleski graduated from the Silesian University of Technology in 2002 with a
Master of Science degree. Following education, he started gaining his first practical
experience in Poland with Energo-Complex company. There, he was responsible for
transformer condition assessment through electrical testing and analysis on on-line
condition tests results. He joined Doble Engineering Company in 2009 as Senior Test
Engineer where he initially continued with transformer condition assessment quickly
expanding his skills across other substation apparatus. Nowadays he holds Principal
Engineer position within Doble and he is responsible for consultancy services related
to purchase of new-built transformers, eg. factory progress inspections, FAT
witnessing etc. He has been an active expert member for two CIGRE working groups
on FRA measurement and interpretations and has ample experiences in field tests Rafal Zaleski
using FRA technique.
2
Table of contents
• Part 1 (Dr Dahlina Sofian)
• Introduction
• Understanding the frequency response
Dr Dahlina Sofian
3
Dr Dahlina Sofian
Part 1
Introduction
Understanding the Frequency Response
4
Introduction
• Frequency Response Analysis (FRA) is Comparative test – relies on
commonly used to assess the mechanical compared responses being
integrity of transformer active part measured in the same way and
in the same transformer
• Normally performed during the following: condition.
Tap winding with partial axial
• Factory fingerprint before transport to site collapse and inter-turn short-circuit
0
-10
-20
commissioning
dB
Magnitude,dB
-40
Amplitude,
-50
-70
5
International Collaborations (2008 – 2020)
Cigre WG A2.26 IEEE WG C57.149 IEC PT 60076-18 Cigre A2.53
Further collaborations needed to share case studies towards effective and reliable diagnosis
6
Cigre WG A2.26
• Highlights on measurement
configurations which were later
implemented in IEEE and IEC standard
documents.
7
IEEE WG C57.149
8
IEC PT 60076-18
Unified way of making FRA measurement with best practice and emphasis on repeatability
9
Cigre A2.53
10
Back to Basic
IEC 60076-18 (2012): Measurement of frequency response
End-to-End End-to-End Short Circuit
Amplitude
The amplitude of the frequency response is the scalar ratio between the response signal
(Vout) and the reference voltage (Vin) (presented in dB) as a function of the frequency.
11
Inductive Inter-Winding
Back to Basic
Typical frequency responses
End-to-End
LV winding response of generator transformer
Capacitive Inter-Winding
12
Back to Basic
What does each end-to-end frequency response mean?
0
Interaction
-10 Core between Winding structure Setup
windings • Frequency response from low to high frequencies
-20 is influenced by different components within power
-30
transformer
• Dependent on the interaction of electrical
Amplitude, dB
13
Understanding of Frequency Response
Simple representation
R
Series LC
C
Resonance (maxima)
R L Parallel LC
Anti-resonance (minima)
14
Understanding of Frequency Response – Model Evolution
TB 812 (2020): Advances in the interpretation of transformer Frequency Response Analysis (FRA) R-L-C-M equivalent circuit
transformer modelling
LV HV LV HV
CgL/N CHL/N CgH/N
Mcore+Mair
Single Core Tank
phase two Lcore+Lair
Single air-
core
winding
More complex transformer model with the following:
• Three-phase power transformers with star and
delta connected windings
• Additional windings (tertiary and tap windings)
15
Single air-core winding
16
Single winding with core
17
Single winding with core and mutual inductive
18
Single phase two winding transformer
19
Identification of Unique Frequency Response Features
“U shape” Feature
Sensitivity studies on transformer model to replicate “U shape” feature
Magnitude (dB)
Magnitude (dB)
E
• ‘U shape’
between 1 kHz
Magnitude (dB)
Magnitude (dB)
50Ω
to 10 kHz V1 V3
• Delta connected
0.5CgL 0.5CHL 0.5CgH
HV windings
• Due high
CsL CsH
inductance/low Core LV HV Tank
series
capacitance
Z.D. Wang, B.Z. Cheng, P.A. Crossley, D. M. Sofian, J. Sanchez, “Fundamental Understanding of
0.5CgL V2 0.5CHL V4 0.5CgH
Frequency Response Analysis ‘U shape’ through Transformer Modelling”, CIGRE COLLOQUIUM
50Ω SCA2 /SCB2/ SCD1 India, November 22, 2019.
20
FRA as Comparative Test
Comparison with previous fingerprint (time based)
The best comparison as differences indicate a problem in a winding, but fingerprint is
often unavailable
Comparison with sister units (type-based)
Can be difficult as need to identify whether “normal differences” or a problem in a winding
Comparison with different phases (construction based)
Can be difficult as need to identify whether “normal differences” or a problem in a winding
“Normal differences” : Differences caused by factors other than problems in a
transformer winding, such as manufacturing tolerances, different lengths of
internal leads to LTC, winding inter-connections and slight variations in similar
design.
• Further collaborations needed to share case studies towards effective and reliable diagnosis
• It is important to ensure the measurements are being made in the same way and the
transformer is in the same condition for correct diagnosis – repeatability and consistent
recording
22
Rafal Zaleski
Part 2
Factors influencing the measurement
Importance of good reference traces
FRA examples
23
Factors Influencing the Measurement
It is important to ensure the measurements are being made in the same way and the transformer is in the
same condition for correct diagnosis – repeatability and consistent recording
Dr Dahlina Sofian
24
Effect of core magnetization
25
Effect of tap position
26
Nominal tap position (N)
27
Effect of state of other winding
28
Effect of state of other winding
HV in 120kV
HV in 60kV
29
Effect of state of other winding
Delta closed
Delta opened
30
Effect of internally grounded delta winding
31
Experiment with delta winding
32
Effect of insulating liquid
Effect of
transportation
bushings
With oil
Without oil
33
Effect of long GIS busbar
34
Effect of missing core earth
35
Effect of poor grounding
36
Effect of poor grounding
37
Importance of Good Reference Results
38
Importance of good reference results
The SFRA results not always give easy to interpret results eg. completely
aligned responses of three phases. Although in some cases experience
plays important role and allows to recognize certain situations,
sometimes additional reference results are extremely helpful in
interpretation.
39
Importance of good reference results
40
Importance of good reference results
Small distribution
transformer
41
FRA Examples
42
Shorted turns
44
Movement of Single Turns
45
Movement of Single Turns
46
Movement of Single Turns
47
Movement of Single Turns
48
Axial Collapse
Initial symptoms
35 year old 400/132 kV 240 MVA auto-transformer
10:53 a.m. Monday 5th November 2001
Buchholz alarm
Transformer switched out for investigation
Analysis of Buchholz gas and main tank oil indicated serious fault
No abnormal system events
Transformer was operating at 80% loading
49
Axial Collapse
50
Axial Collapse
Previous results
51
Axial Collapse
52
Axial Collapse
53
Buckling Deformation
Transformer details:
375/750MVA ONAN/ODAF
400/275/13kV autotransformer
No taps
Built 1966
Deterioration in DGA results
Removed from service for investigation
54
Buckling Deformation
20
120 14
12
10
100
80
4
60 0
18/02/1982 17/02/1985 17/02/1988 16/02/1991 15/02/1994 14/02/1997 14/02/2000 13/02/2003 12/02/2006 11/02/2009
C2H4 C2H2
40
20
0
18/02/1982 17/02/1985 17/02/1988 16/02/1991 15/02/1994 14/02/1997 14/02/2000 13/02/2003 12/02/2006 11/02/2009
55
Buckling Deformation
T4673
A phase B phase C phase
T4971
A phase B phase C phase
Significant difference in capacitance and power factor were noted for phase B
56
Buckling Deformation
57
Buckling Deformation
58
Tap Winding Movement
275/33kV 120MVA YNd1 transformer feeding steelworks suffered flashover
between taps while on ‘hot standby’
Barrier board between tap-changer and main tank broken
SFRA tests indicated movement for tap winding:
Difference for Blue phase at Tap 1 (taps ‘all-in’), but not at Tap 10 ( ‘all-out’)
Compared responses with sister reference transformer
Note faulty transformer was without oil, while reference was oil filled
Internal inspection confirmed conductor tilting for Blue phase tap winding
Special SFRA Tests showed possibility of internal resonant over-voltage
between taps involved in flashover for switching surge at HV line terminal
59
Tap 10 HV SFRA for faulty transformer
60
Tap 10 HV SFRA for reference transformer
61
Tap 1 HV SFRA for faulty transformer
62
Tap 1 HV SFRA for reference transformer
63
Broken tap-changer barrier board
64
Flashover damage between Blue phase tap leads
65
Internal View
66
Part 2 Conclusions
67
Part 2 Conclusions
68
Questions
69