Professional Documents
Culture Documents
Advices in Choosing The Right Neutral Earthing System For Your Installation
Advices in Choosing The Right Neutral Earthing System For Your Installation
Advices in Choosing The Right Neutral Earthing System For Your Installation
your installation
electrical-engineering-portal.com/choosing-neutral-earthing-system
By Edvard February 3,
2020
Yeses and nos in choosing the right neutral earthing system for your design
This technical article will not discuss the basics of neutral earthing systems, and it is
considered that you are already familiar with the subject. Instead, it will focus on the
characteristics that may influence electrical engineers’ decision to select the most suitable
neutral earthing system.
1/14
Don’t forget that the choice of the neutral earthing system has a direct effect on the
electromagnetic compatibility (EMC) of the installation, so that will be covered too.
Table of contents:
1.1 TT system
General principle
Detection of a fault current running through the earth and disconnection of the power
supply by a residual current device (RCD).
2/14
Figure 1 – Insulation fault on the connected load in a TT system
If insulation fault occurs on a receiver, the fault current If circulates in the fault loop. This
circuit includes the fault impedance on:
The fault loop is finally closed by the transformer windings and the power supply circuit.
Advantages of TT system
Simplicity (very few calculations when installing).
Extension with no need to calculate the lengths.
Low fault currents (fire safety).
Very little maintenance (apart from regular testing of the RCDs).
Safety of people when portable devices are supplied or if earthing is defective (with 30
mA RCDs).
Operation on a source at low prospective current ik (generator set).
Disadvantages of TT system
No differential discrimination if only one device at supply end of installation
3/14
Need for RCDs on each outgoing line to obtain horizontal discrimination (cost)
Risk of false tripping (overvoltages)
Interconnection of exposed conductive parts to a single earth connection (widespread
installations) or RCD needed for each group of exposed conductive parts
Level of safety dependent on the value of the earth connections
1.2 TN system
General principle
The fault current changes to a short-circuit current which is broken by the overcurrent
protection devices, and the exposed conductive parts are kept below a safe voltage
threshold.
In TN systems, a point on the power supply, generally the transformer neutral, is earthed.
The exposed conductive parts of the installation are connected to the same point by a
protective conductor.
The system is called TN-C when the neutral function is combined with that of the protective
conductor, which is then called PEN. See the connections of TN-C system here. If these
conductors are separated, the system is named TN-S. See the connections of TN-S system
here.
When both variants cohabit in the same installation, the term TN-C-s can be used ( see
connections), remembering that the TN-C system must always be upstream of the TN-S
system.
4/14
Figure 2 – Insulation fault on the connected load in a TN-C system
If insulation fault occurs at any point in the installation affecting a phase conductor and the
protective conductor or an exposed conductive part, the power supply must be cut off
automatically within the specified breaking time t while complying with the condition:
Zs × Ia ≤ U 0
Where:
Zs – impedance of the fault loop comprising the power supply line, the protective
conductor and the source (transformer windings).
Ia – operating current of the protection device within the specified time
U0 – nominal phase/earth voltage
Advantages of TN system
Low cost (protective devices are used for fault currents and overcurrents)
The earth connection has no effect on the safety of people
Low sensitivity to disturbance (good equipotentiality, neutral earthed)
Low sensitivity to high leakage currents (heating, steam, computing equipment)
Disadvantages of TN system
High fault currents (generation of disturbance and risk of fire in particular with TN-C
system)
5/14
Need for accurate calculation of lines
Risk in the event of refurbishment extensions or uncontrolled use (qualified staff)
1.3 IT system
General principle
Keeping the 1st fault current at a very low value limits the voltage rise of the exposed
conductive parts, and there is thus no need for disconnection. However, 2nd fault is a
different story.
Let’s see what happens with the 1 st fault in this neutral earthing system.
6/14
IT system: 1st fault
The current of the 1 st fault (If) is limited by the sum of the resistances of the earth
connections of the power supply (RB), the exposed conductive parts (RA ) and the impedance
(Z).
The non-breaking condition must be checked, ensuring that the current will not increase the
exposed conductive parts to a voltage higher than the voltage limit UL. The following is
therefore required: RA × I f < 50 V, i.e. in the example: 30 × 0.112 = 3.36 V.
The exposed conductive parts will not reach a dangerous voltage and non-breaking is
permitted.
7/14
IT system: 2nd fault
In the event of a 2 nd fault affecting another phase, on the same or another exposed
conductive part, a loop is created by the exposed conductive parts of the faulty receivers,
the protective conductors and the power supply conductors.
This will cause a high short-circuit current to circulate for which the elimination
conditions are those of the TN or TT system. It should be noted that this double fault
situation is totally independent of the situation of the neutral in relation to earth, which may
be isolated or impedance earthed. The IT double fault current is often lower that it would be
with a TN system. The protected line lengths will be reduced accordingly.
If there is a fault, the voltage of the neutral may increase to that of the faulty phase (phase-
to-neutral voltage). The voltage of the other phases will tend to increase towards the value
of the phase-to-phase voltage.
It is therefore advisable not to supply devices between phase and neutral in IT systems
and thus not to distribute the neutral.
Advantages of IT system
Continuity of service (no breaking on 1 st fault).
1 st fault current very low (fire protection).
Fault current causes little disturbance.
Operation on sources at low prospective current ik (generator set).
Supply of receivers sensitive to fault currents (motors).
8/14
Disadvantages of IT system
Installation cost (protected neutral, Pim, voltage surge protectors).
Operating cost (qualified staff, location of faults).
Sensitivity to disturbance (poor equipotentiality with earth).
Risks on 2nd fault:
Short-circuit overcurrents.
Disturbance (rise in earth voltage).
Appearance of a phase-to-phase voltage (if neutral distributed).
The following tables give general rules for choosing the neutral earthing system according to
the installation, the loads and the operating conditions.
However, in some cases these rules may be inapplicable. The neutral earthing system must
be chosen for the majority of the applications in the installation. If one of them is not
very compatible with this choice, it is preferable to isolate it and treat it separately
(islanding, filtering, separation).
Choosing the overall system based on this single application would be to risk making the
wrong choice for the rest of the installation.
Table 1 – Recommended system acc. to the type and characteristics of the installation
Site installations
Old installations
10/14
Installations with requirement for continuity (medical, pumps,
ventilation, etc.)
The consequences of a lighting strike are partly dependent on the situation of the
power supply in relation to earth, defined by the first letter (I or T).
The transmission of conducted or emitted high frequency disturbance depends on the
connection of the exposed conductive parts of the installation and their
equipotentiality, defined by the second letter (T or N).
The energy transmission distances require a common voltage reference that can be
accessible from the source to the load and can discharge disturbance such as lightning.
Only the earth meets these conditions!
11/14
Separate installation and power supply (public distribution system)
Locally, the earth is not necessary for the equipotentiality of an installation. It is the
equipotential bonding system which provides this equipotentiality. Thus when the energy
source is nearby or standalone (batteries, solar panels, generator set, etc.) it is not
necessary to earth the power supply and the installation.
The protection can be provided simply by ‘local equipotential links’ that are not
earthed. If there is a lightning strike, which is the main risk, the voltage of the whole
installation rises equally, and thus there is no damage.
High altitude weather stations and isolated transmitters use this principle.
Standalone installation
Let’s see now advantages and disadvantages of the neutral earthing systems in
relation to EMC:
12/14
2.1 TT system
Advantages
The neutral voltage is fixed.
The fault currents are low.
Disadvantages
Source earth connection and load earth connection are separated and less
equipotential. impedance of the load earth connection can be high.
PE conductor does not constitute a reliable voltage reference, resulting in the need for
additional equipotential links.
Lightning strike giving differential mode overvoltage (dissymetry of the system).
2.2 IT system
Advantages
The fault currents are low.
Good protection against conducted lightning , but risk of sparkover on the neutral
impedance, resulting in the need for a surge voltage protector.
Disadvantages
“Load” earth voltage not fixed in relation to the source and consequently not fixed in
relation to that of the exposed conductive parts.
Increase in earth voltage (direct lightning strike) or after the 1 st fault: loss of reference
for electronic devices.
Circulation of permanent currents by capacitive coupling between live and earth
conductors.
13/14
2.3 TN-S
Advantages
A single “source” and “load” voltage reference, the earth is not used as a
conductor, and good equipotentiality of the exposed conductive parts.
Low impedance of the protection circuit due to the need to carry high fault
currents.
Disadvantages
Specific installation rules and equipment (5 wires).
Possible rejection of disturbance on the neutral if the equipotentiality is uncertain
between the neutral and the Pe conductor or if their paths are different.
High fault currents.
Lightning strike giving differentiel mode overvoltage (dissymetry of the system).
Use, on each outgoing circuit, of RCBOs compatible with the leakage currents will limit the
currents in the event of a fault.
The TN-C system is not recommended due to the circulation of high fault currents in the
PEN conductor.
14/14