RISK ANALYSIS WITHOUT LPS


DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: HS
CHECKED BY: BA

Type of Building Industrial

COLOR INDICATES FACTORS RELEVANT TO THE BUILDING & TO BE ENTERED

SR.NO. INPUT DESCRIPTION BRIEF UNIT

BASIC STRUCTURE DIMENSIONS

1 L Length of the building m


2 W Width of the building m
3 H Height of the building m
4 HP Height of Prtorusion Height of elevated roof, lift m
machine room, etc.

ADJACENT STRUCTURE DIMENSIONS

5 L
DJ Length of the adjacent building
W
6 DJ Width of the adjacent building
H
7 DJ Height of the adjacent building

STRUCTURE ATTRIBUTES

8 w
m1 Mesh widhts of grid like spatial shield Refer IEC 62305-2 Pg. No. 36 m
9 w
m2 Mesh widhts of grid like spatial shield m
K
10 S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Power Line) shielded/ unshielded cable?
11 K
S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Telecommunication Line) shielded/ unshielded cable?

ENVIRONMENTAL INFLUENCES

12 NG Lightning ground flash density Ng of the area where the 1/sq.km x year
structure is located

13 CD Location factor of the structure Surrounding structures / an


exposed location
C
14 DJ Loaction factor of the adjacent structure Surrounding structures / an
exposed location
15 CE Environmental factor Is environement rural, urban,
etc.

SERVICE LINES

POWER LINES

16 CT Line type factor Type of power line in the area

17 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and isolation Is the power/LV line buried,shielded,
18 C
LD
conditions of the line to which the internal etc.?
system is connected
19 UW Ratedd impulse withstand voltage of the system to KV
be protected
C
20 LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?

21 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.
Probability value depending on the resistance of the Line characteristics in terms of
22 P
LD
cable screen and the impulse withstand voltage of the bonding
equipment

TELECOMMUNICATION LINES

23 CT Line type factor Type of power line in the area

24 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and Is the power/LV line buried,shielded,
25 C
LD
isolation conditions of the line to which the internal system is etc.?
connected
26 UW Ratedd impulse withstand voltage of the system to KV
be protected
C
27 LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?
28 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the cable Line characteristics in terms of
29 P
LD
screen and the impulse withstand voltage of bonding
the equipment

PROTECTION MEASURES

Probability that a flash to a structure will cause shock Type of additional protection
30 P
TA
to living beings due to dangerous touch and step voltages measures provided

31 PB Probability that a flash will cause physical damage Level of Lightning Protection

32 P
SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Power line) coordinated & Level of LPS?

33 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is


(Power line) provided for the structure?
34 P
SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Telecommunication line) coordinated & Level of LPS?

35 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is


(Telecommunication line) provided for the structure?
34 rt Factor reducing the loss of human life depending on Type of surface
the type of soil or floor

Factor reducing the loss due to physical damage depending


35 rp on the provisions taken to reduce the Provisions in case of fire
consequences of fire
36 P
EB Probability value as a function of LPL for which SPDs Equipotential bonding & LPL
are designed
Probability value depending on theline type and the Line and equipment charateristics
P
impulse withstand voltage of the equipment (Power line)
37 LI

Probability value depending on theline type and the Line and equipment charateristics
38 P
LI
impulse withstand voltage of the equipment
(Telecommunication line)
VALUE

86
40
42
4.5

86
40
42

0.2

0.2

3.7

0.25

0.5

0.01

0.2

0.5

1
1

0.5

Not Provided

Not Provided

0.001

0.5

0.1

0.2
SR.NO. INPUT DESCRIPTION BRIEF UNIT

LOSS OF HUMAN LIFE (L1)

Typical mean relative numbers of victims injured by electric Type of structure, industrial, hotel,
39 LT shock due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by physical Type of structure, industrial, hotel,
40 LF damage due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by failure of Type of structure, industrial, hotel,
41 LO internal systems due to one dangerous public, etc.
event
Factor reducing the loss due to physical damage
42 rf depending on the risk of fire or on the risk of explosion of Risk of explosion of structure
structure
43 hz Factor increasing the loss due to physical damage Level of panic
when a special hazard is present

44 nz Number of persons in the zone


45 nt Total number of persons in the structure
46 tz Time in hours per year for which the persons are
present in the zone

UNACCEPTABLE LOSS OF SERVICE (L2)

Typical mean relative number of users not served, Type of service, gas, water supply,
47 LF resulting from physical damage due to one dangerous event etc.

Typical mean relative numbers of users not served resulting Type of service, gas, water supply,
48 LO from failure of internal systems due to one etc.
dangerous event

LOSS OF CULTURAL HERITAGE (L3)

Typical mean relative value of all goods damaged by physical Type of structure, museum, galleries,
49 LF damage due to one dangerous event etc.

50 cz Value of cultural heritage in the zone


51 ct Total value of building and content of the structure

LOSS OF ECONOMIC VALUE (L4)

Typical mean relative value of all goods damaged by electric Type of structure, industrial, hotel,
52 LT shock due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by physical Type of structure, industrial, hotel,
53 LF damage due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by failure of Type of structure, industrial, hotel,
54 LO internal systems due to one dangerous public, etc.
event
55 ca Valus of animals in the zone
56 cb Value of building relevant to the zone
57 cc Value of content in the zone
58 cs Value of internal systems including their activities in
the zone
VALUE

0.01

0.01

0.01

240
240
8760

0
100000

0.1

0.0001

0
10000
0
0
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR NAGENDRA CS
CHECKED BY: COLOR INDICATES FACTORS RELEVANT TO THE BUILDING & TO BE ENTERED

Type of Building Residential

SR.NO. INPUT DESCRIPTION BRIEF UNIT

BASIC STRUCTURE DIMENSIONS

1 L Length of the building m


2 W Width of the building m
3 H Height of the building m
4 HP Height of Prtorusion Height of elevated roof, lift m
machine room, etc.

ADJACENT STRUCTURE DIMENSIONS

L
5 DJ Length of the adjacent building
W
6 DJ Width of the adjacent building
7 H
DJ Height of the adjacent building

STRUCTURE ATTRIBUTES

8 w
m1 Mesh widhts of grid like spatial shield Refer IEC 62305-2 Pg. No. 36 m
w
9 m2 Mesh widhts of grid like spatial shield m
K
10 S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Power Line) shielded/ unshielded cable?

11 K
S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Telecommunication Line) shielded/ unshielded cable?

ENVIRONMENTAL INFLUENCES

12 NG Lightning ground flash density Ng of the area where the 1/sq.km x year
structure is located
13 CD Location factor of the structure Surrounding structures / an
exposed location

14 C
DJ Loaction factor of the adjacent structure Surrounding structures / an
exposed location

15 CE Environmental factor Is environement rural, urban,


etc.

SERVICE LINES

POWER LINES

16 CT Line type factor Type of power line in the area

17 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and isolation Is the power/LV line buried,shielded,
18 C
LD
conditions of the line to which the internal etc.?
system is connected
19 UW Ratedd impulse withstand voltage of the system to KV
be protected

20 C
LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?
21 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the Line characteristics in terms of


22 P
LD
cable screen and the impulse withstand voltage of the bonding
equipment

TELECOMMUNICATION LINES

23 CT Line type factor Type of power line in the area

24 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and Is the power/LV line buried,shielded,
25 C
LD
isolation conditions of the line to which the internal system is etc.?
connected
26 UW Ratedd impulse withstand voltage of the system to KV
be protected
27 C
LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?

28 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the cable Line characteristics in terms of
29 P
LD
screen and the impulse withstand voltage of bonding
the equipment

PROTECTION MEASURES

Probability that a flash to a structure will cause shock Type of additional protection
30 P
TA
to living beings due to dangerous touch and step voltages measures provided

31 PB Probability that a flash will cause physical damage Level of Lightning Protection

P
32 SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Power line) coordinated & Level of LPS?
33 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is
(Power line) provided for the structure?
P
34 SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Telecommunication line) coordinated & Level of LPS?
35 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is
(Telecommunication line) provided for the structure?

34 rt Factor reducing the loss of human life depending on Type of surface


the type of soil or floor
Factor reducing the loss due to physical damage depending
35 rp on the provisions taken to reduce the Provisions in case of fire
consequences of fire
P
36 EB Probability value as a function of LPL for which SPDs Equipotential bonding & LPL
are designed
Probability value depending on theline type and the Line and equipment charateristics
37 P
LI
impulse withstand voltage of the equipment (Power line)

Probability value depending on theline type and the Line and equipment charateristics
38 P
LI
impulse withstand voltage of the equipment
(Telecommunication line)

LOSS OF HUMAN LIFE (L1)


Typical mean relative numbers of victims injured by electric Type of structure, industrial, hotel,
39 LT shock due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by physical Type of structure, industrial, hotel,
40 LF damage due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by Type of structure, industrial, hotel,
41 LO failure of internal systems due to one dangerous event public, etc.

Factor reducing the loss due to physical damage depending


42 rf on the risk of fire or on the risk of Risk of explosion of structure
explosion of structure
43 hz Factor increasing the loss due to physical damage Level of panic
when a special hazard is present
44 nz Number of persons in the zone
45 nt Total number of persons in the structure
46 tz Time in hours per year for which the persons are
present in the zone

UNACCEPTABLE LOSS OF SERVICE (L2)

Typical mean relative number of users not served, resulting Type of service, gas, water supply,
47 LF from physical damage due to one etc.
dangerous event
Typical mean relative numbers of users not served Type of service, gas, water supply,
48 LO resulting from failure of internal systems due to one etc.
dangerous event

LOSS OF CULTURAL HERITAGE (L3)

Typical mean relative value of all goods damaged by physical Type of structure, museum, galleries,
49 LF damage due to one dangerous event etc.

50 cz Value of cultural heritage in the zone


51 ct Total value of building and content of the structure

LOSS OF ECONOMIC VALUE (L4)

Typical mean relative value of all goods damaged by electric Type of structure, industrial, hotel,
52 LT shock due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by physical Type of structure, industrial, hotel,
53 LF damage due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by Type of structure, industrial, hotel,
54 LO failure of internal systems due to one dangerous event public, etc.

55 ca Valus of animals in the zone


56 cb Value of building relevant to the zone
57 cc Value of content in the zone
58 cs Value of internal systems including their activities in
the zone
VALUE

86
40
42
4.5

86
40
42

0.2

0.2

3.7

0.25

0.5

0.01

0.2

0.5

1
1

0.5

Not Provided

Not Provided

0.01

0.5

0.1

0.2
0.01

0.01

0.01

240
240
2920

0
100000

0.1

0.0001

0
10000
0
0
Type of Building Residential
COLOR INDICATES FACTORS RELEVANT TO THE TYPE OF
BUILDING

Collection Area of building


A = L x W + 2 x (3xH) x (L+W) + 3.14 x (3xH)2
D
L= 86
W= 40
H= 42

Collection Area of Protrusion


A ' = 3.14 x (3xH )2
D
H = P 4.5
P
A '= 572.265
D

Total Collection Area = 8.56E+04


Number of dangerous events ND for the structure

N = N x A x C x 10-6
D =
N G D D 3.7
G
A = 85614.905
D
C = 0.25
D

ND = 7.92E-02

Number of dangerous events NDJ for an adjacent structure


(Power Line)
N
DJ
/P= N
G
x DJ/P
A x DJC xTC x 10-6
L= 86
W= 40
H= 42
A =
DJ/P 85042.64
CDJ = 0.5
CT = 0.2

Number of dangerous events NDJ for an adjacent structure


(Telecommunication Line)
-6
N =N xA xC x C x 10
DJ/T G DJ/T DJ T
L= 86
W= 40
H= 42

NUMBER OF DANGEROUS EVENTS COMPONENTS


86
40
42

S EVENTS COMPONENTS
A =
DJ/T 85042.64
C
DJ =
0.5
CT = 1

Average annual number of dangerous events NM


due to flashes near structure
N = N x A x 10-6
M = 2G x 500
A M x (L+W) + 3.14 x 500 x 500
M
L= 86
W= 40
A = 911000
M

N = 3.37E+00
M

Average annual number of dangerous events NL


due to flashes to a line (Power)
N
L/P
=NG
A x IC x EC xTC x 10-6
x L/P
A = 40 x L
L/P L/P

L =
L/P 1000 Assumed
A =
L/P 40000
NG = 3.7
CI = 0.5
CE = 0.01
CT = 0.2

Average annual number of dangerous events NL due to


flashes to a line (Telecommunication)
-6
NL/T = NG x AL/T x CI x CE x CT x 10
A = 40 x L
L/T L/T

L
L/T
=
1000 Assumed
A =
L/T 40000
NG = 3.7
CI = 0.5
CE = 0.01
CT = 1

Average annual number of dangerous events NI


due to flashes near a line (Power)
N =N xA x C x C x C x 10-6 AI/P = 4000 x LL/P
LI/P = G I/P I E T 1000 Assumed
L/P
A = 4000000
I/P

N = 1.48E-02
I/P

Average annual number of dangerous events NI due to


flashes near a line (Telecommunication)
-6
NI/T = NG x AI/T x CI x CE x CT x 10
AI/T = 4000 x LL/T
L = 1000 Assumed
L/T
A = 4000000
I/T

N = 7.40E-02
I/T
86
40

1000 Assumed
40000
3.7
0.5
0.01
0.2

1000 Assumed
40000
3.7
0.5
0.01
1
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


Probability PA that a flash to a structure will cause injury to
living beings by electric shock
PA = PTA x PB
P = 1
TA

PB = 1
1.00E+00
PA =

Probability PC that a flash to a structure will cause failure of


internal systems (Power Line)
P =P xC
C/P SPD LD
P =
SPD
1
C = 1
LD

P = 1.00E+00
C/P

Probability PC that a flash to a structure will cause


failure of internal systems (Telecommunication Line)

P =P xC
C/T SPD LD
P =
SPD
1
C = 1
LD

P = 1.00E+00
C/T

Probability PM that a flash near a structure will cause failure


of internal systems (Power Line)

If Cordinated SPD system is provided , PM = PMS x


P
SPD

If Cordinated SPD system is not provided , PM = PMS


Coordinated SPD system as per inputs = Not Provided P SPD
=
1
2
PMS = (KS1 x KS2 X KS3 x KS4 )

wm1 = ###
wm2 = ###
K
S1 = ###
K =
S2 ###
KS3 =
dP SPD
=
1

0.2
UW = 6
K
S4 =
0.166666667

PMS = 0

PM 1 = 0
PM 2 = 0
P =
M/P 0.00E+00

Probability PM that a flash near a structure will cause failure


of internal systems
(Telecommunication Line)
If Cordinated SPD system is provided , PM = PMS x PSPD

If Cordinated SPD system is not provided , PM = PMS

Coordinated SPD system as per inputs = Not Provided


P =
SPD 1
2
PMS = (KS1 x KS2 X KS3 x KS4 )

wm1 = 0

w =
m2 0
KS1 = 0
KS2 = 0
KS3 = 0.2
UW = 6
KS4 = 0.166666667

P =
MS 0

PM 1 = 0
PM 2 = 0
P =
M/T 0.00E+00

Probability PU that a flash to a line will cause injury to living


beings by electric shock (Power
Line)
P =P xP XP xC
U/P TU EB LD LD

PTU = 1
PEB = 1
PLD = 1
C =
LD 1
Probability PU that a flash to a line will cause
injury to living beings by electric shock (Telecommunication
Line)
P
U/T = PTU x PEB X PLD x CLD
P = 1
TU
P = 1
EB
P = 1
LD
C = 1
LD

P =
U/T 1.00E+00
Probability PV that a flash to a line will cause physical
damage (Power Line)
P =P xP xC
V/P EB LD LD
P =
V/P 1.00E+00
Probability PV that a flash to a line will cause physical
damage (Telecommunication Line)
P =P xP xC
V/T EB LD LD
P =
V/T
1
Probability PW that a flash to a line will cause failure of
internal systems (Power Line)
P =P xP xC
W/P SPD LD LD
P =
SPD
1
P =
W/P 1.00E+00
Probability PW that a flash to a line will cause
failure of internal systems (Telecommunication Line)

P =P xP xC
W/T SPD LD LD
P =
SPD
1
P =
W/T 1.00E+00
Probability PZ that a flash near an incoming line will cause
failure of internal systems (Power Line)
P =P xP xC
Z/P SPD LI LI

PLI = 0.1
C =
LI 1
P =
Z/P 1.00E-01

Probability PZ that a flash near an incoming line will cause


failure of internal systems
(Telecommunication Line)
P =P xP xC
Z/T SPD LI LI

PLI = 0.2
C =
LI 1
P =
Z/T 2.00E-01
Type of Building Residential
COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING

LOSS OF HUMAN LIFE (L1)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x nz/nt x tz/8760

rt = 0.001

LT = 0.01
nz = 240
nt = 240
tz = 8760

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x hz x LF x nz/nt x tz/8760 rp =
0.5

rf = 0.01
hz = 1
LF = 0.01

LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt x tz/8760

LO = 1

LC= LM = LW = LZ = 1.00E+00

UNACCEPTABLE LOSS OF SERVICE TO THE PUBLIC (L2)

LOSS DUE TO DAMAGE D2

LB =LV = rp x rf x LF x nz/nt

rp = 0.5

rf = 0.01
LF = 0
nz = 240
nt = 240
LB = LV = 0.00E+00
LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt

LO = 0

LC = LM = LW = LZ = 0.00E+00

LOSS OF IRREPLACEABLE CULTURAL HERITAGE (L3)

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x LF x cz/ct rp =
0.5

rf = 0.01
Lf = 0
cz = 0
ct = 100000
LB = LV = 0.00E+00

ECONOIC LOSS (L4)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x ca/ct

rt = 0.001

Lt = 0
ca/ct = 1
La = LU = 0.00E+00
A
s
LOSS DUE TO DAMAGE D2 s
LB = LV = rp x rf x LF x (ca + cb + cc + cs)/ct rp = u
m
e 0.5
d
rf = 0.01
LF = 0.1
(ca + cb + cc + cs)/ct = 1
LB = LV = 5.00E-04
A
s
LOSS DUE TO DAMAGE D3 s
u
LC = LM = LW = LZ = LO x cs/ct m
e
d
LO = 0.0001
c /c = 1 Assumed
s t
L =L =L =L = 1.00E-04
C M W Z
0

0.00E+00

0.5

0.01
0
0
100000
0.00E+00

0.001

0.00E+00

0.5

0.01
0.1

5.00E-04

0.0001
Type of Building Residential
COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING

LOSS OF HUMAN LIFE (L1)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x nz/nt x tz/8760

rt = 0.01

LT = 0.01
nz = 240
nt = 240
tz = 2920

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x hz x LF x nz/nt x tz/8760 rp =
0.5

rf = 0.01
hz = 1
LF = 0.01

LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt x tz/8760

LO = 1

LC= LM = LW = LZ = 3.33E-01

UNACCEPTABLE LOSS OF SERVICE TO THE PUBLIC (L2)

LOSS DUE TO DAMAGE D2

LB =LV = rp x rf x LF x nz/nt

rp = 0.5

rf = 0.01
LF = 0
nz = 240
nt = 240
LB = LV = 0.00E+00
LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt

LO = 0

LC = LM = LW = LZ = 0.00E+00

LOSS OF IRREPLACEABLE CULTURAL HERITAGE (L3)

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x LF x cz/ct rp =
0.5

rf = 0.01
Lf = 0
cz = 0
ct = 100000
LB = LV = 0.00E+00

ECONOIC LOSS (L4)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x ca/ct

rt = 0.01

Lt = 0
ca/ct = 1
La = LU = 0.00E+00
A
s
LOSS DUE TO DAMAGE D2 s
LB = LV = rp x rf x LF x (ca + cb + cc + cs)/ct rp = u
m
e 0.5
d
rf = 0.01
LF = 0.1
(ca + cb + cc + cs)/ct = 1
LB = LV = 5.00E-04
A
s
LOSS DUE TO DAMAGE D3 s
u
LC = LM = LW = LZ = LO x cs/ct m
e
d
LO = 0.0001
c /c = 1 Assumed
s t
L =L =L =L = 1.00E-04
C M W Z
0

0.00E+00

0.5

0.01
0
0
100000
0.00E+00

0.01

0.00E+00

0.5

0.01
0.1

5.00E-04

0.0001
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RA = ND x PA x LA
ND = 0.079193787
PA = 1
LA = 0.00001

RB = ND x PB x LB

ND = 0.079193787
PB = 1
LB = 0.00005

R =N xP xL
C/P D C/P C

ND = 0.079193787
P =
C/P 1
LC = 1
R =
C/P 7.92E-02

R
C/T = ND x PC/T x LC

ND = 0.079193787
P
C/T
=
1
LC = 1
R =
C/T 7.92E-02

RC = 1.58E-01

R =N xP xL
M/P M M/P M

NM = 3.3707
P =
M/P 0
LM = 1
R =
M/P 0.00E+00

R =N xP xL
M/T M M/T M

NM = 3.3707
P =
M/T 0
LM = 1
R
M/T =
0.00E+00
RISK COMPONENETS RELATED TO ZONE 1 (BASEMENT)
RM = ###

R = (N +N )xP xL
U/P L/P DJ/P U/P U

N
L.P
=
###
N =
DJ.P

P
U.P =

LU =

R = (N +N )xP xL
U/T L/T DJ/T U/T U

N =
L/T
N =
DJ/T

P =
U/T

LU =

RU = 1.90E-06
R = (N +N )xP xL
V/P L/P DJ/P V/P V
P =
V/P ###

LV = ###

R = (N +N )xP xL P =
V/T L/T DJ/T V/T V V/T

###

LV = ###

RV = 9.48E-06
R = (N +N )xP xL
W/P L/P DJ/P W/P W
P =
W/P 1

LW = 1
R
W/P
=
3.16E-02
R = (N +N )xP xL P =
W/T L/T DJ/T W/T W W/T

LW = 1
R
W/T
=
1.58E-01

RW = 1.90E-01

R
Z/P = NI/P x PZ x LZ

N =
I/P 0.0148
P =
Z/P 0.1
LZ = 1
R
Z/P =
1.48E-03
R =N xP xL N =
Z/T I/T Z/T Z I/T

0.074

P =
Z/T 0.2
LZ = 1
R =
Z/T 1.48E-02

RZ = 1.63E-02

RISK OF HUMAN LIFE (R1)

R1 = RA + RB + RU + RV

In case of Hospitals/structures with risk of explosion


R1 = RA + RB + RC + RM + RU + RV + RW +RZ

R = 3.64E-01
1

RISK OF LOSS OF SERVICE TO THE PUBLIC (R2)


R2 = RB + RC + RM + RV + RW + RZ
R = 1.12E-01
2

RISK OF LOSS OF CULTURAL HERITAGE (R3)


R3 = RB + RV
R = 5.54E-06
3

RISK OF LOSS OF ECONOMIC VALUE (R4)


R4 = RB + RC + RM + RV + RW + RZ
R = 1.11E-01
4

In case where animals my be lost,


R4 = RA + RB + RC + RM + RU + RV + RW +RZ
R = 1.61E-05
4
TO ZONE 1 (BASEMENT)

0.031465777
1
0.00001

0.00074
0.157328884
1
0.00001
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RA = ND x PA x LA
ND = 0.079193787
PA = 1
LA = 3.33333E-05

RB = ND x PB x LB

ND = 0.079193787
PB = 1
LB = 1.66667E-05

R =N xP xL
C/P D C/P C

ND = 0.079193787
P =
C/P 1
LC = 0.333333333
R =
C/P 2.64E-02

R
C/T = ND x PC/T x LC

ND = 0.079193787
P
C/T
=
1
LC = 0.333333333
R =
C/T 2.64E-02

RC = 5.28E-02

R =N xP xL
M/P M M/P M

NM = 3.3707
P =
M/P 0
LM = 0.333333333
R =
M/P 0.00E+00

R =N xP xL
M/T M M/T M

NM = 3.3707
P =
M/T 0
LM = 0.333333333
R
M/T =
0.00E+00
RISK COMPONENTS FOR ZONE 2 (ALL FLOORS EXCEPT BASEMENT)
R = 0.00E+00
M
R = (N +N )xP xL
U/P L/P DJ/P U/P U
N = 0.000148
L.P
N = 0.031465777
DJ.P
P =
U.P
1
L = 3.33333E-05
U

R = 1.05E-06
U/P

R
U/T = (NL/T+NDJ/T) x PU/T x LU
N
L/T
=
0.00074
N =
DJ/T 0.157328884
P
U/T =
1
LU = 3.33333E-05

RU = 6.32E-06

R = (N +N )xP xL
V/P L/P DJ/P V/P V
P =
V/P
1
L = 1.66667E-05
V

R = 5.27E-07
V/P

R = (N +N )xP xL
V/T L/T DJ/T V/T V
P =
V/T
1
L = 1.66667E-05
V

R = 2.63E-06
V/T

RV = 3.16E-06

R = (N +N )xP xL
W/P L/P DJ/P W/P W
P =
W/P 1

LW = 0.333333333
R =
W/P 1.05E-02
R = (N +N )xP xL P =
W/T L/T DJ/T W/T W W/T

LW = 0.333333333
R =
W/T 5.27E-02

RW = 6.32E-02

R =N xP xL
Z/P I/P Z Z

N =
I/P 0.0148
P
Z/P =
0.1
LZ = 0.333333333
R =
Z/P 4.93E-04

R =N xP xL
Z/T I/T Z/T Z

N =
I/T 0.074
P =
Z/T 0.2
LZ = 0.333333333
R =
Z/T 4.93E-03

RZ = 5.43E-03

RISK OF HUMAN LIFE (R1)

R1 = RA + RB + RU + RV

R1 = 1.34E-05

In case of Hospitals/structures with risk of explosion

R1 = RA + RB + RC + RM + RU + RV + RW +RZ
R1 = 1.21E-01

RISK OF LOSS OF SERVICE TO THE PUBLIC (R2)

R2 = RB + RC + RM + RV + RW + RZ

R2 = 3.74E-02

RISK OF LOSS OF CULTURAL HERITAGE (R3)

R3 = RB + RV

R3 = 1.85E-06

RISK OF LOSS OF ECONOMIC VALUE (R4)

R4 = RB + RC + RM + RV + RW + RZ

R4 = 3.69E-02

In case where animals my be lost,


R4 = RA + RB + RC + RM + RU + RV + RW +RZ

R4 = 1.34E-05
LL FLOORS EXCEPT BASEMENT)
RISK COMPONENTS
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR CHECKED BY: NAGENDRA CS

Type of Building Residential


Possibility of Damage to Structure

PA 1.00E+00
PB 1.00E+00
P
C/P 1.00E+00
P
C/T 1.00E+00
P
M/P 0.00E+00
P
M/T 0.00E+00
P
U/P 1.00E+00
P
U/T 1.00E+00
P
V/P 1.00E+00
P
V/T 1.00E+00
P
W/P 1.00E+00
P
W/T 1.00E+00
P
Z/P 1.00E-01
P
Z/T 2.00E-01
Number of Dangerous events per year

ND 7.92E-02
N
DJ/P 3.15E-02
N
DJ/T 1.57E-01
NM 3.37E+00
N
L/P 1.48E-04
N
L/T 7.40E-04
N
I/P 1.48E-02
N
I/T 7.40E-02

Loss of Human Life (L1)


ZONE 1 ZONE 2
LA = LU 1.00E-05 3.33E-05
LB = LV 5.00E-05 1.67E-05
LC= LM = LW = LZ 1.00E+00 3.33E-01
Risk Components
ZONE 1 ZONE 2 STRUCTURE ZONE 1 ZONE 2 STRUCTURE
RA 7.92E-07 2.64E-06 3.43E-06 RU 1.90E-06 6.32E-06 8.22E-06
R
RB 3.96E-06 1.32E-06 5.28E-06 V/P 1.58E-06 5.27E-07 2.11E-06
R R
C/P 7.92E-02 2.64E-02 1.06E-01 V/T 7.90E-06 2.63E-06 1.05E-05
R
C/T 7.92E-02 2.64E-02 1.06E-01 RV 9.48E-06 3.16E-06 1.26E-05

RC 1.58E-01 5.28E-02 2.11E-01 R


W/P 3.16E-02 1.05E-02 4.22E-02
R
M/P 0.00E+00 0.00E+00 0.00E+00 R
W/T 1.58E-01 5.27E-02 2.11E-01
R
M/T 0.00E+00 0.00E+00 0.00E+00 RW 1.90E-01 6.32E-02 2.53E-01
R
RM 0.00E+00 0.00E+00 0.00E+00 Z/P 1.48E-03 4.93E-04 1.97E-03
R R
U/P 3.16E-07 1.05E-06 1.37E-06 Z/T 1.48E-02 4.93E-03 1.97E-02

R
U/T 1.58E-06 5.27E-06 6.85E-06 RZ 1.63E-02 5.43E-03 2.17E-02

Unacceptable Loss os Service to the Public (L2)

ZONE 1 ZONE 2
LB = LV 0.00E+00 0.00E+00
LC = LM = LW = LZ 0.00E+00 0.00E+00
Loss of Irreplaceable Cultural Heritage (L3)

ZONE 1 ZONE 2
LB = LV 0.00E+00 0.00E+00
Economic Loss (L4)
ZONE 1 ZONE 2
LA = LU 0.00E+00 0.00E+00
LB = LV 5.00E-04 5.00E-04
LC = LM = LW = LZ 1.00E-04 1.00E-04
Total Risk
ZONE 1 ZONE 2 STRUCTURE ZONE 1 ZONE 2 STRUCTURE
R1 1.61E-05 1.34E-05 2.96E-05 R3 5.54E-06 1.85E-06 7.39E-06
R2 1.12E-01 3.74E-02 1.50E-01 R4 1.11E-01 3.69E-02 1.48E-01
O

T
H
E

T
Y
P
E

O
F

B
U
I
L
D
I
N
G
RISK ANALYSIS RESULTS
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR
CHECKED BY: NAGENDRA CS

Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RISK TYPE CALCULATED RISK ACCEPTABLE RISK

RISK OF HUMAN LIFE (R1) 2.96E-05 1.00E-05


RISK OF LOSS OF SERVICE TO THE PUBLIC (R2) 1.50E-01 1.00E-03
RISK OF LOSS OF CULTURAL HERITAGE (R3) 7.39E-06 1.00E-04
RISK OF LOSS OF ECONOMIC VALUE (R4) 1.48E-01 1.00E-03
LIGHTNING
PROTECTION

RISK ANALYSIS WITH LPS RISK


ANALYSIS
LYSIS

NEED OF PROTECTION

YES
YES
NO
YES
LIGHTNING
PROTECTION

H LPS RISK
ANALYSIS
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR NAGENDRA CS
CHECKED BY: COLOR INDICATES FACTORS RELEVANT TO THE BUILDING & TO BE ENTERED

Type of Building Commercial

SR.NO. INPUT DESCRIPTION BRIEF UNIT

BASIC STRUCTURE DIMENSIONS

1 L Length of the building m


2 W Width of the building m
3 H Height of the building m
4 HP Height of Prtorusion Height of elevated roof, lift m
machine room, etc.

ADJACENT STRUCTURE DIMENSIONS

L
5 DJ Length of the adjacent building
W
6 DJ Width of the adjacent building
7 H
DJ Height of the adjacent building

STRUCTURE ATTRIBUTES

8 w
m1 Mesh widhts of grid like spatial shield Refer IEC 62305-2 Pg. No. 36 m
w
9 m2 Mesh widhts of grid like spatial shield m
K
10 S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Power Line) shielded/ unshielded cable?

11 K
S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Telecommunication Line) shielded/ unshielded cable?

ENVIRONMENTAL INFLUENCES

12 NG Lightning ground flash density Ng of the area where the 1/sq.km x year
structure is located
13 CD Location factor of the structure Surrounding structures / an
exposed location

14 C
DJ Loaction factor of the adjacent structure Surrounding structures / an
exposed location

15 CE Environmental factor Is environement rural, urban,


etc.

SERVICE LINES

POWER LINES

16 CT Line type factor Type of power line in the area

17 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and isolation Is the power/LV line buried,shielded,
18 C
LD
conditions of the line to which the internal etc.?
system is connected
19 UW Ratedd impulse withstand voltage of the system to KV
be protected

20 C
LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?
21 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the Line characteristics in terms of


22 P
LD
cable screen and the impulse withstand voltage of the bonding
equipment

TELECOMMUNICATION LINES

23 CT Line type factor Type of power line in the area

24 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and Is the power/LV line buried,shielded,
25 C
LD
isolation conditions of the line to which the internal system is etc.?
connected
26 UW Ratedd impulse withstand voltage of the system to KV
be protected

27 C
LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?

28 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the cable Line characteristics in terms of
29 P
LD
screen and the impulse withstand voltage of bonding
the equipment

PROTECTION MEASURES

Probability that a flash to a structure will cause shock Type of additional protection
30 P
TA
to living beings due to dangerous touch and step voltages measures provided

31 PB Probability that a flash will cause physical damage Level of Lightning Protection

P
32 SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Power line) coordinated & Level of LPS?
33 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is
(Power line) provided for the structure?
P
34 SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Telecommunication line) coordinated & Level of LPS?

35 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is


(Telecommunication line) provided for the structure?

34 rt Factor reducing the loss of human life depending on Type of surface


the type of soil or floor

Factor reducing the loss due to physical damage depending


35 rp on the provisions taken to reduce the Provisions in case of fire
consequences of fire
P
36 EB Probability value as a function of LPL for which SPDs Equipotential bonding & LPL
are designed

Probability value depending on theline type and the impulse Line and equipment charateristics
37 P
LI
withstand voltage of the equipment (Power
line)
Probability value depending on theline type and the Line and equipment charateristics
38 P
LI
impulse withstand voltage of the equipment
(Telecommunication line)
VALUE

86
40
42
4.5

86
40
42

0.2

0.2

3.7

0.25

0.5

0.01

0.2

0.5

1
1

0.5

0.2

Not Provided

Not Provided

0.001

0.5

0.05

0.1

0.2
SR.NO. INPUT DESCRIPTION BRIEF UNIT

LOSS OF HUMAN LIFE (L1)

Typical mean relative numbers of victims injured by electric Type of structure, industrial, hotel,
39 LT shock due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by physical Type of structure, industrial, hotel,
40 LF damage due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by Type of structure, industrial, hotel,
41 LO failure of internal systems due to one dangerous event public, etc.

Factor reducing the loss due to physical damage depending


42 rf on the risk of fire or on the risk of Risk of explosion of structure
explosion of structure
43 hz Factor increasing the loss due to physical damage Level of panic
when a special hazard is present

44 nz Number of persons in the zone


45 nt Total number of persons in the structure
46 tz Time in hours per year for which the persons are
present in the zone

UNACCEPTABLE LOSS OF SERVICE (L2)

Typical mean relative number of users not served, Type of service, gas, water supply,
47 LF resulting from physical damage due to one dangerous event etc.

Typical mean relative numbers of users not served resulting Type of service, gas, water supply,
48 LO from failure of internal systems due to one etc.
dangerous event

LOSS OF CULTURAL HERITAGE (L3)

Typical mean relative value of all goods damaged by physical Type of structure, museum, galleries,
49 LF damage due to one dangerous event etc.

50 cz Value of cultural heritage in the zone


51 ct Total value of building and content of the structure

LOSS OF ECONOMIC VALUE (L4)

Typical mean relative value of all goods damaged by electric Type of structure, industrial, hotel,
52 LT shock due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by physical Type of structure, industrial, hotel,
53 LF damage due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by failure of Type of structure, industrial, hotel,
54 LO internal systems due to one dangerous public, etc.
event
55 ca Valus of animals in the zone
56 cb Value of building relevant to the zone
57 cc Value of content in the zone
58 cs Value of internal systems including their activities in
the zone
VALUE

0.01

0.01

0.01

240
240
8760

0
100000

0.1

0.0001

0
10000
0
0
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR NAGENDRA CS
CHECKED BY: COLOR INDICATES FACTORS RELEVANT TO THE BUILDING & TO BE ENTERED

Type of Building Residential

SR.NO. INPUT DESCRIPTION BRIEF UNIT

BASIC STRUCTURE DIMENSIONS

1 L Length of the building m


2 W Width of the building m
3 H Height of the building m
4 HP Height of Prtorusion Height of elevated roof, lift m
machine room, etc.

ADJACENT STRUCTURE DIMENSIONS

L
5 DJ Length of the adjacent building
W
6 DJ Width of the adjacent building
7 H
DJ Height of the adjacent building

STRUCTURE ATTRIBUTES

8 w
m1 Mesh widhts of grid like spatial shield Refer IEC 62305-2 Pg. No. 36 m
w
9 m2 Mesh widhts of grid like spatial shield m
K
10 S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Power Line) shielded/ unshielded cable?

11 K
S3 Factor takes into account the charcteristics of Is internal wiring done with
internal wiring (Telecommunication Line) shielded/ unshielded cable?

ENVIRONMENTAL INFLUENCES

12 NG Lightning ground flash density Ng of the area where the 1/sq.km x year
structure is located
13 CD Location factor of the structure Surrounding structures / an
exposed location

14 C
DJ Loaction factor of the adjacent structure Surrounding structures / an
exposed location

15 CE Environmental factor Is environement rural, urban,


etc.

SERVICE LINES

POWER LINES

16 CT Line type factor Type of power line in the area

17 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and Is the power/LV line buried,shielded,
18 C
LD
isolation conditions of the line to which the internal system is etc.?
connected
19 UW Ratedd impulse withstand voltage of the system to KV
be protected

20 C
LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?
21 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the Line characteristics in terms of


22 P
LD
cable screen and the impulse withstand voltage of the bonding
equipment

TELECOMMUNICATION LINES

23 CT Line type factor Type of power line in the area

24 CI Installation factor of the line Is line aeiral/buried?


Factor depending on shielding, grounding and Is the power/LV line buried,shielded,
25 C
LD
isolation conditions of the line to which the internal system is etc.?
connected
26 UW Ratedd impulse withstand voltage of the system to KV
be protected
C
27 LI Factor depending on shielding, grounding and Is the power/LV line
isolation conditions of the line buried,shielded, etc.?
28 Probability that a flash to an entering line will cause shock to Protection measures against step
living beings due to dangerous touch volatages voltages, such as notices, physical
P
TU restrictions,etc.

Probability value depending on the resistance of the cable Line characteristics in terms of
29 P
LD
screen and the impulse withstand voltage of bonding
the equipment

PROTECTION MEASURES

Probability that a flash to a structure will cause shock Type of additional protection
30 P
TA
to living beings due to dangerous touch and step voltages measures provided

31 PB Probability that a flash will cause physical damage Level of Lightning Protection

32 P
SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Power line) coordinated & Level of LPS?

33 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is


(Power line) provided for the structure?

34 P
SPD Probability value as a function of LPL for which SPDs Is Surge Protection Design
are designed (Telecommunication line) coordinated & Level of LPS?

35 Coordinated SPD system according to IEC 62305-4 Is coordinated SPD system is


(Telecommunication line) provided for the structure?

34 rt Factor reducing the loss of human life depending on Type of surface


the type of soil or floor
Factor reducing the loss due to physical damage depending
35 rp on the provisions taken to reduce the Provisions in case of fire
consequences of fire
36 P
EB Probability value as a function of LPL for which SPDs Equipotential bonding & LPL
are designed

Probability value depending on theline type and the impulse Line and equipment charateristics
37 P
LI
withstand voltage of the equipment (Power
line)
Probability value depending on theline type and the Line and equipment charateristics
38 P
LI
impulse withstand voltage of the equipment
(Telecommunication line)

LOSS OF HUMAN LIFE (L1)


Typical mean relative numbers of victims injured by electric Type of structure, industrial, hotel,
39 LT shock due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by physical Type of structure, industrial, hotel,
40 LF damage due to one dangerous event public, etc.

Typical mean relative numbers of victims injured by failure of Type of structure, industrial, hotel,
41 LO internal systems due to one dangerous public, etc.
event

Factor reducing the loss due to physical damage


42 rf depending on the risk of fire or on the risk of explosion of Risk of explosion of structure
structure
43 hz Factor increasing the loss due to physical damage Level of panic
when a special hazard is present
44 nz Number of persons in the zone
45 nt Total number of persons in the structure
46 tz Time in hours per year for which the persons are
present in the zone

UNACCEPTABLE LOSS OF SERVICE (L2)

Typical mean relative number of users not served, resulting Type of service, gas, water supply,
47 LF from physical damage due to one etc.
dangerous event
Typical mean relative numbers of users not served Type of service, gas, water supply,
48 LO resulting from failure of internal systems due to one etc.
dangerous event

LOSS OF CULTURAL HERITAGE (L3)

Typical mean relative value of all goods damaged by physical Type of structure, museum, galleries,
49 LF damage due to one dangerous event etc.

50 cz Value of cultural heritage in the zone


51 ct Total value of building and content of the structure

LOSS OF ECONOMIC VALUE (L4)

Typical mean relative value of all goods damaged by electric Type of structure, industrial, hotel,
52 LT shock due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by physical Type of structure, industrial, hotel,
53 LF damage due to one dangerous event public, etc.

Typical mean relative value of all goods damaged by Type of structure, industrial, hotel,
54 LO failure of internal systems due to one dangerous event public, etc.

55 ca Valus of animals in the zone


56 cb Value of building relevant to the zone
57 cc Value of content in the zone
58 cs Value of internal systems including their activities in
the zone
VALUE

86
40
42
4.5

86
40
42

0.2

0.2

3.7

0.25

0.5

0.01

0.2

0.5

1
1

0.5

0.2

Not Provided

Not Provided

0.01

0.5

0.05

0.1

0.2
0.01

0.01

0.01

240
240
2920

0
100000

0.1

0.0001

0
10000
0
0
Type of Building Residential
COLOR INDICATES FACTORS RELEVANT TO THE TYPE OF
BUILDING

Collection Area of building


A = L x W + 2 x (3xH) x (L+W) + 3.14 x (3xH)2
D
L= 86
W= 40
H= 42

Collection Area of Protrusion


A ' = 3.14 x (3xH )2
D
H = P 4.5
P
A '= 572.265
D

Total Collection Area = 8.56E+04


Number of dangerous events ND for the structure

N = N x A x C x 10-6
D =
N G D D 3.7
G
A = 85614.905
D
C = 0.25
D

ND = 7.92E-02

Number of dangerous events NDJ for an adjacent structure


(Power Line)
N
DJ
/P= N
G
x DJ/P
A x DJC xTC x 10-6
L= 86
W= 40
H= 42
A =
DJ/P 85042.64
CDJ = 0.5
CT = 0.2

Number of dangerous events NDJ for an adjacent structure


(Telecommunication Line)
-6
N =N xA xC x C x 10
DJ/T G DJ/T DJ T
L= 86
W= 40
H= 42

NUMBER OF DANGEROUS EVENTS COMPONENTS


86
40
42

US EVENTS COMPONENTS
A =
DJ/T 85042.64
C
DJ =
0.5
CT = 1

Average annual number of dangerous events NM


due to flashes near structure
N = N x A x 10-6
M = 2G x 500
A M x (L+W) + 3.14 x 500 x 500
M
L= 86
W= 40
A = 911000
M

N = 3.37E+00
M

Average annual number of dangerous events NL


due to flashes to a line (Power)
N
L/P
=NG
A x IC x EC xTC x 10-6
x L/P
A = 40 x L
L/P L/P

L =
L/P 1000 Assumed
A =
L/P 40000
NG = 3.7
CI = 0.5
CE = 0.01
CT = 0.2

Average annual number of dangerous events NL due to


flashes to a line (Telecommunication)
-6
NL/T = NG x AL/T x CI x CE x CT x 10
A = 40 x L
L/T L/T

L
L/T
=
1000 Assumed
A =
L/T 40000
NG = 3.7
CI = 0.5
CE = 0.01
CT = 1

Average annual number of dangerous events NI


due to flashes near a line (Power)
N =N xA x C x C x C x 10-6 AI/P = 4000 x LL/P
LI/P = G I/P I E T 1000 Assumed
L/P
A = 4000000
I/P

N = 1.48E-02
I/P

Average annual number of dangerous events NI due to


flashes near a line (Telecommunication)
-6
NI/T = NG x AI/T x CI x CE x CT x 10
AI/T = 4000 x LL/T
L = 1000 Assumed
L/T
A = 4000000
I/T

N = 7.40E-02
I/T
86
40

1000 Assumed
40000
3.7
0.5
0.01
0.2

1000 Assumed
40000
3.7
0.5
0.01
1
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


Probability PA that a flash to a structure will cause injury to
living beings by electric shock
PA = PTA x PB
P = 1
TA

PB = 0.2
2.00E-01
PA =

Probability PC that a flash to a structure will cause failure of


internal systems (Power Line)
P =P xC
C/P SPD LD
P =
SPD
1
C = 1
LD

P = 1.00E+00
C/P

Probability PC that a flash to a structure will cause


failure of internal systems (Telecommunication Line)

P =P xC
C/T SPD LD
P =
SPD
1
C = 1
LD

P = 1.00E+00
C/T

Probability PM that a flash near a structure will cause failure


of internal systems (Power Line)

If Cordinated SPD system is provided , PM = PMS x


P
SPD

If Cordinated SPD system is not provided , PM = PMS


Coordinated SPD system as per inputs = Not Provided P SPD
=
1
2
PMS = (KS1 x KS2 X KS3 x KS4 )

wm1 = ###
wm2 = ###
K
S1 = ###
K =
S2 ###
KS3 =
dP SPD
=
1

0.2
UW = 6
K
S4 =
0.166666667

PMS = 0

PM 1 = 0
PM 2 = 0
P =
M/P 0.00E+00

Probability PM that a flash near a structure will cause failure


of internal systems
(Telecommunication Line)
If Cordinated SPD system is provided , PM = PMS x PSPD

If Cordinated SPD system is not provided , PM = PMS

Coordinated SPD system as per inputs = Not Provided


P =
SPD 1
2
PMS = (KS1 x KS2 X KS3 x KS4 )

wm1 = 0

w =
m2 0
KS1 = 0
KS2 = 0
KS3 = 0.2
UW = 6
KS4 = 0.166666667

P =
MS 0

PM 1 = 0
PM 2 = 0
P =
M/T 0.00E+00

Probability PU that a flash to a line will cause injury to living


beings by electric shock (Power
Line)
P =P xP XP xC
U/P TU EB LD LD

PTU = 1
PEB = 0.05
PLD = 1
C =
LD 1
Probability PU that a flash to a line will cause
injury to living beings by electric shock (Telecommunication
Line)
P
U/T = PTU x PEB X PLD x CLD
P = 1
TU
P = 0.05
EB
P = 1
LD
C = 1
LD

P = 5.00E-02
U/T

Probability PV that a flash to a line will cause physical


damage (Power Line)
P =P xP xC
V/P EB LD LD
P = 5.00E-02
V/P

Probability PV that a flash to a line will cause physical


damage (Telecommunication Line)
P =P xP xC
V/T EB LD LD
P = 0.05
V/T

Probability PW that a flash to a line will cause failure of


internal systems (Power Line)
P =P xP xC
W/P SPD LD LD
P =
SPD
1
P =
W/P 1.00E+00
Probability PW that a flash to a line will cause
failure of internal systems (Telecommunication Line)

P =P xP xC
W/T SPD LD LD
P =
SPD
1
P =
W/T 1.00E+00
Probability PZ that a flash near an incoming line will cause
failure of internal systems (Power Line)
P =P xP xC
Z/P SPD LI LI

PLI = 0.1
C =
LI 1
P =
Z/P 1.00E-01

Probability PZ that a flash near an incoming line will cause


failure of internal systems
(Telecommunication Line)
P =P xP xC
Z/T SPD LI LI

PLI = 0.2
C =
LI 1
P =
Z/T 2.00E-01
Type of Building Residential
COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING

LOSS OF HUMAN LIFE (L1)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x nz/nt x tz/8760

rt = 0.001

LT = 0.01
nz = 240
nt = 240
tz = 8760

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x hz x LF x nz/nt x tz/8760 rp =
0.5

rf = 0.01
hz = 1
LF = 0.01

LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt x tz/8760

LO = 1

LC= LM = LW = LZ = 1.00E+00

UNACCEPTABLE LOSS OF SERVICE TO THE PUBLIC (L2)

LOSS DUE TO DAMAGE D2

LB =LV = rp x rf x LF x nz/nt

rp = 0.5

rf = 0.01
LF = 0
nz = 240
nt = 240
LB = LV = 0.00E+00
LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt

LO = 0

LC = LM = LW = LZ = 0.00E+00

LOSS OF IRREPLACEABLE CULTURAL HERITAGE (L3)

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x LF x cz/ct rp =
0.5

rf = 0.01
Lf = 0
cz = 0
ct = 100000
LB = LV = 0.00E+00

ECONOIC LOSS (L4)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x ca/ct

rt = 0.001

Lt = 0
ca/ct = 1
La = LU = 0.00E+00
A
s
LOSS DUE TO DAMAGE D2 s
LB = LV = rp x rf x LF x (ca + cb + cc + cs)/ct rp = u
m
e 0.5
d
rf = 0.01
LF = 0.1
(ca + cb + cc + cs)/ct = 1
LB = LV = 5.00E-04
A
s
LOSS DUE TO DAMAGE D3 s
u
LC = LM = LW = LZ = LO x cs/ct m
e
d
LO = 0.0001
c /c = 1 Assumed
s t
L =L =L =L = 1.00E-04
C M W Z
0

0.00E+00

0.5

0.01
0
0
100000
0.00E+00

0.001

0.00E+00

0.5

0.01
0.1

5.00E-04

0.0001
Type of Building Residential
COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING

LOSS OF HUMAN LIFE (L1)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x nz/nt x tz/8760

rt = 0.01

LT = 0.01
nz = 240
nt = 240
tz = 2920

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x hz x LF x nz/nt x tz/8760 rp =
0.5

rf = 0.01
hz = 1
LF = 0.01

LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt x tz/8760

LO = 1

LC= LM = LW = LZ = 3.33E-01

UNACCEPTABLE LOSS OF SERVICE TO THE PUBLIC (L2)

LOSS DUE TO DAMAGE D2

LB =LV = rp x rf x LF x nz/nt

rp = 0.5

rf = 0.01
LF = 0
nz = 240
nt = 240
LB = LV = 0.00E+00
LOSS DUE TO DAMAGE D3

LC = LM = LW = LZ = LO x nz/nt

LO = 0

LC = LM = LW = LZ = 0.00E+00

LOSS OF IRREPLACEABLE CULTURAL HERITAGE (L3)

LOSS DUE TO DAMAGE D2


LB = LV = rp x rf x LF x cz/ct rp =
0.5

rf = 0.01
Lf = 0
cz = 0
ct = 100000
LB = LV = 0.00E+00

ECONOIC LOSS (L4)

LOSS DUE TO DAMAGE D1

LA = LU = rt x LT x ca/ct

rt = 0.01

Lt = 0
ca/ct = 1
La = LU = 0.00E+00
A
s
LOSS DUE TO DAMAGE D2 s
LB = LV = rp x rf x LF x (ca + cb + cc + cs)/ct rp = u
m
e 0.5
d
rf = 0.01
LF = 0.1
(ca + cb + cc + cs)/ct = 1
LB = LV = 5.00E-04
A
s
LOSS DUE TO DAMAGE D3 s
u
LC = LM = LW = LZ = LO x cs/ct m
e
d
LO = 0.0001
c /c = 1 Assumed
s t
L =L =L =L = 1.00E-04
C M W Z
0

0.00E+00

0.5

0.01
0
0
100000
0.00E+00

0.01

0.00E+00

0.5

0.01
0.1

5.00E-04

0.0001
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RA = ND x PA x LA
ND = 0.079193787
PA = 0.2
LA = 0.00001

RB = ND x PB x LB

ND = 0.079193787
PB = 0.2
LB = 0.00005

R =N xP xL
C/P D C/P C

ND = 0.079193787
P =
C/P 1
LC = 1
R =
C/P 7.92E-02

R
C/T = ND x PC/T x LC

ND = 0.079193787
P
C/T
=
1
LC = 1
R =
C/T 7.92E-02

RC = 1.58E-01

R =N xP xL
M/P M M/P M

NM = 3.3707
P =
M/P 0
LM = 1
R =
M/P 0.00E+00

R =N xP xL
M/T M M/T M

NM = 3.3707
P =
M/T 0
LM = 1
R
M/T =
0.00E+00
RISK COMPONENETS RELATED TO ZONE 1 (BASEMENT)
RM = ###

R = (N +N )xP xL
U/P L/P DJ/P U/P U

N
L.P
=
###
N =
DJ.P

P
U.P =

LU =

R = (N +N )xP xL
U/T L/T DJ/T U/T U

N =
L/T
N =
DJ/T

P =
U/T

LU =

RU = 9.48E-08
R = (N +N )xP xL
V/P L/P DJ/P V/P V
P =
V/P ###

LV = ###

R = (N +N )xP xL P =
V/T L/T DJ/T V/T V V/T

###

LV = ###

RV = 4.74E-07
R = (N +N )xP xL
W/P L/P DJ/P W/P W
P =
W/P 1

LW = 1
R
W/P
=
3.16E-02
R = (N +N )xP xL P =
W/T L/T DJ/T W/T W W/T

LW = 1
R
W/T
=
1.58E-01

RW = 1.90E-01

R
Z/P = NI/P x PZ x LZ
N =
I/P 0.0148
P
Z/P =
0.1
LZ = 1
R =
Z/P 1.48E-03
R =N xP xL N =
Z/T I/T Z/T Z I/T

0.074

P =
Z/T 0.2
LZ = 1
R
Z/T
=
1.48E-02

RZ = 1.63E-02

RISK OF HUMAN LIFE (R1)

R1 = RA + RB + RU + RV

In case of Hospitals/structures with risk of explosion


R1 = RA + RB + RC + RM + RU + RV + RW +RZ

R = 3.64E-01
1

RISK OF LOSS OF SERVICE TO THE PUBLIC (R2)


R2 = RB + RC + RM + RV + RW + RZ
R = 1.12E-01
2

RISK OF LOSS OF CULTURAL HERITAGE (R3)


R3 = RB + RV
R = 8.71E-07
3

RISK OF LOSS OF ECONOMIC VALUE (R4)


R4 = RB + RC + RM + RV + RW + RZ
R = 1.11E-01
4

In case where animals my be lost,


R4 = RA + RB + RC + RM + RU + RV + RW +RZ
R = 1.52E-06
4
TO ZONE 1 (BASEMENT)

0.031465777
0.05
0.00001

0.00074
0.157328884
0.05
0.00001
Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RA = ND x PA x LA
ND = 0.079193787
PA = 0.2
LA = 3.33333E-05

RB = ND x PB x LB

ND = 0.079193787
PB = 0.2
LB = 1.66667E-05

R =N xP xL
C/P D C/P C

ND = 0.079193787
P =
C/P 1
LC = 0.333333333
R =
C/P 2.64E-02

R
C/T = ND x PC/T x LC

ND = 0.079193787
P
C/T
=
1
LC = 0.333333333
R =
C/T 2.64E-02

RC = 5.28E-02

R =N xP xL
M/P M M/P M

NM = 3.3707
P =
M/P 0
LM = 0.333333333
R =
M/P 0.00E+00

R =N xP xL
M/T M M/T M

NM = 3.3707
P =
M/T 0
LM = 0.333333333
R
M/T =
0.00E+00
RISK COMPONENTS FOR ZONE 2 (ALL FLOORS EXCEPT BASEMENT)
RM = 0.00E+00
R = (N +N )xP xL N =
U/P L/P DJ/P U/P U L.P

0.000148

N =
DJ.P 0.031465777
P =
U.P 0.05
LU = 3.33333E-05

R = (N +N )xP xL N =
U/T L/T DJ/T U/T U L/T

0.00074

N
DJ/T
=
0.157328884
P =
U/T 0.05
LU = 3.33333E-05

R = (N +N )xP xL P =
V/P L/P DJ/P V/P V V/P

0.05

LV = 1.66667E-05

R = (N +N )xP xL P =
V/T L/T DJ/T V/T V V/T

0.05

LV = 1.66667E-05

R = (N +N )xP xL P =
W/P L/P DJ/P W/P W W/P

LW = 0.333333333
R =
W/P 1.05E-02
R = (N +N )xP xL P =
W/T L/T DJ/T W/T W W/T

LW = 0.333333333
R =
W/T 5.27E-02

RW = 6.32E-02
R =N xP xL
Z/P I/P Z Z
ALL FLOORS EXCEPT BASEMENT)
N =
I/P 0.0148
P
Z/P =
0.1
LZ = 0.333333333
R =
Z/P 4.93E-04

R =N xP xL
Z/T I/T Z/T Z

N =
I/T 0.074
P =
Z/T 0.2
LZ = 0.333333333
R =
Z/T 4.93E-03

RZ = 5.43E-03

RISK OF HUMAN LIFE (R1)

R1 = RA + RB + RU + RV

R1 = 1.27E-06

In case of Hospitals/structures with risk of explosion

R1 = RA + RB + RC + RM + RU + RV + RW +RZ
R1 = 1.21E-01

RISK OF LOSS OF SERVICE TO THE PUBLIC (R2)

R2 = RB + RC + RM + RV + RW + RZ

R2 = 3.74E-02

RISK OF LOSS OF CULTURAL HERITAGE (R3)

R3 = RB + RV

R3 = 2.90E-07

RISK OF LOSS OF ECONOMIC VALUE (R4)

R4 = RB + RC + RM + RV + RW + RZ

R4 = 3.69E-02

In case where animals my be lost,


R4 = RA + RB + RC + RM + RU + RV + RW +RZ

R4 = 1.27E-06
RISK COMPONENTS
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR CHECKED BY: NAGENDRA CS

Type of Building Residential


Possibility of Damage to Structure

PA 2.00E-01
PB 2.00E-01
P
C/P 1.00E+00
P
C/T 1.00E+00
P
M/P 0.00E+00
P
M/T 0.00E+00
P
U/P 5.00E-02
P
U/T 5.00E-02
P
V/P 5.00E-02
P
V/T 5.00E-02
P
W/P 1.00E+00
P
W/T 1.00E+00
P
Z/P 1.00E-01
P
Z/T 2.00E-01
Number of Dangerous events per year

ND 7.92E-02
N
DJ/P 3.15E-02
N
DJ/T 1.57E-01
NM 3.37E+00
N
L/P 1.48E-04
N
L/T 7.40E-04
N
I/P 1.48E-02
N
I/T 7.40E-02

Loss of Human Life (L1)


ZONE 1 ZONE 2
LA = LU 1.00E-05 3.33E-05
LB = LV 5.00E-05 1.67E-05
LC= LM = LW = LZ 1.00E+00 3.33E-01
Risk Components
ZONE 1 ZONE 2 STRUCTURE ZONE 1 ZONE 2 STRUCTURE
RA 1.58E-07 5.28E-07 6.86E-07 RU 9.48E-08 3.16E-07 4.11E-07
R
RB 7.92E-07 2.64E-07 1.06E-06 V/P 7.90E-08 2.63E-08 1.05E-07
R R
C/P 7.92E-02 2.64E-02 1.06E-01 V/T 3.95E-07 1.32E-07 5.27E-07
R
C/T 7.92E-02 2.64E-02 1.06E-01 RV 4.74E-07 1.58E-07 6.32E-07

RC 1.58E-01 5.28E-02 2.11E-01 R


W/P 3.16E-02 1.05E-02 4.22E-02
R
M/P 0.00E+00 0.00E+00 0.00E+00 R
W/T 1.58E-01 5.27E-02 2.11E-01
R
M/T 0.00E+00 0.00E+00 0.00E+00 RW 1.90E-01 6.32E-02 2.53E-01
R
RM 0.00E+00 0.00E+00 0.00E+00 Z/P 1.48E-03 4.93E-04 1.97E-03
R R
U/P 1.58E-08 5.27E-08 6.85E-08 Z/T 1.48E-02 4.93E-03 1.97E-02

R
U/T 7.90E-08 2.63E-07 3.42E-07 RZ 1.63E-02 5.43E-03 2.17E-02

Unacceptable Loss os Service to the Public (L2)

ZONE 1 ZONE 2
LB = LV 0.00E+00 0.00E+00
LC = LM = LW = LZ 0.00E+00 0.00E+00
Loss of Irreplaceable Cultural Heritage (L3)

ZONE 1 ZONE 2
LB = LV 0.00E+00 0.00E+00
Economic Loss (L4)
ZONE 1 ZONE 2
LA = LU 0.00E+00 0.00E+00
LB = LV 5.00E-04 5.00E-04
LC = LM = LW = LZ 1.00E-04 1.00E-04
Total Risk
ZONE 1 ZONE 2 STRUCTURE ZONE 1 ZONE 2 STRUCTURE
R1 1.52E-06 1.27E-06 2.79E-06 R3 8.71E-07 2.90E-07 1.16E-06
R2 1.12E-01 3.74E-02 1.50E-01 R4 1.11E-01 3.69E-02 1.48E-01
O

T
H
E

T
Y
P
E

O
F

B
U
I
L
D
I
N
G
RISK ANALYSIS RESULTS
DESCRIPTION: LIGHTNING RISK ANALYSIS
PREPARED BY: DISHANT KUMAR
CHECKED BY: NAGENDRA CS

Type of Building Residential

COLOR INDICATES RISKS RELEVANT TO THE TYPE OF BUILDING


RISK TYPE CALCULATED RISK ACCEPTABLE RISK

RISK OF HUMAN LIFE (R1) 2.79E-06 1.00E-05


RISK OF LOSS OF SERVICE TO THE PUBLIC (R2) 1.50E-01 1.00E-03
RISK OF LOSS OF CULTURAL HERITAGE (R3) 1.16E-06 1.00E-04
RISK OF LOSS OF ECONOMIC VALUE (R4) 1.48E-01 1.00E-03
LYSIS

NEED OF PROTECTION

NO
YES
NO
YES