NIM : 1941420083
KELAS : 3D/D4 TKI
MODUL : BASIC PROCESS CONTROL UNIT - LEVEL CONTROL
TANGGAL : 28-Sep-21
TIPS : 1 SAVE AS PEKERJAAN ANDA SEJAK AWAL UNTUK MENGHINDARI HILANGNYA FIL
2 SERING TEKAN CTRL+S UNTUK MENGHINDARI HILANGNYA FILE SAAT PENGERJA
3 DILARANG MENGHAPUS ATAU MENAMBAH CELL
DATA PENGAMATAN
Solenoid Solenoid
Sample Elapsed Level Flowrate
1 2
Number Time
L1 F1
[On/Off] [On/Off]
[mm] [ml/min]
Solenoid
Set Controller
3
Point Output
[On/Off]
[mm] [%]
DATA PENGAMATAN
Sample Elapsed Level Flowrate Level Differential
Number Time Switch Level
L1 F1 Switch
[mm] [ml/min]
DATA PENGAMATAN
Sample Elapsed Level Flowrate Level Differential
Number Time Switch Level
L1 F1 Switch
[mm] [ml/min]
1 12:00:00 AM -17.87109375 0 1 1
2 12:00:10 AM -13.33007813 243.896484375 1 1
3 12:00:20 AM -8.935546875 239.501953125 1 1
4 12:00:30 AM -4.541015625 249.0234375 1 1
5 12:00:40 AM -0.439453125 253.41796875 1 1
6 12:00:50 AM 3.80859375 252.685546875 1 1
7 12:01:00 AM 7.91015625 247.55859375 1 1
8 12:01:10 AM 12.01171875 246.09375 1 1
9 12:01:20 AM 16.11328125 257.8125 1 1
10 12:01:30 AM 20.361328125 252.685546875 1 1
11 12:01:40 AM 24.462890625 249.755859375 1 1
12 12:01:50 AM 28.564453125 255.615234375 1 1
13 12:02:00 AM 32.958984375 256.34765625 1 1
14 12:02:10 AM 36.9140625 252.685546875 1 1
15 12:02:20 AM 41.015625 253.41796875 1 1
16 12:02:30 AM 45.1171875 251.953125 1 1
17 12:02:40 AM 49.365234375 254.8828125 1 1
18 12:02:50 AM 53.466796875 247.55859375 1 1
19 12:03:00 AM 56.103515625 0.732421875 1 1
20 12:03:10 AM 52.880859375 0 1 1
21 12:03:20 AM 48.92578125 0.732421875 1 1
22 12:03:30 AM 44.82421875 0 1 1
23 12:03:40 AM 44.091796875 248.291015625 1 1
24 12:03:50 AM 45.1171875 247.55859375 1 1
25 12:04:00 AM 46.2890625 252.685546875 1 1
26 12:04:10 AM 47.314453125 262.939453125 1 1
27 12:04:20 AM 48.193359375 263.671875 1 1
28 12:04:30 AM 49.21875 259.27734375 1 1
29 12:04:40 AM 50.09765625 258.544921875 1 1
30 12:04:50 AM 51.123046875 265.13671875 1 1
31 12:05:00 AM 52.001953125 265.13671875 1 1
32 12:05:10 AM 52.880859375 262.939453125 1 1
33 12:05:20 AM 50.830078125 262.20703125 1 1
34 12:05:30 AM 45.1171875 259.27734375 1 1
35 12:05:40 AM 39.697265625 262.20703125 1 1
36 12:05:50 AM 34.86328125 268.06640625 1 1
37 12:06:00 AM 29.8828125 255.615234375 1 1
38 12:06:10 AM 25.634765625 262.20703125 1 1
39 12:06:20 AM 21.09375 264.404296875 1 1
40 12:06:30 AM 17.28515625 259.27734375 1 1
41 12:06:40 AM 13.330078125 263.671875 1 1
42 12:06:50 AM 9.66796875 260.7421875 1 1
43 12:07:00 AM 6.298828125 264.404296875 1 1
44 12:07:10 AM 3.076171875 268.06640625 1 1
45 12:07:20 AM 0.146484375 260.009765625 1 1
46 12:07:30 AM 3.369140625 267.333984375 1 1
47 12:07:40 AM 7.763671875 259.27734375 1 1
48 12:07:50 AM 12.158203125 268.798828125 1 1
49 12:08:00 AM 16.69921875 265.13671875 1 1
50 12:08:10 AM 21.09375 265.869140625 1 1
51 12:08:20 AM 25.341796875 262.20703125 1 1
52 12:08:30 AM 29.736328125 259.27734375 1 1
53 12:08:40 AM 33.984375 258.544921875 1 1
54 12:08:50 AM 38.232421875 248.291015625 1 1
55 12:09:00 AM 42.333984375 252.685546875 1 1
56 12:09:10 AM 46.435546875 243.896484375 1 1
57 12:09:20 AM 50.390625 243.1640625 1 1
58 12:09:30 AM 54.345703125 245.361328125 1 1
59 12:09:40 AM 56.103515625 0.732421875 1 1
Solenoid Solenoid Solenoid
1 2 3
DATA PENGAMATAN
Sample Elapsed Level Flowrate PSV
Number Time Position
L1 F1
[mm] [ml/min] [%]
Off Off 50 0
Off Off 50 100
Off Off 50 100
Off Off 50 94.319661458333
Off Off 50 88.460286458333
Off Off 50 82.845052083333
Off Off 50 77.229817708333
Off Off 50 71.370442708333
Off Off 50 65.999348958333
Off Off 50 60.628255208333
Off Off 50 55.501302083333
Off Off 50 50.374348958333
Off Off 50 45.491536458333
Off Off 50 41.097005208333
Off Off 50 36.214192708333
Off Off 50 32.063802083333
Off Off 50 27.913411458333
Off Off 50 24.495442708333
Off Off 50 21.321614583333
Off Off 50 17.659505208333
Off Off 50 14.729817708333
Off Off 50 12.776692708333
Off Off 50 10.091145833333
Off Off 50 8.3821614583333
Off Off 50 6.9173177083333
Off Off 50 6.6731770833333
Off Off 50 6.1848958333333
Off Off 50 5.9407552083333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 4.9641927083333
Off Off 50 4.9641927083333
Off Off 50 4.9641927083333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 4.9641927083333
Off Off 50 4.9641927083333
Off Off 50 5.2083333333333
Off Off 50 4.9641927083333
On Off 50 5.6966145833333
On Off 50 9.8470052083333
On Off 50 12.776692708333
On Off 50 15.462239583333
On Off 50 17.903645833333
On Off 50 20.100911458333
On Off 50 22.054036458333
On Off 50 24.007161458333
On Off 50 25.716145833333
On Off 50 27.180989583333
On Off 50 28.645833333333
On Off 50 29.866536458333
On Off 50 31.331380208333
On On 50 37.923177083333
On On 50 48.177083333333
On On 50 57.454427083333
On On 50 65.999348958333
On On 50 74.300130208333
On On 50 81.868489583333
On On 50 88.704427083333
On On 50 95.052083333333
On On 50 100
On On 50 100
On On 50 100
On On 50 100
On On 50 100
On On 50 100
On On 50 100
Off Off 50 100
Off Off 50 99.690755208333
Off Off 50 93.587239583333
Off Off 50 87.972005208333
Off Off 50 82.356770833333
Off Off 50 76.497395833333
Off Off 50 71.126302083333
Off Off 50 65.755208333333
Off Off 50 60.628255208333
Off Off 50 55.501302083333
Off Off 50 50.618489583333
Off Off 50 45.979817708333
Off Off 50 41.341145833333
Off Off 50 36.946614583333
Off Off 50 32.796223958333
Off Off 50 29.134114583333
Off Off 50 25.472005208333
Off Off 50 22.542317708333
Off Off 50 19.612630208333
Off Off 50 16.682942708333
Off Off 50 13.509114583333
Off Off 50 11.067708333333
Off Off 50 9.3587239583333
Off Off 50 7.8938802083333
Off Off 50 6.6731770833333
Off Off 50 6.4290364583333
Off Off 50 6.1848958333333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
Off Off 50 4.9641927083333
Off Off 50 4.9641927083333
Off Off 50 5.2083333333333
Off Off 50 5.2083333333333
SECTION 3 - OUTFLOW
Section yang digunakan 3
DATA PENGAMATAN
Sample Elapsed Level Flowrate PSV
Number Time Position
L1 F1
[mm] [ml/min] [%]
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On Off 50 100
On On 50 100
On On 50 100
Off On 50 0
Off On 50 0
Off On 50 0
Off On 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
Off Off 50 0
On Off 50 100
SECTION 4 - OUTFLOW
Section yang digunakan 4
DATA PENGAMATAN
Sample Elapsed Level Flowrate PSV
Number Time Position
L1 F1
[mm] [ml/min] [%]
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
100 Off Off 50 100
0 Off Off 50 0
0 Off On 50 0
0 Off On 50 0
0 Off On 50 0
0 Off On 50 0
0 Off On 50 0
0 Off On 50 0
0 Off On 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
0 Off Off 50 0
100 Off Off 50 100
Gunakan sheet ini untuk membahas data pengamatan yang telah didapatkan. Anda dapat menambahkan gambar, grafik atau data penduku
pengamatan harus memenuhi beberapa point yaitu:
1. Bandingkan proses pengendalian antara penetapan set point dan float level switch serta differential level switch, analisa cara kerjanya.
2. Bandingkan efisiensi atau efektivitas SOL1 dan PSV sebagai MV.
3. Bandingkan Section 1 dan Section 2 dalam merespon adanya disturbance.
4. Bandingkan proses pengendalian antara section 3 dan section 4.
5. Bandingkan Section 3 dan Section 4 dalam merespon adanya disturbance.
6. Bandingkan proses pengendalian untuk section inflow dan outflow.
7. Bandingkan bagiaman revers dan direct acting controller dalam system pengendalian.
8. Tuliskan kelebihan dan kekurangan masing-masing pengendali dari section 1 – section 4.
Dapat kita lihat pada grafik bahwa section 1B lebih cepat merespon daripada section 1A karena adanya disturbance. Apabila ditinjau
dari analisis cara kerjanya maka jika menggunakan pengendalian dengan set point maka kita bisa mendapatkan nilai yang ingin
dicapai. Karena nilai PV akan berusaha untuk mendekati nilai dari SP.Apabila menggunakan pengendali float switch dan differential
level switch maka kita tidak bisa memasukkan nilai SPnya, sistemnya hanya menggunakan sensor untuk membaca ketinggian air
dalam vessel, air masuk SOL1 kondisi on, hingga air menyentuh sensor maka SOL1 akan off. Untuk differential level switch maka
ketinggian air mengalami penurunan terlebih dahulu dari sensor hingga menyentuh sensor yang panjang, sehingga SOL1 akan on, lalu
air masuk. Jika ketinggiannya sudah menyentuh sensor yang pendek maka SOL1 akan off, begitu terus sampai keadaan steady state
untuk kedua level switch.
section 1 yang menggunakan SOL1 dan section 2 yang menggunakan PSV. Ketika disturbance dimasukkan dan menggunakan PSV
pada section 2 maka PSV akan merespon lebih cepat karena flowrate yang digunakan dapat diatur besar kecilnya yang berfungsi untuk
mempertahankan SP agar tetsp konstan. Sedangkan pada section 1 yang menggunakan SOL1, flowrate dari valve tidak dapat
dikendalikan karena hanya memiliki intruksi untuk membuka tanpa menutup.
perbandingan antara section 1 dan section 2 yang lebih efektif adalah section 2 karena pada section 2 menggunakan mode controller
yang lebih cepat merespon apabila terjadi perubahan. Sedangkan pada section 1 membutuhkan waktu lebih lama untuk mencapai level
air dalam kondisi konstan. tetapi PSV akan merespon lebih cepat untuk mencapai level konstan ketika sistem dimasukkan
disturbance.
section 3 menggunakan SOL2 dan section 4 menggunakan peristaltik pump. Aliran input kedua section menggunakan PSV sehingga
berdasarkan data yang diperoleh maka bisa disimpulkan section 3 lebih efisien daripada section 4 karena nilai set point yang
diperoleh lebih konstan dan mendekati nilai set point yang diumpankan
5. Perbandingan Section 3 dan Section 4 dalam merespon adanya disturbance
Pada grafik section 3 respon yang dihasilkan untuk menanggapi adanya disturbance mengalami penurunan yang signifikan, kemudian
grafik meningkat sangat ekstrem. Sedangkan pada section 4 tidak terjadi penurunan yang signifikan, sehingga dapat dikatakan bahwa
pada section 4 respon yang ditunjukkan ini lebih cepat dibanding section 3. Saat penambahan disturbance SOL2 tetap berada dalam
kondisi nyala, namun ketika disturbance dihentikan (SOL 3 mati) maka SOL2 juga akan ikut mati sementara untuk kembali
meningkatkan nilai SP. Sedangkan pada section 4, ketika ditambahkan disturbance maka sistem akan mematikan PumpA dan
meningkatkan flowrate yang masuk (dengan bukaan valve PSV sebesar 100%).
an menggunakan PSV
nya yang berfungsi untuk
alve tidak dapat