Professional Documents
Culture Documents
CO MX Rel 4 5 6
CO MX Rel 4 5 6
CO MX Rel 4 5 6
Summary This manual provides detailed instructions for the commissioning of the elevator control
CO MX and covers the control releases 4.0 up to 6.2.
Page 1/57
Table of Contents
1 Safety Advice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Safety Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety Warnings Used in this Manual . . . . . . . . . . . . . . . . . . 3
2 General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 * Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 * Preparation of Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.1 Preconditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 * Car . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 * Control Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 * Inspection Travel with IMOF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Check Inspection Travel with IMOF . . . . . . . . . . . . . . . . . . . 13
5.3 * Setup of Door Interface . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 * Setup of PCBA LONIBV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 * Setup of PCBA LONDIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 * Measuring Travel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.1 * Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2 Execution of Measuring Travel . . . . . . . . . . . . . . . . . . . . . . 19
7 Car I/Os. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2 Setup of MX COP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.3 Setup of CIM (COP Interface Module) . . . . . . . . . . . . . . . . . . 23
8 * Elevator I/Os . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.2 Setup of MX Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.3 Setup of LIM (landing interface module) . . . . . . . . . . . . . . . . . 28
8.4 * Setup of BIO2 Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.5 Setup of BIO2 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . 34
9 * Completion Work Simplex Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
10 * Group Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 * Commissioning Duplex Installation . . . . . . . . . . . . . . . . . . . 38
10.2 * Commissioning Multiplex Installation . . . . . . . . . . . . . . . . . . 39
A1 PCBA ASIXA31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
A2 PCBA ASIXA32 and ASIXA33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
A3 User Interface SMLCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A4 * PCBA LONIC1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
A5 * PCBA LONIC3 and LONICK1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
A6 PCBA LONDIM (door interface module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
A7 Wiring of CIM and LIM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
A8 Service Codes Miconic 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
All people involved must know and follow the company and local safety regulations.
Protective clothing and appropriate safety equipment must be worn.
The following types of safety warnings are used in the present manual.
DANGER
The safety warning with the signal word “Danger” is used to indicate a hazardous situation
which, if not avoided, will result in death or serious injury.
WARNING
The safety warning with the signal word “Warning” is used to indicate a hazardous situation
which, if not avoided, could result in death or serious injury.
NOTICE
The safety warning with the signal word “Notice” is used to address practices that could
result in property damage but not in injury.
Parallel or Serial The following diagram shows the definition for parallel and serial components.
Components
DANGER
Hazardous Voltage
Contact with live parts will result in electric shock causing serious injury or death.
Take the following precautions:
Do not touch live parts.
Switch off the main switch and de-energize the installation completely before starting to
work on the installation.
WARNING
Bypassing of Safety Devices and Safety Contacts
Any bypassing of safety-relevant devices could result in damage to the installation or in
serious injury or death.
Bypassing the safety circuit without explicit instruction is prohibited.
Always take appropriate safety measures if premeditated bypassing is necessary for
specific work on the installation.
Do not use bypassing of safety devices if prohibited by local code.
Always leave the installation with all bypassing disabled.
WARNING
Installation Travel with ESE During Installation and Commissioning
Installation travel with ESE is not limited at the hoistway ends, which could result in damage
to the installation by the car crashing at a hoistway end. Moreover, the presence of people
and material on the construction site in combination with an installation which is only partly
completed makes installation travel during installation and commissioning a potentially
hazardous maneuver, which could result in serious injury or death.
Take the following precautions:
Move the car very carefully through the hoistway.
Make sure that the installation travel puts neither people nor materials at risk.
NOTICE
Plugging/Unplugging Connectors on Energized Devices
Hot plugging - unless explicitly permitted - could result in the destruction of devices.
Prior to plugging in or unplugging connectors on devices, switch off the devices concerned.
Tools
Tool Description
Multimeter > 25 k/V sensitivity
up to 1000 VDC measuring range
diode test and continuity test
test leads with insulated probe tips.
Summary The following steps describe how to prepare the elevator control for "Recall Travel with
IMOF" (Installation Travel).
4.1 Preconditions
4.2 * Car
Preparation Car
No Step
400 Switch ON the hoistway lighting.
401 Check that following switches have been turned OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
JFIS, FI-switch control (if present)
JFIL, FI-switch light (if present).
Refer to the schematics.
402 AS, ASIXA, check that following connector is unplugged:
BAT, emergency power supply.
Preparation
No Step
Control Cabinet
407 Switch JFIS ON (if present)
Switch JFIL ON (if present)
Remain ON during the whole commissioning.
408 AS, Brake Module BCMM, switch SITB ON (if present).
409 ASIXA, set Elevator ID on the user interface rotary switch:
Elevator A = Elevator ID 1 (Simplex)
Elevator B = Elevator ID 2 and so on.
410 ASIXA, check that chip card is plugged in on user interface.
411 ASIXA, check that the following connectors are unplugged:
X15A and X15B, logic signals drive
RS422, communication drive
AGSI, absolute encoder (if present)
SI, shaft information (if present)
Tacho, incremental encoder (if present)
LUET, door zone signal
LONS, LON hoistway
2LONS, LON hoistway Side 2 (if present)
GNT, telealarm device (if present)
GNT RS232, serial interface telealarm (if present)
Ethernet, group connection (if present)
POW236, voltage alarm DM236 (if present).
The internal wiring of the cabinet has to be done according to the schematics.
412 EBBIO, check that the following connectors are unplugged:
BIOS, BIO Bus hoistway (if present)
2BIOS, BIO Bus hoistway Side 2 (if present)
PCBA EBBIO sits on PCBA ASIXA.
413 PDB, check that the following connectors are unplugged:
POWC, power supply to the car
400V, power to car for 3-phase door operator (if present)
SIS, power in for controller
SIL, power in for car light.
414 ASIXA, plug in the following connectors:
SK1, phase control relay (RKPH) (if not present: bridging connector)
SKS, safety circuit hoistway
SKC, safety circuit car
KTS, safety circuit landing doors (wiring from landing door bridging control
station if present)
KV, contact door locking (manual doors) (if not present: bridging connector)
RH, for landing door bridging control station (if not present: bridging
connector)
SK2, reserve (if not present: bridging connector)
KKSA, to the Aramid rope monitoring box (if not present: bridging connector)
KTHM, thermal contact machine room (if not present: bridging connector)
JBRKTS (ASIXA32 only), switch bridge shaft doors (if not present:
bridging connector).
LONC, LON Car
Be aware that SMLCD may display a variation of the indication shown above,
depending on installation and SW version.
428 Turn the following switches OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
429 Continue with:
EJ 41320599 Overall Commissioning - CO MX Rel. 4.x, 5.x, 6.x with VFxxBR
and VFxxPF1.
WARNING
Hoistway Information System SALSIS with End-of-Travel Switch (KNE) Function
Traveling on top of the car without a commissioned SALSIS could result in damage to the
installation or in serious injury or death.
Do not travel on top of the car until SALSIS is commissioned:
Summary This chapter describes the activities for preparing the first travel on the car.
Preconditions All the instructions given in chapter "Preparation of Control" have been carried out fully.
LON communication to PCBA LONIC is established.
SALSIS (if present) is commissioned.
5.1 Preparation
General
No Step
500 AS, check that JMOF switch on user interface is on position "1".
501 Turn the following switches ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
Wait until the boot sequence finishes and the SMLCD displays:
Be aware that the SMLCD may display a variation of the indication shown above,
depending on installation and SW version
502 Turn the following switches OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
503 PDB, plug in the following connector:
POWC, power supply to the car (traveling cable).
400V, power to car for 3-phase door operator (if present).
504 Turn the following switches ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
505 Set JREC to position "INSP" and JHC to position "STOP".
[7582; 03.12.2004]
510 OKR, check the LEDs on PCBA LONICx:
LED 24 V (green), lit
LED SERV (rot), not lit
LED APPL (green), lit, switches OFF every 2 s communication OK.
If the LED "APPL" remains OFF, execute a double reset on PCBA GCIOB 360.
Check Inspection
Travel with IMOF No Step
511 OKR, unlock JHC.
512 Press DREC-D: Car should travel downwards.
Press DREC-U: Car should travel upwards.
513 Carry out an inspection travel and check the operation of JHC.
514 Check the operation of the contacts in the safety circuit.
Refer to the schematics.
515 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
Preparation OKR
No Step
516 Check that the door drive is not blocked mechanically.
517 OKR, LONICx, plug in the following connectors:
LONT1, LON Door 1
LONT2, LON Door 2 (if present)
POWT1, power supply door 1 (if present)
POWT2, power supply door 2 (if present).
518 OKR, plug in the following connector:
400 V, 3-phase power supply for door drive (if present).
519 OKR, LONICx, plug in the following connectors:
POWD400, 3-phase power supply (if present)
POW400T1, 3-phase power supply door 1 (if present)
POW400T2. 3-phase power supply door 2 (if present)
520 OKR, check that JREC is set to position "INSP".
Serial or Parallel The table below shows what kind of door interface is used. In addition it shows in which
Door Drive chapter the corresponding steps for the commissioning can be found.
Varidor 30 CME
No Step
521 On PCBA LONIBV of Varidor 30 CME door drive, enter the following settings for
the sliding switch:
Entrance Side 1: SZ1
Entrance Side 2: SZ2.
522 Check that all wiring between the PCBA LONIBV (Varidor 30 CME) and the
PCBA LONICx (OKR) is done properly.
Refer to the respective schematics.
[7582; 03.12.2004]
524 Check the LEDs on PCBA LONIBV.
525 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
526 OKR, set JREC switch to position "NORMAL".
527 Continue with:
EJ 41320599 Overall Commissioning - CO MX Rel. 4.x, 5.x, 6.x with VFxxBR
and VFxxPF1.
The PCBA LONDIM (LON Door Interface) is installed in the door interface box DIB.
Two door drives require two DIBs.
Interfaces to
Parallel Door No Step
Drives 528 Check that:
All wiring between DIB, OKR and door drive is done according to the
schematics.
I/Os not used on PCBA LONDIM are terminated with a bridging connector
according to the schematics.
529 LONDIM, check that the following connectors are plugged in:
LONT, LON Door
SKT, safety circuit door
POWT, power supply door
400 V, 3-phase power supply for door drive (if present).
530 LONDIM, DOOR TYPE Code (2 rotary switches)
Check and if necessary, adjust the two rotary switches "DOOR TYPE" according
to the schematics. See also appendix.
531 LONDIM, Entrance Side (slide switch)
Enter the following settings for the sliding switch:
Entrance side 1: SZ1
Entrance side 2: SZ2.
532 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control fuse (if present).
Wait until:
The boot sequence finishes.
The LON node SW download finishes (if applicable).
A download in progress shows with a blinking "%"-sign on SMLCD.
After booting, the SMLCD shows the status display, for example:
[7582; 03.12.2004]
533 Perform a reset on GCIOB.
534 LONDIM, check following LON bus and power supply LEDs:
LED 24 V (green), lit, 24 VDC available
LED APPL (green), lit, switches OFF every 5 s, LON Communication OK
LED SERVICE (red), not lit, LON Communication OK.
535 LONDIM, check status of the 7-Segment display (shows the internal status of
the door software in the MX-GC controller):
If the display shows an "8" (Error 8), no valid door type was selected by the
two rotary switches "DOOR TYPE Code". Check the setting according to the
schematics.
A table of all possible status is found in the appendix.
Summary The following steps instruct how to prepare and carry out a measuring travel.
Preconditions All of the preceding steps in the complete commissioning procedure have been carried out.
6.1 * Preparation
General
No Step
600 The operation of all contacts in the safety circuit must be tested. KNE contacts
must be correctly set. All KUET devices must be installed correctly.
601 Check that following switches have been turned OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
Control Cabinet
602 AS, ASIXA, plug in the following connectors:
AGSI, Absolute encoder (if present)
SI, shaft information (if present)
Tacho, incremental encoder (if present)
LUET, Car in door zone signal (traveling cable).
603 The complete safety circuit must be installed and connected properly.
Car
604 OKR, LONICx, plug in the following connectors:
LUET, car in door zone signal (traveling cable)
AGSI, encoder AGSI, ALSIS or SALSIS
SI (LONIC1/LONIC2: AGSI), shaft info (traveling cable)
PHNR-D / PHNR-U releveling (if incremental shaft info)
KSE, contacts hoistway end (if present)
KUET, magnetic / optical switches - KUET / KUET1
2KUET, magnetic / optical switches - 2KUET / 2KUET1 (if present).
NOTICE
Getting Trapped During Measuring Travel
If the car gets blocked during measuring travel, unblocking of the car has to be performed at
the control cabinet. A technician staying in the car, on the car roof or in the hoistway during
measuring travel could get trapped and therefore would depend on outside help for rescue
and unblocking the car.
Always initiate measuring travel from a safe location.
Execution of
Measuring Travel No Step
605 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until the boot sequence finishes, and the SMLCD displays the elevator
status.
Make sure that the car door remains closed during the boot sequence.
606 Move the car using the recall control station and take note of the signal change
from KUETs by checking the LED LUET on the user interface.
Check the correct installation of KUETs by counting the floor numbers.
607 Position the car in the door zone at the uppermost floor. Check that the LED
LUET on the user interface is ON.
During the measuring travel the elevator control compares the number of KUET
signals with the PCT (chip card). It is therefore very important to start at the
uppermost floor.
608 Before proceeding, make sure that nobody is in the car or in the hoistway.
609 AS, execute the following steps to start measuring travel:
1) Use SMLCD to activate the measuring travel:
Login - Commands - Special Trips - JLF - OK
2) Set JMOF to position "0"
3) Set JRH to position "NORMAL".
Be aware that the SMLCD may display a variation of the indication shown above,
depending on installation and SW version
611 SMLCD, execute a "Drive End Commissioning" to save the learned hoistway
image to NVRAM:
Login - Commands - Drv End Commis - OK.
Wait until SMLCD displays:
DrvEndCommis
Success
612 Check that for every entrance side one door movement has been done:
Send the car to a floor with entrance side 1 (and if present to entrance side 2) by
using SMLCD and ensure the door opens and closes.
Login - Commands - Car Call - Floor - Entry Side - OK.
This launches the measuring travel of the door drive.
613 Use SMLCD to execute car calls and check that the car travels to the correct floor
and the door opens properly.
Login - Commands - Car Call - Floor - Entry Side - OK.
Make sure that nobody is in the car and nobody enters the car during these
trips.
For SW versions 2.60, the distance parameter KSERE is set automatically according to
the installation type:
100 mm for MRL elevators with car maintenance platform (for example P23K)
600 mm for MRL elevators without car maintenance platform (for example W38K)
1500 mm for MR elevators.
Summary The following steps instruct how to connect and check the car I/Os.
Preconditions All of the preceding steps in the complete commissioning procedure have been carried out.
7.1 Preparation
OKR
No Step
700 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
701 OKR, LONICx, plug in the following connectors:
LONTC, LON Car Operating Panel(s)
LMI, load measuring interface (if present).
Serial or Parallel The table below shows what kind of car operating panels / indicators or interfaces are used.
Car Operating In addition it shows in which chapter or external Technical Catalogue the corresponding
Panels steps for the commissioning can be found.
Introduction The PCBA LONCOP(E) is the interface between LON bus and car operating and indicating
elements.
LONCOP(E) - LON Car Operating Panel (E Fixtures)
MX COP
No Step
702 Make sure that the electrical connections between PCBA LONCOP(E) and PCBA
LONICx (OKR) are made correctly. Check against the corresponding schematics
if in doubt.
703 LONCOP(E), the LONTC connector must be plugged in.
704 Check the settings on PCBA LONCOP:
MODE, row / sequence
OUT1, setting ZS1/ZS2 for column 1
OUT2, setting ZS1/ZS2 for column 2
OUT3, setting ZS1/ZS2 for column 3.
705 Check the settings on the configurable NW PCBAs (connected to PCBA
LONCOP) according to the schematics.
706 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until:
The boot sequence finishes.
The LON node SW download finishes (if applicable).
A download in progress shows with a blinking "%"-sign on SMLCD.
After booting, the SMLCD shows the status display, for example:
[7582; 03.12.2004]
707 Check the LEDs on PCBA LONCOP(E).
708 Travel to all floors and check that:
All car calls are being answered
The COP display functions properly
The doors function properly (DT-O / DT-S)
Key switches and additional lamp elements function properly.
709 Continue with chapter "Elevator I/Os".
Introduction The COP Interface Module (CIM) is normally mounted on the car roof and consists on a
combination of the following hardware:
LONCPI, LON COP and position indicator
NWIOD6, Neuron Wire 6 I/O car calls (4-cable wiring)
NWIO36, Neuron Wire 6 I/O car calls (3-cable wiring)
NWIOC3, Neuron Wire 3 I/O configurable.
Interfaces to
Parallel COPs No Step
710 Make sure that the electrical connections between CIM, COP and indicators are
made correctly. Check against the corresponding schematics if in doubt. See also
appendix "PCBA LONIC1".
711 LONCPI, check that connector LONTC is plugged in.
712 Check the settings on PCBA LONCPI:
Hoist. Entr (entrance side)
DT-O / DT-S, normally open or normally closed contacts
Blink Enable, activating of blinking car calls acknowledge lamps
Gray Binary, gray or binary code for position indicator
Gray Inversion, inverse function of the gray or binary code
Rotary Switch, (not used with MX-GC).
See the respective appendix for the wiring.
713 Check the settings on PCBA NWIOC3 (if present):
BMK I/O 1 - I/O 3, BMK function according to schematics
Inversion I/O 1 - I/O 3, normally open or normally closed contacts,
"ON" = normally closed
Mode, mode A or B for the wiring
Jumper I/O 1 - I/O 3, all jumpers have to be plugged either in position "A" or in
position "B".
See the respective appendix for the wiring.
714 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until:
The boot sequence finishes.
The LON node SW download finishes (if applicable).
A download in progress shows with a blinking "%"-sign on SMLCD.
After booting, the SMLCD shows the status display, for example:
[7582; 03.12.2004]
715 Check the LEDs on the following PCBAs:
LONCPI, NWIOD6, NWIO36 and NWIOC3 (if present).
Introduction The following steps instruct how to connect and check the elevator I/Os.
Preconditions All of the preceding steps in the complete commissioning procedure have been carried out.
8.1 Preparation
Control Cabinet
No Step
800 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
801 On ASIXA, plug in the following connector(s):
LONS, LON hoistway
2LONS, LON hoistway Side 2 (if present).
Refer to the respective schematics.
802 Applicable for BIO2 bus only. On EBBIO, plug in the following connector(s):
BIOS, BIO Bus hoistway (if present)
2BIOS, BIO Bus hoistway Side 2 (if present)
The PCBA EBBIO (if present) sits on the PCBA ASIXA.
Refer to the respective schematics.
Serial or Parallel The table below shows what kind of Landing Operating Panels / Indicators or Interfaces are
Fixtures used. In addition it shows in which chapter or external Technical Catalogue the
/Indicators corresponding steps for the commissioning can be found.
MX Fixtures
No Step
803 Check the correct wiring and settings of the LOPs, LIPs and BIBs (Building
Interface Box) according the schematics.
804 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until:
The boot sequence finishes.
The LON node SW download finishes (if applicable).
A download in progress shows with a blinking "%"-sign on SMLCD.
After booting, the SMLCD shows the status display, for example:
[7582; 03.12.2004]
805 Use SMLCD to "Freeze" the LON node tree
Login - Commands - Freeze Node Tr - OK.
Check on SMLCD display (upper right corner):
"?" = "freeze" not yet done
"?"(blinking) = executing "freeze" command
"!" = different or missing LON nodes after "freeze"
"!"(blinking) = "freeze" was not successful
no display = "freeze" done and no changes with the nodes
The LON nodes are saved in a list on the PCBA GCIOB. For diagnostic reasons,
this list is periodically checked against the existing LON nodes.
The freeze is mandatory in order to enable the controller to recognize the
critical (safety-relevant) I/Os.
Introduction The Landing Interface Modules LIM are mounted in the hoistway near the operating /
indicating panels and consist of a combination of the following hardware:
LOP (landing operating panel):
LONIO2, PCBA LON with 2 I/Os for DE up / down (4-cable wiring)
LONIO32, PCBA LON with 2 I/Os for DE up / down (3-cable wiring)
LONIOC3/5, PCBA LON with 3 / 5 configurable I/Os
LIP (landing indicator panel):
LONDGI, PCBA LON with direction indicator and gong interface
LONPII, PCBA LON with position indicator and gong interface
LIOP (landing indicator/operating panel):
LONDGIO, PCBA LON with direction indicator, gong interface and I/Os
LONPGIO, PCBA LON with position indicator, gong interface and I/Os
Safety Circuit Disconnection and Bypassing (Korea only):
LONUESK, PCBA LON with relays to disconnect and bypass safety circuit pit
contacts (defined as critical I/Os)
LIM
No Step
809 Make sure that the electrical connections between the LIM, operating panels and
indicators are made correctly. Check against the corresponding schematics if in
doubt. See also appendix "PCBA LONIC1".
810 Check settings on LONIO2, LONIO32, and LONDGIO PCBAs (if present)
Hoist. Entr (entrance side)
Floor Number.
811 Check settings on LONIOC3/5 PCBAs (if present):
Hoist. Entr (entrance side)
Floor Number
BMK I/O 1 - I/O 3/5, BMK function according to schematics
Inversion I/O 1 - I/O 3/5, normally open or normally closed contacts,
"ON" = normally closed
Mode, mode A or B for the wiring
Jumper I/O 1 - I/O 3/5, all jumpers have to be plugged either in position "A" or
in position "B".
See the respective appendix for the wiring.
812 Check settings on LONDGI PCBAs (if present):
Hoist. Entr (entrance side)
Floor Number.
813 Check settings on LONPII and LONPGIO PCBAs (if present):
Hoist. Entr (entrance side)
Floor Number
Binary / Gray, gray or binary code for position indicator
Selector, selector or position shown on position indicator, selector = "ON"
Fire Mode, mode out of order indicator
Inversion, inverse function of the gray or binary code.
See the respective appendix for the wiring.
[7582; 03.12.2004]
815 Check the LEDs on the following PCBAs:
LONIO2, LONIOC3/5, LONDGI and LONPII (if present).
816 Use SMLCD to "Freeze" the LON node tree
Login - Commands - Freeze Node Tr - OK.
Check on SMLCD display (upper right corner):
"?" = "freeze" not yet done
"?"(blinking) = executing "freeze" command
"!" = different or missing LON nodes after "freeze"
"!"(blinking) = "freeze" was not successful
no display = "freeze" done and no changes with the nodes
[7585; 03.12.2004]
The LON nodes are saved in a list on PCBA GCIOB. For diagnostic reasons, this
list is periodically checked against the existing LON nodes.
The freeze is mandatory in order to enable the controller to recognize the
critical (safety-relevant) I/Os.
817 Travel to all floors and check that:
All landing calls are being answered
The LIP displays function properly
Key switches and additional lamp elements function properly.
818 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
819 Continue with chapter "Completion Work Simplex Installation".
About BIO2 In this chapter the BIO2 Landing Fixtures Teach-in procedure is described. With those
Landing Fixtures procedure:
The elevator control learns all LIPs and LOPs and their location (floor number and
entrance side). Further the LIPs and LOPs themselves learn their location and can be
addressed by the elevator control.
Important to know:
After power on, single or double reset wait 5 minutes before starting Teach-in.
Key switches/lamps need further configuration. This is done on the node itself with a
separate mechanical setting (e.g. DIP switch) or with programmable PCBAs (see next
chapter).
If the configuration data resulting from a teach-in requires correction, there is no other
way than redo the teach-in. A teach-in always overwrites the existing configuration data.
For floors with restricted access see "Restricted Access" (Locked floors will not be
served during Teach-in)
For parallel operated doors, see "Parallel Operated Doors".
If there are unintended landing calls during the "Teach-in" procedure see "Unintended
landing calls during Teach-in Mode with opened/closed doors"
A single reset on GCIOB360 is needed before starting Teach-in.
CADI-GC or SMLCD shall not be used to generate car calls during the Teach-in
procedure.
With the BIO2 landing bus for MX-GC the following hardware components will be used:
PCBA BIODCE (BIO Direction, Calls, E-Fixtures)
Landing Indicating / Operating Panel with Further Travel Indicator
PCBA BIOPCSE (BIO Position, Calls, Switches, E-Fixtures)
Landing Indicating / Operating Panel with Position- and Further Travel-Indicator
PCBA BIOAPI (BIO Asia Pacific Indicator)
Landing Indicating / Operating Panel for Asia / Pacific
PCBA SLCU2 (Smart Landing Call Unit 2), (DE, JBF or JDE)
PCBA SLCUM2 (Smart Landing Call Unit 2 Main Floor)
(DE-U/D, JBF or JDE, direction arrows, gong, gray code indicator)
PCBA SLCUX1 (Smart Landing Call Unit X), (4 Inputs / Outputs)
PCBA BPC(S)DG or BPC(S)DR (BIO Positions indicators with Calls (and Switches) for
D-fixtures (Green or Red) - D-fixtures landing indicating and operating panel for D-AP
LOP.
BIO2 Landing
No Step
Fixtures Teach-In
Procedure 820 Make sure that the electrical connections between all landing elements are made
correctly. Check against the corresponding schematics if in doubt.
[7582; 03.12.2004]
822 Use the SMLCD to issue a car call to the floor where the controller cabinet is
located
Login - Commands - Car Call - Floor - OK.
823 Make a single reset and wait five minutes for the complete scan of all BIO nodes.
824 Use the SMLCD to activate the "Teach-in" mode:
Login – Commands – Teach-in – ON – OK.
Check displays on SMLCD:
[7586; 03.12.2004]
The elevator control opens the door and keeps it open.
In case of operational LIPs on landing, "Out-of-Service" is indicated to the
passengers.
XX = floor number.
825 In car give a call to the landing location which has to be configured (start with the
floor farthest from the controller cabinet).
The car moves to the requested landing, opens the door and keeps it opened.
If there are selective operated entrance sides, for each side a separate car
call must be issued.
If there are parallel operated entrance sides, the car call must be issued
twice. The first will start the Teach-in for one side, the second will start the
Teach-in for the opposite side (see Parallel Operated Doors).
In teach-in mode, one car call per trip is accepted only.
Parallel Operated
829 If there are two entrance sides with parallel operated doors on the same landing,
Doors
execute the following steps:
On entrance side 1, press the LOP pushbutton UP (or the only LOP button) for
5 seconds. The LOP pushbutton must be pressed within 12 seconds after the
doors are open.
Three seconds after releasing the pushbutton on the LOP, the acknowledge
lamps on the LOP turns on for 3 seconds and the buzzer in the COP beeps
830 Go back in the car and execute a car call for the same floor again:
On entrance side 2, press the LOP pushbutton UP (or the only button) for
5 seconds. The LOP pushbutton must be pressed within 12 seconds after the
doors are open.
Three seconds after releasing the button on the LOP, the acknowledge lamp on
the LOP turns on for 3 seconds and the buzzer in the COP beeps.
Restricted
Access 831 If there are locked floors by restricted access feature, execute the following steps:
1) Disable the restricted access.
2) On entrance side 1, press the LOP pushbutton UP (or the only LOP button) for
5 seconds.
The LOP pushbutton must be pressed within 12 seconds after the doors are
open.
Three seconds after releasing the button on the LOP:
The acknowledge lamps on the LOP switches on for 3 seconds
The buzzer in the COP beeps for 1 second.
Unintended
Landing Calls 832 If an unintended landing call is entered this landing operating panel will be
During Teach-in configured with the location of the landing on which the car is located. The buzzer
in the COP beeps. Any further configuration is disabled until another car call is
Mode with
Opened Doors entered.
In this case the wrong configured landing operating panel has to be configured
again.
In "Teach-in" mode, landing calls are not served as such but work as
configuration inputs.
Unintended Landing calls for configuration purpose are not accepted if the car door is not fully open.
Landing Calls This prevents unintended configuration by elevator passengers.
During Teach-in
Mode with Closed 833 Perform a single reset and wait for 5 minutes.
Doors
[7585; 03.12.2004]
The BIO2 nodes are saved in a list on PCBA GCIOB. For diagnostic reasons, this
list is periodically checked against the existing BIO2 nodes.
The freeze is mandatory in order to enable the controller to recognize the
critical (safety-relevant) I/Os.
835 After freeze is complete perform a double reset.
836 Travel to all floors and check that:
All landing calls are being answered
The LIP displays function properly
Key switches and additional lamp elements function properly (I/Os for SLCUX
see next chapter).
837 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
838 Continue with chapter "Completion Work Simplex Installation".
About the BIO2 In this chapter the settings of the BIO2 Landing Interface SLCUX for parallel fixtures are
Landing Interface described.
For Learning the location (floor and entrance side) of single LIPs and LOPs the "Teach-in"
procedure is used.
For the teach-in procedure, refer to chapter "Setup of BIO2 Fixtures" in this document.
The settings have to be completed before starting with the I/O configuration.
Reassigning a function to a redundant I/O requires a 2-step procedure:
1) Assign "No Function" to the respective I/O (this deletes the old function).
This step has be carried out on both controls that are associated with the redundant I/O.
2) Assign the desired new function to the respective I/O.
This procedure is required even if the reassigned new function is non-redundant.
No Step
839 Check the correct wiring and settings of all landing elements according to the
schematics.
840 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until:
The boot sequence finishes.
The LON node SW download finishes (if applicable).
A download in progress shows with a blinking "%"-sign on SMLCD.
After booting, the SMLCD shows the status display, for example:
[7582; 03.12.2004]
841 Use SMLCD to activate "Service Visit" in order to disable the monitoring of critical
I/Os.
Login - Commands - Service Visit - ON - OK.
SMLCD displays a blinking "*" and an acoustic signal sounds when "Service
Visit" is activated.
842 Use the SMLCD to activate the I/O configuration
Login - Commands - Program IO Fun.
The SMLCD shows a list of all programmable PCBAs:
[7587; 03.12.2004]
[7588; 03.12.2004]
844 Choose the PCBA that has to be programmed and press "OK" (SMLCD shows
the current IO configuration):
[7589; 03.12.2004]
845 Select the Input or Output which has to be programmed by scrolling trough the list
and press "OK".
[7590; 03.12.2004]
846 Select the desired "BMK" name and press "OK". For confirmation press "OK"
again:
The system stores the BMK code permanently on the PCBA.
Go back with "ESC".
847 Continue with the single I/O configurations by repeating the steps 839 to 843.
848 Finish the configuration by pressing the "ESC" button.
849 Perform a single reset and wait 5 minutes.
[7585; 03.12.2004]
The BIO2 nodes are saved in a list on PCBA GCIOB. For diagnostic reasons, this
list is periodically checked against the existing BIO2 nodes.
The freeze is mandatory in order to enable the controller to recognize the
critical (safety-relevant) I/Os.
851 Perform a single reset and wait until the SMLCD displays "N".
852 Use the SMLCD to deactivate "Service Visit" in order to enable the monitoring of
critical I/Os.
Login - Commands - Service Visit - OFF - OK.
853 Travel to all floors and check that:
All landing calls are being answered
The LIP displays function properly
Key switches and additional lamp elements function properly.
854 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
855 Continue with chapter "Completion Work Simplex Installation".
Summary The following steps describe how to connect and to test further components.
Preconditions All of the preceding steps in the complete commissioning procedure have been carried out.
No Step
900 Check the following function:
Emergency light in the car must come ON.
901 LONICx, plug in the following connectors:
SOA, alarm horn on car
MVEC, car fan motor (if present)
TT, telephone wire (traveling cable) (if present)
GNT, to the car operating panel intercom (if present)
RAC, connection car relay alarm (if present)
Close the OKR cover.
902 If there is a Building Interface Box (BIB) check the correct wiring and setting.
Refer to the schematics.
903 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until the boot sequence is finished and the display on SMLCD shows the
elevator status.
904 Check the following function:
When the various alarm buttons are pressed, the alarm horn must sound.
905 If there is a Building Interface Box (BIB) check the correct function of the Inputs
and / or outputs.
Refer to the schematics.
906 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
907 If no further work in hoistway has to be done, turn hoistway lighting OFF.
908 Continue with:
EJ 41320599 Overall Commissioning - CO MX Rel. 4.x, 5.x, 6.x with VFxxBR
and VFxxPF1.
Summary The commissioning of elevators in the group can be done singly or as a whole. Refer to the
schematics if necessary.
A difference is made between duplex (n = 2) and multiplex installations (n > 2).
Preconditions All of the preceding steps in the complete commissioning procedure have been carried out.
Check that the power supply units are wired according to the schematics.
Check that the critical I/Os are wired according to the schematics.
Unless stated otherwise, the following steps are valid for both elevator control cabinets.
No Step
1000 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
1001 ASIXA, check that the following connectors are plugged in:
ETHERNET, Ethernet connection to the next elevator.
Ethernet connections for duplex must have blue connectors. With a gateway for
Lobby Vision also a duplex installation needs an Ethernet hub.
1002 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until the boot sequence finishes and SMLCD displays the elevator status.
When an elevator control detects another elevator control for the first time, the
controller performs a reset.
1003 Travel to all floors and check that:
All floor calls are being answered
The displays are functioning
Group functions are carried out (if present).
1004 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
1005 Continue with:
EJ 41320599 Overall Commissioning - CO MX Rel. 4.x, 5.x, 6.x with VFxxBR
and VFxxPF1.
Unless indicated otherwise, the following steps are valid for all elevator control cabinets.
No Step
1006 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
1007 ASIXA, check that the following connectors are plugged in (all elevator controls
in group):
ETHERNET, connection to Ethernet hub (in AS 1).
Ethernet connections for 3 ore more elevators in a group must have green
connectors.
1008 Elevator 1: Ethernet hub, check that the following connectors are plugged in:
24 V Power supply
Ethernet connection to PCBA ASIXA
Ethernet connections to all remaining elevator controller.
1009 Turn the following switches and circuit breakers ON:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present)
Wait until the boot sequence finishes and the SMLCD shows the elevator status.
When an elevator control detects another elevator control for the first time, the
controller performs a reset.
1010 Travel to all floors and check that:
all floor calls are being answered
the displays are functioning
group functions are carried out (if present).
1011 Turn the following switches and circuit breakers OFF:
JH, main power switch
SIL, lighting mains fuse (if present)
JHO, options main switch (if present)
SIS, control main switch (if present).
1012 Continue with:
EJ 41320599 Overall Commissioning - CO MX Rel. 4.x, 5.x, 6.x with VFxxBR
and VFxxPF1.
Overview and
Designations 18a 18b 18c 18d 18e 18f 18g
27
28
29
19
17 30
20
16
21
15
14 22
23
13
24
12 25
11 26
10
6 5 4 3 2 1c 1b 1a
PCBA ASIXA31 [5154; ]
Overview and
Designations 18a 18b 18c 18d 18e 18f 18g
27
28
29
19
17 30
20
16
21
15
14 ASIXA 32.Q 31 22
34
13
Id.No. 591853 23
32
ASIXA 33.Q 24
12 25
Id.No. 594217
11 26
10
9
33
6 5 4 3 2 1c 1b 1a
PCBA ASIXA32 and 33 [26112; 28.07.2008]
Overview and
Description
3
2
5 4
1
[4307; 28.09.2004]
Pos. Description
1 Status voltage supply and LED Door Trigger
2 Safety circuit
3 Chip Card, Elevator-ID
4 Direction and Floor Level LEDs
5 Installation travel mode switch
6 Status information group communication and LON/BIO2 Bus
7 4-line SMLCD (Service Module LCD)
8 Operation keys SMLCD
MX-UI: Layout with Descriptions
For detailed information about SMLCD, see K 604454 Diagnostics "Miconic MX-GC.
Overview and
Designations
Overview and
Designations
Overview
The 7-segment display shows the internal status of the door software in the MX-GC
controller.
The real status of the door may be different and can be verified by viewing the status
LEDs.
Diagnosis via
Display Display Description Remarks
O Opened Door has been opened by door control SW.
O. Opened manually (not by Door has been opened either manually or by
command from control DRET-O.
software) Revision car was switched ON with open door.
LONDIM has just powered up with open door.
C Closed Door has been closed by door control SW.
C. Closed manually (not by Door has been closed either manually or by DRET-S.
command from control Revision car was switched ON with closed door.
software)
LONDIM has just powered up with closed door.
L Locked Door has been locked by door control SW.
S Stopped (door is neither Door has been stopped by door control SW.
fully open nor fully
closed)
S. Stopped in revision Door has been stopped under revision control car
control (door is neither (on-board buttons DRET-O/S).
fully opened nor fully LONDIM has just powered up with neither fully
closed) opened nor fully closed door.
H. Manual operated Door is in manual mode and can be moved by hand:
Communication to door control is broken (LED APPL
is OFF).
JKFM is ON and a landing door has been opened
(KTS).
P. Powerless All relays on LONDIM are OFF:
Emergency stop button pressed (JHCT, JHC, JHM,
JHSG).
o Opening Door is opening by command from door control SW.
CIM (COP
interface module)
LIM (landing
interface module)
Introduction Several services in basic elevator function M10 can be activated and deactivated using
service code entries on the Z-Line or Z-Line II Terminals.
Standard Service Service codes are identified by a four or three digit number and have the following initial
Codes values (length and assignment can be changed, see below):
Change Length of The length of the service codes can be switched between 4 digits (default setting, see figure
Service Codes below) and 3 digits using CADI GC in the menu 'Miconic10 Parameter Terminals
Floor Terminal':
[6876; 12.11.2004]
Thus it may be required, depending on the individual installation, to skip a trailing 0 from the
codes indicated in the table (for example entry of 066 instead of 0066 for normal travel).
[6875; 12.11.2004]
Change Service To fulfill customer requirements, the number assignment of the service codes can be also
Codes on Keypad be changed on ZRTL:
Initiate the code change by execution of the special service code 255.
Upon entry of this code, 'OC' (Old Code) is displayed to request the code which has to
be changed. Before the first change of a specific code, this value is identical to its
standard code as listed in the code table above.
Enter the number of the code to be changed
Upon the request 'NC' (New Code) enter the new code number
Upon the request 'VC' (Verify Code) enter the new code number a second time for
verification.