A B C D E F G H I J

EPOXY POWDER COATED HOT DEEP GALVANIZED WIRE MESH CABLE TRAY
7 7
WIDTH HEIGHT THICKNESS WIDTH HEIGHT THICKNESS WIDTH HEIGHT DIAMETER
No. DESCRIPTION H(mm) W(mm T(mm) No. DESCRIPTION H(mm) W(mm T(mm) No. DESCRIPTION H(mm) W(mm (mm)

1 CABLE LADDER 1 CABLE LADDER 1 WIRE MESH ( INOX)

200 100 1.2 200 100 2.0 50 50 5

300 100 1.2 300 100 2.0 100 50 5

400 100 1.5 400 100 2.0 150 50 5

500 100 1.5 500 100 2.0 200 50 5

600 100 1.5 600 100 2.0 300 50 5

800 100 2.0 800 100 2.0 400 50 5

1000 100 2.0 1000 100 2.0 500 50 5


6 6
600 50 5

WIRE MESH
2 CABLE TRAY 2 CABLE TRAY 2 (HOT DEEP GALVANIZED STEEL)

50 100 1.2 50 100 2.0 50 50 5

100 100 1.2 100 100 2.0 100 50 5

200 100 1.2 200 100 2.0 150 50 5

300 100 1.2 300 100 2.0 200 50 5

400 100 1.5 400 100 2.0 300 50 5

500 100 1.5 500 100 2.0 400 50 5


5 5
600 100 1.5 600 100 2.0 500 50 5

800 100 2.0 800 100 2.0 600 50 5

3 CABLE TRUNKING 3 CABLE TRUNKING

50 100 1.2 50 100 2.0

100 100 1.2 100 100 2.0


THIS'S DESIGN DRAWING, THE CONTRACTOR MUST BE CHECKED AT SITE TO MAKE
CONSTRUCTION DRAWING.
200 100 1.2 200 100 2.0

300 100 1.2 300 100 2.0

400 100 1.5 400 100 2.0

500 100 1.5 500 100 2.0 4


00 16-SEP-'16 H.N.THUAN
4 600 100 1.5 600 100 2.0
H.C
REV DATE DRAW BY MODIFICATIONS

DESIGN CONDITION 4. SHORT CIRCUIT FAULT LEVEL (MINIMUM) 8. VOLTAGE DROP CONSIDERATION SANTOMAS BAC NINH FACTORY
a) MAIN SWITCH BOARD 100KA at 400V (2,500KVA) PLOT No. 106B/113A VSIP BAC NINH INDUSTRIAL PARK, BAC NINH PROVINCE, VIETNAM
1. TEMPERATURE CONDITION b) MCCB 3% 2 - 5%

a) INDOOR (AIR CONDITIONING) 1) UP TO 100A : 25KA APPROVED BY


b) INDOOR (SUB-STATION) 2) 250 UP TO 630A : 35KA ONLY TENTATIVE VALUE
BASED ON CALCULATION MCC FINAL LOAD TOTAL: 8%
c) OUTDOOR (UNDER GROUND) 2) 630A & ABOVE : 50KA
ACTUAL SHORT CURRENT
c) MCB LEVEL SHALL BE CHOSEN MSB SDB LP LIGHTING TOTAL: 6%
2. ELECTRICAL SYSTEM 3
1) FOR LIGHTING : 6KA
3 a) FREQUENCY TR TOTAL: 8%
DB FINAL LOAD
2) FOR SOCKET OUTLET : 6KA
b) INCOMING VOLTAGE GENERAL DIRECTOR

c) TRANSFORMER SECONDARY VOLTAGE 11. APPLIED FOR CONDUITS

3 4W, 400/230V+PE 5. EARTHING SYSTEM a) EMT (ELECTRICAL METALLIC TUBING) LIGHTING POWER, SOCKET AND ELV SERVICES AT
3 3W, 210V+PE HIGH LEVEL INSTALLATION INCLUDING ABOVE CEILING
TN-S & EQUIPOTENTIAL BONDING SYSTEM
TO IEC364 WITHIN WHOLE PROJECT b) IMC (INTERMEDIATE METAL CONDUIT) EXPOSED ARRANGEMENT IN FACTORY FOR MOTOR
d) RATED VOLTAGE FOR: EQUIPMENT AND SOCKET LAYOUT
1) HVAC 3 4W, 380V/220V+PE c) LIQUID-TIGHT FLEXIBLE STEEL CONDUIT FINAL CONNECTION TO MOTOR, LIGHTING FIXTURE,
6. WIRING ACCESSORIES DESIGN MANAGER
2) PLUMBING 3 4W, 380V/220V+PE (MECHA-FLEKI (MF)) AND NOT EXCEEDING 18"(460mm) IN LENGTH
a) LIGHTING SWITCH
3) PIPEPING 3 4W, 380V/220V+PE
1) STANDARD COMPLYING WITH LOCAL STANDARD (NEMA TYPE)
4) LIGHTING 1 2W, 220V+PE d) RIGID PVC CONDUIT CONCEALED INSTALLATION BY WALL, CONCRETE SLAB
2) RATING 16A AT 250V
5) SOCKET OUTLET 1 2W, 220V+PE 2
3) INSTALLING 1,350 mmABOVE THE FLOOR e) FLEXIBLE PVC CONDUIT FINAL CONNECTION IN PROTECTED AREA, SUCH AS D:\1.PROJECT\2016\3.
2 6) PRODUCTION EQUIPMENT 3 4W, 380V/220V+PE HEIGHT FINISHING LEVEL (CENTER OF PLATE) SANTOMAS\2.INPROGRESS\1.EE\2.BASIC\2.DRAWING\2.1.CAD
INTO LGS WALL OR IN CONCRETE SLAB
1 2W, 220V+PE
b) SOCKET OUTLET
f) HDPE FLEXIBLE CONDUIT (FEP) UNDERGROUND Ninh thuan
16-SEP-2016

1) STANDARD COMPLYING WITH LOCAL STANDARD (NEMA TYPE)


3. CABLE COLOURING SCHEDULE
2) RATING 16A AT 250V 2PIN+E TYPE (2GANGS)

PHASE WIRE VOLTAGE PHASE NEUTRAL 3) INSTALLING OFFICE : 300mm FL (CENTER OF PLATE)
HEIGHT FACTORY : 1800mm FL (CENTER OF PLATE)
() (W) (V) L1 L2 L3

3 4 380/220 RED YELLOW BLUE BLACK


7. BASIC WIRING
EARTHING GREEN_YELLOW
a) LV FEEDER Cu/XLPE/PVC-0.6/1kV CABLES
ON CABLE LADDER / CABLE TRAY
(NOTE) IF COLOURING CABLE/WIRE IS NOT AVAILABLE, COLOUR
MARKER SHALL BE INSTALLED AT END OF CABLE. b) FINAL CIRCUIT (FOR LIGHTING & SOCKET) Cu/PVC WIRE
ELECTRICAL SYSTEM
c) FINAL CIRCUIT (FOR A OR B CLASS Cu/PVC/PVC CABLE
1 MOTOR EQUIPMENT) 1

d) FINAL CIRCUIT (FOR F CLASS Cu/XLPE/PVC CABLE


MOTOR EQUIPMENT) GENERAL NOTES

REV. :
EE-003 00 16-SEP-2016 NTS

A B C D E F G H I J

You might also like