Outside Screw and Yoke (OS&Y) Gate Valve - Flanged: Technical Features
Outside Screw and Yoke (OS&Y) Gate Valve - Flanged: Technical Features
OSF
Control Valves
Technical Features
• Sizes available (Nominal) : 2”/DN50, 2½”/DN65,
3”/DN80, 4”/DN100, 5”/DN125, 6”/DN150,
8”/DN200, 10”/DN250 and 12”/DN300
• Pressure data :
Working pressure : 300 psi (21 bar)
• Seat type : Resilient wedge
• Finish : Fusion bonded epoxy coated internal and
external
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Design and dimensions conform to
AWWA C515.
• Features : Pre-notched, stainless steel stem for easy
attachment of supervisory switch
• Note : Size 5” is only UL listed
Outside Screw and Yoke (OS&Y) Gate Valve - Flanged - OSF Physical Data
Nominal Pipe
Dimensions (mm) Reference*
Size Weight
H1 H2 D1 n-ØL (kg)
inch Metric L D C ANSI PN10 PN16
(Closed) (Open) ANSI PN16 PN10 ANSI PN16 PN10
2” DN50 178 348 400 152 16.0 120.7 125 4-Ø19.1 OSF-0200 OSF-0200PN 14.7
2½” DN65 190 373 440 178 17.5 139.7 145 4-Ø19.1 OSF-0250 OSF-0250PN 17.7
3” DN80 203 408 490 191 19.1 152.4 160 4-Ø19.1 8-Ø19.1 OSF-0300 OSF-0300PN 23.1
4” DN100 229 471 573 229 19.1 190.5 180 8-Ø19.1 8-Ø19.1 OSF-0400 OSF-0400PN 31.6
5” DN125 254 541 665 254 19.1 215.9 210 8-Ø22.2 8-Ø19.1 OSF-0500** OSF-0500PN** 42.2
6” DN150 267 601 755 279 19.1 241.3 240 8-Ø22.2 8-Ø23 OSF-0600 53.2
8” DN200 292 774 975 343 22.2 298.5 295 8-Ø22.2 12-Ø23 8-Ø23 OSF-0800 OSF-0800PN10 OSF-0800PN16 91.3
10” DN250 330 939 1193 406 23.8 362.0 355 350 12-Ø25.4 12-Ø28 12-Ø23 OSF-1000 OSF-1000PN10 OSF-1000PN16 134.6
12” DN300 356 1065 1370 483 25.4 431.8 410 400 12-Ø25.4 12-Ø28 12-Ø23 OSF-1200 OSF-1200PN10 OSF-1200PN16 200.0
* Valve flange drilling (size and location of bolt holes and pitch circle diameter) allows mating with the following flange types :
ANSI = ANSI B16.1 Class 125 PN10 = DIN 2501, BS 4504, EN 1092 - PN10 PN16 = DIN 2501, BS 4504, EN 1092 - PN16
** UL Listed only
Outside Screw and Yoke (OS&Y) Gate Valve - Flanged - OSF Materials List
Item Description Material Specification Item Description Material Specification
1 Valve Body Ductile Iron ASTM A536, 65-45-12 10 Stem Nut Brass HPb59-1
2 Wedge Disc Ductile Iron ASTM A536, 65-45-12 & EPDM 11 Handwheel Ductile Iron ASTM A536, 65-45-12
3 Stem Stainless Steel AISI 420 12 Washer Brass HPb59-1
4 Bonet Gasket EPDM Commercial 13 Gland Nut Carbon Steel Zinc Plated
Datasheet Created
5 Bonnet Ductile Iron ASTM A536, 65-45-12 14 Stud Carbon Steel Zinc Plated
6 Washer Brass HPb59-1 15 Flat Washer Carbon Steel Zinc Plated
7 Yoke Ductile Iron ASTM A536, 65-45-12 16 Bolt Carbon Steel Zinc Plated
8 Stem Bushing Brass HPb59-1 17 O-Ring EPDM Commercial
9 Gland Ductile Iron ASTM A536, 65-45-12 18 Plug Bronze ASTM B583 C89833
11-03-2015
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
Outside Screw and Yoke (OS&Y) Gate Valve - Flanged
OSF
Control Valves
Installation Inspection and Maintenance
1. Piping systems and valves should be 1. Valves should be inspected periodically and
thoroughly cleaned and free from ingress of should be cycled to prevent buildup of foreign
foreign materials. materials in the piping system and valve body.
2. Visually inspect the valve seating and 2. In the event of a packing leak adjust the
ports for cleanliness immediately prior to packing nuts to increase pressure on the stem
installation. packing. Packing nuts should be tightening
3. All valves should be independently supported evenly approximately a quarter turn in a
against movement and stress from the clockwise direction.
connected piping system. 3. Always shut down the system before repacking
4. Ensure that the valve pressure rating is the valve. Valves are designed with backseats
compatible with service conditions. for repacking under pressure but this is not
5. Operate the valve at least once from the recommended.
open to closed position.
6. Verify that packing nuts are tight before
pressurizing the system.
7. Gate valves are not suitable for throttling
applications.
8. Gate valves should be installed in the vertical
position on horizontal pipework and in the
horizontal position on vertical pipework.
Operation
Gate valves are manually operated multi-turn
valves and are opened by a handwheel or
other operating device, generally in a counter
clockwise direction and then closed clockwise.
FireKing™ is a trademark of The Viking Corporation. Refer to Manufacturer’s datasheet. Specifications subject to change without notice.
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
GENERAL INFORMATION
The OSYSU is used to monitor the open position of an OS screws and hex keys are available. See ordering informa-
& Y (outside screw and yoke) type gate valve. This device tion on page 4.
is available in two models; the OSYSU-1, containing one OPTIONAL COVER TAMPER SWITCH
set of SPDT (Form C) contacts and the OSYSU-2, con- A field installable cover tamper switch is available as an
taining two sets of SPDT (Form C) contacts. These option which may be used to indicate removal of the cover.
switches mount conveniently to most OS & Y valves See ordering information on page 4.
ranging in size from 2" to 12" (50mm to 300mm). They will
mount on some valves as small as 1/2" (12,5mm). TESTING
The OSYSU and its associated protective monitoring sys-
The cover is held in place by two tamper resistant screws tem should be inspected and tested in accordance with
that require a special tool to remove. The tool is furnished applicable NFPA codes and standards and/or the authority
with each device and should be left with the building owner having jurisdiction (manufacturer recommends quarterly or
or responsible party. Replacement or additional cover more frequently).
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" (12,5mm THRU 63,5mm) SIZES
THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME
VALVES AS SMALL AS 1/2" (12,5MM). J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.
FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" (76mm THRU 300mm) SIZES
LARGE VALVE INSTALLATION (9,5mm) round, non-tapered file. Round and smooth the
edges of the groove to prevent damage to the valve
1. With the valve in the FULL OPEN position, locate the
packing and to allow the trip rod to move easily in and out
OSYSU across the valve yoke as far as possible from the
of the groove as the valve is operated.
valve gland, so that the trip rod lays against the non-
threaded portion of the valve stem. 6. Mount the OSYSU loosely with the trip rod centered in
groove.
2. Mount the OSYSU loosely with the carriage bolts and
clamp bar supplied. 7. Final adjustment is made by loosening 2 screws (see Fig.
2) and sliding the OSYSU on the bracket. Adjustment is
3. Loosen the locking screw that holds the trip rod in place
correct when switches are not activated with the trip rod
and adjust the rod length (see Fig. 4). When adjusted
seated in the valve stem groove and that the switches
properly, the rod should extend past the valve screw, but
activate within one turn when the valve is operated from the
not so far that it contacts the clamp bar. Tighten the
FULL OPEN towards the CLOSED position.
locking screw to hold the trip rod in place.
8. Tighten the adjustment screws and mounting hardware.
NOTE: If trip rod length is excessive, loosen the locking
Check to insure that the rod moves out of the groove
screw and remove the trip rod from the trip lever. Using
easily and that the switches activate within one turn when
pliers, break off the one 1" (25mm) long notched section
the valve is operated from the FULL OPEN towards the
(see Fig. 5). Reinstall trip rod and repeat Step 3 proce-
CLOSED position.
dure.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
4. Mark the valve stem at the center of the trip rod.
THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove THE SWITCH BEING ACTIVATED BY THE STEM THREADS
centered on the mark of the valve stem utilizing a 3/8" COULD RESULT IN A FALSE VALVE OPEN INDICATION.
CAUTION:
An uninsulated section of a single conductor Contacts shown in normal (valve open) condition.
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervi- TYPICAL SWITCH ACTION
sion of the connection in the event that the wire
becomes dislodged from under the terminal.
ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490344
-- Hex Key for Cover Screws and Installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.
Check Valves
Technical Features
• Sizes available (Nominal) : DN50/2”, DN65/21/2”,
DN80/3”, DN100/4”, DN150/6”, DN200/8”,
DN250/10” and DN300/12”
• Pressure data :
Working Pressure : 21 bar (300 psi).
• Working Temperature : 0.0°C to 80.0°C
• Seat Type : Bronze clapper face ring and valve body seat
• Finish : Fusion bonded epoxy coated interior & exterior
• Connections : Flange diameter and thickness according
to ANSI B16.1 Class 125, EN1092-2 PN10 or EN1092-2
PN16
• Specifications : Complys with AWWA C508, clear water-
way design.
FireKing™ is a trademark of The Viking Corporation. Specifications subject to change without notice.
VSR-CR
CORROSION RESISTANT VANE TYPE
WATERFLOW ALARM SWITCH
WITH RETARD
Important:
instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
General Information Enclosure
The VSR-CR switches and retard device are enclosed in a general
sprinkler systems where external corrosion is a concern. It is UL Listed purpose, die-cast housing. The cover is held in place with two tamper
and CUL Listed for use on a steel pipe; schedules 5 through 40, sizes
2" - 6" and is UL and CUL Listed for use on steel pipe; schedules installable cover tamper switch is available as an option which may
10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). See Ordering be used to indicate unauthorized removal of the cover. See bulletin
Information chart. number 5401103 for installation instructions of this switch.
large systems. The VSR-CR contains two single pole, double throw,
snap action switches and an adjustable, instantly recycling pneumatic
(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise
LOAD TO BELL
BREAKER
1. The Model VSR-CR has two switches, one can be used to operate a
central station, proprietary or remote signaling unit, while the other
contact is used to operate a local audible or visual annunciator.
2. For supervised circuits, see “Switch Terminal Connections”
drawing and warning note (Fig. 4). NOTE:
When connecting to a UL Listed
control panel, use the panel’s
resistor value for circuit supervision.
Testing
The frequency of inspection and testing for the Model VSR-CR and its associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
Fig. 6 Mounting Dimensions 5.56 in Fig. 7
3.50 in (141.2 mm)
2.00 in
(89.0 mm) (50.8 mm) GREEN GROUND
SCREWS
2.34 in
(59.4 mm)
PIPE DIA.
SS U-BOLT NUT + 5.25 in
(+ 133.4 mm)
SS U-BOLT WASHER
PIPE
PLASTIC PADDLE DWG. 1146-14
replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection.
pipe
1.
2. Disconnect the power source for local bell (if applicable).
3.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6.
7. Re-install the (2) original mounting screws.
8.
DWG# 1146-10
•
removed or replaced.
1. DESCRIPTION
Viking Pressure Gauges give visual indication of the
-
tem.
3. TECHNICAL DATA
Connection: 1/4” NPT
Working Pressure:
• Water Gauge: 300 PSI (20.7 bar)
• Water Gauge: 600 PSI (41.4 bar)
• Air Gauge: 250 PSI (17.2 bar) (Air gauge includes Water Pressure Gauge Air Pressure Gauge
a “Retard Zone” between 80 and 250 PSI)
Material Standards !
Case and window: Plastic
Bourdon Tube: Bronze
Socket: Brass
Ordering Information
Available since 1977.
300 PSI (20.7 bar) Water Pressure Gauge - VWATERSF
600 PSI (41.4 bar) Water Pressure Gauge - VWATERSF600
250 PSI (17.2 bar) Air Pressure Gauge - VAIRSF
4. INSTALLATION
1. Gauges are to be installed in accordance with the latest published standards of the National Fire Protection Association or other
similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable.
2.
5. AVAILABILITY
The water and air gauges are available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
6. GUARANTEES
Form No. F_052197 19.08.12 Rev 19.1 Revised Form No. F_052197, Rev P65
(Removed Figure 1; revised material standards.)
FIRE PROTECTION
0686EN July 2019
TEST AND DRAIN VALVE
A61 SERIES
Technical data
• Rated pressure: 300 psi
Materials
• Forged brass body
• Chrome plated ball
• Steel handle
• Valve seat in PTFE
• Indication disk in brass
• Sight glasses in polycarbonate
Approvals
Description
A61 Giacomini Test and Drain valve for sprinkler systems combines the H
B
functions of test and drain for wet sprinkler systems.
D
A61 valves have forged brass body with chrome plated brass ball valve and
PORT
PTFE seats. The valves complies with the requirements of NFPA-13, NFPA-
13R and NFPA-13D. The A61 valves are single handle ball valves with three
working positions. They include tamper resistant test orifice and sight glass
A
for the visual control.
Size C (plug) PORT A B C D H
1 1/4” Groove
x
2” Groove
A
Orifice codes
Valves size Size K factor Size C (plug) PORT A B C D H
1/2” 5,6
1 1/4” C
17/32” 8,0
5/8” 11,2
H H
3/4” 14,0 B
7/16” 4,2 D
PORT
1/2” 5,6
17/32” 8,0
MicrofastHP® QUICK
RESPONSE UPRIGHT HIGH
TECHNICAL DATA
PRESSURE SPRINKLER
VK315 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
1. DESCRIPTION
The Viking MicrofastHP® Quick Response Upright High Pressure Sprinkler
VK315 is a small, thermosensitive, glass-bulb spray sprinkler available in
several different finishes and temperature ratings to meet design require-
ments. The special Polyester and Electroless Nickel PTFE (ENT) coatings
can be used in decorative applications where colors are desired. In addition,
these coatings have been investigated for installation in corrosive atmospheres
and are listed/approved as corrosion resistant as indicated in the Approval
Charts.
Refer to Approval Chart 1 and Design Criteria on for cULus Listing requirements.
3. TECHNICAL DATA !
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: 250 psi (17 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric*)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/16” (56 mm)
* Metric K-factor measurment shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
Form No. F_060714 18.10.18 Rev 17.1.P65 Replaces Form No. F_060714 Rev 17.1
(Added P65 Warning.)
Page 2 of 3
MicrofastHP® QUICK
RESPONSE UPRIGHT HIGH
TECHNICAL DATA
PRESSURE SPRINKLER
VK315 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
7. AVAILABILITY
The Viking MicrofastHP® Quick Response Upright High Pressure Sprinkler VK315 is available through a network of domestic and
international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
1 2
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or
suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that
the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
MicrofastHP® QUICK
RESPONSE UPRIGHT HIGH
TECHNICAL DATA
PRESSURE SPRINKLER
VK315 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
(
3
1
SIN
NPT BSP U.S. 2
cULus VdS LPCB
12281 VK315 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B2 -- -- --
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
1 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6
286 °F (141°C)
2 - ENT6
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada
5
Other colors are available on request with the same Listings and Approvals as the standard colors.
6
cULus Listed as corrosion resistant.
The Viking MicrofastHP® Quick Response Upright High Pressure Sprinkler VK315 is cULus Listed as indicated in Approval Chart 1 for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
Form No. F_060714 18.10.18 Rev 17.1.P65 Replaces Form No. F_060714 Rev 17.1
(Added P65 Warning.)
Page 1 of 7
1. DESCRIPTION
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-
profile cover assembly that provides up to ½” (12.7 mm) of vertical adjustment. The
two-piece design allows installation and testing of the sprinkler prior to installation of
the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assem-
bly allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out of
service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been
investigated for installation in corrosive environments and is cULus Listed as indicated
in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the
cover plate is not plated.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
3. TECHNICAL DATA
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Form No. F_103005 18.10.11 Rev 18.2.P65 Replaces Form No. F_103005 Rev 18.2
(Added P65 Warning.)
Page 2 of 7
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-C51000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Maximum
Cover Plate
Temperature Base Part Plate Base Part Plate Base Part Bulb Color
Temperature
Number3 Number3 Number3
1
Temperature2
135 °F (57 °C) cULus
Ordinary 155 °F (68° C) 100 °F (38 °C) 13504 or 218765 13642 or 218755 15394 Red
139 °F (59 °C) FM and LPCB
Intermediate 175 °F (79° C) 150 °F (65° C) 165 °F (74 °C) 13504 or 218765 13642 or 218755 15394 Yellow
Intermediate 200 °F (93° C) 150 °F (65° C) 165 °F (74 °C) 13504 or 21876 5
13642 or 21875 5
15394 Green
5
: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted
Ivory, or Painted Black
Brass and ENT
: ENT
1
The sprinkler temperature rating is stamped on the sprinkler deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
4
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including
the waterway, but the Belleville spring is exposed.
5
Stainless Steel versions are not available with any finishes or paint.
CUSTO
IED M
PL
PA
P
TORY A
INT
COLO
FAC
Maximum
SIN Size
Base Part No. 1
mm U.S. metric2 Pressure cULus5 NYC VdS7 LPCB 12
13503A VK462 1/2” -- 5.6 80.6 175 psi (12 bar) -- -- AY1, CZ1 AY1, BZ1 AY1, CZ18 AY3 --
19785A VK462 1/2” -- 5.6 80.6 175 psi (12 bar) -- -- -- -- -- -- AY2, CZ2
21356A VK462 -- 15 5.6 80.6 175 psi (12 bar) -- -- -- -- -- -- AY2, CZ2
AV1, BX1,
13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AV1, BX16 -- -- -- AY3 --
AS3, BT3
AV1, BX1,
13503JN11 VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AV1, BX16 -- -- -- -- --
AS3, BT3
13667A VK463 1/2” 15 5.6 80.6 250 psi (17.2 bar)3 AV1, BX1 AV1, BX16 -- -- -- -- --
T - 165 °F (74 °C) cover 21876 or 21875 (large diameter) 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique
V - 135 °F (57 °C) cULus Listed cover 13504, 13642 (large
A - 155 °F (68 °C) Brass, Brushed Brass, Brushed Copper, Painted White,
diameter), or 15394 (square cover plate)
B - 175 °F (79 °C) and 200 °F Painted Ivory, or Painted Black
X - 165 °F (74 °C) cover 13504, or 13642 (large diameter)
(93 °C) 2 - Brass
Y - 135 °F (57 °C) cover 13504 LPCB Approved as 139 °F
C - 200 °F (93 °C) (59 °C) 3 - Stainless Steel
Z - 165 °F (74 °C) cover 13504
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
The Water Working Pressure rating is stamped on the deflector.
4
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
approvals.
5
Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
6
Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32.
7
VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021.
8
CE Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40249.
9
The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label.
10
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and
approvals apply for any paint manufacturer. Contact Viking for additional information.
11
cULus Listed as corrosion resistant.
12
MED Certified, Standard 12259-1, EC-certificate 0832-MED-1003.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
• For hazard occupancies up to and including Ordinary Hazard, Group II.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials.
b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-
cies, except in OH4.
NOTES: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
1. Prepare the sprinkler key.
2. Remove the plastic cover.
3. Hold the sprinkler with the wrench and fasten it.
4. Replace the plastic cover and do not remove until the cover is installed.
Maximum
FM Approvals3
SIN
Part No.1
mm U.S. metric2 Pressure
13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AW1, BX1, AY2, BZ2
5
Y - 139 °F (59 °C) cover 21875 or 21876
1 - Polished Chrome, Brushed Chrome, Bright
Z - 165 °F (74 °C) cover 21875 or 21876
Brass, Antique Brass, Brushed Brass,
A - 155 °F (68 °C) W - 139 °F (59 °C) cover 13504, 13642 (large diameter), or
Brushed Copper, Painted White, Painted
B - 175 °F (79 °C) and 200 °F (93 °C) 15394 (square cover plate)
Ivory, or Painted Black
X - 165 °F (74 °C) cover 13504, 13642 (large diameter), or
2 - Stainless Steel
15394 (square cover plate)
1
3
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4
3
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
5
approvals.
4
The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
5
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. N
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
• Protective cap
removed
•
Step 1: Step 2:
frame arms
Maximum
(55 mm)
NOTE:
to approximately 13/16” (21 mm) below the sprinkler body.
Form No. F_103005 18.10.11 Rev 18.2.P65 Replaces Form No. F_103005 Rev 18.2
(Added P65 Warning.)
Page 1 of 6
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
1. DESCRIPTION
The Viking Microfast® Standard/Quick Response Extended Coverage Horizontal
Sidewall Sprinkler VK605 is thermosensitive spray sprinklers available in several dif-
ferent finishes and temperature ratings to meet varying design requirements. The ori-
fice design allows efficient use of available water supplies for hydraulically designed
fire-protection systems. The glass bulb operating element and special deflector
characteristics meet the challenges of quick response extended coverage standards.
The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in
decorative applications where colors are desired. In addition, the Electroless Nickel
PTFE (ENT) coating has been investigated for installation in corrosive environments
and is listed/approved as indicated in the Approval Chart(s).
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that
must be followed. !
3. TECHNICAL DATA
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance require-
ments.
7. AVAILABILITY
Viking Model VK605 is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking
Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
1 2
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
The corrosion-resistant coatings have passed the standard corrosion tests required by the approving agencies as indicated in the Approval Chart.
These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are
compatible with or suitable for the proposed environment. For ENT automatic sprinklers, the waterway is coated. Note that the spring is exposed on
sprinklers with ENT coatings.
4
cULus Listed as corrosion resistant.
5
For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester coatings.
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
1
SIN
U.S. 2
12120 VK605 1/2 15 5.6 80.6 175 psi (12 Bar) 2-11/16 68
3
SIN 6 6
cULus 4
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) B1X, B2X
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This chart shows listings and approvals available at time of printing. Check with the manufacturer for any additional approvals.
4
cULus Listed for use in the U.S. and Canada for Light-Hazard occupancies only.
5
Listings are limited to Light Hazard Occupancies where allowed by the installation standards being applied.
6
For areas of coverage smaller than shown, use the “Minimum Water Supply Requirement” for the next larger area listed. Flows and pressures listed
are per sprinkler.
7
Listed area of coverage measured along ceiling slope. Consult Figure 6 for installation notes.
8
cULus Listed as corrosion resistant.
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
DESIGN CRITERIA
(Also refer to the Approval Chart.)
Microfast® EC/QREC Horizontal Sidewall Sprinkler VK605 is cULus Listed as indicated in the Approval Chart for instal-
lation in accordance with the latest edition of NFPA 13 for extended coverage sidewall spray sprinklers:
• Sprinkler VK605 is cULus Listed for Light Hazard occupancies with smooth, flat, horizontal ceilings. Sprinkler VK605 is also listed for ceilings with
slopes to 4/12 (18.4°), as a QREC “Specific Application Sprinkler”.
• For sprinkler VK605 in sloped ceiling applications, Sections 11.2.3.2.3 and 11.2.3.2.4 of the 2007 Edition of NFPA-13 do not apply regarding System
Area of Operation. Sprinkler VK605 should be installed according to the areas of coverage, and flows and pressures listed in the Approval Chart.
• In sloped ceiling installations, sprinkler VK605 is listed for installation at the high-point intersection of the wall and the ceiling. In sloped ceiling
installations, the spray must be directed down the slope. Spray may NOT be directed across the slope. Refer to Figure 6.
• Listed area of coverage for sloped ceilings corresponds to ceiling slope. (For sloped ceiling applications, actual floor coverage will be less than
the listed area.)
• Refer to the Approval Chart for required deflector distance below the ceiling. Install with the leading edge of the deflector oriented parallel to the
ceiling (see Figure 4).
• Minimum distance from end walls is 4 in. (102 mm).
• Maximum distance from the end wall shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage sidewall spray sprinklers must be followed.
13655
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Cup
NOTES:
1. In sloped ceiling installations, sprinkler VK605 is listed for instal-
lation at the high-point intersection of the wall and the ceiling.
In sloped ceiling installations, the spray must be directed
down the slope. Spray may NOT be directed across the slope.
2. Listed area of coverage for sloped ceilings corresponds to
ceiling slope. (For sloped ceiling applications, actual floor
coverage will be less than the listed area.)
Form No. F_072414 20.06.04 Rev 20.1 Replaces Form No. F_072414 Rev 19.2
(Remove Black PTFE)
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
A155-A156 1 1/2”
Set number Cv
1 4,40
2 6,20
3 6,95
4 7,60
A155 A156
5 7,78
Description 6 8,03
The valves are capable of adjustment to provide a range of the outlet 7 10,09
pressures under flowing condition only.
8 12,70
For Hose Connections to be used on fire protection standpipe system with
maximum working pressure up to 300 PSI. 9 13,91
10 16,63
15 19,67
Versions and product codes
F.O. 28,00
Series Size Type Finishing
4 25,50
5 28,10
Technical data
6 30,05
Materials
• Body: forged brass CuZn40Pb2 in accordance with European Standard EN 7 30,90
12165 CW617N, similar to American Standard ASTM B124 C37700 8 34,08
- Yield stress of the material in the shape of bar: 360 MPa
9 35,78
- Stress for permanent distortion R(0.2): 138 MPa
- Elongation: 10 % 10 37,60
• Bonnet: forged brass CuZn40Pb2 in accordance with European Standard EN 11 38,40
12165 CW617N, similar to American Standard ASTM B124 C37700
12 39,45
• Stem: brass EN 12164 CW614N similar to American Standard ASTM B124 C37700
• Handwheel: red painted aluminum 13 40,45
14 41,80
Approvals 15 43,39
16 46,80
LISTED 12HO 12HO
300 PSI 175 PSI 175 PSI 17 51,20
18 58,36
19 65,60
20 73,32
F.O. 125,00
1
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
Determining the proper outlet pressure A155 - A156 1 1/2” SETTING: 1-6
1- The valves are reducing the downstream water pressure under flowing
(residual) condition only. 150
The valve should not be set to provide less than the minimum pressure
Flow [gpm]
required by NFPA 14 while flowing 250 GPM for 2 1/2” size and 100 GPM for 130
1 1/2” size.
NFPA 14 requires that Standpipe systems shall be hydraulically designed to 110
provide the required water flow rate at a minimum residual pressure of 100
90 set-06
PSI at the outlet of hydraulically most remote 2 1/2” hose connection and 65 set-05
set-04
PSI at the outlet at the hydraulically most remote 1 1/2” hose station.
set-03
70 set-02
There will be a pressure drop due to friction between the outlet and the nozzle.
30
The amount of this loss should be calculated by qualified personnel, to assure 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
that the nozzle receives water pressure sufficient to its design needs. Pressure difference Inlet-Outlet [PSI]
Note that some fire hose nozzles may not operate properly when valve outlet
pressure is set at the 100 PSI minimum authorized in the 2007 edition of NFPA 14.
The installer should consult with the fire authorities concerning pressures A155 - A156 1 1/2” SETTING: 7-F.O.
needed by their equipment.
The outlet pressures indicated in the curves are at the outlet of the valve. 320
F.O.
2- To determine the pressures at the hose nozzle, the hydraulic calculation 300
280
information provided in NFPA. Fire Protection Handbook should be followed.
Flow [gpm]
260
3- The valves are designed and Listed to reduce inlet pressures under flowing 240
conditions: see the following graphs. 220 set-15
Authorities having jurisdiction should be consulted to confirm that the outlet 200
set-10
pressures and flowrates are acceptable. 180
160
set-09
140 set-08
Warning.
120
The graphs are referred only to the indicated conditions of flow and set-07
100
pressure, as tested at Giacomini test station.
80
Should the local codes or the designing Engineer require graphs for
different conditions, or the test procedure on the field is specified, 60
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
please contact the factory or your local representative for alternate Pressure difference Inlet-Outlet [PSI]
graphs to suit field conditions.
450
430
Flow [gpm]
set-10
410
390
set-8
370
350
330 set-6
310
290 set-4
270
250
230
set-2
210
190
170
150 set-1
130
110
90
70
50
30
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Pressure difference Inlet-Outlet [PSI]
set-20
700
680
Flow [gpm]
660
640 set-18
620
600
580
560
540
520 set-16
500
480
460 set-14
440 set-12
420
400
380
360
340
320
300
280
260
240
220
200
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Pressure difference Inlet-Outlet [PSI]
2
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
Installation Dimensions
1- Pipe unions or rubber-gasketed fittings are to be installed immediately A155 - DOUBLE FEMALE - ANGLE
upstream and downstream of the valve to permit easy replacement. A
2- Connect the valve to the piping.
3- Select setting number from proper graph.
4- Close valve hand-tight.
5- Loosen set screw in collar.
6- Rotate indicator-cap untill top collar reaches selected setting number. B
7- Tighten set screw in collar. Valve is now set.
8- To override pressure restriction, pull spring clip. See Fig.1.
• These valves are intended for use in Class III Standpipe systems. D
• Pipe unions or rubber-gasketed fittings are to be installed immediately
upstream of the valve to permit easy replacement. C
• If the valve fail to perform as intended, the valve would need to be replaced.
The valves must be installed on threaded end NPT pipe line using appropriate Size A B C D
tools through the hexagon at the bottom of the body. During the installation 1 1/2” 4 1/32” 7 19/32” 2 5/32” 1 7/8”
pay attention not to deform the bonnet or other valve parts, as this could
2 1/2” 5 1/8” 10 19/32” 3 5/16” 2 5/8”
compromise the valve functioning. By turning the handle counterclockwise,
the valve opens and it closes by turning the handle clockwise. After
installation, verify the tightness through a pressure test. A156 - FEMALE x MALE HOSE THREAD - ANGLE
A
Size A B C D
Maintenance
The valves require no special maintenance. Conduct periodic hydraulic Product specifications
tightness test and check the correct manoeuvrability. In case of damage A155 1 1/2”
of the seal seat or of the bonnet, the valve must be replaced. However it is Angle pressure restricting valves for water pressure control by adjustable flow
recommended to replace the valve after a lifetime of ten years. restriction; forged brass body with 1 1/2” female-female NPT threads and red
painted aluminum, handweel. Rated pressure 175 PSI. Complete with spring
Maintenance and testing should be done in accordance with NFPA 25. clip to override the setting when full flow is required.
1- In the event the valve leaks, the test valve should be opened again to flush A155 2 1/2”
the valve. Angle pressure restricting valves for water pressure control by adjustable flow
2- The valve should be inspected for damage or corrosion annually. restriction; forged brass body with 2 1/2” female-female NPT threads and red
3- The valve is not designed to accept replacement parts. painted aluminum, handweel. Rated pressure 175 PSI. Complete with spring
4- The system should be drained every two to three years and all valves clip to override the setting when full flow is required.
opened fully and lubricant applied to the valve stem. The valve seat should
be inspected for debris. A156 1 1/2”
5- The valve should be operated by hand, never using a torque bar or other Angle pressure restricting valves for water pressure control by adjustable flow
device to exert pressure. Excess torque may damage the seat and or stem, restriction; forged brass body with 1 1/2” female NPT - 1 1/2” male hose thread
disc, and other working parts. and red painted aluminum, handweel. Rated pressure 175 PSI. Complete with
6- If the valve fails to perform as intended, the valve should be replaced. spring clip to override the setting when full flow is required.
A156 2 1/2”
Angle pressure restricting valves for water pressure control by adjustable flow
restriction; forged brass body with 2 1/2” female NPT - 2 1/2” male hose thread
and red painted aluminum, handweel. Rated pressure 175 PSI. Complete with
spring clip to override the setting when full flow is required.
3
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
A155-A156 1 1/2”
Set number Cv
1 4,40
2 6,20
3 6,95
4 7,60
A155 A156
5 7,78
Description 6 8,03
The valves are capable of adjustment to provide a range of the outlet 7 10,09
pressures under flowing condition only.
8 12,70
For Hose Connections to be used on fire protection standpipe system with
maximum working pressure up to 300 PSI. 9 13,91
10 16,63
15 19,67
Versions and product codes
F.O. 28,00
Series Size Type Finishing
4 25,50
5 28,10
Technical data
6 30,05
Materials
• Body: forged brass CuZn40Pb2 in accordance with European Standard EN 7 30,90
12165 CW617N, similar to American Standard ASTM B124 C37700 8 34,08
- Yield stress of the material in the shape of bar: 360 MPa
9 35,78
- Stress for permanent distortion R(0.2): 138 MPa
- Elongation: 10 % 10 37,60
• Bonnet: forged brass CuZn40Pb2 in accordance with European Standard EN 11 38,40
12165 CW617N, similar to American Standard ASTM B124 C37700
12 39,45
• Stem: brass EN 12164 CW614N similar to American Standard ASTM B124 C37700
• Handwheel: red painted aluminum 13 40,45
14 41,80
Approvals 15 43,39
16 46,80
LISTED 12HO 12HO
300 PSI 175 PSI 175 PSI 17 51,20
18 58,36
19 65,60
20 73,32
F.O. 125,00
1
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
Determining the proper outlet pressure A155 - A156 1 1/2” SETTING: 1-6
1- The valves are reducing the downstream water pressure under flowing
(residual) condition only. 150
The valve should not be set to provide less than the minimum pressure
Flow [gpm]
required by NFPA 14 while flowing 250 GPM for 2 1/2” size and 100 GPM for 130
1 1/2” size.
NFPA 14 requires that Standpipe systems shall be hydraulically designed to 110
provide the required water flow rate at a minimum residual pressure of 100
90 set-06
PSI at the outlet of hydraulically most remote 2 1/2” hose connection and 65 set-05
set-04
PSI at the outlet at the hydraulically most remote 1 1/2” hose station.
set-03
70 set-02
There will be a pressure drop due to friction between the outlet and the nozzle.
30
The amount of this loss should be calculated by qualified personnel, to assure 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
that the nozzle receives water pressure sufficient to its design needs. Pressure difference Inlet-Outlet [PSI]
Note that some fire hose nozzles may not operate properly when valve outlet
pressure is set at the 100 PSI minimum authorized in the 2007 edition of NFPA 14.
The installer should consult with the fire authorities concerning pressures A155 - A156 1 1/2” SETTING: 7-F.O.
needed by their equipment.
The outlet pressures indicated in the curves are at the outlet of the valve. 320
F.O.
2- To determine the pressures at the hose nozzle, the hydraulic calculation 300
280
information provided in NFPA. Fire Protection Handbook should be followed.
Flow [gpm]
260
3- The valves are designed and Listed to reduce inlet pressures under flowing 240
conditions: see the following graphs. 220 set-15
Authorities having jurisdiction should be consulted to confirm that the outlet 200
set-10
pressures and flowrates are acceptable. 180
160
set-09
140 set-08
Warning.
120
The graphs are referred only to the indicated conditions of flow and set-07
100
pressure, as tested at Giacomini test station.
80
Should the local codes or the designing Engineer require graphs for
different conditions, or the test procedure on the field is specified, 60
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
please contact the factory or your local representative for alternate Pressure difference Inlet-Outlet [PSI]
graphs to suit field conditions.
450
430
Flow [gpm]
set-10
410
390
set-8
370
350
330 set-6
310
290 set-4
270
250
230
set-2
210
190
170
150 set-1
130
110
90
70
50
30
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Pressure difference Inlet-Outlet [PSI]
set-20
700
680
Flow [gpm]
660
640 set-18
620
600
580
560
540
520 set-16
500
480
460 set-14
440 set-12
420
400
380
360
340
320
300
280
260
240
220
200
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Pressure difference Inlet-Outlet [PSI]
2
FIRE PROTECTION
0692EN September 2017
PRESSURE RESTRICTING ANGLE VALVES
A155 AND A156 SERIES
Installation Dimensions
1- Pipe unions or rubber-gasketed fittings are to be installed immediately A155 - DOUBLE FEMALE - ANGLE
upstream and downstream of the valve to permit easy replacement. A
2- Connect the valve to the piping.
3- Select setting number from proper graph.
4- Close valve hand-tight.
5- Loosen set screw in collar.
6- Rotate indicator-cap untill top collar reaches selected setting number. B
7- Tighten set screw in collar. Valve is now set.
8- To override pressure restriction, pull spring clip. See Fig.1.
• These valves are intended for use in Class III Standpipe systems. D
• Pipe unions or rubber-gasketed fittings are to be installed immediately
upstream of the valve to permit easy replacement. C
• If the valve fail to perform as intended, the valve would need to be replaced.
The valves must be installed on threaded end NPT pipe line using appropriate Size A B C D
tools through the hexagon at the bottom of the body. During the installation 1 1/2” 4 1/32” 7 19/32” 2 5/32” 1 7/8”
pay attention not to deform the bonnet or other valve parts, as this could
2 1/2” 5 1/8” 10 19/32” 3 5/16” 2 5/8”
compromise the valve functioning. By turning the handle counterclockwise,
the valve opens and it closes by turning the handle clockwise. After
installation, verify the tightness through a pressure test. A156 - FEMALE x MALE HOSE THREAD - ANGLE
A
Size A B C D
Maintenance
The valves require no special maintenance. Conduct periodic hydraulic Product specifications
tightness test and check the correct manoeuvrability. In case of damage A155 1 1/2”
of the seal seat or of the bonnet, the valve must be replaced. However it is Angle pressure restricting valves for water pressure control by adjustable flow
recommended to replace the valve after a lifetime of ten years. restriction; forged brass body with 1 1/2” female-female NPT threads and red
painted aluminum, handweel. Rated pressure 175 PSI. Complete with spring
Maintenance and testing should be done in accordance with NFPA 25. clip to override the setting when full flow is required.
1- In the event the valve leaks, the test valve should be opened again to flush A155 2 1/2”
the valve. Angle pressure restricting valves for water pressure control by adjustable flow
2- The valve should be inspected for damage or corrosion annually. restriction; forged brass body with 2 1/2” female-female NPT threads and red
3- The valve is not designed to accept replacement parts. painted aluminum, handweel. Rated pressure 175 PSI. Complete with spring
4- The system should be drained every two to three years and all valves clip to override the setting when full flow is required.
opened fully and lubricant applied to the valve stem. The valve seat should
be inspected for debris. A156 1 1/2”
5- The valve should be operated by hand, never using a torque bar or other Angle pressure restricting valves for water pressure control by adjustable flow
device to exert pressure. Excess torque may damage the seat and or stem, restriction; forged brass body with 1 1/2” female NPT - 1 1/2” male hose thread
disc, and other working parts. and red painted aluminum, handweel. Rated pressure 175 PSI. Complete with
6- If the valve fails to perform as intended, the valve should be replaced. spring clip to override the setting when full flow is required.
A156 2 1/2”
Angle pressure restricting valves for water pressure control by adjustable flow
restriction; forged brass body with 2 1/2” female NPT - 2 1/2” male hose thread
and red painted aluminum, handweel. Rated pressure 175 PSI. Complete with
spring clip to override the setting when full flow is required.
3
BALL VALVES
0149EN March 2020
VALVE FOR WATER FOR HEATING/COOLING SYSTEMS
AND NOT DANGEROUS GAS
STANDARD PORT - R250D SERIES
Description
Ball valve, with female-female threaded connections.
Standard port.
R250D
1
BALL VALVES
0149EN March 2020
VALVE FOR WATER FOR HEATING/COOLING SYSTEMS
AND NOT DANGEROUS GAS
STANDARD PORT - R250D SERIES
Technical data
Main features and materials Field of applications
• Suitable for water for heating/cooling systems and not dangerous gas • Min. working temperature: -20 °C with 50 % glycol solutions
• Standard port • Max. working temperature with dry saturated steam:
• Valve made of UNI EN 12165 CW617N rough or chrome plated brass 185 °C with 1,05 MPa (10,5 bar)
• Stem with double O-Ring • Max. working pressure at 20 °C with water and not dangerous gas:
• Nut with anti-corrosion coating, with guarantee seal and hologram 4,2 MPa (42 bar) for 1/4”, 3/8”, 1/2”, 3/4”
• Steel lever handle with anti-corrosion treatment and red PVC coating 3,5 MPa (35 bar) for 1”, 1-1/4”, 1-1/2”, 2”
2,8 MPa (28 bar) for 2-1/2”, 3”, 4”
Dimensions and Kv
Product code DN A [mm] I [mm] B [mm] J [mm] C [mm] H [mm] Kv
B
R250ZX006 28 84 42 82 28 94 wr.48 73,5
J
R250ZX007 35 93 46 100 33 136 wr.55 105
Product specifications
R250D - Red lever
Ball valve, with female-female threaded connections. Suitable for water for heating/cooling systems and not dangerous gas. Valve made of UNI EN 12165 CW617N
rough or chrome plated brass. Standard port. Steel lever handle with anti-corrosion treatment and red PVC coating. Stem with double O-Ring. Nut with anti-
corrosion coating, with guarantee seal and hologram. Min. working temperature: -20 °C with 50 % glycol solutions. Max. working temperature with dry saturated
steam: 185 °C with 1,05 MPa (10,5 bar). Max. working pressure at 20 °C with water and not dangerous gas: 4,2 MPa (42 bar) for 1/4”, 3/8”, 1/2”, 3/4”; 3,5 MPa (35 bar)
for 1”, 1-1/4”, 1-1/2”, 2”; 2,8 MPa (28 bar) for 2-1/2”, 3”, 4”.
2
BALL VALVES
0149EN March 2020
VALVE FOR DANGEROUS GAS AND LIQUID HYDROCARBONS
STANDARD PORT - R250D SERIES
Description
Ball valve, with female-female threaded connections.
Standard port.
R250D
Technical data
Main features and materials Field of applications
• Suitable for dangerous gas and liquid hydrocarbons* • Temperature range: -20÷60 °C
• Standard port • Max. working pressure at 20 °C with liquid hydrocarbons*: 1,2 MPa (12 bar)
• Valve made of UNI EN 12165 CW617N chrome plated brass • Max. operating pressure (MOP) with gas: 0,5 MPa (5 bar)
• Stem with double O-Ring
• Nut with anti-corrosion coating, with guarantee seal and hologram * Please consult Giacomini technical support, to check the compatibility of the
• Steel lever handle with anti-corrosion treatment and yellow PVC coating product with the specific hydrocarbon.
3
BALL VALVES
0149EN March 2020
VALVE FOR DANGEROUS GAS AND LIQUID HYDROCARBONS
STANDARD PORT - R250D SERIES
Dimensions
Product code DN A [mm] I [mm] B [mm] J [mm] C [mm] H [mm]
R250X021 8 43 21 36 10 43 wr.17
R250X022 10 46 23 45 13 77 wr.21
R250X023 14 54 27 49 15 77 wr.25
R250X024 18 63 31 64 18 94 wr.32
R250X025 22 75 38 73 23 94 wr.39
R250X026 28 84 42 82 28 94 wr.48
B
R250X031 90 207 104 207 77 187 wr.122
J
R250ZX061 8 43 21 36 10 43 wr.17
R250ZX062 10 46 23 45 13 77 wr.21
I
A
R250ZX063 14 54 27 49 15 77 wr.25
R250ZX064 18 63 31 64 18 94 wr.32
R250ZX065 22 75 38 73 23 94 wr.39
R250ZX066 28 84 42 82 28 94 wr.48
Product specifications
R250D - Yellow lever
Ball valve, with female-female threaded connections. Suitable for dangerous gas and liquid hydrocarbons. Valve made of UNI EN 12165 CW617N chrome plated
brass. Standard port. Steel lever handle with anti-corrosion treatment and yellow PVC coating. Stem with double O-Ring. Nut with anti-corrosion coating, with
guarantee seal and hologram. Temperature range: -20÷60 °C. Max. working pressure at 20 °C with liquid hydrocarbons: 1,2 MPa (12 bar). Max. operating pressure
(MOP) with gas: 0,5 MPa (5 bar).
Additional information
For more information, go to www.giacomini.com or contact our technical assistance service: +39 0322 923372 +39 0322 923255 consulenza.prodotti@giacomini.com
This document provides only general indications. Giacomini S.p.A. may change at any time, without notice and for technical or commercial reasons, the items included herewith.
The information included in this technical sheet do not exempt the user from strictly complying with the rules and good practice standards in force.
Giacomini S.p.A. Via per Alzo, 39 - 28017 San Maurizio d’Opaglio (NO) Italy
4