Trip Time Calculations

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

REU615 (Overvoltage Relay)

Curve Type: Inv. Curve B


Parameters for calculation of time for Inv. Curve
B
A 480 U 1.4
B 32 U> 1.16
C 0.5 k 0.5
D 0.035
E 2

Calculation of Trip Time in Seconds


(U-U>)/U> 0.206897
((B*(U-U>)/U>)-C)^2 37.46284
t(s) = k*A/((B*(U-U>)/U>)-C)^2+D 6.441348

Ref: Page1146 of 615 Series Technical Manual


k 3
M 1.338
V/Hz> 1.15
top 20.20569 1.338583
7SJ602 (Thermal Overload) of ATB-02 & ATB-03
Calculated Trip time
I(applied) 3 Formula:
Tcon 13 Trip Time (min) = Tcon *
k 1.14 LN 〖 (𝐼𝑎𝑝𝑝/(𝑘∗𝐼𝑛)) 〗 ^2/( 〖 (𝐼𝑎𝑝𝑝/(
In 1 𝑘∗𝐼𝑛)) 〗 ^2−1)
Trip Time (min) 2.02738
Trip Time (s) 121.6428
7SJ602 (Thermal Overload) of T-5 & T-6
Calculated Trip time
I(applied) 3 Formula:
Tcon 10 Trip Time (min) = Tcon *
k 1.1 LN 〖 (𝐼𝑎𝑝𝑝/(𝑘∗𝐼𝑛)) 〗 ^2/( 〖 (𝐼𝑎𝑝𝑝/(
In 1 𝑘∗𝐼𝑛)) 〗 ^2−1)
Trip Time (min) 1.443837
Trip Time (s) 86.63023

You might also like