IEC62591 Flash Firmware (W68280) Release Notes

March 2021

IEC62591 Flash Firmware Release Notes


(W68280)
Version: 1.23 11-March-2021

Description
This document describes release 1.23 of the IEC62591 Flash Firmware Image (W68280). It describes the items addressed in
this release, details compatibilities, provides upgrade instructions, and includes a revision history.

Items Addressed
 Resolved field devices malfunction issue (SCR SmtIO00000847)
 Added debug bits for error condition monitoring (SCR SmtIO00000853)
 Resolved compatibility for THUM with Rosemount® 8732 Flow Transmitter sub device (SCR SmtIO00000851, SN
156717)

Compatibility
Item Part Number Version / Revision
ICE62591 Module Assembly 400181-01-0 C
ROC800/L Boot ROM Image W68232 2.01 or greater
ROC800 Flash Image W68233 3.85 or greater
ROC800 CPU Module W48093 A
ROC800 Fixed Backplane W48072 B
ROC800 CPU Backplane W48090 A
ROC800 I/O Backplane W48091 A
ROC800L Flash Image W68258 1.65 or greater
FB107 Boot ROM Image W68181 1.00 or greater
FB107 Flash Image W68182 1.85 or greater
FB107 CPU Module W40159 A/B
FB107 Backplane W48085 A/B/C/D
ROCLINK 800 W68130 2.61 or greater
ControlWave Micro Firmware XXXXXX 5.92

www.Emerson.com/SupportNet
IEC62591 Flash Firmware (W68280) Release Notes
March 2021

Known Limitations and/or Issues


 After certain network failures, the module may not recover requiring the removal and re-insertion of the module.

Firmware Update Instructions


1. Create a folder named Upgrade in the root of the USB drive (such as ”F:\Upgrade”).
2. Copy firmware file (ras-wihart-1.23-release.zip) to upgrade folder.
3. Insert USB drive in the USB port on IEC62591 module.
4. Connect to the LOI port of the ROC/FloBoss using ROCLINK 800.
5. Collect and save all data and configuration files.
6. Select Upgrade Firmware from the Utilities menu.
7. The upgrade process displays its stages; wait until a dialog displays indicating the upgrade has competed.
8. Remove the USB drive.

Change History
Version 1.22 (30-August-2019)
 Resolved issue with transmitter statuses not properly clearing in radio failure scenarios (SCR SmtIO00000827,
SupportNet 147582)
 Resolved issue with IEC module status freeze and transmitter value freeze occurrences (SCR SmtIO00000828,
SupportNet 148824)
 Resolved issue with the IEC module not properly recovering from IEC Server Failure Alarms scenarios (SCR
SmtIO00000833, SupportNet 150024)

Version 1.21 (21-March-2019)


 Added support for Rosemount 928 Gas Monitor (SCR SmrIO00000818)
 Disabled event notification feature in transmitters addressing multiple issues (SCR SmtIO00000825, SupportNet
146108 & 146078):
o Increased transmitters’ “sleep time” to extend battery life
o Reduced amount of time to commission devices and enter the bursting mode
o Enabled the connection of multiple 705 transmitters on the same network

Version 1.20 (05-November-2018)


 Added support for Rosemount WPG45 Wireless Pressure Gauge transmitter
 Added support for Rosemount 705 Totalizing Flowmeter transmitter (SCR SmtIO00000670)
 Added compatibility for new hardware/software version of 648 X-well temperature transmitter (SCR SmtIO00000812)
 Added sub device info in live list (SCR SmtIO00000757)
 Added additional parameters for configuring burst mode operation (SCR SmtIO00000556, SCR SmtIO00000799,
SCR SmtIO00000809)
 Added support for retrieving and acknowledging device events (SCR SmtIO00000676)
 Delayed bursting until device is commissioned (SCR SmtIO00000492)
 Enhanced the ability to retrieve logs via USB flash drive (SCR SmtIO00000813, SCR SmtIO00000663)

Version 1.12 (30-August-2016)


 “More Status Available” now handled by OpenEnterprise (SCR SmtIO00000783)
 Reconfigures THUM Sub Device when network issues occur (SCR SmtIO00000775)
 Fixed inconsistency with Device Status Updates (SCR SmtIO00000763)
 Resolved intermittent communication not enabling bursting with THUM Sub Devices (SCR SmtIO00000703).

2 www.Emerson.com/SupportNet
IEC62591 Flash Firmware (W68280) Release Notes
March 2021

Version 1.11 (25-February-2015)


 Updated radio interface software providing ETSI Compliance (SCR SmtIO00000665)
 Enhanced module firmware to allow HART Passthru on empty networks (SCR SmtIO00000360)
 Capped Network ID to the maximum value of 36863 (SCR SmtIO00000662)
 Enhanced USB boot up process (SCR SmtIO00000669)
 Eliminated the possibly of the transmitters recognizing multiple join keys (SCR SmtIO00000655)
 Eliminated the possibility of unpredictable module operation due to extreme clock changes (SCR SmtIO00000667)
 Enhanced memory and communication management for more reliable module operation (SCR SmtIO00000642,
SmtIO00000605)
 Prevented updating of transmitter values through the controllers when the transmitter is not actively communicating
(SCR SmtIO00000537)
 Enhanced diagnostics data by updating Error Device Status for transmitters with commissioning issues (SCR
SmtIO00000352)
 Eliminated the potential of stale data by pushing all variables to the controller on cold start (SCR SmtIO00000621)
 Enhanced the handling of tags on THUM sub-devices (SCR SmtIO00000657)
 Enhanced the process of pulling diagnostic logs (SCR SmtIO00000462)
 Added protection against Shellshock vulnerability (SCR SmtIO00000677)

Version 1.10 (20-August-2014)


 Added support for Discrete Input/Output Transmitters (see Product Data Sheet for list of supported transmitters).
 Added option allowing user to enable Active Advertising to decrease join time.
 Added support for Process Variable Health.
 Improved communication stability and performance with RTU.
 Improved reliability for Field Upgrades.

Version 1.02 (05-May-2014)


 Eliminated the possibility of IEC module lockup when writing diagnostic logs to memory (SCR SmtIO00000607).

Version 1.01 (05-January-2013)


 Enhanced communication between application code and HART server to detect and prevent lockups.

Version 1.00 (26-July-2012)


 Initial Release.

3 www.Emerson.com/SupportNet
IEC62591 Flash Firmware (W68280) Release Notes
March 2021

www.facebook.com/RemoteAutomationSolutions

www.twitter.com/Emerson_RAS

www.youtube.com/c/RemoteAutomationSolutions

© 2010-2021 Emerson Automation Solutions. All rights reserved.

The contents of this publication are presented for informational purposes only. While every
effort has been made to ensure informational accuracy, they are not to be construed as
warranties or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. Emerson Automation Solutions reserves the right to modify
Emerson Automation Solutions or improve the designs or specifications of such products at any time without notice. All sales
Remote Automation Solutions are governed by Emerson Automation Solutions’ terms and conditions which are available upon
6005 Rogerdale Road request. Emerson Automation Solutions does not assume responsibility for the selection, use or
Houston, Texas 77072 maintenance of any product. Responsibility for proper selection, use and maintenance of any
www.Emerson.com/RemoteAutomation Emerson Automation Solutions product remains solely with the purchaser and end-user.

www.Emerson.com/SupportNet

You might also like