Earting Equipment
Earting Equipment
Ref . E7
August 2005
Estates
Technical Services Team
1.0 Introduction p3
5.1 MV p6
5.2 LV p7
This Technical Policy Statement sets out the technical requirements for
earthing the College’s main MV and LV electrical distribution equipment.
At the South Kensington campus the MV networks are privately owned by
Imperial College and operated on their behalf by EDF Energy. EDF also
operate the CHP plant, which is embedded into the 11kV system. Therefore,
it is important for Consultants and Contractors to understand and adhere to
this established practice and, under no circumstance, introduce dissimilar
earthing systems. At other campuses where the Imperial College supply is
usually taken at LV the MV network provider will largely determine the
earthing requirements. A typical arrangement for substation earthing at the
South Kensington campus is shown in Appendix 1
2.1.3 Continuity of the MV earth is made at each substation via the steel wire
armour (SWA) of the MV feeder cables. Where practical, two additional
earth electrodes shall be connected to the substation earth bar, each with a
target earth resistance of ≤ 10 ohms.
2.1.4 At each substation the incoming cable SWA shall first be bonded to the
switchgear earth bar via the cable gland earth tag. For ring main units
(RMUs) a separate earth conductor shall be made from the switchgear earth
bar to the substation main earth bar. Where the MV switchgear is of the
panel type an earth bar running the length of the switchboard shall be
provided and two connections made to the substation earth, one at each end.
2.1.5 Transformers are provided with either two earth tangs or bosses and
these shall be bonded directly to the substation main earth bar. If the
transformer is controlled by a close coupled RMU the MV switchgear earth
can be bonded directly to the transformer earth conductor.
2.1.7 If the substation is located away from ground or, basement level, then
the main MV earth shall be provided by the feeder cable SWA. In addition,
separate, insulated, earth conductors of ≥ 70 mm² Cu shall be run with each
feeder cable and bonded to the incoming MV switchgear earth bar and at the
other end to either a) the corresponding switchgear earth or b) the nearest
ground, or basement level, substation main earth bar providing it is part of
the same MV network..
2.2.1 The 6.6kV network is supported from the 11kV system via two
10MVA transformers and is isolated from the 11kV earth by virtue of the
Dy11 transformation. The star windings of these transformers are solidly
earthed to the College earth mass and separate earth electrodes.
2.2.2 In addition, the two 4.75MVA CHP generators are each separately
earthed via 5A 10s neutral earthing resistors. These are in circuit only when
the machines are running up to speed; once synchronised they are
disconnected and the 6.6kV earths described in 2.2.1 become effective.
2.1 Where transformers are located in outdoor enclosures all metal posts,
palings and chain link fencing or other forms of metalwork construction shall
be bonded together and then to the substation main earth using an insulated
conductor ≥ 70 mm² Cu. Gates shall be bonded to the enclosure earthing
system using braided Cu conductor and suitable clamps.
3.1 Whether supplied from the 11kV or 6.6kV network, the main LV bus-bar
is usually incorporated in the LV switchboard, which is then bonded to the
substation main earth. Therefore, the MV and LV earths are effectively
bonded together.
3.2 Earth systems shall be TN-S. Systems utilising combined neutral and
earth conductors (CNE) shall not be used at the South Kensington campus.
3.3 A separate earth conductor, ≥ 70 mm² Cu, shall be installed between each
transformer LV bus-bar section of the switchboard earth bar and the
substation main earth bus-bar.
3.5 The range of zero sequence impedance, Zo, at the main LV bus-bars is
0.007 to 0.012 ohms. Actual fault levels for individual substations are
available on request from Imperial College Estates Engineering Team or
EDF site office
4.0 LV Neutral Earths
4.1 The neutral connection to earth shall be made within the main LV
switchboard and be effected by removable links at each incoming
transformer circuit breaker. The connection to the switchboard earth bar
shall be via copper links of c.s.a. not less than the earth bar.
4.2 The arrangement of 4.1 enables restricted earth fault (REF) current
transformers (CTs) to be installed at each transformer incoming panel.
Neutrals shall not be earthed at transformer star points as this would require
an additional CT at this point.
4.3 The single point earthing achieved by 4.1 facilitates all power sources,
transformers and generators, to be controlled by 3-pole, solid neutral circuit
breakers.
5.1 MV
5.1.3 The earthed end of the earthing resistor shall normally be bonded to the
nearest substation main earth. If the nearest main earth is too distant, then a
local earth electrode shall be installed with an earth resistance ≤ 10 ohms
5.2 LV
5.2.3 With this arrangement there is no requirement for circuit breakers with
switched neutrals.
6.1 Metal cable ladder rack, traywork, trunking, conduits and supporting
metalwork shall be bonded to the substation main earth.
6.2 Distribution gear within substations shall be bonded to the main earth bar
6.3 Lightning conductors and earthing pits shall not be sought as a means to
provide the earthing requirements of paragraph 2.1.3. Bonding to lightning
earthing grids shall only be made for substations located at roof level as
described in paragraph 2.1.8
6.1 The network supplier will determine this. If not a TN-S system a TN-C-
S is often offered as an alternative. Combined protective conductor and
neutral systems (TN-C) extended into the College’s installation are not
permitted. Currents on the outer conductor of cables produced for this
arrangement are likely to cause interference with sensitive scientific
instruments e.g. electron microscopes.
6.2 Greenfield sites requiring substations to provide exclusive supplies to
Imperial College premises shall be earthed as described above for the main
South Kensington campus. An exception would be the provision of separate
MV and LV earths where required by the network provider. In this case a
buried earth system comprising of electrodes supplemented, if necessary, by
bare copper conductors with a measured earth resistance of ≤ 1ohm shall be
installed for the LV earth. Bonding of MV and LV earths will be at the
discretion of the network provider.
6.3 Electrical installations shall be in accordance with BS 7671.