Professional Documents
Culture Documents
Instruction Manual High-Impedance Differential Protection IED GR200 Series (GRH200)
Instruction Manual High-Impedance Differential Protection IED GR200 Series (GRH200)
03)
Instruction manual
Safety Precautions
Before using this equipment, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GR
equipment. Before installing and using the equipment, this chapter must be thoroughly read
and understood.
Explanation of symbols used
Signal words such as DANGER, WARNING, and CAUTION, will be followed by
important safety information that must be carefully reviewed.
DANGER
•Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to
be opened while the primary system is live. Opening the CT circuit will produce a
dangerously high voltage.
WARNING
•Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage
generated is dangerous.
•Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
•Fiber optic
CLASS 1 LASER PRODUCT.
ii
6F2S1958 (0.03)
CAUTION
•Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
•Operating environment
The equipment must only be used within the range of ambient temperature, humidity and
dust detailed in the specification and in an environment free of abnormal vibration.
•Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check
that they conform to the equipment ratings.
•Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is
on, as this may cause the equipment to malfunction.
•External circuit
When connecting the output contacts of the equipment to an external circuit, carefully
check the supply voltage used in order to prevent the connected circuit from overheating.
•Connection cable
Carefully handle the connection cable without applying excessive force.
•Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
•Short-wire (Short-bar)
Do not remove the short-wire/short-bar(s) connected to the frame earth (FG) at the terminal
block on the rear of cases.
•Electric wire between #35 - #37 on the power-supply terminal block
Make sure the wire is connected.
(Exception: This wire needs to be detached for performing the dielectric voltage test.)
iii
6F2S1958 (0.03)
•Disposal
This equipment contains neither expendable supplies nor parts that can be recycled. When
disposing of this equipment, the customer must contact an operator responsible for
industrial waste disposal, and request that the operator dispose of this equipment in
accordance with the local waste disposal regulations; otherwise the person who disposes
of this equipment may be punished under local regulations. When disposing of this
equipment is practiced by the customer acting on their own behalf, it must be done so in a
safe manner according to local regulations. For further information in terms of the disposal,
the customer shall contact to a local dealer and sales staff at Toshiba Energy Systems &
Solutions Corporation (Toshiba ESS, Japan).
This equipment contains neither expendable supplies nor recyclables.
•Plastics material
This equipment contains the following plastics material.
- ABS, Polycarbonate, Acrylic resins, Nylon 66, and others.
•Equipment operation
The user shall have responsibilities to use and install the equipment where the
specifications are designated by the manufacture. Never operate the equipment on the
condition where the manufacture cannot intend. Otherwise, the safety function furnished
into the equipment may not be operated properly.
•Symbols
Symbol Description
iv
6F2S1958 (0.03)
•Copyright
© Toshiba Energy Systems & Solutions Corporation 2021.
All rights reserved.
•Registered Trademarks
Product/Equipment names (mentioned herein) may be trademarks of their respective
companies.
v
6F2S1958 (0.03)
Contents
1 Introduction ......................................................................................................................................... 1
Configuration of high impedance relay ....................................................................................... 2
Control and monitoring application ............................................................................................. 3
Monitoring and recording functions ............................................................................................ 4
Hardware overview....................................................................................................................... 5
Symbols used in logical diagrams ................................................................................................ 6
Abbreviation................................................................................................................................ 10
Function Block (FB), Function ID, Signal number (Data ID) .................................................. 12
2 Relay application ............................................................................................................................... 14
High-impedance differential protection (DIFHZ)...................................................................... 15
2.1.1 Principle of high-impedance differential protection .......................................................... 15
2.1.2 Current transformer requirements .................................................................................... 17
2.1.3 Setting guide ........................................................................................................................ 17
2.1.4 Three phases high-impedance differential protection (DIF) ............................................. 19
2.1.5 Single phase restricted earth fault protection (REF) ........................................................ 22
2.1.6 Cold load Protection (CL) .................................................................................................... 24
2.1.7 Settings ................................................................................................................................ 27
2.1.8 Signals.................................................................................................................................. 28
Three-phase trip circuit (TRC) ................................................................................................... 31
2.2.1 Scheme logic ........................................................................................................................ 33
2.2.2 Setting .................................................................................................................................. 35
2.2.3 Signals.................................................................................................................................. 36
3 General control function .................................................................................................................... 38
Control scheme ........................................................................................................................... 39
Control mode ............................................................................................................................... 42
3.2.1 Select-before-operation mode (SBO) ................................................................................... 42
3.2.2 Direct-operation mode (DIR) ............................................................................................... 43
Control hierarchy........................................................................................................................ 45
3.3.1 Control level and control point ........................................................................................... 46
3.3.2 Selector switches and bay operations ................................................................................. 46
3.3.3 Programming of control-right distributions ....................................................................... 46
Common controls (CMNCTRL) .................................................................................................. 48
3.4.1 Double command blocking (DCB) ....................................................................................... 49
3.4.2 PLC_BIT/UNIT/BOOL signal ............................................................................................. 51
3.4.3 Provision of selected status ................................................................................................. 51
3.4.4 Miscellaneous settings ........................................................................................................ 51
3.4.5 Setting .................................................................................................................................. 53
3.4.6 Signal ................................................................................................................................... 55
vi
6F2S1958 (0.03)
vii
6F2S1958 (0.03)
viii
6F2S1958 (0.03)
ix
6F2S1958 (0.03)
x
6F2S1958 (0.03)
xi
6F2S1958 (0.03)
xii
6F2S1958 (0.03)
xiii
6F2S1958 (0.03)
xiv
6F2S1958 (0.03)
1 Introduction
Contents Page
Abbreviation 12 Hardware overview 5
Busbar application 2 Monitoring and metering functions 4
Control 3 Symbols used in logical diagrams 6
Function identifies and signals (FB) 12
The differential protection relay in GRH200 is an over current relay. GRH200 takes differential
current Id flowing on the differential circuit via a varistor unit, which converts developed
differential voltage Vd to differential current Id.
Ide
Busbar
Phase-A
Phase-B High impedance relay
Phase-C
Transformer
GRH200
Ida
Idb
Figure 1.1-1 High impedance relay composed with GRH200 and varistor units
Monitoring function:
This function supervises status of protection functions, and displays power system quantities.
It also shows failure information in the CT.
Hardware overview
The IED has human machine interface (HMI), which is made of LCD screen, indication lights,
operation and function keys, monitoring jacks, and a USB connector. Voltage, current input
terminals, and binary input and output circuits are provided on the rear..
HMI features:
- Menu-driven human interfaces for settings or viewing of stored data.
- A standard LCD or a large LCD (MIMIC) screen, LEDs, function keys and operation keys
Communication features:
- USB for GR-TIEMS
- 100BASE-TX(or FX) for SAS in the IEC 61850 protocol
- RS485 or the fiber optic I/F in the IEC 60870-5-103 protocol
3. Marked with : PLC connection points designated by Element ID and its name
Element ID (or Signal No.) Signal name corresponding to Element or Signal No.(Data ID)
Note that the symbol can be used for the reception point coming from the output of PLC
logics.
4. Marked with : Mapping points designated by Signal No. (Data ID) and its name
Signal number (Data ID) Signal name corresponding to Signal No. (Data ID)
1Note that the symbol can be used as a signal reception-point coming from the SAS. The
reception point is mapped to the LN of the IEC61850.
XXX
t 0
Variable timer (XXX ─ YYY: Setting range)
XXX ─ YYY
Delayed drop-off timer
0 t Fixed timer (XXX: Set time)
XXX
0 t
Variable timer (XXX ─ YYY: Setting range)
XXX ─YYY
One-shot timer
A Output A
A B Output
A
1 1 1
& Output
B 1 0 0
0 1 0
0 0 0
OR gate
A B Output
A
1 1 1
≥1 Output
B 1 0 1
0 1 1
0 0 0
XOR gate
A B Output
A
1 1 0
=1 Output
B 1 0 1
0 1 1
0 0 0
Signal inversion
A Output
0 1
A 1 Output
1 0
A S 0 0 No change
Output 1 0 1
B R 0 1 0
1 1 0
Switch Output
+ Output
On On 1
Off 0
Abbreviation
Abbreviation Description
ADC Analog to digital converter
CB Circuit Breaker
CT Current Transformer
DS Disconnecting Switch
EF Earth Fault
ES Earthing Switch
LCD Liquid Crystal Display for IED screen (standard LCD screen)
NA Not Applicable
SC Station Computer
Abbreviation Description
UTC Coordinated Universal Time
VT Voltage Transformer
FB (Function ID=123456)
80000xxxx0 8000xxxxxx
A & ≥1 XX1_OPT
81000xxxx1
XX1 B &
82000xxxx2
C
&
Element ID Signal name
&
8000011xxx0 XX_BLOCK 1
2 Relay application
Contents Pages
Three phases high-impedance differential
15
protection (DIF)
Single phase restricted earth fault
22
protection (REF)
Cold load protection (CL) 24
Trip circuit (TRC) 31
The fault current develops a high differential voltage (Vd) across the relay unit. To suppress
the high differential voltage being developed, it is usual to install a varistor unit for the relay
unit.
Equivalent circuit
High
CT1 i1 CT2 i2 Vd R impedance
relay
Incoming Incoming
side ZE R ZE side
Busbar Fault
In this case, the CT secondary current is circulating around the CT secondary circuit and is
not entering into the high impedance relay unit. In Figure 2.1-2, Vd is the differential voltage
and is developed due to the unbalanced circulating current in the CTs; and thus, the relay does
not operate.
Equivalent circuit
High
CT1 i1 CT2 i2 Vd R impedance
relay
Incoming Out going
side ZE R ZE side
Busbar
CT3 i3
Fault
In such condition, a differential voltage Vd will be generated due to the flowing current and
the impedance of incoming terminals and an outgoing terminal on the secondary circuit [RS +
RL].
where,
RS: Resistance of CT secondary winding
RL: Resistance of secondary wiring for CT connecting lead loop – worst case
The differential voltage will be generated in the event of an external fault. The DIF relay
settings must be considered in order to avoid the unwanted-operation because of that
differential voltage, accordingly.
Equivalent circuit
High
CT1 i1 CT2 i2 Vd R impedance
relay
RS + RL
CT3 is
saturated
For an internal fault case, current transformer(s) have to produce sufficient output to operate
the relay. Therefore, take care for any current transformer ratio errors and ensure a high speed
of operation the current transformers.
Step1: Calculation of setting values so that the DIF relay does not operate
unnecessarily in an external fault with CT saturation condition.
As described in section 2.1.1(iii), the DIF function of high impedance relay must be set in order
not to operate with the differential voltage during the external fault with CT saturation.
The differential voltage, Vd developed during the external fault with CT saturation, can be
calculated using the equation (2.1-1):
IFmax
Vd = (R S + R L ) × (2.1-1)
N
If the operation of the DIF relay is based on the voltage, a setting value Vset can be
calculated using the equation (2.1-2) shown below, wherein, K1 represents a safety factor.
Furthermore, the Vset should be set less than at least half of the CT knee point voltage Vk
shown in the equation (2.1-3).
Vset ≥ K1 × Vd (2.1-2)
Vk
Vset ≤ (2.1-3)
2
Meanwhile, the GRH200 is a current relay, actually; hence, the setting value of the DIF relay
should be determined by the Iset expressed by the equation (2.1-4).
I
(R S +R L )× Fmax
Iset =
Vset
→ Iset ≥ K1 × N (2.1-4)
RV RV
where,
Vd: High differential voltage developed due to the fault current
Vset: Voltage correspond to current setting value for relay operation
Vk: CT knee-point voltage
Iset: Current setting value for relay operation
IFmax: Maximum through fault current
RS: Resistance of CT secondary winding
RL: Resistance of secondary wiring for CT connecting lead loop – worst case
N: CT ratio
RV: Resistance of varistor unit
K1: Safety factor – for the GRH200, K1=1.2
Factor K1 is associated with the design of the GRH200 relay. The K1 relates to its inherent
capability to block the unidirectional transient component of the fault current.
There is another inherent safety factor in addition to the factor K1, because it is an extreme
case of unbalance that the basic assumption of complete saturation of one current transformer
with no ratio error of the complementary one.
In practice, it is unlikely to occur such as when one current transformer begins to saturate,
and its burden is transferred to the other current transformer(s). It is an obvious fact that they
are made of the same components, and they may carry the same secondary voltage.
Step2: Check that the DIF relay can operate with the minimum current in an
internal fault
When the setting value Iset is calculated on the Step1, the equation (2.1-5) gives the
minimum current value of the CT primary side at which the DIF relay can operate:
If the below equation (2.1-6) is satisfied, the DIF relay is able to operate with the minimum
current for an internal fault.
Imin: Minimum current value on the CT primary side when the relay can operate
n: Number of current transformers connected to GRH200
Ie: Value of current transformer secondary excitation current at calculated voltage
Vset in Step1
Ir: Varistor current at calculated voltage Vset, this is obtained from the varistor V-I
characteristic†
Iset: Calculated current setting value in step1
IFmin: Minimum internal fault current on the CT primary side
8000011B60
≥1
DIF1-OR
TDIF1 To TRC
8000011C20 8000011B67 8800011B20
t 0
DIF1 A DIF-OPT-A
8100011C21 & & 8100011B68 ≥1 8900011B21
t 0
B DIF-OPT-B
8200011C22 & & 8200011B69 ≥1 8A00011B22
t 0
C DIF-OPT-C
& & ≥1
0.00-300.00s 8000011B6D 8300011B64
DIF1-EN On
≥1 ≥1
DIF-OPT
8100011B61
TDIF-S2 8000011B27
DIF2-OR t 0
≥1 DIF-S2-OPT
&
TDIF2 0.00-300.00s
8400011C24 8400011B6A
t 0
DIF2 A
8500011C25 & & 8500011B6B
t 0 DIF-S2-EN On
B
8600011C26 & & 8600011B6C
C t 0
& &
0.00-300.00s 8400011B6E
DIF2-EN On
≥1
8000011BB0
800001EBB0 DIF1-TP_BLOCK 1
8000011BB1 ≥1
800001EBB1 DIF2-TP_BLOCK 1
800001EBB2 ≥1
800001EBB2 DIF-TP_BLOCK
DIF-SV-DET 800001EBB3
800001EBB3 DIF_BLOCK DIF_BLOCK
Trip signal
In case of fault occurrences, the DIF1 and DIF2 operations are taken by single-phase
basis, but those outputs are integrated into a signal of three-phase basis—called “DIF-
TRIP” signal†. It is combined with other trip signals in the trip circuit (TRC). The TRC
is discussed later.
The operation of DIF relay will be blocked when a supervisory signal (DIF-SV-DET) is
generated using PLC.
8000041B60
≥1
DIF-SV-OR
TDIF-SV
8000041C20 8000041B61
t 0
DIF-SV A
≥1
DIF-SV-DET
8100041C21 & &
t 0
B
8200041C22 & & 8000061B60
t 0
C
& & ≥1
DIF-REF-SV-DET
0.10-60.00s
DIF-SV-EN On
From REF
8000041BB0 REF-SV-DET
800004EBB0 DIF-SV_BLOCK 1
≥1
DIF_BLOCK
From Test
AMF_OFF 1
If the monitoring function is not required, the user can terminate the operation using PLC
connection point “DIF-SV_BLOCK”. The monitoring function can also be stopped when the
AMF_OFF signal† is injected.
†Note:The user can switch off the monitoring function during the test. To generate the
AMF_OFF signal, set Off for setting [A.M.F]. For the operation, see chapter User
interface: Test sub-menu.
8000021BB0
800002EBB0 REF1-TP_BLOCK 1
8000021BB1 ≥1
800002EBB1 REF2-TP_BLOCK 1
8000021BB2 ≥1
800002EBB2 REF-TP_BLOCK
8000021BB3
800002EBB3 REF_BLOCK REF_BLOCK
Trip signal
In case of fault occurrences, the REF1 and REF2 operations are taken by single-phase
basis, but those outputs are integrated into a signal of three-phase basis—called
“REF-TRIP” signal†. It is combined with other trip signals in the trip circuit (TRC).
The TRC is discussed later.
spuriousness in the differential current is feasible during the CT circuit failure. The user can
introduce the time delay in the operation using the setting [TREF-SV]. To operate the REF-SV
function, the user should set scheme switch [REF-SV-EN] On; setting [CHK_ID] is also
provided to set the monitoring level.
The REF operation will be blocked when a supervisory signal (REF-SV-DET‡) is generated
using PLC.
TREF-SV To DIF
8000041C20 8000051B60
t 0
REF-SV
& &
REF-SV-DET
0.10-60.00s
REF-SV-EN On
8000051BB0
800005EBB0 REF-SV_BLOCK 1
≥1
REF_BLOCK
From Test
AMF_OFF 1
If the monitoring function is not required, the user can terminate the operation using PLC
connection point “REF-SV_BLOCK”. The monitoring function can also be stopped when the
AMF_OFF signal† is injected.
†Note:The user can switch off the monitoring function during the test. To generate the
AMF_OFF signal, set Off for setting [A.M.F]. For the operation, see chapter User
interface: Test sub-menu.
Off
CL
CL-Test Non-CL
1
8000031BB1
800003EBB1 CLP_BLOCK 1
CB_FOR_CLP
(CB closing command)
CL STATE
(Cold load state) [TCLP]
CB close
CB_FOR_CLP
CB open
(CB contact signal)
CL STATE
(Cold load state) [TCLR] [TCLE]
The cold load state judgement has the forcible control function to generate or not generate “CL
STATE” signal compulsorily, and it can be controlled by using the [CL-Test] switch.
Example
Following techniques show an example of how to change the operation value of high
impedance protection during cold load state. The cold load protection is realized by using
the DIF1 protection function for the normal state, whereas it is realized by using DIF2
protection function for the cold load state.
As a result, the DIF1 protection function will be blocked, but the DIF2 protection
function will be living in the cold load state.
≥1
DIF1-OR
TDIF1
t 0
DIF1 A
& &
t 0
B
& &
t 0
C
& &
0.00-300.00s
DIF1-EN On
DIF2-OR
≥1
TDIF2
t 0
DIF2 A
& &
t 0
B
& &
C t 0
& &
0.00-300.00s
DIF2-EN On
2.1.7 Settings
DIFHZ (Function ID: 415001)
Setting items Range Unit Contents Defaultt Note
CL-TEST Off / CL / Non-CL Forcibly establishing the cold load condition Off
2.1.8 Signals
DIFHZ (Function ID: 415001)
DIF connection points
Element ID Name Description
800004EBB0 DIF-SV_BLOCK DIF Supervision protection block command
CL connection points
Element ID Name Description
800003EBB0 CB_FOR_CLP CB closed signal for CL judgement
8000021B65 REF1-OPT
8100021B66 REF2-OPT
DIF-OPT-C OPT-TRIP-C
REF-TRIP
REF
GEN.TRIP_ALARM
Alarm signal
OPT.PHASE-A Recording
generation
OPT.PHASE-B function
OPT.PHASE-C
OPT.PHASE-N
The TRC logic has PLC connection points to collect alternate trip signals. For example, if the
user wishes to trip the CB by the output of an external relay, the user has to connect the
alternate trip signals to the TRC logic using the following PLC connection points: TRIP-A_ADD,
TRIP-B_ADD, TRIP-C_ADD and TRIP_ADD.
8300001B63
Protection
functions OPT-TRIP
OPT-TRIP ≥1
8000001B60
830000EBB2 ADD_OPT_COM
8000001B60
Trip-command collection scheme
OPT-TRIP-A
8100001B61
OPT-TRIP-B ≥1
8200001B62
8300001B78 To CB
OPT-TRIP-C
8300001B63 & ≥1 TRIP COMMAND
OPT-TRIP
810000EBB1 ADD-FS
≥1
820000EBB0 USE-FS 1
reliability of tripping further, then the PLC connection points ‘ADD-FS’ and ‘USE-FS’ can be
used in the Trip-signal generation scheme. That is, the external check signal is connected at
the ‘ADD-FS’ point; the ‘On/Off ’ state of the external relay should also be connected using
‘USE-FS’.
8100001B67
DIF-OPT-B ≥1 8000001B72
OPT-BR &
≥1 OPT.PHASE-B
890000EBB9 OPT.P-B_ADD
8200001B68
8000001B73
DIF-OPT-C OPT-CR ≥1 &
OPT.PHASE-C
≥1
8A0000EBBA OPT.P-C_ADD
8000001B74
8400001B69 &
OPT.PHASE-N
OPT-ABR
≥1
OPT-BCR
≥1
8D0000EBBC OPT.P-BC_ADD
8600001B6B
OPT-CAR
≥1
8E0000EBBD OPT.P-CA_ADD
8400001B64
GEN.ALARM ≥1
≥1
840000EBB7 OPT-ALARM_ADD
800000EBBE OPT.P-N_ADD
When an additional relay, external to the IED is utilized, an alarm signal can be
provided, indicating for example a Line-to-Line (LL) fault and others. If the user
wishes to record the alarm, then PLC connection points ‘OPT.P-A_ADD’ and
others can be used. If the additional relay is designed to operate for a ground
fault, use the alternative PLC connection point ‘OPT.P-N_ADD’
2.2.2 Setting
(No setting items exist)
2.2.3 Signals
Signal monitoring points
TRC-D (Function ID: 4A1001)
Element ID Name Description
8100001BB1 ADD_FS Additional fail-safe command
810000EBB1 ADD_FS Reception of the result signal of the check relay (fail-safe)
Control scheme
Figure 3.1-1 shows the control overview for the control function; there are two control stages:
“Wait for a command” and “Receiving commands”. The function will wait for a command from
the server in the first stage. During the receiving stage, the function will respond to “Select”,
“Cancel”, and “Operate” commands. Specific logic is provided for each command for each
receiving stage. A decision is required from each logic block to move to the next step (i.e., ‘Failed’
or ‘Success’). When a ‘success’ decision is determined in the operate logic, the respective
command is issued to the relevant device; the device commences with its operation (for example,
a 43-switch is changed to “ON” from “OFF”). The waiting and receiving stages loop around at
the receipt of every command.
Waiting stage
The type of control can be categorized in accordance with its origin, (Remote/Local/PLC)
and modes (SBO/DIR). That is, the respective control scheme should respond to the respective
origin and mode. The user should be aware of the context of the control action, “On (or Closing)
control” and “Off (or Open) control” in relationship to its origin and mode†.
†Note:The “On control” and “Off control” can be found in the SPOS and other functions.
For more information on these functions, see the explanations provided for each
respective function.
Control mode
Either Select-Before-operation (SBO) or Direct-Operate-control (DIR) is provided as a control
mode for the device. The user can select the preferred control mode.
SBOw
Selection Command
Answer#1 R esponse
Oper. Command
Operation
Answer#2 R esponse
Process Server IE D
(SAS) (Control function) Target device
Selection SBOw
Command
Answer Response
Oper.
Operation
Command
Answer
Response
Process SAS IE D
(Server) (Control function) Target device
Oper.
Operation Command
Answer#1 R esponse
Device status changed
Answer#2 Command
termination
R esult
SAS IE D
Process
(Server) Control function Target device
Operation
Control
Command
Answer#1
Response
Control hierarchy
It is important that the user understand the meaning of the terms ‘control-right’ and ‘control-
hierarchy’ in connection with the functioning of the control and monitoring applications in the
sub-station automation system (SAS) and the sub-station control and monitoring system
(SCMS). For instance, when we wish to operate a device (such as a piece of switchgear or
others), the system has the device forbidden to operate if the system is unable to give a ‘control-
right’ for the device using the ‘control-hierarchy’. Figure 3.3-1 depicts the control-hierarchy;
the control-hierarchy is made of three control-levels, two selector-switches, and three control-
points. Either control command of three control-points is permitted so that the other
commands will be forbidden in the system. On this account, no collision of control-points exists
within the system.
Control-point in RCC
Network level
Control-point in OWS/EWS
Communication
EWS OWS
Selector switch
(43R) RCC EWS/OWS
Station level
Control-point in LCP
ON/OFF operation on LCD(MIMIC)
Bay level
Control-right
Switchgear and others
Control levels Selector switches Control points and positions of selector switches
The part ○
1 and ○
2 logics are programmed so that, the control-right signal can be
distributed to the respective control applications. With regard to the SPOS01 function, PLC
connection point “SPOS01IN_TMP_28” has been programmed using DOUT_BOOL feature (for
example). Therefore, the control-right signal is transferred to the select and operate-condition
logic‡ when the user connects the control-hierarchy with the SPOS01 function using
“SPOS01IN_TMP_28”.
‡Note:The select-condition and operate-condition logic are used to decide upon the
execution of a select command or an operate command in the SPOS01 function.
For more detail, see chapter Control and monitoring application: SPOS function:
Operate condition and Select condition. DPOS and TOPS have similar logics; the
user is required to do the connection.
○
1 Checking the bay level ○
3 Distribution of the control-right
SPOS01_CTRL_RIGHT for Control & Monitor
RemoteLocalKey_43BCU
From LOCMT DOUT_BOOL
DIN_UNIT UNIT_TO_BOOL FID ST
LRSW01_LR_ST FID DO
DTYPE
(530001 3109001001) DTYPE ST
DID
DID
DI
To SPOS01
510001 820101ED50 SPOS01IN_TMP_28 Select
condition logic
SPOS02_CTRL_RIGHT
DOUT_BOOL
Operate
FID ST
condition logic
DTYPE
○
2 Distribution of the control-right DID
DI
for General controls To SPOS02
LEDR_CTRL_RIGHT
DOUT_BOOL 510001 820102ED50 SPOS02IN_TMP_28 Select
FID ST
condition logic
DTYPE
DID Operate
condition logic
DI
To LEDR
DPOS01_CTRL_RIGHT
528001 820701ED50 LEDR01_CTRL_RIGHT Select DOUT_BOOL
condition logic FID ST
DTYPE
Operate
condition logic DID
GCNT_CTRL_RIGHT
DI
DOUT_BOOL To DPOS01
FID ST
DTYPE 512001 820301ED50 DPOS01IN_TMP_28 Select
DID condition logic
DI DPOS02_CTRL_RIGHT Operate
To GCNT DOUT_BOOL condition logic
540001 800E00ED5A GCNT01IN_TMP_51 FID ST
Select
DTYPE
condition logic
DID
Operate
DI
condition logic To DPOS02
512001 820302ED50 DPOS02IN_TMP_28 Select
condition logic
Operate
condition logic
TPOS01_CTRL_RIGHT
DOUT_BOOL
FID ST
DTYPE
DID
DI
To TPOS02
513001 810401ED50 TPOS02IN_TMP_21 Select
condition logic
TPOS02_CTRL_RIGHT Operate
DOUT_BOOL condition logic
FID ST
DTYPE
DID
DI
To TPOS02
513001 810402ED50 TPOS02IN_TMP_21 Select
condition logic
Operate
condition logic
SPOS20 function
SPOS20_STD_RPT
DPOS function
≥1
Reception of “DCB”
DPOS01 function
DPOS72 function
DPOS72_STD_RPT
TPOS function
SOFTSW function
In Figure 3.4-1, the CMNCTRL1 function generates a message denoted with the number
1; Figure 3.4-2 exemplifies that the IED-1 generates the “stVal” message 1. In addition, IEDs-
2 to -10 are also required to receive message 1, this is denoted with the number 2. For
IEC61850 communication, the “stVal” messages 1 and 2 are carried by GOOSE publish and
GOOSE subscribe. Thus, for all IEDs (i.e., IED-1 to IED-10 of Figure 3.4-2), it is required to
set the GOOSE publish destination corresponding to the message.
1 2 2 2
Figure 3.4-3 demonstrates how the GOOSE publish destination is set with regard to the
DCB message. The user is required to set the destination for each respective IED by selecting
the signal “DCB SND OR”, corresponding to the GOOSE publish, this must be performed at
the respective screens in GR-TIEMS†. That is, the user should select the “stVal” item for each
IED. After setting, the user should write the setting date for each respective IED.
○
1 Selected IED
○2 Required settings in
the respective IEDs.
CMNCTRL2
function
PLC_O_BIT_0201 For
・Event record function
5A0101 800200EF40 PLC_BIT_0201 (5A0101 8002001F40)
・Communication (required mapping)
Information ・LEDs
cascaded§ ・IED screen display
・Binary output module
etc…
†Note:The user should recognize that the reason messages are only available for
operation with the GCS1000 control system manufactured by Toshiba.
3.4.5 Setting
CMNCTRL (FunctionID:5A0001)
Setting items Range Unit Contents Default Note
3.4.6 Signal
PLC connection points
CMNCTRL (Function ID: 5A0001)
Element ID Name Description
800800EDE1 ADD_DCB_SND Additional condition for double command blocking
800800EFB7 LAN_CONN_FAIL_IN
… …. …
800800EFB8 TIME_SYN_FAIL_IN
8008001FB7 LAN_CONN_FAIL
8008001FB8 TIME_SYN_FAIL
… …. …
…. …. ….
…. …. ….
Local to remote
&
1≥
If the user does not touch the
operation/function keys on the front panel &
within 35 min. in the local control, the IED
will be changed for the remote control
unconditionally.
†Note:As a rule, the control commands have parameters. For example, the “Off to On”
and “On to Off” control directions that are used in commands are pre-configured
as parameters in the communication protocol. Note that the parameters vary
depending upon the respective protocol used, such as IEC61850 and others. For
IEC61850, Table 3.5-1 shows the parameters defined: the rule for control direction
can be found in “ctlVal”, the command publisher is recognized using the parameter
“origin”. For more information about the parameters, see Appendix IEC61850
MICS, PICS, PIXIT and TICS.
Figure 3.5-2 Example of user-preferred control scheme using PLC user logic
Note: The user-preferred control scheme implemented by users can only be operated in
the DIR mode.
3.5.5 Signal
Signal monitoring points
LOCRMT_SW (Function ID: 530001)
Element ID Name Description
3109001001 LRSW01_LR_ST S43BCU state
1Note: For the operation, see Chapter User interface: Outline. Note that pressing the
“CLEAR” key causes the Reset of the LEDs.
2Note: For more information, see Chapter Engineering tool.
Operate logic
0 t
Failed
0.3s
Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL
[LEDDR1_EN]
On
Table 3.6-2 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
Operate logic
Operate command
Operate logic
“Do nothing”
Operation Failed
Failed Do nothing
Failed Do nothing
Cancel logic
Cancel command
Cancel logic
Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL
From KEYINPUT
240001 31000E1730
LEDR_KEY_CLEAR
CLEAR
[LEDDR1_EN]
On
Figure 3.6-9 Settings for LED-03 circuit provided by “Setting I/O menu” of GR-TIEMS
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.
Table 3.6-5 Mapping signals required for LEDRs object for LLN0
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/LLN0$LEDRs$Oper ctlVal BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper ctlNum INT8U CO
Ctrl/LLN0$LEDRs$Oper T Timestamp CO
Ctrl/LLN0$LEDRs$Oper Test BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper Check Check CO 5280017007016D08 LEDR01_CONTROL_REQ
Ctrl/LLN0$LEDRs$Oper$origin orCat orCategory CO
Ctrl/LLN0$LEDRs$Oper$origin orIdent Octet64 CO
Ctrl/LLN0$LEDRs ctlModel ctlModel CF
Ctrl/LLN0$LEDRs sboClass sboClass CF
3.6.6 Setting
Reset Control (Function ID: 528001)
Setting items Range Unit Contents Default Note
3.6.7 Signal
Signal monitoring points
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
8007011D53 LEDR01_SC Select command
Mapping point
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
7007016D08 LEDR01_CONTROL_REQ Dev01 control request
Closed/Open signals
GCNT01_ CNT_ VAL
Inputs 320E 011D20
Changes in device status
(e.g., operations of 43S) BI 540001 800E 01E DE 0 GCNT01_ PLC_ SGNL GCNT01
Signal acquisition timing must be adjusted in accordance with the application, in that the
acquisition should be regulated for the nature of the signal; hence, several settings are
provided in the GCNT functions. Thirty-two independent GCNT counters† are available. That
is, counters GCNT01 to GCNT32† can operate simultaneously. The values counted are stored
in the non-volatile memory so that they are not erased if the power supply to the IED is
interrupted.
For simplicity, only the GCNT01 function is discussed; the features in the remaining GCNT02–
GCNT32 functions are identical to the GCNT01 function.
a. On (Closed) signals
Counter 1 2 … n …
Counter 1 2 … n …
Counter 1 2 … n …
CNTMAX] and set a user-preferred value. Note that the user can set the maximum number
from 9 to 2147483647.
Counter
10 10 10
5 5 5
Operate logic
Operate command
Operate logic
Output signal to BO
The GCNT01 function can issue a “Complete” signal at the output point
“GCNT01_SLD_CSCN”, when the GCNT01 function determines that the input signal
“Remote-Reset-Control” is true. If the GCNT01 function determines that the “Remote-Reset-
Control” is not true, the GCNTS01 function returns to the “Wait for a command” stage.
[GCNT01-HMI]
On
[DPOS01-EN]
On
Table 3.7-3 PLC Connection point (Input signals from the control hierarchy logic)
Signal Number Signal Name Description M/O
Table 3.7-4 PLC Monitoring points (Signal “select complete/ failed” for BIO)
Signal Number Signal Name Description
540001 000E011D91 GCNT01_TMP_01 GCNT01 count change selected signal(stSeld) for SAS
540001 000E021D91 GCNT02_TMP_01 GCNT02 count change selected signal(stSeld) for SAS
540001 000E031D91 GCNT03_TMP_01 GCNT03 count change selected signal(stSeld) for SAS
540001 000E041D91 GCNT04_TMP_01 GCNT04 count change selected signal(stSeld) for SAS
… … …
540001 000E201D91 GCNT32_TMP_01 GCNT32 count change selected signal(stSeld) for SAS
Operate logic
Operate command
Operate logic
Output signal to BO
The GCNT01 function can issue a “Success to cancel” signal at the monitoring point
“GCNT01_CC_SSCN”, when the GCNT01 function has determined that the signal “Remote-
cancel” is true. Another signal “Operation failed” is issued if the function is able to determine
that the signal “Remote-cancel” is not true.
Input Cancel logic in GCNT01 Output
“Do nothing”
Operation Failed
Failed Do nothing
Output signal to BO
The GCNT01 function, in Figure 3.7-11, can provide a signal at the point “GCNT01_OK_CSC”,
when the GCNT01 function determines that the signal “Remote-Reset-Control” is true.
Input Operate logic in GCNT01 Output
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
Statics-counter
Failed Do nothing
Counter
10:48 1/8
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0
Output signal to BO
The GCNT01 function can provide a signal at the point “GCNT01_OK_CSC”, when the new
value applied from the sub-menu is appropriate.
[GCNT01-HMI]
On
[DPOS01-EN]
On
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
Origin
ctlmodel (choice ”SBOes or SBOns” )
Table 3.7-9 Mapping signals required for GIGO3302 object in GCNT01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$origin orCat orCategory ST 540001300e011D23 GCNT01_CNT_ORCAT
Ctrl/GGIO3302$ISCSO$origin orIdent Octet64 ST 5400016A0e011FA7 GCNT01_CNT_ORIDENT
Ctrl/GGIO3302$ISCSO stVal INT32 ST 540001320e011D20 GCNT01_CNT_VAL
Ctrl/GGIO3302$ISCSO q Quality ST 3010013110041005 Qual_Val
Ctrl/GGIO3302$ISCSO t Timestamp ST 2003019010001006 SYS_TIME
Ctrl/GGIO3302$ISCSO stSeld BOOLEAN ST 540001000E011D91 GCNT01_TMP_01
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.
Table 3.7-10 Mapping signals required for ISCSO object for GIGO3302
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO3302$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO3302$ISCSO$Oper T Timestamp CO
Ctrl/GGIO3302$ISCSO$Oper Test BOOLEAN CO
Ctrl/GGIO3302$ISCSO$Oper Check Check CO 540001 700E016D09 GCNT01_CMM_REQ
Ctrl/GGIO3302$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO3302$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO3302$ISCSO ctlModel ctlModel CF
Ctrl/GGIO3302$ISCSO sboClass sboClass CF
Check “Input”
3.7.5 Setting
Counter (Function ID: 540001)
Setting items Range Unit Contents Default Note
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The number of counters in the GCNT depends on IED model. We omit the setting
tables of GCNT04 etc. because the setting items are the same except the device
number.
3.7.6 Signal
Signal monitoring points in GCNT01
GCNT (Function ID: 540001)
Element ID Name Description
000E001F41 GCNT00_CCTRL_COUNTER GCNT00 cmnctrl counter correction summarize
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the GCNT function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “GCNT02_CTR_SGUCN” point
for the 2nd device, use the description of “GCNT01_CTR_SGUCN” in place
of “GCNT02_CTR_SGUCN”. The user can obtain the ID value of
3.8.1 Function
(i) Mode sensor
The MDCTRL function can monitor the state change (On to TEST / TEST to Off) in the IED.
To use this monitoring function, On should be set for the scheme switch [MDCTRL-EN] prior to
operation. During the operation, a select signal and an operate signal are provided for the
TEST-FB when the SAS provides a test command for the IED; hence, the MDCTRL function
comes with two time-out timers. Setting [MDCTRL-SELRST] provides a time-out timer for
canceling a select command; setting [MDCTRL-EXERST] provides a time-out timer for
canceling an operate command.
Table 3.8-2 PLC connection point (Input signal for select condition logic)
Signal Number Signal Name Description M/O
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Table 3.8-4 Mapping signals required for LLNO object in MDCTRL01 function
Object_reference Attribute Type FC Signal Number Signal Name
System/LLN0$Mod$SBOw ctlVal Mod CO
System/LLN0$Mod$SBOw ctlNum INT8U CO
System/LLN0$Mod$SBOw T Timestamp CO
System/LLN0$Mod$SBOw Test BOOLEAN CO
System/LLN0$Mod$SBOw Check Check CO
System/LLN0$Mod$SBOw$origin orCat orCategory CO
System/LLN0$Mod$SBOw$origin orIdent Octet64 CO
System/LLN0$Mod$Oper ctlVal Mod CO
System/LLN0$Mod$Oper ctlNum INT8U CO
System/LLN0$Mod$Oper T Timestamp CO
System/LLN0$Mod$Oper Test BOOLEAN CO
System/LLN0$Mod$Oper Check Check CO 5500017013016D08 MDCTRL01_CONTROL_REQ
System/LLN0$Mod$Oper$origin orCat orCategory CO
System/LLN0$Mod$Oper$origin orIdent Octet64 CO
System/LLN0$Mod$Cancel ctlVal Mod CO
System/LLN0$Mod$Cancel ctlNum INT8U CO
System/LLN0$Mod$Cancel T Timestamp CO
System/LLN0$Mod$Cancel Test BOOLEAN CO
System/LLN0$Mod$Cancel$origin orCat orCategory CO
System/LLN0$Mod$Cancel$origin orIdent Octet64 CO
System/LLN0$Mod ctlModel ctlModel CF
System/LLN0$Mod sboTimeout INT32U CF
System/LLN0$Mod sboClass sboClass CF
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Check “Input”
3.8.3 Setting
3.8.4 Signal
Signal monitoring point
MDCTRL(Function ID: 550001)
Element ID Name Description
8013011D55 MDCTRL01_EC_OWS MDCTRL01 execute command by OWS(HMI)
8313011E89 MODE01_OEC_F_CS MDCTRL01 Test direction execute command fail condition signal
Mapping point
MDCTRL(Function ID: 550001)
Element ID Name Description
7013016D08 MDCTRL01_CONTROL_REQ MDCTRL01 correction request from cmm
A number of devices can be controlled separately, i.e. the SPOS function has separate sets
of logic for control (i.e., SPOS01, SPOS02 etc. functions). For simplicity, only the SPOS01
function is discussed here; the features in the SPOS02 etc. functions are identical to the
SPOS01 function.
†Note:Binary IO module has binary input circuits (BIs) and binary output circuits (BOs);
the user makes the connection between the SPOS01 function and the binary IO
module using a signal number (is made of a function ID and an “Element ID”).The
signal name and number of the SPOS01 function are listed later.
Tips: If the user wishes to apply the SPOS function quickly, go to sections 4.1.4 and
4.1.5, where setting of the BI and BO circuits and the mapping of signals for IEC
61850 communication is described.
Cancel logic
Select command Off from remote-end
Output signal to BO
The SPOS01 function can issue an output “Selection success” signal at the output point
“SPOS01_OSL_BO_CSF”, when the SPOS01 function determines that the “Remote-ON-
Control” signal received is true. If the SPOS01 function determines that the “Remote-ON-
Control” signal is not true, the SPOS01 function returns to the “Wait for a command” stage.
Cancel logic
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The SPOS01 function, in Figure 4.1-4, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF” when the SPOS01 function determines that the “Select command Off
(Remote-OFF-Control)” signal is true. If the SPOS01 function determines that the “Remote-
OFF-Control” signal is not true, the SPOS01 function returns to the “Wait for a command”
stage.
Cancel logic
Cancel command
Select command On from remote-end
0.6s
[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_OSL_BO_CSF”.
Note: The signal “SPOS01_OSL_BO_CSF” is the same as the signal shown in Figure
4.1-2. If the “Local-ON-Control” signal is not true, the SPOS01 function returns to
the “Wait for a command” stage.
Cancel logic
Select command On from remote-end Cancel command
Cancel logic
Select command On from front panel
0.6s
[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other SPOS logics, see Table 4.1-8.
Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_FSL_BO_CSF”.
1Note: The signal “SPOS01_FSL_BO_CSF” is the same as the signal shown in Figure
4.1-4. If the “Local-OFF-Control” signal is not true, the SPOS01 function returns
to the “Wait for a command” stage.
Cancel logic
Cancel command
Select command On from remote-end
Operate logic
Select command On by PLC
Failed Operate command
function
command not requiring the interlock check. That is, for the SPOS01 function, when the “select
command ‘On’ (PLC-On-Control) signal generated in the user-programmed logic is applied, and
when the interlock check is required in the select logic, use the connection point (PLC#1;e.g.,
DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2); e.g., DEV01_CL_COMMAND”. PLC#1 and PLC#2 are shown in
510001 7001016D08
Table 4.1-1.
Signals from user-PLC logic Selection logic in SPOS01 Output
1≥ &
ON-control command requiring ILK checking† To “Wait for a next
For DIR operation
(PLC#1 connection point) command”
Operate command
To BO connection
510001 800101EE33 DEV01_CL_INTERLOCK with ILK† condition
& “SPOS01_OSL_BO_CSF”
(510001_8601011DC6)
ILK† condition (“ON”) passed DIR
SPOS01-On 0 t Selection “success”
0.1s
ON-control command requiring no ILK checking† For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Selection “Failed”
510001 800101EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s
DIR
Output signal to BO
The SPOS01 function, in Figure 4.1-10, can issue a “Select success” signal at the output-point
“SPOS01_OSL_BO_CSF”1.
1Note: The signal “SPOS01_OSL_BO_CSF” is the same as that shown in Figure 4.1-2.
Cancel logic
Cancel command
Select command On from remote-end
Operate logic
Select command On by the PLC
function Operate command
1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
510001 800101EE31 Operate command with To BO connection
DEV01_OP_INTERLOCK
ILK† condition & “SPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (510001_8601011DC6)
SPOS01-Off 0 t Selection “success”
0.1s
OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Selection “Failed”
510001 800101EE30 DEV01_OP_COMMAND &
without ILK† condition 0.6s
Select condition‡
Output signal to BO
The SPOS01 function, in Figure 4.1-12, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF”1.
1Note: The output point “SPOS01_FSL_BO_CSF” is the same signal as shown in Figure
4.1-4.
[SPOS01-CTREN]
On
4Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a command
is not identical to “IED test status”.
5Note: The “Event suppression” function can detect chattering on BI circuits. (See section
4.1.4(i)-2)
6Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
7Note: The common control (CMNCTRL) function can test and check the ‘On’ and ‘Off”
operations performed by the logic. When the user sets Off for scheme switch
(SCDEN), the operation of the logic is blocked if the logic is running in the same
operation- direction compared with the previous operation direction. (i.e., when
On (Off) is performed sequentially). On the other hand, if On is set for the scheme
switch, the logic is not blocked.
8Note: The user will need to program the PLC logic “Control hierarchy condition” The
user is also required to connect the logic condition with the select condition logic
using the connection point “SPOS01IN_TMP_28”. For more information, see
chapter “Control and monitoring application: Control hierarchy” see PLC#3 of
Table 4.1-6.
9Note: To identify the input point of the other SPOS, see Table 4.1-6 for PLC#1 and
PLC#2.
Table 4.1-1 PLC connection points (Input points for command ‘On’)
Signal Number Signal Name Description M/O
Table 4.1-2 PLC connection points (Input points for command ‘Off’)
Signal Number Signal Name Description M/O
570001 3101011DA0 SPOS01-Off SPOS01 interlock condition for Off control. N/A
570001 3101021DA0 SPOS02-Off SPOS02 interlock condition for Off control. N/A
570001 3101031DA0 SPOS03-Off SPOS03 interlock condition for Off control. N/A
…. …. ….
570001 3101141DA0 SPOS020-Off SPOS20 interlock condition for Off control. N/A
570001 3101011DA2 SPOS01-On SPOS01 interlock condition for On control. N/A
570001 3101021DA2 SPOS02-On SPOS02 interlock condition for On control. N/A
570001 3101031DA2 SPOS03-On SPOS03 interlock condition for On control. N/A
…. …. ….
570001 3101141DA2 SPOS20-On SPOS20 interlock condition for On control. N/A
Table 4.1-6 PLC connection points (Input signal for select condition logic)
Signal Number Signal Name Description M/O
…. …. ….
510001 800114EE61 SPOS20IN_TMP_31 SPOS20 additional failure condition (PLC#1) O
510001 810101EE62 SPOS01IN_TMP_32 SPOS01 user configurable select condition (PLC#2) O
510001 810102EE62 SPOS02IN_TMP_32 SPOS02 user configurable select condition (PLC#2) O
510001 810103EE62 SPOS03IN_TMP_32 SPOS03 user configurable select condition (PLC#2) O
…. …. ….
510001 810114EE62 SPOS20IN_TMP_32 SPOS20 user configurable select condition (PLC#2) O
510001 820101ED50 SPOS01IN_TMP_28 SPOS01 control hierarchy condition (PLC#3) M
510001 820102ED50 SPOS02IN_TMP_28 SPOS02 control hierarchy condition (PLC#3) M
510001 820103ED50 SPOS03IN_TMP_28 SPOS03 control hierarchy condition (PLC#3) M
…. …. ….
510001 820114ED50 SPOS20IN_TMP_28 SPOS20 control hierarchy condition (PLC#3) M
Table 4.1-7 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
510001 8601011DC6 SPOS01_OSL_BO_CSF SPOS01 select (ON) command for Binary Output.
510001 8601021DC6 SPOS02_OSL_BO_CSF SPOS02 select (ON) command for Binary Output.
510001 8601031DC6 SPOS03_OSL_BO_CSF SPOS03 select (ON) command for Binary Output.
…. …. ….
510001 8601141DC6 SPOS20_OSL_BO_CSF SPOS20 select (ON) command for Binary Output.
510001 8A01011DC4 SPOS01_FSL_BO_CSF SPOS01 select (OFF) command for Binary Output.
510001 8A01021DC4 SPOS02_FSL_BO_CSF SPOS02 select (OFF) command for Binary Output.
510001 8A01031DC4 SPOS03_FSL_BO_CSF SPOS03 select (OFF) command for Binary Output.
…. …. ….
510001 8A01141DC4 SPOS020_FSL_BO_CSF SPOS20 select (OFF) command for Binary Output.
Operate logic
“Do nothing”
Cancel condition† &
“SPOS01_CC_FS” (510001_8701011E96)
Operation Failed
Output signal to BO
The SPOS01 function can issue an output signal “Success to cancel” at the monitoring point
“SPOS01_CC_SS”, when the SPOS01 function has determined that the “Remote-cancel” signal
is true. Another “Operation failed” signal is issued at the monitoring point “SPOS01_CC_FS”
if the SPOS01 function is able to determine that the “Remote-cancel” signal is not true.
Operate logic
Operation Failed
Output signal to BO
The SPOS01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancel” signal
at the monitoring point “SPOS01_CC_SS”, when the SPOS01 function determines that the
“Local-Cancel” signal is true.
[SPOS01-LGSLFFCT]
User configurable condition (PLC connection point)
Fixedlogic
510001 800101EE69 SPOS01IN_TMP_46 &
If the original logic does not meet with the requirements of the user, it can be replaced
with another logic using the connection point “User Configurable condition”:
1. Connect the user-customized logic with the “SPOS01IN_TMP_46”.
2. Set scheme switch [SPOS01-LGCNFFCT] to PLC.
Table 4.1-11 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
SPOSxx-LGCNFFCT Logic selector for cancel condition in SPOSxx Fixedlogic Fixedlogic / PLC
Failed Do nothing
Select command Off from front panel Off control from front-panel
“SPOS01-OEC_OK_CSF”
Command “Remote-On-Control” (510001_8001011E7F)
[SPOS01-CPW]
510001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[SPOS01-LGCFEXOT]
User configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL
[SPOS01-PLSM]*
Var To “Wait for a command”
Fix
Latch “SPOS01_EX_FFL”
[SPOS01-RST]
0 t (510001_8601011E91) ††
“SPOS01-EX_CMP”
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed
“SPOS01-FEX_BO”
(510001_8101011DD0)
§§Note: The “SPOS01_OEX-BO” signal is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed “signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.
Output signal to BO
The SPOS01 function, in Figure 4.1-20, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the received signal “Remote-
On-Control” is true.
Failed Do nothing
Operation Cmd.
without ILK† condition
ILK† condition (“Off”) passed S
&
SPOS01-Off R
[SPOS01-LGCFEXOT]
User Configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ§ function is in progress
ASEQ_MULTI_SEL
To “Wait for a command”
[SPOS01-PLSM]*
“SPOS01_EX_FFL” † †
Var [SPOS01-RST] (510001_8601011E91)
Fix
0 t
“SPOS01-EX_CMP
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed
Output signal to BO
The SPOS01 function, in Figure 4.1-22, can issue an “Operate” signal at the output-point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the signal “Remote-Off-
Control” is true.
Select command On from the remote-end Operate command On from the local-end
Select command Off from the remote-end Operate command Off from the local-end
Failed Do nothing
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
“SPOS01-OEC_OK_CSF”
(510001_8001011E7F)
Operate Cmd.
Command “Local-On-Control” [SPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK† condition (“ON”) passed
SPOS01-On
S
&
ILK† bypassing ( Bypass) 1≥
R
ICB_STATE
[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL
Output signal to BO
The SPOS01 function, in Figure 4.1-24, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the signal “Local-On-Control”
is true.
Select command Off from the remote-end Operate command Off from remote-end
Select command On from the local-end Operate command On from the local-end
Failed Do nothing
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point)
& Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
PLC#2
ASEQ function§” is in progress
ASEQ_MULTI_SEL
0 t
“SPOS01-EX_CMP
(5A0101_8001011E93)
1.0s- 100.0s Operation Failed
Output signal to BO
The SPOS01 function, in Figure 4.1-26, can issue a signal “Operate” at the output point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the input signal “Local-Off-
Control” is true.
Select command Off from remote-end Operate command Off control from remote-end
Select command On from front panel Operate command On control from front-panel
Select command Off from front panel Operate command Off control from front-panel
Failed Do nothing
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Figure 4.1-28 depicts the operate logic when a signal “Operate Command Off (PLC-Off-
Control)” is generated by the PLC function. There are two input points for reception of this
command signal, unlike the signal “Operate Command On (PLC-On-Control)”. That is, if an
inter-lock check is required, apply the signal at connection point (PLC#3; i.e.,
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at connection point (PLC#4; i.e., DEV01_OP_COMMAND).
PLC#1 an PLC#2 shown in Table 4.1-2 should be treated as PLC#3 and PLC#4 here.
Note that the user should set PLC for scheme switch [SPOS01-LGCFEXOT]
4.1-16.
2. Set scheme switch [SPOS01-LGEXFFCT] to Fixedlogic.
Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “SPOS01IN_TMP_28” in
Figure 4.1-29.
Note: The output of the operate condition logic is provided separately for On-execution
and for Off-execution. To see the outputs, refer to Table 4.1-17.
SPOS01 function (Function ID: 510001)
Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Operate condition
Traveling OR
Unmatched condition detected *4
Function “Automatic sequence control” is in progress
ASEQ_MULTI_SEL Event suppression detected *5
= SPOS01_F_QLT_SPP
(510001 810101F59)
[SPOS01-CTREN]
On
Table 4.1-13 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
Table 4.1-14 PLC connection points (Input point for PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
Table 4.1-15 PLC connection points (Input point for PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
Table 4.1-16 PLC connection points (Input point PLC#1/#2 of additional and operate
conditions)
Signal Number Signal Name Description M/O
510001 8201011DD3 SPOS01_OEX_BO SPOS01 operate (ON) command for Binary Output.
510001 8201021DD3 SPOS02_OEX_BO SPOS02 operate (ON) command for Binary Output.
510001 8201031DD3 SPOS03_OEX_BO SPOS03 operate (ON) command for Binary Output.
…. …. ….
510001 8201141DD3 SPOS20_OEX_BO SPOS20 operate (ON) command for Binary Output.
510001 8101011DD0 SPOS01_FEX_BO SPOS01 operate (OFF) command for Binary Output.
510001 8101021DD0 SPOS02_FEX_BO SPOS02 operate (OFF) command for Binary Output.
510001 8101031DD0 SPOS03_FEX_BO SPOS03 operate (OFF) command for Binary Output.
510001 8101141DD0 SPOS20_FEX_BO SPOS20 operate (OFF) command for Binary Output.
… …. ….
510001 8101141E82 SPOS20_OEC_OK_CS SPOS20 on direction execute command
510001 8001011E81 SPOS01_FEC_OK_CS SPOS01 off direction execute command
510001 8001021E81 SPOS02_FEC_OK_CS SPOS02 off direction execute command
510001 8001031E81 SPOS03_FEC_OK_CS SPOS03 off direction execute command
… … …
510001 8001141E81 SPOS20_FEC_OK_CS SPOS20 off direction execute command
Note that the SPOS01 function commences operation when the scheme switch [SPOS01-EN]
is set to On.
“SPOS01_STATE”
Event suppression detector (510001_0001011001)
BI signal connected by
setting [SPOS01-NOPSG]
& 1≥
&
[SPOS01-EN] Status before chattering S
R “SPOS01_F_QLT_SPP”
On
(510001_8101011F59)
On
& To select and operate
condition logics
Event suppression
If the status of a device “chatters” for a short time, the SPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the SPOS function;
hence, event suppression can be required to reduce the additional burden created.
[SPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[SPOS-TELD] [SPOS-TELR]
Time................. A B C D E
Figure 4.1-31 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [SPOS-NELD] is provided so
that the suppression commences at Time B. The setting [SPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [SPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [SPOS01-SPPEN].
Terminal and
Selection logic in SPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire
“SPOS01_SL_BO_FLG”
(510001_8501011F76)
“SPOS01_OSL_BO_CSF”
Terminal and
Operate logic in SPOS01 BO2 and BO3 circuit at IO#1 (Function ID: 200B01) wire
“SPOS01_OEX_BO”
(510001_8201011DD3)
“BO2”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8102011112) command
“Operate command On
[Input signal 2] DRIVER BO2
On” & ≥1
[Input signal 3]
“BO2-RB”
[Input signal 4] [BO2_CPL] On &
Connected by Off
(200B01_8102011113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
Figure 4.1-33 Example of operate commands connected with BO2 and BO3 at IO#1
†Note:Table 4.1-26 shows the remaining signals excepting “SPOS01_OEX_BO” and
“SPOS01_FEX_BO”.
†Note:Table 4.1-28 shows settings for the health check feature in the other SPOS
functions.
Result of contact
BO1 circuit at & health check in SPOS01 selection
IO_SLOT1
“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [SPOS01-SLBORD]
Figure 4.1-34 Example of connection of “Select command On” for the health check feature
Operate logic in
SPOS01
Result of contact
BO2 circuit at & Health check
IO_#1
“BO2-RB”
“200B01_8102011113”
Signal designated by
setting [SPOS01-OEXBORD]
Figure 4.1-35 Example connection of “Operate Command On” for the health check
Result of contact
BO3 circuit at & health check
IO_#1
“BO3-RB”
“200B01_8102021113”
Signal designated by
setting [SPOS01-FEXBORD]
Figure 4.1-36 Example connection of “Operate command off” for the health check feature
Proper setting for the contact health check (normal setting, example #1)
Figure 4.1-37 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1, BO2 and BO3 contacts. To check that the contact health check function is
working correctly, the respective points of the BO-RBs should be connected as shown in Table
4.1-21, to demonstrate that the settings are physically matched with the BO contacts.
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“SPOS01_SL_BO_FLG”
(510001_8501011F76) SW1 driven with
BO1 at IO_SLOT1
Select BO1 SW 1
command ON/OFF
“BO1-RB”
(200B01_8002001113) SW 2 On
Command
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB”
Minus (−)
(200B01_8102011113)
“SPOS01_FEX_BO”
(510001_8101011DD0)
BO3 SW3 driven with
Operate-Off BO3 at IO_SLOT1
command “BO3-RB”
(200B01_8202021113)
Figure 4.1-37 Contact health check setting and 43SW scheme for example #1
Setting for erroneous contact health check (improper setting, example #2)
Figure 4.1-38 shows a setting example for an improper setting of the 43SW scheme. The
settings are implemented incorrectly, as shown in Table 4.1-22. BO1-RB is not chosen,
instead BO1 is actually chosen. In this case, the setting [SPOS01-SLBORD] is meaningless;
hence, the issue of a select command is blocked.
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
43SW
Remote/Local-end “BO1” (not BO1-RB) Plus (+)
“SPOS01_SL_BO_FLG” mistakenly chosen with
(510001_8501011F76) “200B01_8002001112” SW1 driven with
BO1at IO_SLOT1
Select BO1 SW 1
Command
ON/OFF
SW 2 On
“SPOS01_OEX_BO” Command
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB” designated with Minus (−)
“SPOS01_FEX_BO” “200B01_8102011113”
(510001_8101011DD0)
Figure 4.1-38 Contact health check setting and 43SW diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.1-39 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “SPOS01_SL_BO_FLG” is actually chosen for the
setting [SPOS01-SLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command; which is called “operated by internal select function”. The user
does not need to consider of a BO circuit for a select command, when there are no BO circuits
available.
Table 4.1-23 Extra setting example for contact health check
Example #3 Setting for example #3
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
43SW
Remote/Local end “SPOS01_SL_BO_FLG” Plus (+)
SW1 is not driven with
(510001_8501011F76) Plus (+)
any BO1
SW 1
Select
command Physical BO is
ON/OFF
virtualized.
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW2 is driven with
BO2 at IO#1
Operate-On BO2 SW 2 On
command Command
“BO2-RB”
“SPOS01_FEX_BO” (200B01_8102011113) SW3 is driven with SW 3 Off
(510001_8101011DD0) BO3 at IO#1 Command
Figure 4.1-39 Contact health check setting and 43SW diagram for example #3
Table 4.1-24 PLC monitoring points (Output signal for event suppression function in SPOSxx)
Signal Number Signal Name Description
510001 8201011DD3 SPOS01_OEX_BO SPOS01 operate (ON) command for Binary Output.
510001 8201021DD3 SPOS02_OEX_BO SPOS02 operate (ON) command for Binary Output.
510001 8201031DD3 SPOS03_OEX_BO SPOS03 operate (ON) command for Binary Output.
… … …
510001 8201141DD3 SPOS20_OEX_BO SPOS20 operate (ON) command for Binary Output.
510001 8101011DD0 SPOS01_FEX_BO SPOS01 operate (OFF) command for Binary Output.
510001 8101021DD0 SPOS02_FEX_BO SPOS02 operate (OFF) command for Binary Output.
510001 8101031DD0 SPOS03_FEX_BO SPOS03 operate (OFF) command for Binary Output.
… …. ….
510001 8101141DD0 SPOS20_FEX_BO SPOS20 operate (OFF) command for Binary Output.
SPOSxx-SLBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal
SPOSxx-OEXBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal
SPOSxx-FEXBORD Select BO signal (BO*-RB) from signal list *user-preferred BO readback signal
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Table 4.1-30 Mapping signals required for SPCSO object for GIG01501
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1501$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO1501$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw Check Check CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Oper T Timestamp CO
Ctrl/GGIO1501$SPCSO$Oper Test BOOLEAN CO
5100017 001016D08 DEV01_CONTROL_REQ
Ctrl/GGIO1501$SPCSO$Oper Check Check CO
Ctrl/GGIO1501$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO1501$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO ctlModel ctlModel CF
Ctrl/GGIO1501$SPCSO sboClass sboClass CF
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Check “Input”
4.1.6 Setting
SPOS01 (FunctionID:510001)
Setting items Range Unit Contents Default Note
4.1.7 Signal
Signal monitoring points in SPOS01
SPOS01(FunctionID:510001)
Element ID Name Description
8001011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
0001001F74 SPOS_SEL_OR SPOS multi select check signal for Auto sequence
0001011001 SPOS01_STATE SPOS01 state
0001011D90 SPOS01_SLD_RPT SPOS01 selected signal(stSeld) for SAS
0001011D97 SPOS01_EX_BO_OPOK SPOS01 execute binary output signal for SAS
0001011F52 SPOS01_TRA SPOS01 travelling info
0001011F53 SPOS01_TRA_CTR SPOS01 travelling info for control
0001011F75 SPOS01_SE_RCV SPOS01 select or execute command received
3101011D00 SPOS01_MMC_ST SPOS01 state for MIMIC
3101011D01 SPOS01_LCD_ST SPOS01 state for LCD
3101011D80 SPOS01_TMP_06 SPOS01 control event data (selected)
3101011D81 SPOS01_TMP_07 SPOS01 control event data (select fail)
3101011D82 SPOS01_TMP_08 SPOS01 control event data (select release)
3101011D83 SPOS01_TMP_09 SPOS01 control event data (execute output on)
3101011D84 SPOS01_TMP_10 SPOS01 control event data (execute command ng)
3101011D86 SPOS01_TMP_11 SPOS01 control event data (execute fail)
8001011D02 SPOS01_ST_OFF SPOS01 status Off
8001011D51 SPOS01_SC_OWS SPOS01 select command by OWS(HMI)
8001011D52 SPOS01_SC_RCC SPOS01 select command by RCC
8001011D53 SPOS01_SC_RMT SPOS01 select command by Remote
8001011D54 SPOS01_SC_LCD SPOS01 select command by LCD
8001011D55 SPOS01_EC_OWS SPOS01 execute command by OWS(HMI)
8001011D56 SPOS01_EC_RCC SPOS01 execute command by RCC
8001011D57 SPOS01_EC_RMT SPOS01 execute command by Remote
8001011D58 SPOS01_EC_LCD SPOS01 execute command by LCD
8001011D59 SPOS01_EC_PLC SPOS01 execute command by PLC
8001011E76 SPOS01_SLD_CS SPOS01 selected condition signal
8001011E7D SPOS01_SLR_CS SPOS01 select release condition signal
8001011E7E SPOS01_FEC_OK_CSF SPOS01 off direction execute command OK condition signal by fixedlogic
8001011E7F SPOS01_OEC_OK_CSF SPOS01 on direction execute command OK condition signal by fixedlogic
8001011E81 SPOS01_FEC_OK_CS SPOS01 off direction execute command OK condition signal
8001011E93 SPOS01_EX_CMP SPOS01 execute complete signal
8001011F54 SPOS01_SC_ST_ERR SPOS01 select command mode err
8001011F55 SPOS01_EC_ST_ERR SPOS01 execute command mode err
8001011F56 SPOS01_NSL_CS06 SPOS01 no direction select condition signal 06
8001011F66 SPOS01_SLD_CS04 SPOS01 selected condition signal 04
8101011D03 SPOS01_ST_ON SPOS01 status On
8101011DD0 SPOS01_FEX_BO SPOS01 off direction execute binary output signal
8101011E7B SPOS01_SLF_CS SPOS01 no direction select fail condition signal
8101011E82 SPOS01_OEC_OK_CS SPOS01 on direction execute command OK condition signal
8101011E85 SPOS01_FEC_F_CSF SPOS01 off direction execute command fail condition signal by fixedlogic
8101011E86 SPOS01_OEC_F_CSF SPOS01 on direction execute command fail condition signal by fixedlogic
8101011E9A SPOS01_ECF_FCT_EIS SPOS01 execute command fail factor signal except interlock/synchronism check
8101011F59 SPOS01_F_QLT_SPP TEMP31
8101011F64 SPOS01_FSL_CS21 SPOS01 off direction select condition signal 21
8201011DD3 SPOS01_OEX_BO SPOS01 on direction execute binary output signal
8201011E88 SPOS01_FEC_F_CS SPOS01 off direction execute command fail condition signal
8201011F5A SPOS01_F_BI_ERR TEMP32
8201011F5F SPOS01_NSL_CS10 SPOS01 no direction select condition signal 10
8301011E89 SPOS01_OEC_F_CS SPOS01 on direction execute command fail condition signal
8301011E9C SPOS01_CCF_FCT_CS TEMP21
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “SPOS01_SC_OWS” point for
the 2nd device, use the description of “SPOS01_SC_OWS” in place of
“SPOS02_SC_OWS”. The user can obtain the ID value of
“SPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for SPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“SPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
Figure 4.2-1 shows the eight switches and their controller functions. The statuses of the S43
switches are stored in the IED non-volatile memory; hence, the IED can retrieve their status
while power is not being supplied to the IED.
Switches for
CMDBLK ILKBYP special purposes
(CBK) (ICB)
The SOFTSW function can control a number of S43 software switches separately. To
simplify the explanation provided below only the SOFTSW1 function is discussed. The features
provided in CBK, ICB and SOFTSW2–61 switches are similar to the SOFTSW1 switch.
Tips: The user can operate CBK and ICB without user programming. Jump to section
4.2.5 where we discuss how to map their signals for IEC61850 communication.
When the user wishes to program the SOFTSW functions using the S43-01–S43-
61 switches, the user is required to read from section 4.2.2 onwards.
0 t Select “success”
0.1s
Figure 4.2-5 Select logic for ‘ON’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.2-5 and Table 4.2-8.
‡Note:“Select condition” signal is provided from select condition scheme. For more
information, see Figure 4.2-11.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SOFTSW1 function is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
*Note:The SOFTSW1 function can run on either the “SBO mode” or the “DIR mode”. The
user can use the signal “ctlmodel” in the IEC61850 communication.
(ii) Receiving “select command for Off operation” from the remote end
Input point required mapping
Figure 4.2-6 shows the logic when a “Select command (Remote-OFF-Control)” signal is applied
at the SOFTSW1 function. The input-point “S4301_CONTROL_REQ” is used for the reception
of the select command (Remote-OFF-Control).
Input Select logic in SOFTSW1 Output
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.2-6 Select logic for ‘OFF’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.2-5 and Table 4.2-8.
‡Note:“Select condition” signal is provided in Figure 4.2-11.
panel
Input signal
Figure 4.2-7 shows the logic when a “Select command (Local-ON-Control)” signal is applied to
the SOFTSW1 function. The input signal is provided when “On” key is pressed on the IED
front panel; the input-point is not required to be mapped. Note that the user should set scheme
switch [S4301-CTRAHMI] to SBO when the operation from the IED front panel is performed;
chapter User interface: Control sub-menu discusses how to operate.
Input Select logic in SOFTSW1 Output
0.6s
[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.2-7 Select logic for ‘ON’ operation at the IED locally in SOFTSW1†
†Note: To identify the output points of the other SOFTSW logics, see Table 4.2-8.
‡Note:Signal “select condition” is provided. See Figure 4.2-11.
§Note:The SOFTSW1 function is blocked when the ASEQ function is in operation.
(iv) Receiving “Select command for Off operation” from the front panel
Input signal
Figure 4.2-8 shows the logic when a “Select command (Local-OFF-Control)” signal is applied
to the SOFTSW1 logic. The input signal is provided when the user presses “OFF” key on the
IED front panel; the input-point is not required to be mapped.
& “S4301_FSD_CSF”
(522001_8D0A041F45)
DIR
0 t
Select “success”
0.1s
0.6s
[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.2-8 Select logic for ‘OFF’ operation at the IED locally in SOFTSW1†
†Note: Figure 4.2-8 is used for the discussion of SOFTSW1 logic. To identify the output
points of the other SOFTSW logics, see Table 4.2-8.
‡Note:Signal “select condition” is provided. See Figure 4.2-11.
& “S4301_OSD_CSF”
(522001_8F0A411F49)
0 t Select “success”
0.1s
(vi) Receiving “Select command for Off operation” using PLC function
Input signal required to connect
Figure 4.2-10 shows the SOFTSW1 logic for a “Select command (PLC-OFF-Control)” signal.
The input signal is generated using the user-programmed PLC logic; the user can connect the
signal for the PLC connection point “S4301_CHG_TO_OFF”.
510001 7001016D08
& “S4301_FSD_CSF”
(522001_8D0A411F45)
0 t Select “success”
0.1s
[S4301-EN]
On
Table 4.2-3 PLC connection point #2 (Input points for ‘Off’ control)
Signal Number Signal Name Description M/O
Table 4.2-4 PLC connection point #3 (Input points on select condition logic)
Signal Number Signal Name Description M/O
5A0001 0008001F41 DCB RCV OR Double Command Blocking (DCB) is in progress. N/A
5A0001 0008001F40 Traveling OR Travelling events are detected. N/A
5A0001 3108003F40 SDCEN (This is setting of CMNCTRL) N/A
5A0101 3100001F43 SERI_ERR Serious Error detected N/A
523001 000D001F40 ASEQ_MULTI_SEL Automatic sequence control is in progress. N/A
Table 4.2-8 PLC monitoring points (ON and OFF selection completion)
Signal Number Signal Name Description
…. …. … ….
S4361-EN Function activation in SOFTSW61 (S43-61) On Off / On
CBK-CTRAHMI HMI activation in CBK On Off / On
ICB-CTRAHMI HMI activation in ICB On Off / On
S4301-CTRAHMI HMI activation in SOFTSW1 (S43-01) On Off / On
S4302-CTRAHMI HMI activation in SOFTSW2 (S43-02) On Off / On
S4303-CTRAHMI HMI activation in SOFTSW3 (S43-03) On Off / On
…. …. … …
S4361-CTRAHMI HMI activation in SOFTSW61 (S43-61) On Off / On
Operation Failed
Unmatched condition &
detected†
Figure 4.2-12 Cancel logic by the reception of the command from the remote end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.
Cancel command
Command “Local-cancel”
Successes to cancel
&
Unmatched condition
& Operation Failed
detected†
Figure 4.2-13 Cancel logic by the reception of the command at local end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.
“S4301_OEC_CHG”
Command “Remote-On-Control” (522001_890A041F5A)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
“S4301_FEC_CHG”
Command “Remote-OFF-Control” (522001_8A0A041F5B)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
“S4301_OEC_CHG”
(522001_890A041F5A)
Operate Command
Command “Local-On-Control”
& OFF to ON
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
“S4301_FEC_CHG”
(522001_8A0A041F5B)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.2-11, Table 4.2-12, and Table 4.2-13.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.2-20.
§Note: The ASEQ function can provide sequential signals for automatic control.
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_810A041D03 Operate completed
S4301_ST_ON &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_830A041D02 Operate completed
S4301_ST_OFF &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s
[S4301-EN]
On
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Table 4.2-18 shows the required mapping signals in SOFTSW1 function to the IEC 61850
communications. Figure 4.2-24 shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Table 4.2-19 Mapping signals required for SPCSO object in SOFTSW1 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO701$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO701$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw Check Check CO
Ctrl/GGIO701$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Oper T Timestamp CO
Ctrl/GGIO701$SPCSO$Oper Test BOOLEAN CO
522001 700A046D08 S4301_CONTROL_REQ
Ctrl/GGIO701$SPCSO$Oper Check Check CO
Ctrl/GGIO701$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO701$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO ctlModel ctlModel CF
Ctrl/GGIO701$SPCSO sboClass sboClass CF
Check “Input”
4.2.6 Setting
SOTFSW(FunctionID:522001)
Setting items Range Unit Contents Default Note
4.2.7 Signal
Signal monitoring points
SOFTSW(Function ID:522001)
Element ID Name Description
000A011001 CBK_STATE CMDBLK status
…. …. ….
….. …. …..
860A3FEDE0 S4360_CHG_TO_OFF SOFT 43 switch60 change to off
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SOFTSW function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “S4301_EC_LCD” point for the
2nd device, use the description of “S4302_EC_LCD” in place of
“S4301_EC_LCD”. The user can obtain the ID value of “S4302_EC_LCD” by
using the following steps:
Step 1 Find the element ID for S4301_EC_LCD (i.e.,
“8C00041F45”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “4”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8C00051F45” of
“S4302_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
864,000,000sec
60sec
Operation time
0sec The TOTALTIM function
checks the state of the
operation signal every
second. If the operation
signal is in the “On” state,
TOTALTIM accumulates
TOTALTIM process the “On” time.
Figure 4.3-2 illustrates that 12 signals can be accommodated from external devices using
BIs. For example, when binary input circuit BI1 receives operating signal1, provided signal-
monitoring point “BI1” is applied for the acquisition of the signal, the user can make the logic
to connect “BI1” with TT01 of the TOTALTIM function using the PLC function.
IED TOTALTIM
Device
TOTAL12_PLC_SGNL
TT12
PLC
SAS
Device #12 BI12-NC BI12 BI12-CPL
Photo- Filter CPL
Operating signal #12
coupler
TOTAL02_PLC_SGNL
TT02
PLC
Operating signal #1
Photo- Filter CPL
coupler
Contact-switch Binary IO module (BIO)
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
Oper
origin
ctlmodel (choice ”DOes or DOns”)
Note: “Status (ST)” and “Measurement (MX)” are defined in the function constraint (FC)
of the IEC 61850 standard.
Table 4.3-4 Mapping signals required for GGIO1301 object in TTIM01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1301$ISCSO1$SBOw ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$SBOw ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$SBOw T Timestamp CO
Ctrl/GGIO1301$ISCSO1$SBOw Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$SBOw Check Check CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Oper T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Oper Test BOOLEAN CO
5410017015016D08 TOTAL01_CMM_REQ
Ctrl/GGIO1301$ISCSO1$Oper Check Check CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Cancel T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Cancel Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1 ctlModel ctlModel CF
Ctrl/GGIO1301$ISCSO1 sboClass sboClass CF
4.3.4 Setting
TOTALTIM(Function ID: 541001)
Setting items Range Unit Contents Default Note
4.3.5 Signal
Signal monitoring points
TOTALTIM(Function ID: 541001)
Element ID Name Description
0015001F41 TTIM00_CCTRL_TIME TTIM00 total time correction summarize
0015011D91 TTIM01_TMP_01 TTIM01 total time change selected signal(stSeld) for SAS
0015021D91 TTIM02_TMP_01 TTIM02 total time change selected signal(stSeld) for SAS
0015031D91 TTIM03_TMP_01 TTIM03 total time change selected signal(stSeld) for SAS
0015041D91 TTIM04_TMP_01 TTIM04 total time change selected signal(stSeld) for SAS
0015051D91 TTIM05_TMP_01 TTIM05 total time change selected signal(stSeld) for SAS
0015061D91 TTIM06_TMP_01 TTIM06 total time change selected signal(stSeld) for SAS
0015071D91 TTIM07_TMP_01 TTIM07 total time change selected signal(stSeld) for SAS
0015081D91 TTIM08_TMP_01 TTIM08 total time change selected signal(stSeld) for SAS
0015091D91 TTIM09_TMP_01 TTIM09 total time change selected signal(stSeld) for SAS
00150A1D91 TTIM10_TMP_01 TTIM10 total time change selected signal(stSeld) for SAS
00150B1D91 TTIM11_TMP_01 TTIM11 total time change selected signal(stSeld) for SAS
00150C1D91 TTIM12_TMP_01 TTIM12 total time change selected signal(stSeld) for SAS
When using the ILK function, an interlock-check formula is required. The interlock-check
formula examines the operational conditions for all devices, and is stored in the ILK database.
The ILK function provides an output signal “OK/NG decision information”; the “OK/NG
decision information” is transferred to the control functions†, which control the external
devices. Following which, the control functions can commence with the control of the selected
devices in response to the respective “OK/NG decision information”.
†Note:Details of SPOS, DPOS, and TPOS features are discussed separately elsewhere in
the instruction manual under the Chapter Control and monitoring applications.
Prior to controlling a device, the interlock-check function is used to determine whether the
control of a device is correct or not. If the interlock-check finds that the conditions for device
control have not been satisfied in accordance with the appropriate interlock condition, control
of the device is forbidden. Figure 4.4-1 provides an overview of the interlock-check process.
Formulae for interlock-check are stored in an ILK database; these formulae are used in order
to enable the interlock-check function to output a decision. If the proposed operation of a
particular device is deemed correct then an “OK-decision” is determined by the formulae, and
device control is allowed. However, if the proposed operation of the device is deemed incorrect
then an “NG-decision” is determined by the formulae, and device control is not allowed.
Device IED
Binary
Circuit input Control
breaker Interlock Control
Device status circuits Device status Functions
(CB) Device status Function (ILK)
SPOS
DPOS
Dis- Binary OK/NG decision Interlock
and
connector Output
others
(DS) circuits
Device control Control Database
Other IE Ds
GOOSE GOOSE receiving information
GOOSE subscription
data
transmission
data
PC(GR-TIEMS)
Interlock formulas
Q0 Q0B
Q53
Q9 Q8
Q69
F52VT
F27L
In accordance with the arrangement of the devices shown in Figure 4.4-2, interlock-check
formulae can be configured from equations (4.4-1) to (4.4-9). The status of respective devices,
(stVal) and interlock operators (“•” and “+”) are placed on the right-hand side of the equations;
and the interlock condition (e.g. Q0(Closing)) is placed on the left-hand side of the equations.
The interlock operators are also shown in Table 4.4-1.
̅̅̅̅ ∙ Q2
Q1 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q15 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.4-1)
+ (Q2 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
̅̅̅̅ ∙ Q1
Q2 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q25 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.4-2)
+ (Q1 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
Q9 = (Q0 ̅̅̅̅̅ ∙ Q53
̅̅̅̅ ∙ Q52 ̅̅̅̅̅ ∙ Q8
̅̅̅̅) (4.4-3)
Q0(Closing ‡) ̅̅̅̅̅̅̅̅̅ ∙ ̅̅̅̅̅̅̅̅̅
= 63QBE 63GBE
̅̅̅̅ ∙ ̅̅̅̅
∙ ((Q1 Q2 ∙ ̅̅̅̅
Q9) + ((Q1 + Q2) ∙ Q9)) (4.4-4)
∙ Closing Blocking
Q0(Opening ‡ ) = ̅̅̅̅̅̅̅̅̅
63QBF ∙ ̅̅̅̅̅̅̅̅̅
63GBE (4.4-5)
̅̅̅̅ ∙ Q69 ∙ F27L(No voltage) ∙ F52VT)
Q8 = (Q9 (4.4-6)
̅̅̅̅ ∙ ̅̅̅̅
Q52 = (Q9 Q1 ∙ ̅̅̅̅
Q2) (4.4-7)
̅̅̅̅ ∙ ̅̅̅̅
Q53 = (Q9 Q1 ∙ ̅̅̅̅
Q2) (4.4-8)
Q69 = Q8 (4.4-9)
where,
For example in equation (4.4-12), the interlock condition for DS (Q1) is satisfied when CB
(Q0), DS (Q2), ES for the Bus-bar1-A (Q15), ES (Q52) and ES (Q53) are open. In addition, the
interlock condition for DS (Q1) is also satisfied when DS (Q2), CB (Q0), DS (Q9), CB (Q0), DS
(Q1), and DS (Q2) are closed.
Node
stVal OR (+)
Input(A)
stVal
Quality Output
Quality
Input(B) stVal
Quality
Node #1
Node #2 Node #7
OR (+) AND(• )
Input A AND(• )
Input B
Output
Input C
Input D Node #4
Node #3
OR (+)
AND(• )
Input E
Input F
Input G
Node #5 Node #6
AND(• )
OR (+)
Input H
Input I
Input J
We can see that equation (4.4-10) is a representation of Figure 4.4-4. This equation is computed
in accordance with the priority order of the interlock-operators: the first is parentheses [()], the
second is AND [•], followed by OR [+].
Output = ((A+B) •C) + (D+E•F) + (G•(H+I) •J) (4.4-10)
Figure 4.4-5 shows the logic symbol for the interlock operator “AND” with input signals
and an output signal. Figure 4.4-5 can be represented by equations (4.4-11) and (4.4-12).
stVal = stVa(A) • stVa(B) (4.4-11)
Quality=(Quality(A)+Quality(B))•(stVa(A)+ Quality(A))
(4.4-12)
•(stVa(B)+Quality(B))
For example, when the interlock operator “AND” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–OK) using the equations (4.4-11) and (4.4-12). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the AND operator; the AND
operator produces zero (0) which is defined as “OK” in ‘Quality’. A note regarding the values
AND (• )
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B)
Quality
OR interlock operator
When quality information (Quality) is applied to the interlock operator “OR”, the quality
information is affected by device status (stVal). Table 4.4-4 shows two-input-signals (A, B) and
the output signal for “OR”
Table 4.4-4 Output signals (stVal–Quality) of OR
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
0–OK 0–OK – – –
Input A 0–NG 0–NG 0–NG – –
(stVal–Quality) 1–OK 1–OK 1–OK 1–OK –
1–NG 1–NG 1–NG 1–OK 1–NG
As shown in Table 4.4-4, if ‘0’ represents the status value “stVal” for all input signals, and
if the quality information of “NG” is given for an input signal, then the output signal “Quality”
is represented as “NG”. On the other hand, if all input signals “stVal” are represented by “1”,
and if the quality information for the input signals “stVal(1)” is given, then the representation
“OK” can be weighted for the output signal “Quality” . Note that quality information (OK) for
input signals with “stVal(1)” get priority if there are two or more input signals, which are
represented as “stVal(1)”.
Figure 4.4-6 shows the logic symbol for the interlock operator “OR” with input signals and an
output signal, which can be represented by equations (4.4-13) and (4.4-14).
OR (+)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality
For example, when the interlock operator “OR” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–NG) using the equations (4.4-13) and (4.4-14). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the OR operator; the OR
operator produces one (1) which is defined as “NG” in ‘Quality’. A note regarding the values
used for Quality can be found immediately below Table 4.4-2
Figure 4.4-7 depicts the logic symbol for the interlock operator “NOT” with input signals
and an output signal, which can be represented by equations (4.4-15) and (4.4-16).
NOT(!)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality
Figure 4.4-8 depicts the logic symbol for the interlock operator “COMP” with input signals
and an output signal, which can be represented by equations (4.4-17) and (4.4-18).
stVal=stVa(A) COMP stVa(B) (4.4-17)
Quality=Quality(A) † (4.4-18)
†Note: Input signal (B) does not have quality information because its signal is a
threshold value.
COMP
Input(A) stVal
Quality
stVal
Output
Quality
Input(B) stVal
4.4.5 Signal
Signal monitoring point
ILK (Function ID: 570001)
Element ID Name Description
3100A11001 ILK_MID_UPDATING ILK condition number during counting
Cancel logic
Select command Off from the remote-end
Output signal to BO
The DPOS01 function can issue a “Select success” signal at the output point
“DPOS01_OSL_BO_FLG”, when the DPOS01 function determines that the “Remote-ON-
Control” signal is true. If the DPOS01 function determines that the “Remote-ON-Control”
signal is not true, the DPOS01 function returns to the “Wait for a command” stage.
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Cancel logic
Output signal to BO
The DPOS01 function, in Figure 4.5-4, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_FLG” when the DPOS01 function determines that the received “Select
command Off (Remote-OFF-Control)” signal is true. If the DPOS01 function determines that
the “Remote-OFF-Control” signal is not true, the DPOS01 function returns to the “Wait for a
command” stage.
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Cancel logic
Cancel command
Select command On from the remote-end
Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_OSL_BO_CSF”.
Note: The “DPOS01_OSL_BO_CSF” signal is the same as the signal shown in Figure
4.5-2. If the input signal “Local-ON-Control” is not true, the DPOS01 function
returns to the “Wait for a command” stage.
0.6s
[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Cancel logic
Select command On from the remote-end Cancel command
Cancel logic
Select command On from the local-end
Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_FSL_BO_FLG”.
1Note: The signal “DPOS01_FSL_BO_FLG” is the same as the signal shown in Figure
4.5-4. If the signal “Local-OFF-Control” is not true, the DPOS01 function returns
to the “Wait for a command” stage.
0.6s
[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Cancel logic
Cancel command
Select command On from the remote-end
Operate logic
Select command On by PLC function
Failed Operate command
Output signal to BO
The DPOS01 function, in Figure 4.5-10, can issue a “Select success” signal at the output-point
“DPOS01_OSL_BO_CSF”1.
1Note: The “DPOS01_OSL_BO_CSF” signal is the same signal as that shown in Figure
4.5-2.
1≥ &
ON-control command requiring ILK† checking To “Wait for a next
For DIR operation
(PLC #1 connection point) command”
Operate command
512001 800301EE33 DEV01_CL_INTERLOCK To BO connection
with ILK† condition
& “DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
ILK† condition (“ON”) passed
DPOS01-Close 0 t
Select “success”
0.1s
ON-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Select “Failed”
512001 800301EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s
Select condition‡
Cancel logic
Cancel command
Select command On from the remote-end
Operate logic
Select command On by the PLC function
Operate command
Output signal to BO
The DPOS01 function, in Figure 4.5-12, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_CSF”1.
1Note: The output point “DPOS01_FSL_BO_CSF” is the same signal as that shown in
Figure 4.5-4.
1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
Operate command with To BO connection
512001 800301EE31 DEV01_OP_INTERLOCK
ILK† condition & “DPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (512001_8A03011DC4)
DPOS01-Open 0 t
Select “success”
0.1s
OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Select “Failed”
512001 800301EE30 DEV01_OP_COMMAND
without ILK† condition & 0.6s
Select condition‡
On
7Note: The Common control (CMNCTRL) function can test and check the ‘On and Off
operations performed by the logic. When the user sets Off for scheme switch
[SCDEN], the operation of the logic is blocked if the logic is running in the same
operation-direction compared with the previous operation-direction (i.e., when on
(off) is performed sequentially). On the other hand, if On is set for the scheme
switch, the logic is not blocked.
8Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “DPOS01IN_TMP_28”. For more information, see
Chapter Control and monitoring application: Control hierarchy. See PLC#3 of
Table 4.5-6.
9Note: To identify the input point of the other DPOS, see Table 4.5-6 for PLC#1 and
PLC#2.
Table 4.5-2 PLC Connection points (Input points for Command ‘Off’)
Signal Number Signal Name Description M/O
Table 4.5-6 PLC Connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
Table 4.5-7 PLC Monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
512001 8A03011DC4 DPOS01_FSL_BO_FLG DPOS01 select (Off) command for Binary Output.
512001 8A03021DC4 DPOS02_FSL_BO_FLG DPOS02 select (Off) command for Binary Output.
512001 8A03031DC4 DPOS03_FSL_BO_FLG DPOS03 select (Off) command for Binary Output.
…. …. ….
512001 8A03481DC4 DPOS72_FSL_BO_FLG DPOS72 select (Off) command for Binary Output.
512001 8603011DC6 DPOS01_OSL_BO_FLG DPOS01 select (ON) command for Binary Output.
512001 8603021DC6 DPOS02_OSL_BO_FLG DPOS02 select (ON) command for Binary Output.
512001 8603031DC6 DPOS03_OSL_BO_FLG DPOS03 select (ON) command for Binary Output.
…. …. …..
512001 8603481DC6 DPOS72_OSL_BO_FLG DPOS72 select (On) command for Binary Output.
Operate logic
Output signal to BO
The DPOS01 function can issue a “Success to cancel” signal at the monitoring point
“DPOS01_CC_SS”, when the DPOS01 function has determined that the signal “Remote-cancel”
is true. Another signal “Operation failed” is issued at monitoring point “DPOS01_CC_FS” if
the DPOS01 function is able to determine that the signal “Remote-cancel” is not true.
“DPOS01_CC_FS”
(512001_8703011E96)
Operation Failed
Operate logic
Operation Failed
Output signal to BO
The DPOS01 function, illustrated in Figure 4.5-17, is able to issue a “Success of cancel” signal
at the monitoring point “DPOS01_CC_SS”, when the DPOS01 function determines that the
signal “Local-Cancel” is true.
[DPOS01-LGCNFFCT]
PLC#1
User configurable condition (PLC connection point)
Fixedlogic
512001 800301EE69 DPOS01IN_TMP_44 &
If the original logic does not meet with the requirement of the user, it can be relpced using
the connection point “User configurable condition”.
Table 4.5-10 PLC connection points (Input signal for ‘cancel’ condition logic)
Signal Number Signal Name Description M/O
Table 4.5-11 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
DPOSxx-LGCNFFCT Logic selector for cancel condition in DPOSxx Fixedlogic Fixedlogic / PLC
Failed Do nothing
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.5-20, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the received signal “Remote-
On-Control” is true.
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
Command “Remote-On-Control” (512001 8103011E82)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.5-13 for PLC#1, Table 4.5-14 for PLC#2, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [DPOS01-RST] has been reached.
Select command On from the remote-end Operate command On from the remote-end
Failed Do nothing
Select command On from the local-end Operate command On l from the local-end
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.5-22, can issue an “Operate” signal at the output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Remote-
Off-Control” is true.
“DPOS01_FEC_OK_CSF”
(512001 8003011E7E)
DPOS01 function (Function ID: 512001)
“DPOS01_FEC_OK_CS”
Command “Remote-Off-Control” (512001 8003011E81)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
“DPOS01_FEC_OK_CSF &
1.0s- 100.0s Operate Failed
††Note: To identify the input and output signals of the other DPOS logics, see Table
4.5-14 for PLC#2, Table 4.5-15 for PLC#3, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command On from the remote-end Operate command On from the local-end
Select command Off from the remote-end Operate command Off from the local-end
Failed Do nothing
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.5-24, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “Local-On-Control”
is true.
To BO connection
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS1 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
(512001 8103011E82)
Operate Cmd.
Command “Local-On-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“ON”) passed
DPOS01-Close
S
&
ILK† bypassing 1≥
R
ICB_STATE
[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.5-13 for PLC#1, Table 4.5-14 for PLC#2, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command Off from the remote-end Operate command Off from remote-end
Select command On from the local-end Operate command On from the local-end
Failed Do nothing
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.5-26, can issue an “Operate” signal at the output point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Local-Off-
Control” is true.
“DPOS01_FEC_OK_CSF”
DPOS1 function (Function ID: 512001) (512001 8003011E7E)
“DPOS01_FEC_OK_CS”
Operate Cmd. (512001 8003011E81)
Command “Local-Off-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“Off”) passed
DPOS01-Open
S
&
ILK† bypassing 1≥
R
ICB_STATE
[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
††Note: To identify the input and output signals of the other DPOS logics, see Table
4.5-14 for PLC#2, Table 4.5-15 for PLC#3, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Select command Off by the PLC function Operate command Off by the PLC
Output signal to BO
The DPOS01 function, in Figure 4.5-28, can issue an “Operate” signal at output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “PLC-On-Control”
is true.
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
Command “PLC-On-Control” requiring ILK† check
(512001 8103011E82)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE33 DEV01_CL_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” not requiring ILK† check 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE32 DEV01_CL_COMMAND Operate Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††Note: To identify the input and output signal-points in the other DPOS logics, see Table
4.5-13 for PLC#1, Table 4.5-14 for PLC#2, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting to timer [DPOS01-RST].
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Output signal to BO
The DPOS01 function, in Figure 4.5-30, can issue an “Operate” signal at output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the signal “PLC-Off-Control”
is true.
“DPOS01_FEC_OK_CSF” “DPOS01_FEC_OK_CS”
Command “PLC-On-Control” with ILK†
(512001 8003011E7E) (512001 8003011E81)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE31 DEV01_OP_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” without ILK† 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE30 DEV01_OP_COMMAND Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
changed.
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.5-14 for PLC#2, Table 4.5-15 for PLC#3, Table 4.5-17 and Table 4.5-19 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
1Note: “Command Blocking” disables all operation except for its own; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter Control and monitoring application: Software
switch controller. See the signal ““CBK_STATE” in Table 4.5-5.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.5-5. For more information see Chapter Control and
monitoring application :Common controls.
3Note: Detection of event “device-travelling” signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is being detected. The detection signal is denoted
as “Travelling OR” in Table 4.5-5.
4Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
5Note: The “Event suppression” function can detect chattering in BI circuits. (See section
4.5.6(i)-3)
6Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
7Note: The Common control (CMNCTRL) function can test and check the operation-
direction of logic. When the user sets Off for scheme switch [SCDEN], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alernatively, if On is set for the
scheme switch, the logic is not blocked.
8Note: The user must program the PLC logic “Control hierarchy condition”. The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “DPOS01IN_TMP_28”. For more information, see Chapter
Control and monitoring application: Control hierarchy. See PLC#3 of Table
4.5-6.Note that the logic outputs are generated separately for both On and Off.
Table 4.5-13 PLC connection points (Input point for PLC#1 User configurable condition)
Signal Number Signal Name Description M/O
Table 4.5-14 PLC connection points (Input point for PLC#2 User configurable condition)
Signal Number Signal Name Description M/O
Table 4.5-15 PLC connection points (Input point for PLC#3 User configurable condition)
Signal Number Signal Name Description M/O
Table 4.5-16 PLC connection points (Input point for PLC#1 and PLC#2 for additional and
operate condition)
Signal Number Signal Name Description M/O
512001 8203011DD3 DPOS01_OEX_BO DPOS01 operate (ON) command for Binary Output.
512001 8203021DD3 DPOS02_OEX_BO DPOS02 operate (ON) command for Binary Output.
512001 8203031DD3 DPOS03_OEX_BO DPOS03 operate (ON) command for Binary Output.
… …. …
512001 8203481DD3 DPOS72_OEX_BO DPOS72 operate (ON) command for Binary Output.
512001 8103011DD0 DPOS01_FEX_BO DPOS01 operate (OFF) command for Binary Output.
512001 8103021DD0 DPOS02_FEX_BO DPOS02 operate (OFF) command for Binary Output.
512001 8103031DD0 DPOS03_FEX_BO DPOS03 operate (OFF) command for Binary Output.
…. …. ….
512001 8103481DD0 DPOS72_FEX_BO DPOS72 operate (OFF) command for Binary Output.
Off state
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See chapter User interface: Monitoring sub-menu.
“DPOS01_SLD_CSCN”
(512001 8A03031F86)
Command “change value for counter”
512001_7003016D09 DEV01_3PH_REQ Operate Command
&
Operate condition‡
Figure 4.5-34 Changing counter value for three-phase† with operation from the remote-end in
DPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic of
Figure 4.5-36.
†Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.5-22. The resultant signals for the other DPOS02-72 logics are
shown in Table 4.5-23.
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.
Figure 4.5-35 Changing counter value by operation from the front panel in DPOS01
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.
Figure 4.5-36 Operate condition logic for changing the counter in DPOS01
1Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch controller. See the signal ““CBK_STATE”
of Table 4.5-5.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.5-5. For more information see Chapter Control and
monitoring application: Common controls.
3Note: If the event “device-travelling” is detected in the CMNCTRL function, it indicates
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted by “Travelling OR” in Table 4.5-5.
512001 7003016D09 DEV01_3PH_REQ DPOS01 change command received. (Mapping Data) for 3-phase counter value
512001 7003026D09 DEV02_3PH_REQ DPOS02 change command received. (Mapping Data) for 3-phase counter value
512001 7003036D09 DEV03_3PH_REQ DPOS03 change command received. (Mapping Data) for 3-phase counter value
… … …
512001 7003486D09 DEV72_3PH_REQ DPOS72 change command received. (Mapping Data) for 3-phase counter value
512001 7003016D0A DEV01_APH_REQ DPOS01 change command received. (Mapping Data) for A-phase counter value
512001 7003026D0A DEV02_APH_REQ DPOS02 change command received. (Mapping Data) for A-phase counter value
512001 7003036D0A DEV03_APH_REQ DPOS03 change command received. (Mapping Data) for A-phase counter value
… … …
512001 7003486D0A DEV72_APH_REQ DPOS72 change command received. (Mapping Data) for A-phase counter value
512001 7003016D0B DEV01_BPH_REQ DPOS01 change command received. (Mapping Data) for B-phase counter value
512001 7003026D0B DEV02_BPH_REQ DPOS02 change command received. (Mapping Data) for B-phase counter value
512001 7003036D0B DEV03_BPH_REQ DPOS03 change command received. (Mapping Data) for B-phase counter value
… … ….
512001 7003486D0B DEV72_BPH_REQ DPOS72 change command received. (Mapping Data) for B-phase counter value
512001 7003016D0C DEV01_CPH_REQ DPOS01 change command received. (Mapping Data) for C-phase counter value
512001 7003026D0C DEV02_CPH_REQ DPOS02 change command received. (Mapping Data) for C-phase counter value
512001 7003036D0C DEV03_CPH_REQ DPOS03 change command received. (Mapping Data) for C-phase counter value
… … …
512001 7003486D0C DEV72_CPH_REQ DPOS72 change command received. (Mapping Data) for C-phase counter value
DPOSxx-CNTS Mode selection of the counter in DPOSxx *user-preferred NA / C-On / C-Off / C-OnOff
Signal “DPOS01_FEX_BO”
Sensing
intermediate state
On Intermediate Off
Signal POS01_FEX_BO”
Sensing
intermediate state
Off Intermediate On
The user can clear the intervals (OT1 to OT4) by key-operation of the “Operation time”
sub-menu Figure 4.5-39 or operation from the remote-end. See chapter User interface:
Monitoring sub-menu.
512001 7003006D0D DEV01_RESET_REQ DPOS01 operation time reset command received (Mapping Data)
512001 7003016D0D DEV02_RESET_REQ DPOS02 operation time reset command received (Mapping Data)
512001 7003026D0D DEV03_RESET_REQ DPOS03 operation time reset command received (Mapping Data)
512001 7003486D0D DEV48_RESET_REQ DPOS72 operation time reset command received (Mapping Data)
Note that the DPOS01 function commences operation when the scheme switch [DPOS01-EN]
is set to On.
DPOS01
To select and operate
condition logics
“DPOS01_3PH_STATE”
(512001 3103011001)
Phase-A signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
&
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Phase-B signals
BI signal selected by & Faulty
N/O contact setting [DPOS01B-NOPSG]
signal &
Phase-C signals
BI signal selected by
N/O contact setting [DPOS01C-NOPSG]
signal & &
Close
BI signal selected by
N/C contact setting [DPOS01C-NCLSG]
signal &
[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
3-Pole
[DPOS01-OPC]
And
&
[DPOS01-CLC]
And
DPOS01
To select and operate
condition logics
“DPOS01_3PH_STATE”
(512001 3103011001)
Single phase signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Faulty
&
Intermediate
&
Close
[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
1-Pole
Event suppression
If the status of a device “chatters” for a short time, the DPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPOS function;
hence, event suppression can be required to reduce additional burden created.
The DPOS function has an event suppression detector. The user should take into account
of the scheme switches [DPOS-NELD], [DPOS-TELD] and [DPOS-TELR]†. Set On for scheme
switch [DPOS01-SPPEN].
[DPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[DPOS-TELD] [DPOS-TELR]
Time................. A B C D E
Figure 4.5-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [DPOS-NELD] is provided so
that the suppression commences at Time ‘B’. The setting [DPOS-TELD] pertains to the
operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to Time ‘E’).
To initiate the event suppression the user should set On for scheme switch [DPOS01-
SPPEN].
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select logic for select command On “BO1” Select
Signal captured by command
in DPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
On to the
DRIVER BO1 device
[Input signal 2]
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Select logic for select command check
Off in DPOS01 [Input signal 7]
[Input signal 8]
Terminal and
BO2 circuit at IO#1 (Function ID: 200B01) wire
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) Select
“BO2”
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112) Off to the
device
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Figure 4.5-43 Example of select commands connected with BO1 & BO2 at IO#1
†Note:Table 4.5-8 shows the remaining signals with the exception of
Terminal and
Operate logic in DPOS01 BO3 and BO4 circuit at IO#1 (Function ID: 200B01) wire
“DPOS01_OEX_BO”
(512001 8203011DD3)
Operate
“BO3” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) On to the
device
“Operate command [Input signal 2] DRIVER BO3
On” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by Off
(200B01_8202021113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
Figure 4.5-44 Example of operate commands connected with BO3 and BO4 at IO#1
†Note:Table 4.5-17 shows the remaining signals with the exception of
“DPOS01_OEX_BO” and “DPOS01_FEX_BO”.
“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [DPOS01-OSLBORD]
Figure 4.5-45 Example connection of “Select command On” for the health check feature
“BO2-RB”
(200B01_8102001113)
Signal connected by
setting [DPOS01-FSLBORD]
Figure 4.5-46 Example connection of “Select command Off” for the health check feature
“BO3-RB”
“200B01_8202021113”
Signal designated by
setting [DPOS01-OEXBORD]
Figure 4.5-47 Example connection of “Operate command On” for the health check feature
“BO4-RB”
“200B01_8302031113”
Signal designated by
setting [DPOS01-FEXBORD]
Figure 4.5-48 Example connection of “Operate command Off” for the health check feature
Setting for the contact health check (normal setting, example #1)
Figure 4.5-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.5-28, to
demonstrate that the settings are physically matched with the BO contacts.
“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK
Figure 4.5-49 Contact health check setting and 43SW scheme for example #1
Settings for erroneous contact health check (improper setting, example #2)
Figure 4.5-50 shows a setting example of an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.5-29, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPOS01-OSLBORD] is
meaningless ; hence, the issue of a select command is blocked.
“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001112 (BO1) set for [DPOS01-OSLORD] NG
“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK
Figure 4.5-50 Contact health check setting and 43SW scheme for example#2
Settings for extra contact health check (special setting, example #3)
Figure 4.5-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPOS01_OSL_BO_FLG” is actually chosen for the
setting [DPOS01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special setting
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BIO
circuits available.
“DPOS01_FEX_BO_CSF” is connected to “BO4” at IO#1 200B01 8202021113 (BO3-RB) set for [DPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select command On SW1 is not driven with any BO
SW 1
On
command
Physical BOs
are virtualized. SW 3
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) SW2 is not driven with any BO
Select command Off SW 2
Off
command
SW 4
“DPOS01_OEX_BO”
SW3 is driven with
(512001 8203011DD3)
BO3 at IO#1
Operate command On BO3
Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPOS01_FEX_BO”
(512001 8103011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command Off
“BO4-RB”
(200B01_8302031113)
Figure 4.5-51 Contact health check setting and 43SW scheme for example#3
Table 4.5-31 PLC monitoring points (Output signal for event suppression function in DPOSxx)
Signal Number Signal Name Description
DPOSxx-OSLBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-FSLBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-OEXBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
DPOSxx-FEXBORD Select BO signal (BO*-RB) from signal list *user- BO read-back number
preferred
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Table 4.5-35 Mapping signals required for DPC object for CSWI4
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO
Ctrl/CSWI4$Pos$SBOw T Timestamp CO
Ctrl/CSWI4$Pos$SBOw Test BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw Check Check CO
Ctrl/CSWI4$Pos$SBOw$origin orCat orCategory CO
Ctrl/CSWI4$Pos$SBOw$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Oper ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Oper ctlNum INT8U CO
Ctrl/CSWI4$Pos$Oper T Timestamp CO
Ctrl/CSWI4$Pos$Oper Test BOOLEAN CO
512001 7003016D08 DEV01_CONTROL_REQ
Ctrl/CSWI4$Pos$Oper Check Check CO
Ctrl/CSWI4$Pos$Oper$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Oper$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Cancel ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel ctlNum INT8U CO
Ctrl/CSWI4$Pos$Cancel T Timestamp CO
Ctrl/CSWI4$Pos$Cancel Test BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Cancel$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO
Check “Input”
4.5.8 Setting
DPOS01(Function ID: 512001)
Setting items Range Unit Contents Default Note
FixedLogic /
DPOS01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
DPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
DPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
DPOS01-LGFEXOT - FixedLogic
PLC output
FixedLogic / Change logic about on direction execute
DPOS01-LGOEXOT - FixedLogic
PLC output
FixedLogic /
DPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
DPOS01-PLSM Fix / Var - pulse mode Fix
DPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
DPOS01-RST 1.0 - 100.0 s response check timer 30.0
NA / C-On / C-
DPOS01-CNTS - count status NA
Off / C-OnOff
DPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
DPOS01-APBD Process / Bay - status change origin Process
DPOS01-CTRDIR Off / On - Capable control direction On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPOS function is available for a 2nd Device and other devices. We have
omitted the other tables because this will be the same as the table for the 1st
device with the exception of the device number.
4.5.9 Signal
Signal monitoring points in DPOS01
DPOS01(Function ID: 512001)
Element ID Name Description
8003011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
3103011001 DPOS01_3PH_STATE DPOS01 3ph_state
3103011FE5 DPOS01_APH_STATE DPOS01 aph_state
3103011FEA DPOS01_BPH_STATE DPOS01 bph_state
8603011F7B DPOS01_CNT_CS07 DPOS01 count change selected fail condition signal
0003011D91 DPOS01_CNT_SEL DPOS01 count change selected signal(stSeld) for SAS
3203011D20 DPOS01_CNT_VAL DPOS01 count value
3103011FEF DPOS01_CPH_STATE DPOS01 cph_state
8B03011F79 DPOS01_CTR_SGU DPOS01 selected signal
8903011F99 DPOS01_CTR_SGUCN DPOS01 count change selected signal
8203011E8B DPOS01_EC_F_CS DPOS01 execute command fail condition signal
8103011E9A DPOS01_ECF_FCT_EIS DPOS01 execute command fail factor signal except interlock/synchronism check
0003011D97 DPOS01_EX_BO_OPOK DPOS01 execute binary output signal for SAS
8003011E93 DPOS01_EX_CMP DPOS01 execute complete signal
8F03011F5E DPOS01_EX_CMP_TMO DPOS01 timeout after execute completion
8903011F9E DPOS01_EX_CMP_TMOCN DPOS01 count change timeout after execute completion
8603011E91 DPOS01_EX_FFL DPOS01 execute fail signal by fixedlogic
8503011E8F DPOS01_EX_SFL DPOS01 execute success signal by fixedlogic
8003011E81 DPOS01_FEC_OK_CS DPOS01 off direction execute command OK condition signal
8103011DD0 DPOS01_FEX_BO DPOS01 off direction execute binary output signal
8403011F45 DPOS01_FLT_DET1 DPOS01 Faulty Detected (3 phase concentration data only)
8A03011DC4 DPOS01_FSL_BO_FLG DPOS01 off direction select binary output signal
8A03011F81 DPOS01_FSL_CS19 DPOS01 select receive open signal check answer
3103011D01 DPOS01_LCD_ST DPOS01 state for LCD
3103011D00 DPOS01_MMC_ST DPOS01 state for MIMIC
8903011DC0 DPOS01_NSL_BO_FLG DPOS01 select binary output signal
8603011F7E DPOS01_NSL_CS07 DPOS01 select receive signal check answer
8103011E82 DPOS01_OEC_OK_CS DPOS01 on direction execute command OK condition signal
8203011DD3 DPOS01_OEX_BO DPOS01 on direction execute binary output signal
8603011DC6 DPOS01_OSL_BO_FLG DPOS01 on direction select binary output signal
8803011F73 DPOS01_OSL_CS41 DPOS01 on direction select condition signal 41
8603011F8B DPOS01_RST_CS07 DPOS01 reset time selected fail condition signal
0003011F57 DPOS01_RST_SIG DPOS01 reset time signal
8503011F87 DPOS01_SE_RCV_RMTCN DPOS01 count change selected fail condition signal check
8503011F8A DPOS01_SE_RCV_RMTRT DPOS01 reset time selected fail condition signal check
8003011E76 DPOS01_SLD_CS DPOS01 selected condition signal
8003011F67 DPOS01_SLD_CS04 DPOS01 selected condition signal 04
8103011F68 DPOS01_SLD_CS05 DPOS01 selected condition signal 05
8203011F69 DPOS01_SLD_CS06 DPOS01 selected condition signal 06
8A03011F86 DPOS01_SLD_CSCN DPOS01 count change selected condition signal
8A03011F89 DPOS01_SLD_CSRT DPOS01 reset time selected condition signal
0003011D90 DPOS01_SLD_RPT DPOS01 selected signal(stSeld) for SAS
8E03011F5D DPOS01_SLD_TMO DPOS01 time out after selected
8A03011F9D DPOS01_SLD_TMOCN DPOS01 count change time out after selected
8103011E7B DPOS01_SLF_CS DPOS01 no direction select fail condition signal
8703011E98 DPOS01_SLF_FCT_EIS DPOS01 select fail factor signal except interlock/synchronism check
8803011F9B DPOS01_SLF_FCT_F03CN DPOS01 count change select fail factor signal by fixedlogic 03
8703011F9C DPOS01_SLF_FCT_F04CN DPOS01 count change select fail factor signal by fixedlogic 04
8303011F9A DPOS01_SLF_FCT_F07CN DPOS01 count change selected timer for a check
8503011F65 DPOS01_SLF_FCT_FLG05 DPOS01 select fail factor signal by fixedlogic 05
8803011F6C DPOS01_SLF_FCT_FLG07 DPOS01 selected timer for a check
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the DPOS function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device; hence, the
user can find the same ones for all of the other devices. For example, when the user
wishes to find the “DPOS02A_FLT_DET” point provided for the 2nd device, use the
description of “DPOS01A_FLT_DET”. The user can obtain the ID value of
“DPOS02A_FLT_DET” by using the following steps:
Step 1 Find the element ID for DPOS01A_FLT_DET (i.e., “8303011F49”)
Step 2 Identify the numbers at the fifth and sixth digit from the ID. (i.e.,
“01”)
Step 3 Choose a new device number. (i.e., pick the number “2” for the 2nd
device)
Step 4 Replace the sixth and fifth digit numbers with the new device
number. (i.e., get new ID “8303021F49” of “DPOS02A_FLT_DET”) The
ID is expressed in hexadecimal notation. Thus, the user must change
the device number from decimal notation to hexadecimal notation.
P1 P2 P3
The TPOS function has “Operation counters” and “Operation time measurement”; these
features are used to examine the devices; these features are useful when the user wishes to
assess the operating time of the device; these features are performed by counting the state-
changes for the device. The BO circuits connected with the TPOS function are used for issuing
commands; the BI circuits are used for receiving responses; hence, the user should connect the
BO and BI circuits with the TPOS function†. The TPOS function includes three logic groups:
1. Select logic, 2. Cancel logic, and 3. Operate logic.
EDS devices (43-switches) can be controlled separately; i.e., the function has a number of
separate sets for control (i.e., TPOS01, TPOS02, etc.). For simplicity, only the TPOS01 function
is discussed here; the features in the other TPOS functions are identical to the TPOS01
function.
†Note:A binary IO module has binary input circuits (BIs) and binary output circuits
(BOs); the user makes the connection between the TPOS01 function and the
binary IO module using a signal number (is made of a “Function_ID” and an
“Element_ID”). The signal numbers and names in the TPOS01 function are listed
later.
Tips: If the user wishes to apply the TPOS function quickly, go to sections 4.6.6 and
4.6.5, where settings of the BI and BO circuits and the mapping of signal-points
for IEC61850 communication is described.
Cancel logic
P2 control from the remote-end
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The TPOS01 function can issue an signal “Select success” at the output point
“TPOS01_P1SL_BO_FLG”, when the TPOS01 function determines that the input signal
“Remote-P1-Control” received is true. If the TPOS01 function determines that the “Remote-
P1-Control” is not true, the TPOS01 function returns to the “Wait for a command” stage.
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The TPOS01 function, in Figure 4.6-5, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command (Remote-P2-Control)” is true. If the TPOS01 function determines that the
“Remote-P2-Control” signal is not true, the TPOS01 function returns to the “Wait for a
command” stage.
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The TPOS01 function, in Figure 4.6-7, can issue a signal “Select success” at the output point
“TPOS01_P3SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command P3 (Remote-P3-Control)” is true. If the TPOS01 function determines that the
“Remote-P3-Control” is not true, the TPOS01 function returns to the “Wait for a command”
stage.
Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.6-9 Selection logic for P1-control at the IED locally in TPOS01††
†Note:The ILK function provides the operation criteria for “P1-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.6-20
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.6-5,
Table 4.6-6 and Table 4.6-9.
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P1SL_BO_FL”.
Note: The signal “TPOS01_P1SL_BO_FL” is the same as the signal shown in Figure
4.6-3. If the input signal “Local-P1-Control” is not true, the TPOS01 function
returns to the “Wait for a command” stage.
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.6-20.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.6-5,
Table 4.6-6, and Table 4.6-9.
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue “Select success”
signal at the output-point “TPOS01_P2SL_BO_FLG”.
1Note: The “TPOS01_P2SL_BO_FLG” signal is the same as the signal shown in Figure
4.6-5. If the “Local-P2-Control” signal is not true, the TPOS01 function returns to
the “Wait for a command” stage.
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P3SL_BO_FLG”.
1Note: The “TPOS01_P3SL_BO_FLG” signal is the same signal as shown in Figure 4.6-7.
If the “Local-P3-Control” signal is not true, the TPOS01 function returns to the
“Wait for a command” stage.
Operate logic
P1control by the PLC function
Failed Operate command
510001 7001016D08
1≥ &
P1-control command requiring ILK† check To “Wait for a next
For DIR operation
(PLC connection point #1) command”
Operate command
513001 800401EE31 DEV01_P1_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
ILK† condition (“P1”) passed
TPOS1-P1 0 t Select “success”
0.1s
P1-control command not requiring ILK† checking For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE30 DEV01_P1_COMMAND
without ILK† condition & 0.6s
Select condition‡
Output signal to BO
The TPOS01 function, in Figure 4.6-15, can issue a “Select success” signal at the output-point
“TPOS01_P1SL_BO_FLG”1.
1Note: The “TPOS01_P1SL_BO_FLG” signal is the same as the signal shown in Figure
4.6-13.
Operate logic
P1 control by the PLC function
Operate command
Operate logic
PLC logic programmed Select
Selection logic Signal output
by the user decision Success
510001 7001016D08
1≥ &
P2-control command requiring ILK †check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE33 DEV01_P2_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
ILK† condition (“P2”) passed
TPOS1-P2 0 t Select “success”
0.1s
P2-control command not requiring ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE32 DEV01_P2_COMMAND
without ILK† condition & 0.6s
Figure 4.6-17 Select logic ‘P2-control’ using the PLC function in TPOS01††
††Note: To identify the input and output points of the other TPOS logics, see Table 4.6-2
for PLC#1 and #2, and Table 4.6-9 for the outputs.
†Note:The ILK function provides the operation criteria for “P2-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.6-20.
Output signal to BO
The TPOS01 function, in Figure 4.6-17, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FLG”1.
1Note: The output point “TPOS01_P2SL_BO_FLG” is the same as the signal shown in
Figure 4.6-5.
Operate logic
P1 control by the PLC function
Operate command
P2 control by the PLC function
510001 7001016D08
1≥ &
P3-control command requiring with ILK† check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE37 DEV01_P3_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
ILK† condition (“P3”) passed
TPOS1-P3 0 t Select “success”
0.1s
P3-control command not requiring without ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE36 DEV01_P3_COMMAND
without ILK† condition & 0.6s
Select condition‡
Output signal to BO
The TPOS01 function, in Figure 4.6-19, can issue a “Select success” signal at the output point
“TPOS01_P3SL_BO_FLG”1.
1Note: The output point “TPOS01_P3SL_BO_FLG” is the same as the signal shown in
Figure 4.6-7.
TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3
&
[TPOS01-DEVTYPE]*8
&
EDS
[TPOS01-CTREN]
On
513001 800401EE31 DEV01_P1_INTERLOCK P1-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE31 DEV02_P1_INTERLOCK P1-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE31 DEV03_P1_INTERLOCK P1-control checking with interlock in TPOS03 (for PLC#1) O
… …. ….
513001 800418EE31 DEV24_P1_INTERLOCK P1-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE30 DEV01_P1_COMMAND P1-control without checking in TPOS01 (for PLC#2) O
513001 800402EE30 DEV02_P1_COMMAND P1-control without checking in TPOS02 (for PLC#2) O
513001 800403EE30 DEV03_P1_COMMAND P1-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE30 DEV24_P1_COMMAND P1-control without checking in TPOS24 (for PLC#2) O
513001 800401EE33 DEV01_P2_INTERLOCK P2-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE33 DEV02_P2_INTERLOCK P2-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE33 DEV03_P2_INTERLOCK P2-control checking with interlock in TPOS03 (for PLC#1)
… …. ….
513001 800418EE33 DEV24_P2_INTERLOCK P2-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE32 DEV01_P2_COMMAND P2-control without checking in TPOS01 (for PLC#2) O
513001 800402EE32 DEV02_P2_COMMAND P2-control without checking in TPOS02 (for PLC#2) O
513001 800403EE32 DEV03_P2_COMMAND P2-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE32 DEV24_P2_COMMAND P2-control without checking in TPOS24 (for PLC#2) O
513001 800401EE37 DEV01_P3_INTERLOCK P3-control checking with interlock in TPOS01 (for PLC#1) O
513001 800402EE37 DEV02_P3_INTERLOCK P3-control checking with interlock in TPOS02 (for PLC#1) O
513001 800403EE37 DEV03_P3_INTERLOCK P3-control checking with interlock in TPOS03 (for PLC#1) O
… …. ….
513001 800418EE37 DEV24_P3_INTERLOCK P3-control checking with interlock in TPOS24 (for PLC#1) O
513001 800401EE36 DEV01_P3_COMMAND P3-control without checking in TPOS01 (for PLC#2) O
513001 800402EE36 DEV02_P3_COMMAND P3-control without checking in TPOS02 (for PLC#2) O
513001 800403EE36 DEV03_P3_COMMAND P3-control without checking in TPOS03 (for PLC#2) O
…. …. ….
513001 800418EE36 DEV24_P3_COMMAND P3-control without checking in TPOS24 (for PLC#2) O
Table 4.6-6 PLC connection points Interlock for P1, P2, and P3-control
Signal Number Signal Name Description M/O
Table 4.6-7 PLC connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
… … ….
513001 820418ED50 TPOS24IN_TMP_21 TPOS24 control hierarchy condition(PLC#3) M
Table 4.6-8 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
513001 8A04011DC4 TPOS01_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS01
513001 8A04021DC4 TPOS02_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS02
513001 8A04021DC4 TPOS03_P1SL_BO_FLG Select command (P1) for Binary Output in TPOS03
… … …
513001 8A04181DC4 TPOS241SL_BO_FLG Select command (P1) for Binary Output in TPOS24
513001 8A04011DC6 TPOS01_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS01
513001 8A04021DC6 TPOS02_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS02
513001 8A04031DC6 TPOS03_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS03
… …. ….
513001 8A04181DC6 TPOS24_P2SL_BO_FLG Select command (P2) for Binary Output in TPOS24
513001 8A04011DC8 TPOS01_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS01
513001 8A04021DC8 TPOS02_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS02
513001 8A04031DC8 TPOS03_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS03
… …. ….
513001 8A04181DC8 TPOS24_P3SL_BO_FLG Select command (P3) for Binary Output in TPOS24
Operate logic
P3 control by the PLC function
“Do nothing”
“TPOS01_CC_FS”
(513001_8704011E96)
Operation Failed
Output signal to BO
The TPOS01 function can issue a “Success to cancel” signal at the monitoring, point
“TPOS01_CC_SS”, when the TPOS01 function has determined that the “Remote-cancel” signal
is true. Another “Operate failed” signal is issued at monitoring point “TPOS01_CC_FS” if the
TPOS01 function is able to determine that the “Remote-cancel” signal is not true.
Select stage
Wait for a next command
P1 control from remote-end
Cancel from the remote-end
P2 control from remote-end
Cancel from the local-end
Success
P3 control from remote-end
Operate logic
P3 control by PLC function
Input signal
Figure 4.6-24 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the TPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal, provided that the “cancel
condition” checking is satisfied.
510001 7001016D08
Cancel command
Command “Local-cancel”
& To “Wait for a command”
“TPOS01_ CC_SS”
(513001_8604011E95)
Cancel condition &
Successes to cancel
“Do nothing”
“TPOS01_CC_FS”
(513001_8704011E96)
Operation Failed
at the monitoring point “TPOS01_CC_SS”, when the TPOS01 function determines that the
“Local-Cancel” signal is true.
[TPOS01-LGCNFFCT]
User configurable condition (PLC connection point)
Fixedlogic
513001 800401EE69 TPOS01IN_TMP_40 &
If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User Configurable condition”:
Connect the user-customized logic, with the “TPOS01IN_TMP_40”, which is listed
in Table 4.6-11.
Set scheme switch [TPOS01-LGCNFFCT] to PLC.
Table 4.6-11 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
… … …
513001 800418EE69 TPOS24IN_TMP_40 TPOS3 user configurable cancel condition O
Table 4.6-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
TPOSxx-LGCNFFCT Logic selector for cancel condition (TPOS01-24) Fixedlogic Fixedlogic / PLC
Failed Do nothing
“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command “Remote-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
Output signal to BO
The TPOS01 function, in Figure 4.6-27, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the received “Remote-P1-
Control” signal is true.
Failed Do nothing
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command “Remote-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.6-15 for PLC#2, Table 4.6-16 for PLC#3 and Table 4.6-19 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.6-29, can issue an “Operate” signal at the output-point
“TPOS01_P2EX_BO”, when the TPOS01 function determine that the input signal “Remote-P2-
Control” is true.
Failed Do nothing
“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “Remote-P3-Control” (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
logic programmed by the user in place of the logic shown in Figure 4.6-26. The
user-programmed logic is connected internally to the “operate completed” signal,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.6-31, can issue an “Operate” signal at the output-point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the input signal “Remote-
P3-Control” is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command Local-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
ILK† condition (“P1”) passed
S
TPOS1-P1 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
†Note:The ILK function can provide the operation criteria for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.6-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.6-14 for PLC#1, Table 4.6-15 for PLC#2 and Table 4.6-19 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the scheme
switch [TPOS01-LGP1EXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.6-26. The user-programmed logic is connected internally to the “operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.6-33, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the “Local-P1-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
Output signal to BO
The TPOS01 function, in Figure 4.6-35, can issue an “Operate” signal at the output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “Local-P2-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P3-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
logic programmed by the user in place of the logic shown in Figure 4.6-26. The
user-programmed logic is connected internally to the signal “operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.6-37, can issue an “Operate” signal at the output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the “Local-P3-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
apply the signal at other connection point (PLC#4; i.e., DEV01_P1_COMMAND). We should
assume the PLC#3 and PLC#4 as PLC#1 and PLC#2 in Table 4.6-1. Note that the user should
set PLC for scheme switch [TPOS01-LGP1EXOT].
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
Figure 4.6-39 Operate P1- control using the PLC function in TPOS01††
†Note:The ILK function can provide the criteria for operation for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.6-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.6-39 using connection point #1
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.6-14 for PLC#1, Table 4.6-15 for PLC#2 and Table 4.6-19 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
failing expiration of the setting applied to timer [TPOS01-RST]
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set the scheme switch
[TPOS01-LGP1EXOT]. If the signal to be issued from the logic programmed by the
user instead of the logic shown in Figure 4.6-26, connect the “operate completed”
signal generated in the user-programmed logic to connection point#2 “User
configurable condition”. That is, set PLC to the scheme switch [TPOS01-
LGP1EXOT] and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.6-39, can issue a “Operate P1-control” signal at output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the signal “PLC-P1-Control”
is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
to be treated as PLC#1 and PLC#2 in Table 4.6-2. Note that the user should set PLC for scheme
switch [TPOS01-LGP2EXOT].
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
LGP1EXOT]. If the signal is to be issued from the logic programmed by the user
instead of the logic shown in Figure 4.6-26, connect the “operate completed” signal
generated in the user-programmed logic to connection point#2 “User configurable
condition”. That is, set the scheme switch [TPOS01-LGP1EXOT] to PLC and use
“TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.6-15 for PLC#2, Table 4.6-16 for PLC#3 and Table 4.6-19 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.6-41, can issue a signal “Operate P2-control” at output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “PLC-P2-Control” signal
is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
switch [TPOS01-LGP3EXOT].
“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “PLC-P3-Control”requiring ILK check (PLC#3
connection point) (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
Operate Cmd.
513001 800401EE37 DEV01_P3_INTERLOCK
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-P3-Control ”not requiring ILK check 0.1 – 50.0 s
(PLC#4 connection point)
513001 800401EE36 DEV01_P3_COMMAND Operation Cmd.
without ILK† condition
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. If the signal is to be issued from the programmed logic by
the user instead of the logic shown in Figure 4.6-26, connect the “operate
completed” signal generated in the user-programmed logic to connection point#2
“User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.6-43, can issue a signal “Operate P3-control” at output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the signal “PLC-P3-Control”
is true.
TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3
&
[TPOS01-DEVTYPE]*8
&
EDS
[TPOS01-CTREN]
On
4.6-5.
*5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
*6Note: The Function “Event suppression” can detect chattering in BI circuits. (See
4.6.6(i)-3)
*7Note: A supervision of the Binary IO module can detect connection errors for BI
circuits.
*8Note: The “Common control” (CMNCTRL) function can test or check the operation
– direction of logic. When the user sets off for scheme switch [SCDEN], operation
of the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
*9Note: The user should set scheme switch [TPOS01-DEVTYPE] EDS when the earth-
switch(ES) is applied for the TPOS01 function.
*10Note: The user must program the PLC logic for “Control hierarchy condition” The
user must connect the “Control hierarchy” condition to the select condition logic
using the connection point TPOS01IN_TMP_21” for more information, see chapter
Control and monitoring application: Control hierarchy” see PLC#3 of Table 4.6-7.
*11Note: To identify the input points of the other TPOS, see Table 4.6-7 for PLC#1 to
#3. Note that the logic outputs are generated separately for P1, P2 and P3-
control.
Table 4.6-14 PLC connection points (Input signal PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE56 TPOS01IN_TMP_27 TPOS01 operate condition configured by the user (for PLC#1) O
513001 800402EE56 TPOS02IN_TMP_27 TPOS02 operate condition configured by the user (for PLC#1) O
513001 800403EE56 TPOS03IN_TMP_27 TPOS03 operate condition configured by the user (for PLC#1) O
… … …
513001 800418EE56 TPOS24IN_TMP_27 TPOS24 operate condition configured by the user (for PLC#1) O
Table 4.6-15 PLC connection points (Input signal PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
513001 820401EE5E TPOS01IN_TMP_38 TPOS01 operate condition configured by the user (for PLC#2) O
513001 820402EE5E TPOS02IN_TMP_38 TPOS02 operate condition configured by the user (for PLC#2) O
513001 820403EE5E TPOS03IN_TMP_38 TPOS03 operate condition configured by the user (for PLC#2) O
… … …
513001 820418EE5E TPOS24IN_TMP_38 TPOS24 operate condition configured by the user (for PLC#2) O
Table 4.6-16 PLC connection points (Input signal PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
513001 810401EE57 TPOS01IN_TMP_28 TPOS01 operate condition configured by the user (for PLC#3) O
513001 810402EE57 TPOS02IN_TMP_28 TPOS02 operate condition configured by the user (for PLC#3) O
513001 810403EE57 TPOS03IN_TMP_28 TPOS03 operate condition configured by the user (for PLC#3) O
…. …. …
513001 810418EE57 TPOS24IN_TMP_28 TPOS24 operate condition configured by the user (for PLC#3) O
Table 4.6-17 PLC connection points (Input signal PLC#4 user configurable condition)
Signal Number Signal Name Description M/O
513001 840401EE58 TPOS01IN_TMP_29 TPOS01 operate condition configured by the user (for PLC#4) O
513001 840402EE58 TPOS02IN_TMP_29 TPOS02 operate condition configured by the user (for PLC#4) O
513001 840403EE58 TPOS03IN_TMP_29 TPOS03 operate condition configured by the user (for PLC#4) O
… … …
513001 840418EE58 TPOS24IN_TMP_29 TPOS24 operate condition configured by the user (for PLC#4) O
Table 4.6-18 PLC connection points (Input point additional, user configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE65 TPOS01IN_TMP_33 Condition added by the user in TPOS01 (for PLC#1) O
513001 800402EE65 TPOS02IN_TMP_33 Condition added by the user in TPOS02 (for PLC#1) O
513001 800403EE65 TPOS03IN_TMP_33 Condition added by the user in TPOS03 (for PLC#1) O
… … …
513001 800418EE65 TPOS24IN_TMP_33 Condition added by the user in TPOS24 (for PLC#1) O
513001 810401EE66 TPOS01IN_TMP_34 Condition added by the user in TPOS01 (for PLC#2) O
513001 810402EE66 TPOS02IN_TMP_34 Condition added by the user in TPOS02 (for PLC#2) O
513001 810403EE66 TPOS03IN_TMP_34 Condition added by the user in TPOS03 (for PLC#2) O
… … …
513001 810418EE66 TPOS24IN_TMP_34 Condition added by the user in TPOS24 (for PLC#2) O
513001 8104011DD0 TPOS01_P1EX_BO Operate command (P1) for Binary Output in TPOS01
513001 8104021DD0 TPOS02_P1EX_BO Operate command (P1) for Binary Output in TPOS02
513001 8104031DD0 TPOS03_P1EX_BO Operate command (P1) for Binary Output in TPOS03
… … …
513001 8104181DD0 TPOS24_P1EX_BO Operate command (P1) for Binary Output in TPOS24
513001 8204011DD3 TPOS01_P2EX_BO Operate command (P2) for Binary Output in TPOS01
513001 8204021DD3 TPOS02_P2EX_BO Operate command (P2) for Binary Output in TPOS02
513001 8204031DD3 TPOS03_P2EX_BO Operate command (P2) for Binary Output in TPOS03
…. …. ….
513001 8204181DD3 TPOS24_P2EX_BO Operate command (P2) for Binary Output in TPOS24
513001 8204011DD6 TPOS01_P3EX_BO Operate command (P3) for Binary Output in TPOS01
513001 8204021DD6 TPOS02_P3EX_BO Operate command (P3) for Binary Output in TPOS02
513001 8204031DD6 TPOS03_P3EX_BO Operate command (P3) for Binary Output in TPOS03
… … …
513001 8204181DD6 TPOS24_P3EX_BO Operate command (P3) for Binary Output in TPOS24
513001 8004011E7E TPOS01_P1EC_OK_CSF TPOS01 P1 direction execute command
513001 8004021E7E TPOS02_P1EC_OK_CSF TPOS02 P1 direction execute command
513001 8004031E7E TPOS03_P1EC_OK_CSF TPOS03 P1 direction execute command
… … …
513001 8004181E7E TPOS24_P1EC_OK_CSF TPOS24 P1 direction execute command
513001 8004011E7F TPOS01_P2EC_OK_CSF TPOS01 P2 direction execute command
513001 8004021E7F TPOS02_P2EC_OK_CSF TPOS02 P2 direction execute command
513001 8004031E7F TPOS03_P2EC_OK_CSF TPOS03 P2 direction execute command
… … …
513001 8004181E7F TPOS24_P2EC_OK_CSF TPOS24 P2 direction execute command
513001 8004011E80 TPOS01_P3EC_OK_CSF TPOS01 P3 direction execute command
513001 8004021E80 TPOS02_P3EC_OK_CSF TPOS02 P3 direction execute command
513001 8004031E80 TPOS03_P3EC_OK_CSF TPOS03 P3 direction execute command
… … …
513001 8004181E80 TPOS24_P3EC_OK_CSF TPOS24 P3 direction execute command
513001 8004011E81 TPOS01_P1EC_OK_CS TPOS01 P1 direction execute command
513001 8004021E81 TPOS02_P1EC_OK_CS TPOS02 P1 direction execute command
513001 8004031E81 TPOS03_P1EC_OK_CS TPOS03 P1 direction execute command
… … …
513001 8004181E81 TPOS24_P1EC_OK_CS TPOS24 P1 direction execute command
513001 8304011E82 TPOS01_P2EC_OK_CS TPOS01 P2 direction execute command
513001 8304021E82 TPOS02_P2EC_OK_CS TPOS02 P2 direction execute command
513001 8304031E82 TPOS03_P2EC_OK_CS TPOS03 P2 direction execute command
… … …
513001 8304181E82 TPOS24_P2EC_OK_CS TPOS24 P2 direction execute command
513001 8404011E83 TPOS01_P3EC_OK_CS TPOS01 P3 direction execute command
513001 8404021E83 TPOS02_P3EC_OK_CS TPOS02 P3 direction execute command
513001 8404031E83 TPOS03_P3EC_OK_CS TPOS03 P3 direction execute command
… … …
513001 8404181E83 TPOS24_P3EC_OK_CS TPOS24 P3 direction execute command
513001 8004011E93 TPOS01_EX_CMP TPOS01 completed control
513001 8004021E93 TPOS02_EX_CMP TPOS02 completed control
513001 8004031E93 TPOS03_EX_CMP TPOS03 completed control
… … …
513001 8004181E93 TPOS24_EX_CMP TPOS24 completed control
513001 8604011E91 TPOS01_EX_FFL TPOS01 failed control
513001 8604021E91 TPOS02_EX_FFL TPOS02 failed control
513001 8604031E91 TPOS03_EX_FFL TPOS03 failed control
… … …
513001 8604181E91 TPOS24_EX_FFL TPOS24 failed control
Closed
Open
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See Chapter User interface: Monitoring sub-menu
on how to operate the sub-menu.
“TPOS01_SLD_CSCN”
(513001 8A04011F8B)
Command “change value for counter”
513001_7004016D09 DEV01_ALLCNT_REQ Operate Command
&
Operate condition‡
Figure 4.6-47 Change counter value in net counter† by the remote-end in TPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic shown
in Figure 4.6-49.
†Note: The user can apply the other counter change commands for P1-control, P2-control
and P3-control as shown in Table 4.6-23. The resultant signals for the other
TPOS02-24 logics are shown in Table 4.6-22.
Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.
Figure 4.6-48 Changing value by the operation of the front panel in TPOS01
Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.
Figure 4.6-49 Operate condition logic for changing the counter in TPOS01
*1Note: “Command Blocking” disables all operation except for its own; the “Command
blocking” function is initiated by the status of “CBK” in a software switch
controller (SOFTSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch control function. See the signal
“CBK_STATE” of Table 4.6-5.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3Note: If the event “device-travelling is detected, it indicates that another operator
is changing the status of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
denoted as “Traveling OR” in Table 4.6-5.
*4Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
… … …
513001 8A04181F8B TPOS24_SLD_CSCN TPOS24 counter selected
513001 7004016D09 DEV01_ALLCNT_REQ TPOS01 counter correction request for summation counter value
513001 7004026D09 DEV02_ALLCNT_REQ TPOS02 counter correction request for summation counter value
513001 7004036D09 DEV03_ALLCNT_REQ TPOS03 counter correction request for summation counter value
… … …
513001 7004186D09 DEV24_ALLCNT_REQ TPOS24 counter correction request for summation counter value
513001 7004016D0A DEV01_P1CNT_REQ TPOS01 counter correction request for P1 counter value
513001 7004026D0A DEV02_P1CNT_REQ TPOS02 counter correction request for P1 counter value
513001 7004036D0A DEV03_P1CNT_REQ TPOS03 counter correction request for P1 counter value
… … …
513001 7004186D0A DEV24_P1CNT_REQ TPOS24 counter correction request for P1 counter value
513001 7004016D0B DEV01_P2CNT_REQ TPOS01 counter correction request for P2 counter value
513001 7004026D0B DEV02_P2CNT_REQ TPOS02 counter correction request for P2 counter value
513001 7004036D0B DEV03_P2CNT_REQ TPOS03 counter correction request for P2 counter value
… … …
513001 7004186D0B DEV24_P2CNT_REQ TPOS24 counter correction request for P2 counter value
513001 7004016D0C DEV01_P3CNT_REQ TPOS01 counter correction request for P3 counter value
513001 7004026D0C DEV02_P3CNT_REQ TPOS02 counter correction request for P3 counter value
513001 7004036D0C DEV03_P3CNT_REQ TPOS03 counter correction request for P3 counter value
… … …
513001 7004186D0C DEV24_P3CNT_REQ TPOS24 counter correction request for P3 counter value
TPOSxx-P1CNTS Mode selection of the counter in P1-control *user-preferred NA / C-On / C-Off / C-OnOff
TPOSxx-P2CNTS Mode selection of the counter in P2-control *user-preferred NA / C-On / C-Off / C-OnOff
TPOSxx-P3CNTS Mode selection of the counter in P3-control *user-preferred NA / C-On / C-Off / C-OnOff
to Figure 4.6-53. The user should set scheme switch [TPOS01-OPETMEN] On.
Signal “TPOS01_P2EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P2-control
Signal “TPOS01_PT_P3”
OT1 OT2
a. Switch motion (P1 to P2) b. Operate command and signals with regard to the switch motion (P1 to P2)
Signal “TPOS01_P1EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P1-control
Signal “TPOS01_PT_P3”
OT3 OT4
a. Switch motion (P2 to P1) b. Operate command and signals with regard to the switch motion (P2 to P1)
Signal “TPOS01_P2EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P2-control
Signal “TPOS01_PT_P3”
OT5 OT6
a. Switch motion (P3 to P2) b. Operate command and signals with regard to the switch motion (P3 to P2)
Signal “TPOS01_P3EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P3-control
Signal “TPOS01_PT_P3”
OT5 OT6
a. Switch motion (P2 to P3) b. Operate command and signals with regard to the switch motion (P2 to P3)
The user can clear the operation-intervals (OT1 to OT8) by key-operation of the
“Operation time” sub-menu or operation from the remote-end. Figure 4.6-54 shows that the
user can clear the eight operation times using this screen. See chapter User interface:
Monitoring sub-menu for the operation.
513001 7004016D0D DEV01_RESET_REQ TPOS01 operation time reset command (Mapping Data)
513001 7004026D0D DEV02_RESET_REQ TPOS02 operation time reset command (Mapping Data)
513001 7004036D0D DEV03_RESET_REQ TPOS03 operation time reset command (Mapping Data)
… … …
513001 7004186D0D DEV24_RESET_REQ TPOS24 operation time reset command (Mapping Data)
Note that the TPOS01 function commences operation when the scheme switch [TPOS01-EN]
is set to On.
“TPOS01_STATE”
Event suppression detector (513001_3104011001)
BI1, BI2, and BI3 signals desig
nated by settings
[TPOS01-P1NOPSG], & 1≥
[TPOS01-P2NOPSG],
and [TPOS01-P3NOPSG] S
Status before chattering
R “TPOS01_ QLT_SPP”
(513001_8204011F59)
On
& To select and operate
condition logics
Figure 4.6-55 BI1, BI2 and BI3 signals provided into TPOS01
†Note:The user should set the actual input- points, see Chapter Technical description:
Binary IO module.
‡Note:In Figure 4.6-55 two signals can be issued: “TPOS01_STATE” and
“TPOS01_QLT_SPP”. The former one is used in the select condition logic and the
operate condition (see Figure 4.6-20 and Figure 4.6-44). The latter is used for an
event suppression detector.
If “On–On–Off” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth switch is still kinetic and is not standstill; thus, the decision is given as
“Intermediate”, the value “3” is given at the connection point ”TPOS01_STATE”.
If “On–On–On” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth-switch may be broken; hence, the value “7” is given.
Table 4.6-29 Decision made by the TPOS01 function
Input signals at IO#1 (200B01) Generated value
Decision by
BI1 BI2 BI3 “TPOS01_STATE”
TPOS01
(8001001110) (8101011110) (8201021110) (513001 3104011001)
Off (0) Off (0) Off (0) Intermediate 0
On (1) Off (0) Off (0) P1 1
Off (0) On (1) Off (0) P2 2
On (1) On (1) Off (0) Intermediate 3
Off (0) Off (0) On (1) P3 4
On (1) Off (0) On (1) Intermediate 5
Off (0) On (1) On (1) Intermediate 6
On (1) On (1) On (1) Faulty 7
Note: When handling the raw information other than the decision, the user can take
respective states of binary input circuits using other monitoring points. That is,
the user can take either state On (1) or state Off (0) corresponding to the BI1
circuit using the monitoring point “TOPS01_PT_P1”. Likewise, the BI2 and BI3
states can be taken using the monitoring points “TOPS01_PT_P2” and
“TOPS01_PT_P3”. (See Table 4.6-34)
[TPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[TPOS-TELD] [TPOS-TELR]
Time................. A B C D E
Figure 4.6-56 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [TPOS-NELD] is provided so
that the suppression commences at Time B. The setting [TPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signal stops. The user can adjust the
point at which event suppression stops using the setting [TPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [TPOS01-SPPEN].
Terminal and
Selection logic in TPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
Selection logic for select “BO1” Select
Signal captured by command
command P1 in TPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
P1
[Input signal 2] DRIVER BO1
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Selection logic for select check
command P2 in TPOS01 [Input signal 7]
[Input signal 8]
Terminal and
Selection logic for select BO2 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P2SL_BO_FLG”
command P3 in TPOS01
(513001 8A04011DC6)
“BO2” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112)
P2
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Terminal and
BO3 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
“BO3” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8202021112)
P3
[Input signal 2] DRIVER BO3
& ≥1
To contact health
[Input signal 3]
check “BO3-RB”
[Input signal 4] [BO3_CPL] On &
(200B01_8102021113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Terminal and
Operate logic in TPOS01 BO4–BO6 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P1EX_BO”
(513001_8104011DD0)
“BO4”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8302031112)
command
P1-control P1
[Input signal 2] DRIVER BO4
in TPOS01 & ≥1
[Input signal 3]
“BO4-RB”
[Input signal 4] [BO4_CPL] On &
Connected by Off
(200B01_8302031113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
†Note:Table 4.6-20 shows settings for the health check feature in the other TPOS
functions.
the command, the user can connect point “BO1-RB “ with the contact health check function
using the setting [TPOS01-P1SLBORD]. Do not key the point “TPOS01_P1SL_BO”. Likewise,
BO2-RB and BO3-RB are required to be set.
Contact health check
Selection logic in TPOS01 logic in TPOS01
“TPOS01_P1SL_BO” (513001 8A04011DC4)
Figure 4.6-59 Example contact health check feature for P1–P3 select commands
Figure 4.6-60 Contact health check logic for P1–P3 operate commands
Proper setting for the contact health check (normal setting, example #1)
Figure 4.6-61 shows a setting example for 43S/EDS driving. Select and operate commands
drive the BO1–BO6 contacts. To check that the contact health check function is working
correctly, the respective points of the BO (RBs) should be connected, as shown in Table 4.6-30,
to demonstrate that the settings are physically matched with the BO contacts.
P1-select BO1
command “BO1-RB”
(200B01 8002001113)
“TPOS01_P1EX_BO”
(513001 8104011DD0)
P1-operate BO4
command “BO4-RB”
(200B01 8302031113)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)
P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)
Minus (−)
Figure 4.6-61 Contact health check setting and EDS scheme for example #1
Setting for erroneous in contact health check (improper setting, example #2)
Figure 4.6-62 shows a setting example for an improper setting of the 43S/EDS scheme. The
settings are implemented incorrectly as shown in Table 4.6-31, BO1-RB is not chosen, instead
BO1 is actually chosen, which is incorrect. In this case, the setting [TPOS01-SLBORD] is
meaningless; hence, the issue of a select command is blocked.
“TPOS01_P1SL_BO_FLG” is connected to “BO1” on SLOT1 200B01 8002001112 (BO1) set for [TPOS01-P1SLBORD] NG
P1-select BO1
command
“TPOS01_P1EX_BO”
(513001 8104011DD0)
P1-operate BO4
command “BO4-RB”
(200B01 8302031113)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)
P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)
Minus (−)
Figure 4.6-62 Contact health check setting and EDS diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.6-63 shows an additional setting example for the EDS scheme; one of the settings is
made hypothetically. That is, the point “SPO01_P1*SL_BO_FLG” is actually chosen for the
setting [TPOS01-P1*SLBORD]; i.e. BO1-RB is not chosen for this selection. This special
example can issue a select command; which is called “operated by internal select function”.
The user does not need to consider the use of a BO circuit for a select command, when there
are no BO circuits available.
Table 4.6-32 Extra setting example for contact health check
Example #3 Setting for example #3
Remote/Local end
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
P1-select
command
“TPOS01_P2SL_BO_FLG” BOs are not connected but virtualized.
(513001 8A04011DC6)
P2-select
command “TPOS01_P3SL_BO_FLG”
EDS
(513001 8A04011DC8)
P3-select
command
Plus (+)
SAS/Local IED
BIO module P1-Operate P2-Operate P3-Operate
“TPOS01_P1EX_BO”
(513001 8104011DD0) Drivers
P1-operate BO4
command “BO4-RB”
(200B01 8302031113) Minus (−)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3EX_BO”
(513001 8204031DD3
P3-operate BO6
command “BO6-RB”
(200B01 8502051113)
Figure 4.6-63 Contact health check setting and EDS diagram for example #3
TPOSxx-P1SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P2SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P3SLBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P1EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P2EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
TPOSxx-P3EXBORD Select BO signal (BO*-RB) from signal list *none BO readback signal
SBO defined in LN
SBOw
Oper
Cancel
origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Table 4.6-38 Mapping signals required for ISCSO object for GIGO2701
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO2701$ISCSO$SBOw ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$SBOw T Timestamp CO
Ctrl/GGIO2701$ISCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$SBOw Check Check CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Oper T Timestamp CO
Ctrl/GGIO2701$ISCSO$Oper Test BOOLEAN CO
5130017 004016D08 DEV01_CONTROL_REQ
Ctrl/GGIO2701$ISCSO$Oper Check Check CO
Ctrl/GGIO2701$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Cancel T Timestamp CO
Ctrl/GGIO2701$ISCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO ctlModel ctlModel CF
Ctrl/GGIO2701$ISCSO sboClass sboClass CF
Check “Input”
4.6.8 Setting
TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note
TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note
FixedLogic /
TPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
TPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about P1 direction execute
TPOS01-LGP1EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P2 direction execute
TPOS01-LGP2EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P3 direction execute
TPOS01-LGP3EXOT - FixedLogic
PLC output
FixedLogic /
TPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
TPOS01-PLSM Fix / Var - pulse mode Fix
TPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
TPOS01-RST 1.0 - 100.0 s response check timer 30.0
TPOS01-CTRDIR P1 / P2 / P3 - Capable control direction P2
TPOS01-P1CNTS Off / On - P1 count status Off
TPOS01-P2CNTS Off / On - P2 count status Off
TPOS01-P3CNTS Off / On - P3 count status Off
TPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
TPOS01-APBD Process / Bay - status change origin Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The TPOS function is available for a 2nd Device and other devices. We have
omitted the others because this will be the same as the 1st device with the
exception of the device number.
4.6.9 Signal
Signal monitoring points in TPOS01
TPOS(FunctionID:513001)
Element ID Name Description
8004001FA3 TPOS00_CH_EC_LCD TPOS00 count change execute command by LCD
8004001D5E TPOS00_CH_EC_OWS TPOS00 count change execute command by OWS(HMI)
8004001D5F TPOS00_CH_EC_RCC TPOS00 count change execute command by RCC
8004001D60 TPOS00_CH_EC_RMT TPOS00 count change execute command by Remote
8004001FA2 TPOS00_CH_SC_LCD TPOS00 count change select command by LCD
8004001D5B TPOS00_CH_SC_OWS TPOS00 count change select command by OWS(HMI)
8004001D5C TPOS00_CH_SC_RCC TPOS00 count change select command by RCC
8004001D5D TPOS00_CH_SC_RMT TPOS00 count change select command by Remote
3204011D20 TPOS01_ALL_CNT_VAL TPOS01 all count value
0004011F7C TPOS01_AUTO_SIG TPOS01 Auto sequence signal
8304011E9C TPOS01_CCF_FCT_CS TEMP21
8704011E96 TPOS01_CC_FS TEMP19
8604011E95 TPOS01_CC_SS TEMP18
8804011E9B TPOS01_CC_ST_ERR TEMP39
0004011F7D TPOS01_CMNCTRL_SIG TPOS01 control receive signal
8604011F8D TPOS01_CNT_CS07 TPOS01 count change selected fail condition signal
0004011D91 TPOS01_CNT_SEL TPOS01 count change selected signal(stSeld) for SAS
0004011F7A TPOS01_CNT_SIG TPOS01 Count correction signal
8004011E9E TPOS01_CTR_SGC TPOS01 control logic stage(select command check)
8004011EA0 TPOS01_CTR_SGE TPOS01 control logic stage(execute command check)
8304011E9D TPOS01_CTR_SGN TPOS01 control logic stage(unselected)
8004011E9F TPOS01_CTR_SGS TPOS01 control logic stage(selected)
8B04011EA2 TPOS01_CTR_SGU TPOS01 control logic stage(under selection)
8904011FAB TPOS01_CTR_SGUCN TPOS01 count change selected signal
8904011FB1 TPOS01_CTR_SGURS TPOS01 reset time selected signal
8004011EA1 TPOS01_CTR_SGW TPOS01 control logic stage(wait for change)
8104011E9A TPOS01_ECF_FCT_EIS TPOS01 execute command fail factor signal except interlock/synchronism check
8004011D58 TPOS01_EC_LCD TPOS01 execute command by LCD
8004011D55 TPOS01_EC_OWS TPOS01 execute command by OWS(HMI)
8004011D59 TPOS01_EC_PLC TPOS01 execute command by PLC
8004011D56 TPOS01_EC_RCC TPOS01 execute command by RCC
8004011D57 TPOS01_EC_RMT TPOS01 execute command by Remote
8004011F55 TPOS01_EC_ST_ERR TPOS01 execute command mode err
0004011D97 TPOS01_EX_BO_OPOK TPOS01 execute binary output signal for SAS
8004011E93 TPOS01_EX_CMP TPOS01 execute complete signal
8F04011F58 TPOS01_EX_CMP_TMO TPOS01 timeout after execute completion
8904011FB0 TPOS01_EX_CMP_TMOCN TPOS01 count change timeout after execute completion
8904011FB6 TPOS01_EX_CMP_TMORS TPOS01 reset time timeout after execute completion
8904011F6F TPOS01_EX_CS01 TPOS01 response supervisory timer for P1
8A04011F70 TPOS01_EX_CS02 TPOS01 response supervisory timer for P2
8B04011F72 TPOS01_EX_CS03 TPOS01 P1 timer for under execution
8C04011F73 TPOS01_EX_CS04 TPOS01 P2 timer for under execution
8A04011F71 TPOS01_EX_CS05 TPOS01 response supervisory timer for P3
8C04011F74 TPOS01_EX_CS06 TPOS01 P3 timer for under execution
8604011E91 TPOS01_EX_FFL TPOS01 execute fail signal by fixedlogic
8504011E8F TPOS01_EX_SFL TPOS01 execute success signal by fixedlogic
8404011F43 TPOS01_FLT_DET1 TPOS01 Faulty Detected (3 phase concentration data only)
8104011F42 TPOS01_FLT_STA TPOS01 Faulty Start
8204011E8B TPOS01_F_CS TPOS01 execute command fail condition signal
3104011D01 TPOS01_LCD_ST TPOS01 state for LCD
3104011D00 TPOS01_MMC_ST TPOS01 state for MIMIC
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the TPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “TPOS01_SC_OWS” point for
the 2nd device, use the description of “TPOS01_SC_OWS” in place of
“TPOS02_SC_OWS”. The user can obtain the ID value of
“TPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for TPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“TPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
IED
ASEQ01_
OUT2 Binary Output
EXEC_STOP circuit4
IED front panel
operation Xxxxxx 8xxxxxxxxx IN2
“Reply Signal” Driver
Open
EMERSTOP_
EXEC_STOP
“Emergency stop”
Table 4.7-3 PLC connection points (Inputs for stopping ASEQ operation)
Signal Number Signal Name Description M/O
The scheme switch [ASEQ01-CTRMENU] is used for a local operation (e.g., the front panel
operation on the IED). When On is set for the scheme switch [ASEQ01-CTRMENU], the PLC
sequence #1 can be instructed locally. The scheme switch [ASEQ01-CTRAHMI] is used to select
either a select-before-operation command (SBO) or a direct command (DIR) when the local
instruction is applied.
t 0 4ASEQ01 in execution
1Start command for ASEQ01 S Q
1s R 5s
S Q t 0 &
Closing Command for Device #2
End of execution of ASEQ01 1s R
≧1 2s 1
Termination of ASEQ01 on Level_1
≥1
Temporary signal 001
5Reset of ASEQ01 execution
Temporary signal 002
& t 0
S Q &
Closing Command for Device #3
Termination of ASEQ01 on Level_2 1s R 2s
1
In selecting device #1 &
In selecting device #2 1
In selecting device #3
In selecting device #2 1
In selecting device #3
1DEV1PLCCTRLFAIL ≥1
6Control failure
1DEV2PLCCTRLFAIL
UTOSEQ01)
1DEV3PLCCTRLFAIL
When a stop command is generated during the selection of Device #3, the control logic
will clear the operation if the control logic can determine that the operation of Device #3 is
complete. Figure 4.7-3 shows that Device #3 unable to operate following reception of the stop
command.
ON
*3The operating state turns to OFF, when the operation of Device#3 finishes
following the reception of a stop command from the ASEQ01 function.
*2The ASEQ01 function generates an operate signal for stopping the control logic.
*1The ASEQ01 function generates a select signal for stopping the control logic.
Figure 4.7-3 Timing chart for an automatic sequence when a stop command is injected during
the operation of Device#3
Figure 4.7-4 depicts the operating sequence when an emergency command is input; the
control logic will cancel the operation in accordance with the execution state given from a
device. If the operation signal is not controlling the device, the control logic will clear the
operation promptly. If the operation signal is controlling the device, the control logic will clear
the operation when the control logic function can determine that the operation of the device is
complete, in this case Device#1.
ON
OFF
Operating state
*4The operation state turns to OFF, when the control logic cancels the
selection of Device#1 following the reception of a stop command from
the ASEQ01 function.
Selection signal for Device #2
Figure 4.7-4 Time chart of automatic sequence when emergency stop command is applied
during the operation of Device#1
Table 4.7-9 PLC monitoring points (Outputs for ASEQ emergency status)
Signal Number Signal Name Description
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down
Oper
Origin
ctlmodel (choice ”DOes or DOns”)
Table 4.7-10 shows the signals in the ASEQ01 function that require mapping to the IEC
61850 communications. Figure 4.7-8 shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Table 4.7-11 Mapping signals required for SPCSO1 object in ASEQ01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GAPC1$SPCSO1$SBOw ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$SBOw T Timestamp CO
Ctrl/GAPC1$SPCSO1$SBOw Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw Check Check CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Oper ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Oper ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Oper T Timestamp CO
Ctrl/GAPC1$SPCSO1$Oper Test BOOLEAN CO
523001 700D016D08 ASEQ01_CONTROL_REQ
Ctrl/GAPC1$SPCSO1$Oper Check Check CO
Ctrl/GAPC1$SPCSO1$Oper$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Cancel ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Cancel T Timestamp CO
Ctrl/GAPC1$SPCSO1$Cancel Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1 ctlModel ctlModel CF
Ctrl/GAPC1$SPCSO1 sboClass sboClass CF
Check “Input”
4.7.7 Setting
Auto Sequence(Function ID: 523001)
Setting items Range Unit Contents Default Note
! Note: The user can enter a preferred setting name using GR-TIEMS.
4.7.8 Signal
Signal monitoring points in ASEQ01
ASEQ(Function ID: 523001)
Element ID Name Description
000D001F40 ASEQ_MULTI_SEL Status flag to not be selected for multiple operations
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the ASEQ function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “ASEQ01_EC_LCD” point for
the 2nd device, use the description of “ASEQ02_EC_LCD” in place of
“ASEQ01_EC_LCD”. The user can obtain the ID value of
“ASEQ02_EC_LCD” by using the following steps:
Step 1 Find the element ID for ASEQ01_EC_LCD (i.e.,
“800D011D58”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “800D021D58” of
“ASEQ02_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
OPTR function
TPOS01 function
Clearing measured time-intervals
“OT1”, “OT2”, “OT3” and “OT4”
‡Note:The measurements in DPOS function are grouped into four intervals in each
respective device. Measurement is possible by sensing the device events. The
measured intervals are accumulated; they are grouped into four intervals (OT1–
OT4), which the user can monitor from the IED screen. Figure 4.8-2 and Figure
4.8-3 exemplify the four intervals upon occurrence of On (Closing)-control event
and Off (Open)-control event, provided that the DPOS function operates.
Sensing
intermediate state On Intermediate Off
Figure 4.8-2 Two intervals (OT1 and OT2) for Off-control event
Issuing On control
Sensing
intermediate state Off Intermediate On
Figure 4.8-3 Two intervals (OT3 and OT4) for On-control event
Tips: If the user wishes to implement the OPTR function quickly, go to section 4.8.4,
which discusses how to map signal-points for the IEC 61850 communication.
Operate logic
0 t
Failed
0.3s
Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL
*Note:The OPTIM function can run on either “the SBO mode” or “the DIR mode” using a
signal “ctlmodel” when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
[OPTR1_EN]
On
Table 4.8-2 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
Operate logic
Operate command
Operate logic
“Do nothing”
Operation Failed
Failed Do nothing
Failed Do nothing
Cancel logic
Cancel command
Cancel logic
Figure 4.8-9 Outline of operate command for resetting intervals OT1 to OT4
OPTR01_RST_CMD
Command “Operating reset”
529001 310C011EA1
529001 700C016D08 OPTR01_CONTROL_REQ Operate command
& Reset all OTs
≥
Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL
Reset All
[OPTR1_EN]
On
SBO defined in LN
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
map the input-point to the Object references having attributes CO and CF†. Figure 4.8-16 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” and “CF”
stands for “Configuration” in the functional constraint (FC).
Check “Input”
4.8.5 Setting
OPTIMRSTCTRL (Function ID: 529001)
Setting items Range Unit Contents Default Note
4.8.6 Signal
Signal monitoring points
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
8B0C011F44 OPTR01_CTR_SGU OPTR01 signal before KC_OPTR_SC001
000C011D90 OPTR01_STSELD OPTR01 the controllable data is in the status selected (StSeld)
Mapping point
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
700C016D08 OPTR01_CTRL_RIGHT Control command
Respective
BIO module output signals
Output from BI1 to BIn†
(at IO#n‡) GENBI for slot #n‡
SLOT1 GBI01_STATE
Device #1 BI1-NC BI1 BI1-CPL GBI01 Status detection about the BI1 at IO#1 slot
Pulse train1 Photo-
Filter
coupler
Signal
from
On On On On On On On On
device
Event No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
[GBI-TELD] [GBI-TELR]
Event suppression
Time................. A B C D E
Figure 4.9-3 illustrates the case where a device produces repetitive signals. From this
figure, it can be seen that the start of event suppression occurs at the tenth state-change (point
B) because the GENBI function counts the number of state-changes. The GENBI function
detects the commencement of the signal repeated from the signal initiation point ‘A’. Scheme
switch [GBI-NELD] is provided to set the number of state-changes so that this function will
start to suppress the signal from this point. The user can set [GBI-TELD] pertaining to the
detection period of the repetitive signals (point A to point C). For example, the user can set the
value “10” for the scheme switch [GBI-NELD]; period A–C is set for the setting [GBI-TELD].
The GENBI function should remove event suppressed operation when the repetitive
signals disappear, (that is, the operation of the device is steady); event suppression operation
is cleared when no repetitive signal is found for a set period. The user can set the period using
scheme switch [GBI-TELR]; this reset operation clears the event suppression function at point
E when the last state change is confirmed at point D. Here, the period D–E is set for the Scheme
switch [GBI-TELR].
The event suppression function is provided for every device; the user should set On for
the scheme switch [SLOT1 GBI01-SPPEN], for example.
Table 4.9-1 shows the event list screen. This event list is in response to the signals shown
in Figure 4.9-3. Table 4.9-2 lists the common settings for event suppression. Table 4.9-3 shows
the settings for a particular slot.
Table 4.9-4 shows the mapping signals that are required within the GENBI function for
IEC 61850 communications. Figure 4.9-5 shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.9-5 Quality signal being mapped into Ind1 object of GGIO101
4.9.3 Setting
General BI (Function ID: 580001)
Setting items Range Unit Contents Default Note
4.9.4 Signal
Signal monitoring points in BI module at IO#1 slot
GENBI (Function ID: 580001)
Element ID Name Description
0010001001 SLOT1 GBI01_STATE Status of binary input circuit BI1 at IO#1 slot
0010011001 SLOT1 GBI02_STATE Status of binary input circuit BI2 at IO#1 slot
0010021001 SLOT1 GBI03_STATE Status of binary input circuit BI3 at IO#1 slot
…. …. ….
00101F1001 SLOT1 GBI32_STATE Status of binary input circuit BI32 at IO#1 slot
… … …
… … ….
…. …. ….
Note: In the table above, the user will only find Element IDs and their names for the 1st
slot, but a 2nd and other slots are also provided in the GENBI function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every circuit;
hence, the user can find the same ones for all of the other circuits. For
example, when the user wishes to find the “SLOT2 GBI02_STATE” point
for the 2nd circuit, use the description of SLOT1 GBI01_STATE in place of
“SLOT2 GBI02_STATE”. The user can obtain the ID value of “SLOT2
GBI02_STATE” by using the following steps:
Step 1 Find the element ID for SLOT1 GBI01_STATE (i.e.,
“0010001001”)
Step 2 Identify the number at the fifth and sixth digits from the
5 Technical Description
Contents Pages Pages
Case structure and slot layout 406 CPU 414
Type using compression terminals 407
-1/2 size case 407
Type using ring terminals 409 Date and time 475
-1/2 size case 409 -Time synchronization 476
-DST(Summer time) 481
Binary IO modules (BI, BO, and BIO) 421 -Time zone 480
-Input circuits 423
-Input features 422 Function keys with LEDs 467
-Output circuits 436
-Output features 434 Group setting for relays 484
-BIO3A module 441
LED indicators 462
Communication modules 415
-100Base-TX/1000Base-T 415 Monitoring jacks 472
-100Base-FX 415
-1000Base-LX 415 Operation keys 474
-RS485 415
-Fiber optic 415 Power supply module (PWS) 456
-IRIG-B000 415 -FAIL contacts 457
-Alarm threshold 459
The IED hardware consists of a case, modules, and a human machine interface (HMI). For
instance, Figure 5-1 shows the structure of the GR-series IED which is mounted in 1/2×19”
rack. The user can find that the IED consists of a transformer module (VCT), a signal
processing and communication module (CPU), binary input and output modules (BI, BI, and
BIO, and a power supply module (PWS), which can be mounted in an order from left to right.
The IED case, which is designed for rack mount as shown in Figure 5-1, has two flanges
attached on the IED sides. Figure 5-2 shows hardware block diagram. The module structure
depends on the GR-series models, IED cases, and the customer specification. Therefore, the
user should check and confirm the actual modules with the ordering number in advance.
(The description of IED case helps to understand the IED structure and its functions.
Based on slot reference, terminal block, slot reference, GR-Series selects different cases. VCT,
CPU, BI, BO and BIO, PWS modules and HMI are described sequentially in this chapter. The
user is required to understand information provided in this chapter when wiring between the
IED and external devices and setting of the IED are performed. Hence, the user is required to
read this chapter thoroughly.)
Figure 5-1 Modules in 1/2 19” rack’s chassis (Front view, removed the front panel)
CPU
VCT
CP1M LAN I/F
I Filter Tele-
A/D
CT×n communication
AC analogue input
V Local PC for
LAN I/F Maintenance
VT×m
HMI
LCD/MIMIC
BIO
LEDs
Binary output
circuits ×8 Binary output
Operation keys
Binary input
Monitoring jacks circuits ×6 Binary input
Function Key
USB
Maintenance I/F
PC
Power supply
PWS
Figure 5.1-1 Terminal type and case structure (1/2 size case, back view)
PWS terminal block is placed on the far left side; hence, the user finds it with alpha-
numeric reference “T4”, and that is discussed later (see section 5.5).
Communication modules, which are placed between VCT and BIOs, are labeled with “C11”
to “C15”. Those are provided for LAN, IEC61850 communication, etc.
1 1 1 1
2 2 2 2 C11
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
9 9 9 9
10 10 10 10
11 11 11 11 C12
12 12 12 12
13 13 13 13
14 14 14 14
15 15 15 15
16 16 16 16
17 17 17 17
18 18 18 18
C13
19 19 19 19
20 20 20 20
21 21 21 21
22 22 22 22
23 23 23 23
24 24 24 24
C14
25 25 25 25
26 26 26 26
27 27 27 27
28 28 28 28
29 29 29 29
30 30 30 30
31 31 31 31
32 32 32 32
33 33 33 33
FG1
C15
34 34 34 34
35 35 35 35
E
36 36 36 36
37 37 37 37
38 38 38 38
39 39 39 39
40 40 40 40
FG FGB FGA
T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
PWS terminal block is placed on the far left side; hence, the user finds it with alpha-
numeric reference “T3”. That circuit is discussed later (see section 5.5)
Communication modules, which are between VCT and BIOs, are labeled with “C11” to
“C15”. Those are used for LAN, IEC61850 communication, etc.
T3 T2 T1 VC1
C11
1 2 1 2
1
2
3 4 3 4
3
4
5 6 5 6
C12
5
6
7 8 7 8
7
8
9 10 9 10
9
10
11 12 11 12
11
12
13 14 13 14
13
14
15 16 15 16 C13
15
16
17 18 17 18
17
18
21 22 21 22
21
22
23 24 23 24
23
24
25 26 25 26
25
26 C14
27 28 27 28
27
28
29 30 29 30
29
30
31 32 31 32
31
32
33 34 33 34
33
34 FG1
C15
35 36 35 36
35
36
37 38 37 38
E
38
FG
FG FGB FGA
T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
5.2.1 VCT39B
Transformer module (VCT39B) has four CTs. The first three CTs are provided for the three
phases high-impedance differential protection (DIF). The last one is provided for the single
phase restricted earth fault protection (REF).
VCT39B
By the way, it is rare to use all 4 CTs, and the actual wiring style differs for each protection
using a varistor unit as shown in Figure 5.2-2.
VCT39B VCT39B
Varistor Unit
Resistor Ida
Varistor
Ida Ida
Idb
Idb Idb
Idc
Idb Idb
Varistor unit
Resistor Ide
Ide Varistor
Ide
VC1
VC1
VCT Alpha-
numeric Module type
reference
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
Short-bar 21
22
23
FG1
24
Frame ground 25
terminal on the case
26
27
28
29
30
1
Short-bar
FG1
CPU
CP1M
COM#1
CPU COM#2
COM#3
COM#4
COM#5
CPU COM#1
LAN network
BIO#1
CP1M
COM#2
VCT#1 VCT#2
BIO#2 COM#3
BIO#3
BIO#4
BIO#5
BIO#6 COM#4
BIO#7
BIO#8
COM#5 IRIG-B
Symbol
TX
RX
Symbol
RX
B2 B2(Disuse)
COM-B
A3 A3
B3 B3
COMM TX GND
C11
C12
C11 C11
C12 C12
Figure 5.3-4 100Base-FX module (left for single port; right for dual ports)
C12
4. RS485 module
RS485 module has a PCB connector. The module should be connected with a shielded-twisted-
pair cable; it is used for the communication of the IEC60870-5-103. The terminal arrangement
and references are shown below. The cable sheath should be connected with the frame ground
(FG) in the IED case. For the use of the a shielded-twisted-pair cable, the user should note that
the total length should be less than 1200 meter (0.75 miles); the terminal resistor (150 ohms)
should be connected when any connector is not connected. For setting the parameters, see
Chapter Communication protocol: RS485 communication.
Sheath
Top
PCB connector A1 A cable for
A1 B1 B1 an IED
COM-A(+)
A2
A2 B2 Sheath
COM-B(−) B2
A cable for
A3 B3 A3
another
Bottom
COMM(GND) B3
IED
0V
C11
C12
6. IRIG-B000 module
IRIG-B000 module is used to receive the digital signal generated with an external clock; the
signal is in conformity to serial IRIG-B000 format. Note that the IRIG-B000 module is able to
receive digital signal (TTL) only (i.e., the reception of AM signal is not applicable). This module
is isolated using a photo coupler; the user should note A2 and B2 connectors are not used. The
peak value of IRIG-B000 signal should be greater than 3.5 volts; the IRIG-B000 module has
the input resistor (about 3k ohm). Thus, the terminal resistor can be required when the IRIG-
B000 signal is delivered for several devices; the value of the terminal resistor depends on the
number of deliveries and the performance of the external clocks. For setting of time
synchronization, see Chapter Technical Description: Clock function.
Top
PCB connector A1
A1 B1 B1 SIG
A2 (Disuse)
A2 B2
B2 (Disuse)
A3 B3 A3
Bottom B3 GND
a. View from connector edge b. Port circuit
C11
C12
Figure 5.3-9 exemplifies IED has a LAN module (1000BASE-FX) at C11. RS485 and IRIG-B
modules are located at C13 and C15.
C12
RS485
C12 Blank
Blank C13
C13 •A1
485
•A2•
B1 COM-A
•B2
•A3• COM-B
•B3
• • COMM
C14
C14 Blank
IRIG-B000
FG1
E C15
C15
FGE
FG1
Figure 5.3-10 illustrates a structure, which has 100BASE-FX, RS385, and IRIG-B000 modules.
C12
RS485
C12 100BASE
-FX
Blank C13
C13 •A1
485
•A2•
B1 COM-A
•B2
•A3• COM-B
•B3
• • COMM
C14
C14 Blank
IRIG-B000
FG1
E C15
C15
FGE
FG1
-Polarity dependent
1
(+)
-Independent circuit 2
BI1
(−)
2 BI2A -Isolated using photo Circuit
number
coupler
Screw on terminal block
-Polarity dependent
- Independent circuit
-Variable threshold
3 BI3A -Isolated using photo
Polarity
coupler Terminal screw
number
-Polarity dependent (+)
1
BI1 BI1
-Sharing common
Circuit number
connections (+)
2
BI2
Circuit
number
Terminal screw
number
34
(+)
BI32
35
(−) Photo coupler
36
(−)
37
(−)
38
(−)
4 BIO1A
5 BIO2A Same as BI1A Same as BI1A and BI2A
6 BIO3A
The user can find the connector of binary IO modules, the terminal number and
arrangement of the binary input circuits in section 5.4.5.
Table 5.4-3 Setting items for binary input circuits in the standard type
Units
Setting item1 Range Contents Default
Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A module)
Units
Setting devices Range Contents Default
As an example, Figure 5.4-1 shows the binary input circuit of the BI1A in order to help
understand the settings. The BI1A consists of 18 binary input circuits and each circuit has
three settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches (“Delayed pick-up and delayed drop-off signal” and “Logic level
inversion”), used as basis of input signal characteristics.
Normal On &
[INVERSE-SW]
Inverse [BI1-CPL] Off
8101011111 8101011110
On Delay Timer Off Delay Timer 8101011172
BI2-NC BI2
t 0 0 t & ≥1
BI2 BI2-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BI2-CPL] Off
8201021110 8201021110
On Delay Timer Off Delay Timer
BI3-NC BI3 8201021172
t 0 0 t & ≥1
BI3 BI3-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BI3-CPL] Off
8********** BIn
BIn-NC BIn
On Delay Timer Off Delay Timer 8**********
t 0 0 t & ≥1
BIn BIn-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BIn-CPL] Off
Low
[THRES_Lvl]
High
R1
R1
Respective element IDs (i.e., 8001001172 and others) designate respective signal
monitoring points of the binary input circuits (i.e., BI1-CPL and others). Thus, the user can
handle the signals on the binary input circuit using element ID together with function ID.
When we assume that the BI1A module is at IO#1 slot in the IED case, and if the user wishes
to see the first circuit signal of this BI1A module, the user can identify its signal† using the
element ID (8001001172) and the function ID of IO#1 slot‡.
†Note:The user can see the signals of the binary input circuits on the IED screen.
Chapter User interface: Monitoring-sub menu discusses how to see the state of the
binary input circuits.
‡Note:Function IDs identify every IO slots. For example, IO#1 slot has been identified by
the function ID “200B001”. Therefore, when the user wishes to program the signal
“BI1-CPL” on the BI1A at IO#1, the user should designate its signal using the
function ID “200B001” and Element ID “8001001172”. On the other hand, when
the signal “BI2-CPL” on the BI1A at IO#2 is required to program, the user should
designate that signal using the function ID “200B002” and Element ID
“8001001172”. For more information with regard to the function ID and the Data
ID at IO#1, see sections 5.4.6(i), 5.4.7(i), and others.
Table 5.4-5 shows the threshold voltage of picking-up/dropping-off for binary inputs at the high
and low level. This also shows how to set them with the selection switch.
Selection switch
Low Typical 71V This is default.
[THRES_Lvl] = Low
Selection switch
Low Typical 15V This is default.
[THRES_Lvl] = Low
As the threshold voltage is expressed with Table 5.4-5, the user should set High or Low to
match to the voltage value to input to binary inputs. Table 5.4-6 shows the recommended
settings.
This matter means that the user should also set a threshold voltage at the power supply unit
to determine the degree of the power failure (see Chapter: Technical description: Power supply
module).
Binary input circuits #1 to #3 follow the setting [BI1-3_PICKUP] and the user should set
the value between 18 to 222V DC2 for this setting. For the setting [BI4-6_PICKUP], the above
mentioned value holds true for #4 to #6 binary input circuits; similarly the setting [BI7-
9_PICKUP] is used for #7 to #9 binary input circuits; and finally the setting [BI10-12_PICKUP]
is used for #10 to #12 binary input circuits.
1Note: The threshold value is fixed for all types of BIO modules except the BI2A. The
user should notice that “binary IO module voltage type” influences these values
(see the 1st note in Table 5.4-1). These particular values are found when 220V dc
type is used.
2Note: In the variable type, the user can set the threshold arbitrarily between 18 to 222V
in DC, and can regulate its threshold voltage in a voltage step. Table 5.4-7 shows
the corresponding values with regard to guaranteed and typical thresholds in
response to the setting values. Note that the operation in the variable type is
segmented into ‘Operate’, ‘Intermediate’, ‘and ‘Non-operate’ areas, which are
decided by the guaranteed-pick-up, typical-pick-up, and guaranteed-drop-off
levels, as illustrated in Figure 5.4-2.
Input voltage
Operating area
Non-operating area
Imported signal by
binary input circuit
t
IO#n
IO#4
IO#2
IO#3
IO#1
IO_SLOT1 IO_SLOT3
Setting table (input) Setting table (in & out)
Figure 5.4-4 BO and BIO setting tables related to IO_slot1 and IO_slot3
The setting table of section 5.4.6 is available for all binary IO modules except for the BI2A
module; thus, the user should understand and select the setting points that are relevant to the
BI1A module. That is, for the BI1A, the user should choose the setting items of reference (i.e.,
binary input circuits #1 to #18) from IO_SLOT1 setting table. On the other hand, for the BIO1A
module, the user should choose the setting items of reference (i.e., binary input circuits #1 to
#7) from IO_SLOT3 setting table. The IO_SLOT3 setting table for the binary input circuits are
shown in sec. 5.4.6. The setting operation via the IED screen is discussed later. (See chapter
User interface: I/O setting sub-menu)
The arrangement of the BO types is determined for every binary IO module, as shown in
Table 5.4-1 and Table 5.4-8. The difference in the types and number of BOs are also found in
section 5.4.5.
Table 5.4-8 Output circuits and features associated with binary IO module
No Type Binary output feature Example Symbol Applied
sign module
1 Fast -Normally open (N/O) Terminal screw BIO3A
-Dry contact BO1(F) number
operating
-Closure is the fastest 1
(F) amongst all of the BO types. 2
Type
-Make & Carry: 5A cont.
BO number
-Break: 0.15A at 290Vdc
-OP Time: 3ms (typical) N/O contact
connections 37
-Make and carry: 8A cont. BO number
36
-Break: 0.1A at 250Vdc N/O
0.2A at 125Vdc 38
-OP Time: 8ms (typical) N/C
Contact
Unit
Setting items Contents Default
Data_ID
BO1_CPL Off / On – Switch On for programmable operation Off
BO1 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO1. Not assigned1
Input signal2 (Preferred Data ID) – Set a Data ID at the second input on BO1. Not assigned1
Input signal3 (Preferred Data ID) – Set a Data ID at the third input on BO1. Not assigned1
Input signal4 (Preferred Data ID) – Set a Data ID at the forth input on BO1. Not assigned1
Input signal5 (Preferred Data ID) – Set a Data ID at the fifth input on BO1. Not assigned1
Input signal6 (Preferred Data ID) – Set a Data ID at the sixth input on BO1. Not assigned1
Input signal7 (Preferred Data ID) – Set a Data ID at the seventh input on BO1. Not assigned1
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO1. Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO1 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO1 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO1 0.000
INVERSE-SW Normal / Inverse s Inversion operation of BO1 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO1 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
BO2_CPL Off / On – Switch On for programmable operation Off
BO2 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO2. Not assigned1
….. ….. ….. …..
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO2 Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO2 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO2 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO2 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BO2 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO2 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
…..
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BOn Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BOn AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BOn 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BOn 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BOn signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BOn OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
1Note: The user can set a reset signal and eight input signals with Data IDs. Data IDs
are listed as a signal monitoring point for each function. Setting items are
summarized in each slot. (See sections 5.4.8(i) and 5.4.8(ii))
Figure 5.4-5 shows the binary output circuits on the BO1A module in order to help
understand the settings. The BO1A consists of 18 binary output circuits and every circuit has
timers and switches. The features of the CPLs are divided into the five components as listed
below:
CPL switch
Selection of input signals
Logic gate switch
Delayed pick-up/delayed drop-off
Logic level inversion
Logic timer switch
From relay
application and To external
control functions devices
8002001112 Contact
On Delay Timer Off Delay Timer
[LOGIC-SW] & ≥1
t 0 0 t BO1
Input signal 1 DRIVER BO1
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8002001113
≥1 [INVERSE-SW]
Normal
Off
Inverse On &
XOR Delay &
0.000-300.000s [BO1_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310200E11D BO1-SOURCE
810201112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO2
Input signal 1 t 0 0 t DRIVER BO2
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
810201113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO2 RB
XOR Delay &
0.000-300.000s [BO2_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310201E11D BO2-SOURCE
820202112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO3
Input signal 1 t 0 0 t DRIVER BO3
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8202021113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO3 RB
XOR Delay &
0.000-300.000s [BO3_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310202E11D BO3-SOURCE
8********* Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BOn
Input signal 1 t 0 0 t DRIVER BOn
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
8*********
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BOn RB
XOR Delay &
0.000-300.000s [BOn_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
3102E**11D BOn-SOURCE
Figure 5.4-5 Binary Output Circuit for the BO1A (#1 to #n=18)
In Figure 5.4-5 respective element IDs (i.e., 8002001112 and others) designate respective
signal monitoring points of the binary output circuits. The user can monitor the operations of
the binary output circuit using element ID together with function ID. When we assume that a
BO1A module is at IO#2 slot in the IED case, and if the user wishes to monitor the first-circuit
in the BO1A module, the user can see the operation using the element ID (8002001112) and
the function ID† of IO#2 slot.
†Note: A function ID identifies every IO slots. For example, with regard to the function
ID and the Data ID at IO#1 slot, see section 5.4.9(i). On the other hand, for IO#2
slot see section 5.4.9(ii).
Instant type
When the user uses a binary output signal without the following characteristics, the user
should set Off for the scheme switch [TIMER-SW].
Delay type
If the user requires a binary output signal with a delayed characteristic, the user should set
Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting [Logic
timer].
Dwell type
For instance, if the user requires a binary output signal as a one shot pulse, the user should
set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer]. If the input signals received have a shorter duration than the set value in the
setting [Logic timer], the pulse width will be equal to the setting value. On the other hand, if
the duration of the input signals are longer than that of the set value, the pulse width will be
equal to the width of the input signals.
Latch type
If the user requires a binary output signal to be removed by a reset signal, the user should set
Latch for scheme switch [TIMER-SW] and key the Data ID of the reset signal for setting [Reset
signal]. Since the binary output signal is removed with the Data ID, the user should determine
the Data ID from other functions. The Data ID is designated by the signal monitoring point for
each function and the user should set the [Reset signal] setting.
Note: When Latch is set, the state of BO circuit will be sustained during power turn-
on/off.
IO#n
IO#2
IO#4
IO#3
IO#1
BO1A BIO1A
IO_SLOT2 IO_SLOT3
Setting table (output) Setting table (in & out)
Figure 5.4-6 BO and BIO modules and setting tables related to IO_SLOT2 and IO_SLOT3
Figure 5.4-6 illustrates an example of a binary IO module arrangement and the binary
output circuit printed circuit boards (PCBs). If the user wishes to set the binary output circuits,
the setting targets are on BO1A and BIO1A at locations IO#2 and IO#3. The user should key
the CPL settings from the setting tables for the IO2_SLOT and IO3_SLOT.
The setting table is available for all binary IO modules; thus, the user should understand
and select setting points that are relevant to the BO1A and BIO1A. That is, for the BO1A the
user should choose the setting terms of reference (i.e., binary output circuits #1 to #18) from
IO_SLOT2. On the other hand, for the BIO1A, the setting terms of reference (i.e., binary output
circuits #1 to #10) are from IO_SLOT3. These setting tables are shown in section 5.4.8(ii).
Figure 5.4-10 shows a diagram of how an actual terminal block connects with circuits of the
module. The use can identify the correspondence using the left side block figure and the right
side schematic figure. If the user takes account of wiring works on the BI1A, their targets are
designated with terminal screw numbers (1 to 40) that are shown next to the terminal block.
Slot number labeled by alpha-numeric reference “T*” is used to identify the location of the slot,
and the asterisk(*) is substituted for any one of the slot numbers. For the actual
implementation of a binary IO module, the user should examine the arrangement of binary IO
modules from External connection figures, which are shown separately. (See Appendix: Typical
external connection)
Polarity is shown on some input-and-output circuits, hence, the user should check the polarity
sign (+) or (−), respectively.
FG
BO1A BO2A
1 1
(+)
BO1(SF) 2 BO1(H) 2
(−)
3 3
(+)
BO2(SF) 4 BO2(H) 4
(−)
5 5
(+)
BO3(SF) 6 BO3(H) 6
(−)
7 7
(+)
BO4(SF) 8 BO4(H) 8
(−)
9 9
(+)
BO5(SF) 10 BO5(H) 10
(−)
11 11
(+)
BO6(SF) 12 BO6(H) 12
(−)
13 13
(+)
BO7 14 BO7(H) 14
(−)
15 15
(+)
BO8 16 BO8(H) 16
(−)
17 17
(+)
BO9 18 BO9(H) 18
(−)
21 21 (+)
BO10 22 BO10(H) 22 (−)
23 23 (+)
BO11 24 BO11(H) 24 (−)
25 25 (+)
BO12 26 BO12(H) 26 (−)
27 27 (+)
BO13 28 BO13(H) 28 (−)
29 29 (+)
BO14 30 BO14(H) 30 (−)
31 31 (+)
BO15 32 BO15(H) 32 (−)
33 33 (+)
BO16 34 BO16(H) 34 (−)
35
BO17 36
37
BO18 38
Schematic figures
(+) 1 1 (+) 1
BI1 (+) BI1 BI1
(−) 2 2 (−) 2
(−)
(+) 3 3 (+) 3
BI2 (+) BI2 BI2
(−) 4 4 (−) 4
(−)
(+) 5 5 (+) 5
BI3 (+) BI3 BI3
(−) 6 6 (−) 6
(−)
(+) 7 7 (+) 7
BI4 (+) BI4 BI4
(−) 8 8 (−) 8
(−)
(+) 9 9 (+) 9
BI5 (+) BI5 BI5
(−) 10 10 (−) 10
(−)
(+) 11 11 (+) 11
BI6 (+) BI6 BI6
(−) 12 12 (−) 12
(−)
(+) 13 13 (+) 13
BI7 (+) BI7 BI7
(−) 14 14 (−) 14
(−)
15 15 15
BO1(SF) (+) (+)
16 16 BI8 16 BI8
(−) (−)
17 17
BO2(SF) (+) BI9
18 18
(−)
21 21 21
BO3(SF) 22 (+) 22 BI10 BO1(F) 22
23 (−) 23 23
BO4(SF) 24 (+) 24 BI11 BO2(F) 24
25 (−) 25 25
BO5(SF) 26 (+) 26 BI12 BO3(F) 26
27 (−) 27 27
BO6(SF) 28 BO1(SF) 28 BO4(F) 28
29 29 29
BO7 30 BO2(SF) 30 BO5(F) 30
31 31 31
BO8 32 BO3(SF) 32 BO6(F) 32
33 33 33
BO9 34 BO4 34 BO7 34
35 35 35
37 37 37
BO10 36 BO5 36 BO8 36
38 38 38
Schematic figures
Figure 5.4-9 Input and output arrangements in BIO1A, BIO2A and BIO3A
Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-8.
BIO3A
T* T*
(+) 1
1 2 BI1
2 (−)
(+) 3
3 1 2 BI2
(−) 4
4
3 4 (+) 5
5 BI3
(−) 6
6
5 6 (+) 7
7 BI4
(−) 8
8 7 8
(+) 9
9 BI5
(−) 10
10 9 10
(+) 11
11 BI6
12 11 12 (−) 12
13 (+) 13
13 14 14 BI7
14 (−)
15 (+) 15
15 16 16 BI8
16 (−)
17 17 18
18
19 21 22
20
23 24
25 26
21 21
27 28 BO1(F)
22 22
23 29 30 23
BO2(F) 24
24
25 31 32 25
BO3(F) 26
26 33 34
27 27
BO4(F) 28
28 35 36
29 29
30 37 38 BO5(F) 30
31 31
32 BO6(F) 32
33 Ring type terminal 33
34 BO7 34
35
36 35
37 Terminal screw numbers 37
38 are denoted with the BO8 36
39 same one.
40 38
FG FG
Figure 5.4-11 The BI2A module and its frame ground screw
Note: The BI2A is earthed to the frame’s ground screw (FG) using a short wire.
…… …… …… …… ……
…… …… …… …… ……
Units
Setting item Range Contents Notes
value
There are two types for the PWS module about the DC rated voltage. The first type is for “110-
250 Vdc” rated, and the second is for “24-60Vdc” rated. One of DC rated voltage types is chosen
with the ordering table, and then the type is applicable in the PWS.
Note: The IED composed of a PWS module whose DC rated voltage is “110-250 Vdc”, can
run on AC power supply (100–220Vac).
However, it is recommended to input AC power only for temporary operations such
as tests where DC power cannot be inputted. In addition, if the supervision function
is enabled, the IED detects the Power failure (error) when AC power is inputted.
Figure 5.5-1 shows the difference between ‘Compression plug type terminal’ and ‘Ring type
terminal’. Alpha-numeric reference “T*” identifies slot locations, and an asterisk “*” shows its
slot number. An external connection figure illustrates the PSW location (see Appendix: Typical
External connection).
Alpha-numeric reference of PWS. Sign “*” is Alpha-numeric reference of PWS. Sign “*” is
substituted for actual slot location number.2(A) substituted for actual slot location number. 2(B)
T
T
* *
PWS PWS
*
T
1
Ring plug type
2
3 terminal block
4
5 T*
6 2
2
7
8 4
4 1 2
9
10 FAIL1 3 4
FAIL1
3 3
11
12 5 6 1
1
13
14 7 8
15
9 10
16
17 8 11 12 8
18
10 13 14 10
19
20
FAIL2 9 15 16 FAIL2 9
17 18
7 7
21 21 22
22 23 24
23
24 25 26
25 29 29
26 Positive(+) DC 27 28 Positive(+) DC
30 30
27 / 29 30 /
28
29 31 DC 31 DC
Negative(−) 31 32 Negative(−)
30 32 32
31 33 34 Short-wire
35 35
32
33 35 36
Short-wire 36 36
34 37 38
35 37 37
36 FG
Short-bar
37 38 38
38 Short-wire
39
40
E E
FG FG
FG
1 1
E E
CAUTION
1Note: For installation, the user should connect the case earth screw labeled “E” to the
protective earth of the panel or others using earthing wire, such that its cross-
section is AWG9 or larger.
2ANote: The user–for Type using compression terminals–can connect a cable to this
terminal directly without a cable ferrule; hence, the recommended cables are
AWG14 and their stripping lengths are 10mm. Use “AI 2.5 -10 BU” ferrule for
AWG14 when the user wishes to use a cable ferrule made by PHOENIX
CONTACT®.
1 Note)
This contact will close when relay is
Used to output
in fail status or DC voltage is off.
FAIL1 2 or 4 that relay is in
N/O contact is used for output.
fail status.
3 Note)
This contact will open when relay is
in fail status or DC voltage is off.
7 Same as N/C contact of FAIL1
FAIL2 8 or 10 Same as FAIL1
9 Same as N/O contact of FAIL1
Table 5.5-5 shows the threshold voltages for detection/non-detection of the power error at the
level high and low. This also shows how to set them with a shunt connector.
This is
3
Insert a shunt connector
Low Typical 85V 2
1
to position”2-3” at JP4 default.
This is
3
Insert a shunt connector
Low Typical 19V 2
1
to position”1-2” at JP4 default.
After that, the user should set the threshold voltage about the picking-up/dropping-off of the
binary input (see Chapter: Technical description: Binary IO module (BI, BO and BIO)).
LED indicators
(#1–#26) Screen
Indicator label
Operation keys
Function keys
(F1–F7)
Monitoring jacks
(Term A/B/C) USB port
The LED indicators‡ (#3 to #26) are also provided as user-programmable indicators.
Figure 5.6-2 shows the schematic diagrams. Each LED indicator can be lit and controlled using
a logic-gate-switch setting and others. For simplicity, we discuss setting the LED indicator #3
only, but the user can take account that setting the other LED indicators (#4 to #26) is the
same as the #3. Table 5.6-1 shows the LED indicator settings; Table 5.6-2 shows the signal
monitoring points on all LED indicator logics.
‡Note:Setting menus of the LED indicator are also discussed in Chapter User interface:
I/O setting sub-menu.
LED-03
3100031001
[On Delay Timer] [Off Delay Timer] LED indicator #3
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
[LOGIC-SW] Dwell & Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
LED-04
3100041001 LED indicator #4
[On Delay Timer] [Off Delay Timer]
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2]
0.000-300.000s 0.000-300.000s 1
[Input signal 3] & 0 t
&
≥1 OR 0.000-300.000s
[INVERSE-SW] Normal
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
LED-26
31001A100
[On Delay Timer] [Off Delay Timer] LED indicator #26
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s 1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
Instant type
When required not to have the below characteristics (v)-2, (v)-3, and (v)-4, the user should set
Off for the scheme switch [TIMER-SW].
Delay type
If the user requires lighting the LED indicator with a delayed characteristic, the user should
set Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer].
Dwell type
For instance, if the user requires lighting the LED indicator as a one shot pulse, the user
should set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using
setting [Logic timer]. If the input signals received have a shorter duration than the set value
in the setting [Logic timer], the pulse width will be equal to the setting value. On the other
hand, if the duration of the input signals are longer than that of the set value, the pulse width
will be equal to the width of the input signals.
Latch type
If the user requires lighting the LED indicator to be removed by a reset signal, the user should
set Latch for scheme switch [TIMER-SW]; the user should set the Data ID of the reset signal
for setting [Reset signal]. Since lighting the LED indicator is cleared with the Data ID, the
user should determine the Data ID from other functions. The Data ID is designated by the
signal monitoring point for each function and the user should set the [Reset signal] setting.
Default setting
Setting items Range Units Contents
value
Table 5.6-2 Signal monitoring points on all LED indicator (Function ID: 201B01)
Element ID Name Description
3100021001 ERROR Error LED
For testing, the user can also program to generate binary signals when the user presses
the F1 to F7 keys. The F1 to F7 circuits have LEDs; accordingly, the user can also program to
light the LEDs using the settings.
“BO1”
Setting Data ID “F1 Signal designated by
setting [Input signal 1] ≥1 (200B01_8002001112)
SIGNAL” for the Signal to the
device
“FUNC-KEY1” [Input signal 1] [Input signal 2] DRIVER BO1
& ≥1
Pressing the F1 key (240001_ 3100001730)
[Input signal 3]
& “BO1-RB”
F1 [Input signal 4] [BO1_CPL] On
Off
&
(200B01_8002001113)
[Input signal 5]
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
“F1 SIGNAL”
Setting Data ID (240001_ 3100001737) PLC connection point in BO1
“BO1_SOURCE”
&
for the [Signal]† 200B01 310200E11D BO1_SOURCE
[Logic] Instant
Toggle
The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.6-4. Thus, the user can substitute “F1-SIGNAL (240001
310001737)” for the “FUNC-KEY1 SIGNAL (240001 310001730)”, provided the Toggle mode
is preferred. In the Table 5.6-7 the other FUNC-KEY2 to FUNC-KEY7 are shown.
Table 5.6-4 Signal mode selection using setting [LOGIC]
Setting Generated signal corresponding to pressing the function key
Pressing Key
Toggle
Binary signal
Pressing Key
Instant
Binary signal
31001B1001
[On Delay Timer] [Off Delay Timer] F1 LED logic
& ≥1
t 0 0 t LED-F1
[Input signal 1] DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
[On Delay Timer] [Off Delay Timer] 31001C1001 F2 LED logic
& ≥1
[Input signal 1] t 0 0 t LED-F2
DRIVER
& AND 0.000-300.000s 0.000-300.000s 1 & [Logic Timer] ≥1
[Input signal 2] & 0 t
[Input signal 3]
[INVERSE-SW]
&
≥1 OR Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
……….
Screen Jump / Assign Signal /
Function - Operation mode for the F7 key Screen Jump
No Assign
F7
Signal (Preferred Data ID) - Set a Data ID at the input on F7 key (No Assigned)
Logic Instant / Toggle - Switch for logic-gate operation on F7 Instant
Table 5.6-6 Settings of LEDs on the Function keys (Function ID: 240001)
Default setting
Setting items Range Units Contents
value
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F1 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F1. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F1. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F1. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F1. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F1. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F1. (No Assigned)
F1 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F1. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F1 AND
INVERSE-SW Normal / Inverse - Inversion operation of F1 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F1 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F1 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F1 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F2 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F2. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F2. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F2. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F2. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F2. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F2. (No Assigned)
F2 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F2. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F2 AND
INVERSE-SW Normal / Inverse - Inversion operation of F2 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F2 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F2 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F2 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
……….
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F7 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F7. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F7. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F7. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F7. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F7. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F7. (No Assigned)
F7 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F7. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F7 AND
INVERSE-SW Normal / Inverse - Inversion operation of F7 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F7 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F7 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F7 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Table 5.6-7 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100001737 F1 SIGNAL Signal generated when pressing F1 referring the setting [LOGIC]
3100011737 F2 SIGNAL Signal generated when pressing F2 referring the setting [LOGIC]
3100021737 F3 SIGNAL Signal generated when pressing F3 referring the setting [LOGIC]
3100031737 F4 SIGNAL Signal generated when pressing F4 referring the setting [LOGIC]
3100041737 F5 SIGNAL Signal generated when pressing F5 referring the setting [LOGIC]
3100051737 F6 SIGNAL Signal generated when pressing F6 referring the setting [LOGIC]
3100061737 F7 SIGNAL Signal generated when pressing F7 referring the setting [LOGIC]
Table 5.6-8 Signal monitoring points for function LEDs (Function ID: 201B01)
Element ID Name Description
31001B1001 LED-F1 Signal generated during pressing the F1 key
When the user wishes to test the phase-A element the OC1 relay using an oscilloscope,
for example, set the phase-A monitoring point (44001 8000011C20†) for the setting [Term A],
as shown in Figure 5.6-5. Consequently, the OC1 operating signal is outputted to the jack at
the Term A. The LED at the Term A is also lit in step with the output signal. The user can use
to monitor the phase-B and phase-C signals using by settings respective Data IDs for the [Term
B] and [Term C]. We shall see the menus for the Term A to Term C in Chapter User interface:
Test sub-menu: Signal monitoring screen.
OC function
(Function ID: 440001) Monitoring jack (Function ID: 201301) Jacks and LEDs
Signal designated by
setting [Term A] DRIVER Term Signal to the
440001 8000011C20
A oscilloscope
A
OC1 440001 8100011C21
B “TEST-A”
440001 8200011C22 (201B01_3100221001)
C
Term A LED
Signal designated by
setting [Term B] DRIVER Term Signal to the
B oscilloscope
“TEST-B”
(201B01_3100231001)
Term B LED
Signal designated by
setting [Term C] DRIVER Term Signal to the
C oscilloscope
“TEST-C”
(201B01_3100241001)
Term C LED
Table 5.6-11 Signal monitoring points for monitoring jack LEDs (Function ID: 201B01)
Element ID Name Description
3100221001 TEST-A TEST-A
Table 5.6-12 Signal monitoring points for L/R LEDs (Function ID: 201B01)
Element ID Name Description
3100251001 LOC LED Local
Table 5.6-13 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100081730 CANCEL Key situation of CANCEL
Clock function
Clock function (or time function) provides the time information for recording upon occurrence
of the fault; it includes a synchronization function when the reference clock is available out of
the IED. The clock is operated referring the Coordinated Universal Time (UTC‡) when the
UTC is selected; the clock can run in accordance with the user’s time zone and summer
time(DST)† by referring the UTC when the time zone and the DST are set. The explanation is
also found in Chapter User interface: Time sub-menu.
†Note:In other words, it is called “daylight saving time (DST)”. For setting, see section
5.7.5.
‡Note:For example, the Internet and World Wide Web standards run in the UTC. For
more information, see section 5.7.4.
LAN
………….
IED_1 IED_2 IED_n
Setting procedure
The user should make the following steps in respective IEDs.
1) Set SNTP for the setting [Time Sync Src]; then set On for the setting [SNTP].
2) Set the address of a time server using settings [Server1]. The settings [Server2],
[Server3], and [Server4] are provided for other time-servers.
3) Check that the SNTP is shown under the ActivSyncSrc, as shown in Figure 5.7-4.
4) Check to see that the time zone and the DST are set correctly (see 5.7.4 and 5.7.5).
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] > Check “SNTP” being shown under ActiveSyncSrc.
SNTP
IED
IRIG-B000†
Clock
10:00 1/2
Signal [Time] +
A1 2012-11-21 10:00:05
IRIG-B signal
[Format]
generator Unit GND
A3 YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
IRIG-B
Figure 5.7-5 IED connected with the signal generator unit using IRIG-B000 module
†Note:See Chapter Technical description: Signal processing and communication module.
Setting procedure
The user should make the following steps in respective IEDs.
1) Set IRIG-B for the setting [Time Sync Src]; then set On for the setting [IRIG-SYNC].
2) Check that the IRIG-B is shown under the ActivSyncSrc, as shown in Figure 5.7-6.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
Check “IRIG-B” being shown under ActiveSyncSrc.
IRIG-B
IED
BI1
BI1A (200B01 8001001111)
1
2 BI1
3
4 BI2
5
6 BI3
7
8 BI4
9
10 BI5 Setting [BI_ID]
11
12 BI6
13
14 BI7
15
16 BI8
17
18 BI9 Clock
21
22 BI10
23
24 BI11
25
26 BI12
27
Signal generator 28 BI13
29
30 BI14
31
32 BI15
1Hz squire wave 33
34 BI16
35
36 BI17
37
38 BI18
IO#1
Figure 5.7-7 IED connected with the signal generator via BI module
†Note:The BI1 circuit is just used for the explanation; hence, an actual BI circuit should
be selected in accordance with wiring cables. For more information of the BI
circuit, see Chapter Technical description: Binary IO module.
Setting procedure
The user should make the following steps in respective IEDs.
1) Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2) Check BI is shown under the ActivSyncSrc, as shown in Figure 5.7-8.
3) Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.7-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
BI1(200B01 8001001111) for the setting [BI_ID].
4) Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., −0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI
Beginning of the DST at 01:00 a.m. in Mar. 29 E nding of the DST at 02:00 a.m. in Oct. 25
March October
Mon Tue Wed Thu Fri Sat Sun Mon Tue Wed Thu Fri Sat Sun
1 1 2 3 4
2 3 4 5 6 7 8 5 6 7 8 9 10 11
9 10 11 12 13 14 15 12 13 14 15 16 17 18
16 17 18 19 20 21 22 19 20 21 22 23 24 25
23 24 25 26 27 28 29 26 27 28 29 30
30 31
Transposed Transposed
March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30
March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30
Figure 5.7-11 DST setting examples by the day (1st or 15th) of month
5.7.6 Setting
Setting of CLOCK (Function ID: 200301)
Unit Default setting
Setting item Range Contents Notes
s value
Timezone -14.00 - 14.00 hour Time zone 0.00
--- / SNTP / BI /
TimeSyncSrc - Time sync source SNTP
IRIG-B
YYYYMMDD /
Date_fmt MMDDYYYY / - YMD/MDY/DMY YYYYMMDD
DDMMYYYY
Date_delimiter -///. - - or / or . -
Time_delimiter :/. - : or period :
Sec_delimiter ./, - . or , .
SummerTime Off / On - Summer time enable Off
IS_UTC_base Off / On - Is setting value base on UTC? On
Start_Month 1 - 12 - Start month 3
Start_Week 1-5 - Start week 5
--- / Sun. / Mon. / Tue.
Start_Wday / Wed. / Thr. / Fri. / - Start day of week Sun.
Sat.
Start_Hour 0 - 23 - Start hour 1
End_Month 1 - 12 - End month 10
End_Week 1-5 - End week 5
--- / Sun. / Mon. / Tue.
End_Wday / Wed. / Thr. / Fri. / - End day of week Sun.
Sat.
End_Hour 0 - 23 - End hour 1
Setting
Protection
Group1
Trip DIFHZ
TCS
Group2
Trip DIFHZ
TCS
Group8
Trip DIFHZ
TCS
example logic; hence, the setting number goes back to ‘1’ when the BI1 is open.
GR200 IED
Binary selection
(+) (–)
IO_SLOT1 (200B01)
BI1 8001001110 Entering → Leaving 201400 314000E1A0 PLC_Group_ENUM Operation of
BI1 changing
‘1’ in BOOL ‘2’ in UNIT
‘0’ in BOOL ‘1’ in UNIT
BI2 8101011110
BI2
1
DIN_BOOL
FID DO
DTYPE ST
DID
Figure 5.8-3 exemplifies that selecting a group among eight groups is required by the
usage of three BI circuits (i.e., Group 1→Group2, Group3,… Group8).
Binary input circuits BI1 to BI3 A group number enters
at IO#3 (IO_SLOT1) PLC basic-function PLC basic-function
to “Setting function
(Ondelay) (SEL)
(Function ID: 201400)”
BI3_1
DIN_BOOL TON
UDINT#16#200B03 FID DO IN Q BOOL_TO_UNIT
UDINT#16#80 DTYPE ST
UDINT#16#01001111 Delay time# PT ET
DID ADD
XX ms
BI3_2
DIN_BOOL TON DOUT_UNIT_1
UDINT#16#200B03 FID DO IN Q BOOL_TO_UNIT MUL
DOUT_UNIT
UDINT#16#80 DTYPE ST Unit#16#201400 FID ST
Delay time# PT ET
UDINT#16#01011111 DID UDINT#16#2 Unit#16#31 DTYPE
XX ms
Unit#16#4000E1A0 DID
DI
BI3_3
DIN_BOOL TON
UDINT#16#200B03 ADD ADD
FID DO IN Q BOOL_TO_UNIT
MUL
UDINT#16#80 DTYPE ST
UDINT#16#01021111 DID Delay time# PT ET
XX ms UDINT#16#4
UDINT#16#1
(iii) Setting
Setting_PF (Function ID: 201400)
Un Default setting
Setting item Range Contents Notes
its value
3010011001 COM_CHG
3010031001 CTRL_CHG
3010021001 PRO_CHG
3010001001 SYS_CHG
6 Engineering tool
Contents Pages Pages
Common tools 490 Settings for Relay and control functions 491
Configuration tools 491 Settings for Input and output signals 491
Comparison of settings 490 Settings for Event recorder 492
Configuration in IEC 61850 492 Setting of Interlock (ILK) 492
Configuration in IEC 60870-5-103 492 Signal monitor 490
Connection with PC 489 Status monitor 490
Double command blocking (DCB) 490 Tool for Fault recorder 491
Tool for Disturbance recorder 491
Tool for Event recorder 491
Label creator 490
Logging management 490
MIMIC configuration 492
Project management 490
Overview of GR-TIEMS
When engineering, monitoring, record viewing, and test support functions are required in the
IED, the user can handle these advanced and integrated functions using GR-Series Toshiba
IED Engineering and Monitoring Software (GR-TIEMS). The GR-TIEMS should be installed
into a PC prior to engineering. After that, the user can view the IED states (Table 6.1-1) on a
PC screen connected with the IED. The user can also program the IED using the GR-TIEMS.
The GR-TIEMS is software to retrieve and analyze power system quantities, fault and
event records. The user can change the settings in the respective IEDs when the PC is
connected with the IED via a USB or a LAN. For more information in the GR-TIEMS
operations, see separate manual “Operation manual GR-TIEMS (6F2M1082)”.
Connection
Figure 6.2-1 illustrates that the user can connect the local PC with the IED (type B receptacle)
using a USB cable. Alternatively, the user can connect the local PC with the IED by connecting
a RJ45 cable to the LAN port (if available in the IED). In Figure 6.2-2, when using the LAN
port, the user has to select the communications option, which can be found from the Main menu
in GR-TIEMS (go to “Tool” ->“Option…”; “Option” dialog will be displayed; change
communications option with the second tab – ‘Communication’).
Tip: See Chapter Communication protocol.
IED
LAN
USB Cable
Personal Computer
Common tools
(i) Project management
Project files are required to engage sub-engineering tools. The user can manage to read/write
the project file of the IED using the project management function. The user can also see the
contents of the project files.
(ii) Comparison
When the user wishes to get the comparison between respective IEDs, using the compare
function the user can get the comparison data about Settings, Disturbance record binary
signals, PLCs, Interlock, Large LCD (MIMIC)†, IEC61850, and IEC60870-5-103 data†.
(iv) Logging
The user can view the recorded data with regard to the logging date/time. As the user can also
find operation recorded when an operator/engineer logs into the IED, analyzing a problem is
possible when an error is detected during the IED operations.
Monitoring tools
The user can monitor status and measurement value obtained in the IED using the monitoring
tools. All signals monitored are tabulated in the monitoring list dialog. When the user wishes
to monitor a signal, select a signal in the monitoring list dialog after the operation of the drag-
drop on the monitoring window. The monitoring tools can generate an exporting layout file in
the CSV; it also can obtain the layout file in the CSV.
Record tools
(i) Fault record
Fault records are including measuring information before and after the occurrence of the faults.
Accordingly, the user can see information before the fault so that the user can analyze the fault
more precisely. The user can select a fault from the recorded lists; the user can save it into the
fault information file in the CSV. The user can also view the fault records when the exported
data file in the CSV are retrieved into the IED.
Note: In the IED the date and time is clocked in the coordinated universal time (UTC)
when the clock is selected to operate in UTC. In the record tools within the PC the
date and time is treated in the UTC. Notice that the time in the UTC is converted
for the local time when the recording time is displayed on the PC. For the clock
operation if the user selects neither the UTC, the time zone or the daylight saving
time (the summer time), displaying incorrect time may result in between the IED
and the PC. For more information about the clock and time, see Chapter Technical
description: Clock function.
configurator. The large LCD will be able to display measurement values, diagrams and others
after the configuration. Note that the MIMIC is not available when the standard LCD is equipped
for the IED.
7 PLC function
Contents Pages
About PLC function 495 PLC driver 496
BIT (Boolean) type 496
Error check 495 USINT (Unsigned short integer) type 498
IED screen information 495 UNIT (Unsigned integer) type 498
UDINT (Unsigned double integer) type 499
SINT (Short integer) type 499
INT (Integer) type 499
DINT (Double integer) type 499
Timer variable setting 500
Setting [UTM1] ~ [UTM24] 502
[00000006] [00000000]
[00000000] [00000000]
[00000000] [00000000]
Figure 7.2-1 Error code at 1st row and 1st column on Monitoring sub-menu
PLC driver
The PLC driver is provided for the user-programmed logic.
Figure 7.4-1 shows that a delay timer “TON1” has been set 500ms in the PLC logic, but the
user can set new value using the setting [UTM1] (e.g., the user can change 500ms to 200ms on
the LCD). Since an internal IED memory is able to access the [UTM1], the IED can operate
with new value of the [UTM1] when new one is set.
PLC editor
Timer FB
Constant value set
Fixed PLC = 500ms
Input Output
On
FB output Off
On
FB input Off
Run
Counter Stop
0 15 30 45 60
Timer counter
(millisecond)
[UTM1] = 30 ms [UTM1] = 10 ms
Figure 7.4-2 Input and output time chart on TON1 delay timer
Note: Entering new value for the setting [UTM1] does not make the timer counter reset,
if the timer counter is running.
FB output Off
On
FB input Off
Run
[UTM2] = 30 ms [UTM2] = 60 ms
Figure 7.4-3 Input and output time chart onTON2 delay timer
Note: If the FB output has be yielded already, when new value is set for the timer and
that new value is longer input signal duration, the timer counter is not reset.
UTM24 +
0 ms
8 Recording function
Contents Pages Pages
Disturbance recorder 520 Event recorder 512
-Maximum number of recording 521 -Setup 518
-Recording signals 520 -Trigger signals 512
-Recording time and capacities 520 -Trigger modes 517
Fault recorder 506
-Trigger settings for PLC 523 -Screen information 507
-Types of recording information 523 -Setup 508
The recording function consists of three recording features: (1) Fault recorder, (2) Event
recorder, and (3) Disturbance recorder. The fault recorder collects the information about the
power system quantities when a fault occurs. The event recorder groups state information
when the changes are detected. The disturbance recorder is designed to memory the various
quantities—numerical analog data and logic data (binary data)—from the monitoring function
and the BIO modules; it is possible to analyze the disturbance using the engineering tool (GR-
TIMES), which can draw several chronological waves.
Fault recorder
During the fault, the fault recorder can memorize reasons by equipment failures/operation
states, system information etc. The fault recorder captures the following items for each fault:
Date and time at the fault
Operating mode information
Fault and pre-fault quantities
†Note:A number of the operation identifiers are provided by the protection functions. For
example, the ‘DIF1-OPT’ operation identifier is used to identify the pickup of the
differential function (DIF) of three-phases. See the protection function in Chapter
Relay application.
‡Note:64 logical signals are selectable for recording. For example, in this purpose, the
user may choose an operation signal on the circuits of the BIO modules (BIOs).
messages○ e .
d ○
Figure 8.1-1 Information of the fault recorder displayed on the IED screen
†Note:For more screen information, see Chapter User interface: Record sub-menu.
Fault Record#1 ○
a Record Number (#1)
19:47 1/22
2019-11-28 ○
b Date and Time at Fault (YYYY-MM-DD)
19:47:15.651
Phase A ○
c Mode information
DIF1
Fault values ○
d Fault quantities
Screen scroll down Ida
0.632A
Idb
0.000A
Idc
0.000A
Ide
0.000A
PreFault values ○
e Pre-fault quantities
Ida
0.632A
Idb
0.000A
Idc
0.000A
Ide
0.000A
8.1.4 Setting
Setting of FAULT_RECORD(Function ID: 200602)
Unit Default setting
Setting item Range Contents Notes
s value
Pre-Fault Time 10s/ 50 / 100 / 200 / 300 Sec. Recording time before the fault 10
Op Mode Name1 (Preferred name) – Name of the operation mode for ID1 –
Op Mode ID1 (Preferred DataID) – Signal of the operation identifier –
Op Mode Name2 (Preferred name) – Name of the operation mode for ID2 –
Op Mode ID2 (Preferred DataID) – Signal of the operation identifier2 –
Op Mode Name3 (Preferred name) – Name of the operation mode for ID3 –
Op Mode ID3 (Preferred DataID) – Signal of the operation identifier3 –
…… …… – …… –
…… …… – …… –
…… …… – …… –
…… …… – …… –
Op Mode Name264 (Preferred name) – Name of the operation mode for ID264 –
Op Mode ID264 (Preferred DataID) – Signal of the operation identifier264 –
8.1.5 Signal
Signal monitoring point
FAULT_RECORD (Function ID: 200602)
Name Element ID Description
ADD_F.RECORD_TRIG1 8020001001 Receiving Trigger1
Event recorder
Signals are generated in the logics of BIO modules etc. in the IED. The event recorder can
memory the generated signals as events. To operate the event recorder, the user should pick a
preferred signal as a trigger of the event recorder; the event recorder can have 768 triggers,
some of which have been set as a default. The user can group the triggers into three categories;
consequently, it is possible that a number of the events are divided depending on the degree of
the errors, the meaning of the operations, and the signals of relay elements, etc. The user can
also program how an event is to be detected. An event is recorded with millisecond accuracy.
The information are memorized until the number of the events reaching 1024; the oldest event
will be deleted when a new event appears.
Pulse train
3000001001
FR_CLR List of ‘Event record1’
FAULT RECORD (200602)
Event #3
On 2012-07-25 10:31:12
Event #3 F.Record clear ‘On’
Event #2
3010001001
Active group Active group
2012-07-25 10:56:12
SYS_CHG Set group change
‘3’ Changed to ‘4’
Setting_PF (201400)
Event #2
Figure 8.2-1 Relation between function signals and triggers for Event record1
Figure 8.2-1 illustrates signals connected with triggers in the event recorder. For example,
‘SYS_CHG’ is connected with trigger#7 using the [Trigger ID7] and ‘FR_CLR’ is connected with
trigger#14 using the [Trigger ID14]. Note that the both triggers (#7 and #14) are smaller than
the setting [End of E.Record-1]=256; hence, the both are listed in the ‘Event recored1’ list.
Keep in mind that the event names are set by the [Event Name7] and [Event Name14].Table
8.2-1 and the others tabulate the ones.
†Note:The GR-TIEMS uses terms ‘Level1’, ‘Level2’, and ‘Level3’ to represent the ‘Event
Record1’, ‘Event Record2’, and ‘Event Record3’. The scope of each level is the same
as the scope of each group. The GR-TIEMS does not show unused triggers and
Trigger ID numbers automatically when the triggers are displayed on the screen.
[Trigger ID1] 220001 3110201001 On-Off Serious error [Trigger ID91] (Not Assigned) Off - [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 220001 3110211001 On-Off ErrorLevel2 [Trigger ID92] (Not Assigned) Off - [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 220001 3110221001 On-Off Minor error [Trigger ID93] (Not Assigned) Off - [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 220001 3110231001 On-Off ErrorLevel4 [Trigger ID94] (Not Assigned) Off - [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 220001 3110241001 On-Off ErrorLevel5 [Trigger ID95] (Not Assigned) Off - [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not Assigned) Off - [Trigger ID96] (Not Assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 201400 3200001001 Change Set. group change [Trigger ID97] (Not Assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 201400 3010001001 On System set. change [Trigger ID98] (Not Assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 201400 3010011001 On Comm. set. change [Trigger ID99] (Not Assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 201400 3010021001 On Prot. set. change [Trigger ID100] (Not Assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 201400 3010031001 On Ctrl. set. change [Trigger ID101] (Not Assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not Assigned) Off - [Trigger ID102] (Not Assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not Assigned) Off - [Trigger ID103] (Not Assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 200602 3000001001 On F.Record clear [Trigger ID104] (Not Assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 200710 3001001001 On E.Record1 clear [Trigger ID105] (Not Assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 200710 3002001001 On E.Record2 clear [Trigger ID106] (Not Assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 200710 3003001001 On E.Record3 clear [Trigger ID107] (Not Assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 200401 30A0001001 On D.Record clear [Trigger ID108] (Not Assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not Assigned) Off - [Trigger ID109] (Not Assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not Assigned) Off - [Trigger ID110] (Not Assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not Assigned) Off - [Trigger ID111] (Not Assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not Assigned) Off - [Trigger ID112] (Not Assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not Assigned) Off - [Trigger ID113] (Not Assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not Assigned) Off - [Trigger ID114] (Not Assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not Assigned) Off - [Trigger ID115] (Not Assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not Assigned) Off - [Trigger ID116] (Not Assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not Assigned) Off - [Trigger ID117] (Not Assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not Assigned) Off - [Trigger ID118] (Not Assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not Assigned) Off - [Trigger ID119] (Not Assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not Assigned) Off - [Trigger ID120] (Not Assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not Assigned) Off - [Trigger ID121] (Not Assigned) Off - [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not Assigned) Off - [Trigger ID122] (Not Assigned) Off - [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not Assigned) Off - [Trigger ID123] (Not Assigned) Off - [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not Assigned) Off - [Trigger ID124] (Not Assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not Assigned) Off - [Trigger ID125] (Not Assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not Assigned) Off - [Trigger ID126] (Not Assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not Assigned) Off - [Trigger ID127] (Not Assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not Assigned) Off - [Trigger ID128] (Not Assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not Assigned) Off - [Trigger ID129] (Not Assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not Assigned) Off - [Trigger ID130] (Not Assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not Assigned) Off - [Trigger ID131] (Not Assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not Assigned) Off - [Trigger ID132] (Not Assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not Assigned) Off - [Trigger ID133] (Not Assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not Assigned) Off - [Trigger ID134] (Not Assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not Assigned) Off - [Trigger ID135] (Not Assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not Assigned) Off - [Trigger ID136] (Not Assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not Assigned) Off - [Trigger ID137] (Not Assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not Assigned) Off - [Trigger ID138] (Not Assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not Assigned) Off - [Trigger ID139] (Not Assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not Assigned) Off - [Trigger ID140] (Not Assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not Assigned) Off - [Trigger ID141] (Not Assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not Assigned) Off - [Trigger ID142] (Not Assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not Assigned) Off - [Trigger ID143] (Not Assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] (Not Assigned) Off - [Trigger ID144] (Not Assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not Assigned) Off - [Trigger ID145] (Not Assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not Assigned) Off - [Trigger ID146] (Not Assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not Assigned) Off - [Trigger ID147] (Not Assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not Assigned) Off - [Trigger ID148] (Not Assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] (Not Assigned) Off - [Trigger ID149] (Not Assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] (Not Assigned) Off - [Trigger ID150] (Not Assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not Assigned) Off - [Trigger ID151] (Not Assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not Assigned) Off - [Trigger ID152] (Not Assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not Assigned) Off - [Trigger ID153] (Not Assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not Assigned) Off - [Trigger ID154] (Not Assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not Assigned) Off - [Trigger ID155] (Not Assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not Assigned) Off - [Trigger ID156] (Not Assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not Assigned) Off - [Trigger ID157] (Not Assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not Assigned) Off - [Trigger ID158] (Not Assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not Assigned) Off - [Trigger ID159] (Not Assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not Assigned) Off - [Trigger ID160] (Not Assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A1001 8300001B6F Off GEN.TRIP [Trigger ID161] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A1001 8400001B64 Off GEN.ALARM [Trigger ID162] (Not Assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A1001 8000001B71 Off OPT.PHASE-A [Trigger ID163] (Not Assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A1001 8100001B72 Off OPT.PHASE-B [Trigger ID164] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A1001 8200001B73 Off OPT.PHASE-C [Trigger ID165] (Not Assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not Assigned) Off - [Trigger ID166] (Not Assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not Assigned) Off - [Trigger ID167] (Not Assigned) Off -
[Trigger ID78] (Not Assigned) Off - [Trigger ID168] (Not Assigned) Off -
[Trigger ID79] (Not Assigned) Off - [Trigger ID169] (Not Assigned) Off -
[Trigger ID80] (Not Assigned) Off - [Trigger ID170] (Not Assigned) Off -
[Trigger ID81] (Not Assigned) Off - [Trigger ID171] (Not Assigned) Off -
[Trigger ID82] (Not Assigned) Off - [Trigger ID172] (Not Assigned) Off -
[Trigger ID83] (Not Assigned) Off - [Trigger ID173] (Not Assigned) Off -
[Trigger ID84] (Not Assigned) Off - [Trigger ID174] (Not Assigned) Off -
[Trigger ID85] (Not Assigned) Off - [Trigger ID175] (Not Assigned) Off -
[Trigger ID86] (Not Assigned) Off - [Trigger ID176] (Not Assigned) Off -
[Trigger ID87] (Not Assigned) Off - [Trigger ID177] (Not Assigned) Off -
[Trigger ID88] (Not Assigned) Off - [Trigger ID178] (Not Assigned) Off -
[Trigger ID89] (Not Assigned) Off - [Trigger ID179] (Not Assigned) Off -
[Trigger ID90] (Not Assigned) Off - [Trigger ID180] (Not Assigned) Off -
[Trigger ID257] 5100010001011001 On-Off SPOS1 [Trigger ID347] 5120018303211D02 On DPOS33 Open [Trigger ID437] 5120018203031F43 On DPOS3 Undefined
[Trigger ID258] 5100010001021001 On-Off SPOS2 [Trigger ID348] 5120018103211D03 On DPOS33 Close [Trigger ID438] 5120018403031F45 On DPOS3 Faulty
[Trigger ID259] 5100010001031001 On-Off SPOS3 [Trigger ID349] 5120018303221D02 On DPOS34 Open [Trigger ID439] 5120018203041F43 On DPOS4 Undefined
[Trigger ID260] 5100010001041001 On-Off SPOS4 [Trigger ID350] 5120018103221D03 On DPOS34 Close [Trigger ID440] 5120018403041F45 On DPOS4 Faulty
[Trigger ID261] 5100010001051001 On-Off SPOS5 [Trigger ID351] 5120018303231D02 On DPOS35 Open [Trigger ID441] 5120018203051F43 On DPOS5 Undefined
[Trigger ID262] 5100010001061001 On-Off SPOS6 [Trigger ID352] 5120018103231D03 On DPOS35 Close [Trigger ID442] 5120018403051F45 On DPOS5 Faulty
[Trigger ID263] 5100010001071001 On-Off SPOS7 [Trigger ID353] 5120018303241D02 On DPOS36 Open [Trigger ID443] 5120018203061F43 On DPOS6 Undefined
[Trigger ID264] 5100010001081001 On-Off SPOS8 [Trigger ID354] 5120018103241D03 On DPOS36 Close [Trigger ID444] 5120018403061F45 On DPOS6 Faulty
[Trigger ID265] 5100010001091001 On-Off SPOS9 [Trigger ID355] 5120018303251D02 On DPOS37 Open [Trigger ID445] 5120018203071F43 On DPOS7 Undefined
[Trigger ID266] 51000100010A1001 On-Off SPOS10 [Trigger ID356] 5120018103251D03 On DPOS37 Close [Trigger ID446] 5120018403071F45 On DPOS7 Faulty
[Trigger ID267] 51000100010B1001 On-Off SPOS11 [Trigger ID357] 5120018303261D02 On DPOS38 Open [Trigger ID447] 5120018203081F43 On DPOS8 Undefined
[Trigger ID268] 51000100010C1001 On-Off SPOS12 [Trigger ID358] 5120018103261D03 On DPOS38 Close [Trigger ID448] 5120018403081F45 On DPOS8 Faulty
[Trigger ID269] 51000100010D1001 On-Off SPOS13 [Trigger ID359] 5120018303271D02 On DPOS39 Open [Trigger ID449] 5120018203091F43 On DPOS9 Undefined
[Trigger ID270] 51000100010E1001 On-Off SPOS14 [Trigger ID360] 5120018103271D03 On DPOS39 Close [Trigger ID450] 5120018403091F45 On DPOS9 Faulty
[Trigger ID271] 51000100010F1001 On-Off SPOS15 [Trigger ID361] 5120018303281D02 On DPOS40 Open [Trigger ID451] 51200182030A1F43 On DPOS10 Undefined
[Trigger ID272] 5100010001101001 On-Off SPOS16 [Trigger ID362] 5120018103281D03 On DPOS40 Close [Trigger ID452] 51200184030A1F45 On DPOS10 Faulty
[Trigger ID273] 5100010001111001 On-Off SPOS17 [Trigger ID363] 5120018303291D02 On DPOS41 Open [Trigger ID453] 51200182030B1F43 On DPOS11 Undefined
[Trigger ID274] 5100010001121001 On-Off SPOS18 [Trigger ID364] 5120018103291D03 On DPOS41 Close [Trigger ID454] 51200184030B1F45 On DPOS11 Faulty
[Trigger ID275] 5100010001131001 On-Off SPOS19 [Trigger ID365] 51200183032A1D02 On DPOS42 Open [Trigger ID455] 51200182030C1F43 On DPOS12 Undefined
[Trigger ID276] 5100010001141001 On-Off SPOS20 [Trigger ID366] 51200181032A1D03 On DPOS42 Close [Trigger ID456] 51200184030C1F45 On DPOS12 Faulty
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] 51200183032B1D02 On DPOS43 Open [Trigger ID457] 51200182030D1F43 On DPOS13 Undefined
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] 51200181032B1D03 On DPOS43 Close [Trigger ID458] 51200184030D1F45 On DPOS13 Faulty
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] 51200183032C1D02 On DPOS44 Open [Trigger ID459] 51200182030E1F43 On DPOS14 Undefined
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] 51200181032C1D03 On DPOS44 Close [Trigger ID460] 51200184030E1F45 On DPOS14 Faulty
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] 51200183032D1D02 On DPOS45 Open [Trigger ID461] 51200182030F1F43 On DPOS15 Undefined
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] 51200181032D1D03 On DPOS45 Close [Trigger ID462] 51200184030F1F45 On DPOS15 Faulty
[Trigger ID283] 5120018303011D02 On DPOS1 Open [Trigger ID373] 51200183032E1D02 On DPOS46 Open [Trigger ID463] 5120018203101F43 On DPOS16 Undefined
[Trigger ID284] 5120018103011D03 On DPOS1 Close [Trigger ID374] 51200181032E1D03 On DPOS46 Close [Trigger ID464] 5120018403101F45 On DPOS16 Faulty
[Trigger ID285] 5120018303021D02 On DPOS2 Open [Trigger ID375] 51200183032F1D02 On DPOS47 Open [Trigger ID465] 5120018203111F43 On DPOS17 Undefined
[Trigger ID286] 5120018103021D03 On DPOS2 Close [Trigger ID376] 51200181032F1D03 On DPOS47 Close [Trigger ID466] 5120018403111F45 On DPOS17 Faulty
[Trigger ID287] 5120018303031D02 On DPOS3 Open [Trigger ID377] 5120018303301D02 On DPOS48 Open [Trigger ID467] 5120018203121F43 On DPOS18 Undefined
[Trigger ID288] 5120018103031D03 On DPOS3 Close [Trigger ID378] 5120018103301D03 On DPOS48 Close [Trigger ID468] 5120018403121F45 On DPOS18 Faulty
[Trigger ID289] 5120018303041D02 On DPOS4 Open [Trigger ID379] 5120018303311D02 On DPOS49 Open [Trigger ID469] 5120018203131F43 On DPOS19 Undefined
[Trigger ID290] 5120018103041D03 On DPOS4 Close [Trigger ID380] 5120018103311D03 On DPOS49 Close [Trigger ID470] 5120018403131F45 On DPOS19 Faulty
[Trigger ID291] 5120018303051D02 On DPOS5 Open [Trigger ID381] 5120018303321D02 On DPOS50 Open [Trigger ID471] 5120018203141F43 On DPOS20 Undefined
[Trigger ID292] 5120018103051D03 On DPOS5 Close [Trigger ID382] 5120018103321D03 On DPOS50 Close [Trigger ID472] 5120018403141F45 On DPOS20 Faulty
[Trigger ID293] 5120018303061D02 On DPOS6 Open [Trigger ID383] 5120018303331D02 On DPOS51 Open [Trigger ID473] 5120018203151F43 On DPOS21 Undefined
[Trigger ID294] 5120018103061D03 On DPOS6 Close [Trigger ID384] 5120018103331D03 On DPOS51 Close [Trigger ID474] 5120018403151F45 On DPOS21 Faulty
[Trigger ID295] 5120018303071D02 On DPOS7 Open [Trigger ID385] 5120018303341D02 On DPOS52 Open [Trigger ID475] 5120018203161F43 On DPOS22 Undefined
[Trigger ID296] 5120018103071D03 On DPOS7 Close [Trigger ID386] 5120018103341D03 On DPOS52 Close [Trigger ID476] 5120018403161F45 On DPOS22 Faulty
[Trigger ID297] 5120018303081D02 On DPOS8 Open [Trigger ID387] 5120018303351D02 On DPOS53 Open [Trigger ID477] 5120018203171F43 On DPOS23 Undefined
[Trigger ID298] 5120018103081D03 On DPOS8 Close [Trigger ID388] 5120018103351D03 On DPOS53 Close [Trigger ID478] 5120018403171F45 On DPOS23 Faulty
[Trigger ID299] 5120018303091D02 On DPOS9 Open [Trigger ID389] 5120018303361D02 On DPOS54 Open [Trigger ID479] 5120018203181F43 On DPOS24 Undefined
[Trigger ID300] 5120018103091D03 On DPOS9 Close [Trigger ID390] 5120018103361D03 On DPOS54 Close [Trigger ID480] 5120018403181F45 On DPOS24 Faulty
[Trigger ID301] 51200183030A1D02 On DPOS10 Open [Trigger ID391] 5120018303371D02 On DPOS55 Open [Trigger ID481] 5120018203191F43 On DPOS25 Undefined
[Trigger ID302] 51200181030A1D03 On DPOS10 Close [Trigger ID392] 5120018103371D03 On DPOS55 Close [Trigger ID482] 5120018403191F45 On DPOS25 Faulty
[Trigger ID303] 51200183030B1D02 On DPOS11 Open [Trigger ID393] 5120018303381D02 On DPOS56 Open [Trigger ID483] 51200182031A1F43 On DPOS26 Undefined
[Trigger ID304] 51200181030B1D03 On DPOS11 Close [Trigger ID394] 5120018103381D03 On DPOS56 Close [Trigger ID484] 51200184031A1F45 On DPOS26 Faulty
[Trigger ID305] 51200183030C1D02 On DPOS12 Open [Trigger ID395] 5120018303391D02 On DPOS57 Open [Trigger ID485] 51200182031B1F43 On DPOS27 Undefined
[Trigger ID306] 51200181030C1D03 On DPOS12 Close [Trigger ID396] 5120018103391D03 On DPOS57 Close [Trigger ID486] 51200184031B1F45 On DPOS27 Faulty
[Trigger ID307] 51200183030D1D02 On DPOS13 Open [Trigger ID397] 51200183033A1D02 On DPOS58 Open [Trigger ID487] 51200182031C1F43 On DPOS28 Undefined
[Trigger ID308] 51200181030D1D03 On DPOS13 Close [Trigger ID398] 51200181033A1D03 On DPOS58 Close [Trigger ID488] 51200184031C1F45 On DPOS28 Faulty
[Trigger ID309] 51200183030E1D02 On DPOS14 Open [Trigger ID399] 51200183033B1D02 On DPOS59 Open [Trigger ID489] 51200182031D1F43 On DPOS29 Undefined
[Trigger ID310] 51200181030E1D03 On DPOS14 Close [Trigger ID400] 51200181033B1D03 On DPOS59 Close [Trigger ID490] 51200184031D1F45 On DPOS29 Faulty
[Trigger ID311] 51200183030F1D02 On DPOS15 Open [Trigger ID401] 51200183033C1D02 On DPOS60 Open [Trigger ID491] 51200182031E1F43 On DPOS30 Undefined
[Trigger ID312] 51200181030F1D03 On DPOS15 Close [Trigger ID402] 51200181033C1D03 On DPOS60 Close [Trigger ID492] 51200184031E1F45 On DPOS30 Faulty
[Trigger ID313] 5120018303101D02 On DPOS16 Open [Trigger ID403] 51200183033D1D02 On DPOS61 Open [Trigger ID493] 51200182031F1F43 On DPOS31 Undefined
[Trigger ID314] 5120018103101D03 On DPOS16 Close [Trigger ID404] 51200181033D1D03 On DPOS61 Close [Trigger ID494] 51200184031F1F45 On DPOS31 Faulty
[Trigger ID315] 5120018303111D02 On DPOS17 Open [Trigger ID405] 51200183033E1D02 On DPOS62 Open [Trigger ID495] 5120018203201F43 On DPOS32 Undefined
[Trigger ID316] 5120018103111D03 On DPOS17 Close [Trigger ID406] 51200181033E1D03 On DPOS62 Close [Trigger ID496] 5120018403201F45 On DPOS32 Faulty
[Trigger ID317] 5120018303121D02 On DPOS18 Open [Trigger ID407] 51200183033F1D02 On DPOS63 Open [Trigger ID497] 5120018203211F43 On DPOS33 Undefined
[Trigger ID318] 5120018103121D03 On DPOS18 Close [Trigger ID408] 51200181033F1D03 On DPOS63 Close [Trigger ID498] 5120018403211F45 On DPOS33 Faulty
[Trigger ID319] 5120018303131D02 On DPOS19 Open [Trigger ID409] 5120018303401D02 On DPOS64 Open [Trigger ID499] 5120018203221F43 On DPOS34 Undefined
[Trigger ID320] 5120018103131D03 On DPOS19 Close [Trigger ID410] 5120018103401D03 On DPOS64 Close [Trigger ID500] 5120018403221F45 On DPOS34 Faulty
[Trigger ID321] 5120018303141D02 On DPOS20 Open [Trigger ID411] 5120018303411D02 On DPOS65 Open [Trigger ID501] 5120018203231F43 On DPOS35 Undefined
[Trigger ID322] 5120018103141D03 On DPOS20 Close [Trigger ID412] 5120018103411D03 On DPOS65 Close [Trigger ID502] 5120018403231F45 On DPOS35 Faulty
[Trigger ID323] 5120018303151D02 On DPOS21 Open [Trigger ID413] 5120018303421D02 On DPOS66 Open [Trigger ID503] 5120018203241F43 On DPOS36 Undefined
[Trigger ID324] 5120018103151D03 On DPOS21 Close [Trigger ID414] 5120018103421D03 On DPOS66 Close [Trigger ID504] 5120018403241F45 On DPOS36 Faulty
[Trigger ID325] 5120018303161D02 On DPOS22 Open [Trigger ID415] 5120018303431D02 On DPOS67 Open [Trigger ID505] 5120018203251F43 On DPOS37 Undefined
[Trigger ID326] 5120018103161D03 On DPOS22 Close [Trigger ID416] 5120018103431D03 On DPOS67 Close [Trigger ID506] 5120018403251F45 On DPOS37 Faulty
[Trigger ID327] 5120018303171D02 On DPOS23 Open [Trigger ID417] 5120018303441D02 On DPOS68 Open [Trigger ID507] 5120018203261F43 On DPOS38 Undefined
[Trigger ID328] 5120018103171D03 On DPOS23 Close [Trigger ID418] 5120018103441D03 On DPOS68 Close [Trigger ID508] 5120018403261F45 On DPOS38 Faulty
[Trigger ID329] 5120018303181D02 On DPOS24 Open [Trigger ID419] 5120018303451D02 On DPOS69 Open [Trigger ID509] 5120018203271F43 On DPOS39 Undefined
[Trigger ID330] 5120018103181D03 On DPOS24 Close [Trigger ID420] 5120018103451D03 On DPOS69 Close [Trigger ID510] 5120018403271F45 On DPOS39 Faulty
[Trigger ID331] 5120018303191D02 On DPOS25 Open [Trigger ID421] 5120018303461D02 On DPOS70 Open [Trigger ID511] 5120018203281F43 On DPOS40 Undefined
[Trigger ID332] 5120018103191D03 On DPOS25 Close [Trigger ID422] 5120018103461D03 On DPOS70 Close [Trigger ID512] 5120018403281F45 On DPOS40 Faulty
[Trigger ID333] 51200183031A1D02 On DPOS26 Open [Trigger ID423] 5120018303471D02 On DPOS71 Open
[Trigger ID334] 51200181031A1D03 On DPOS26 Close [Trigger ID424] 5120018103471D03 On DPOS71 Close
[Trigger ID335] 51200183031B1D02 On DPOS27 Open [Trigger ID425] 5120018303481D02 On DPOS72 Open
[Trigger ID336] 51200181031B1D03 On DPOS27 Close [Trigger ID426] 5120018103481D03 On DPOS72 Close
[Trigger ID337] 51200183031C1D02 On DPOS28 Open [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] 51200181031C1D03 On DPOS28 Close [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] 51200183031D1D02 On DPOS29 Open [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] 51200181031D1D03 On DPOS29 Close [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] 51200183031E1D02 On DPOS30 Open [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] 51200181031E1D03 On DPOS30 Close [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] 51200183031F1D02 On DPOS31 Open [Trigger ID433] 5120018203011F43 On DPOS1 Undefined
[Trigger ID344] 51200181031F1D03 On DPOS31 Close [Trigger ID434] 5120018403011F45 On DPOS1 Faulty
[Trigger ID345] 5120018303201D02 On DPOS32 Open [Trigger ID435] 5120018203021F43 On DPOS2 Undefined
[Trigger ID346] 5120018103201D03 On DPOS32 Close [Trigger ID436] 5120018403021F45 On DPOS2 Faulty
[Trigger ID513] 5120018203291F43 On DPOS41 Undefined [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] 5120018403291F45 On DPOS41 Faulty [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] 51200182032A1F43 On DPOS42 Undefined [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] 51200184032A1F45 On DPOS42 Faulty [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] 51200182032B1F43 On DPOS43 Undefined [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] 51200184032B1F45 On DPOS43 Faulty [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] 51200182032C1F43 On DPOS44 Undefined [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] 51200184032C1F45 On DPOS44 Faulty [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] 51200182032D1F43 On DPOS45 Undefined [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] 51200184032D1F45 On DPOS45 Faulty [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] 51200182032E1F43 On DPOS46 Undefined [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] 51200184032E1F45 On DPOS46 Faulty [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] 51200182032F1F43 On DPOS47 Undefined [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] 51200184032F1F45 On DPOS47 Faulty [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] 5120018203301F43 On DPOS48 Undefined [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] 5120018403301F45 On DPOS48 Faulty [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] 5120018203311F43 On DPOS49 Undefined [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] 5120018403311F45 On DPOS49 Faulty [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] 5120018203321F43 On DPOS50 Undefined [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] 5120018403321F45 On DPOS50 Faulty [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] 5120018203331F43 On DPOS51 Undefined [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] 5120018403331F45 On DPOS51 Faulty [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] 5120018203341F43 On DPOS52 Undefined [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] 5120018403341F45 On DPOS52 Faulty [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] 5120018203351F43 On DPOS53 Undefined [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] 5120018403351F45 On DPOS53 Faulty [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] 5120018203361F43 On DPOS54 Undefined [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] 5120018403361F45 On DPOS54 Faulty [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] 5120018203371F43 On DPOS55 Undefined [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] 5120018403371F45 On DPOS55 Faulty [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] 5120018203381F43 On DPOS56 Undefined [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] 5120018403381F45 On DPOS56 Faulty [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] 5120018203391F43 On DPOS57 Undefined [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] 5120018403391F45 On DPOS57 Faulty [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] 51200182033A1F43 On DPOS58 Undefined [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] 51200184033A1F45 On DPOS58 Faulty [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] 51200182033B1F43 On DPOS59 Undefined [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] 51200184033B1F45 On DPOS59 Faulty [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] 51200182033C1F43 On DPOS60 Undefined [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] 51200184033C1F45 On DPOS60 Faulty [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] 51200182033D1F43 On DPOS61 Undefined [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] 51200184033D1F45 On DPOS61 Faulty [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] 51200182033E1F43 On DPOS62 Undefined [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] 51200184033E1F45 On DPOS62 Faulty [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] 51200182033F1F43 On DPOS63 Undefined [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] 51200184033F1F45 On DPOS63 Faulty [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] 5120018203401F43 On DPOS64 Undefined [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] 5120018403401F45 On DPOS64 Faulty [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] 5120018203411F43 On DPOS65 Undefined [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] 5120018403411F45 On DPOS65 Faulty [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] 5120018203421F43 On DPOS66 Undefined [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] 5120018403421F45 On DPOS66 Faulty [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] 5120018203431F43 On DPOS67 Undefined [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] 5120018403431F45 On DPOS67 Faulty [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] 5120018203441F43 On DPOS68 Undefined [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] 5120018403441F45 On DPOS68 Faulty [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] 5120018203451F43 On DPOS69 Undefined [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] 5120018403451F45 On DPOS69 Faulty [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] 5120018203461F43 On DPOS70 Undefined [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] 5120018403461F45 On DPOS70 Faulty [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] 5120018203471F43 On DPOS71 Undefined [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] 5120018403471F45 On DPOS71 Faulty [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] 5120018203481F43 On DPOS72 Undefined [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] 5120018403481F45 On DPOS72 Faulty [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] 522001000A011001 On Command Blocking [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] 523001000D011001 On ASEQ1 Start [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] 523001000D101001 On EMERGENCY Stop [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
of group settings (e.g., the ‘SYS_CHG’ signal; which has been connected with the trigger#9
using the setting [Trigger ID9], as default; we have been discussed in Chapter Technical
description: Group setting for protection functions.)
occurred for the event#1. Preceding event#2, event#3, etc. are shown below the event#1.
Similarly, the information about the ‘Event Record2’ and ‘Event Record3’ groups are displayed
on the IED screen.
†Note:For more information about the screen operation, see Chapter User interface:
Record sub-menu.
Event Record1 ○
a Event record1 list
10:48 1/4
#1 2012-07-26 ○
b The latest event#1
12:34:51.223
F.Record clear ○
c Trigger inform ation
On ○
d Trigger m ode inform ation
#2 2012-07-25
Screen scroll down 10:56:12.021
○
e Event#2
8.2.5 Setting
Setting of EVENTRECORD(Function ID: 200710)
Unit Default setting
Setting item Range Contents Notes
s value
End of E.Record-1 0 to 768 – The last position of the event group1 256
End of E.Record-2 0 to 768 – The last position of the event group2 512
Trigger ID1 (Preferred DataID) – Trigger signal1 for the operation –
Tigger Mode1 On / Off / On-Off / Change – Mode setting for the detection –
Event name1 (Preferred name) – Name of the trigger signal1 –
Trigger ID2 (Preferred DataID) – Trigger signal2 for the operation –
Tigger Mode2 On / Off / On-Off / Change – Mode setting for the detection –
Event name2 (Preferred name) – Name of the trigger signal2 –
…… …… – …… –
…… …… – …… –
…… …… – …… –
Trigger ID768 (Preferred DataID) – Trigger signal768 for the operation –
Tigger Mode768 On / Off / On-Off / Change – Mode setting for the detection –
Event name768 (Preferred name) – Name of the trigger signal768 –
8.2.6 Signal
Signal monitoring point
EVENTRECORD (Function ID: 200710)
Name Element ID Description
ER1_CLR 3001001001 Clearing the data in Event group1
Disturbance recorder
A phenomenon of fault occurring will be recorded in the disturbance recorder and its
phenomenon is recorded within 1ms accuracy. The recorder starts when TRC trip command is
issued. The recorder, additionally, will be instructed by PLC function, so an instruction is
managed with a setting. The amount of recording time and the sampling time are adjustable.
Therefore, measured values, such as current voltage and frequency, are recorded in accordance
with the amount and the sampling time. Logic signals are also recorded together with
disturbance phenomena. The recorder can hold up to 256 logic signals. The number of
disturbance phenomena to be recorded is limited by the amount of recording time and the
sampling time.
Start of recording Operating mode information of fault recorder is generated. End of recording
also check the maximum number on the IED screen (See Figure 8.3-2).
Table 8.3-1 Max number depending on time settings
Recording Max. recording number for Disturbance phenomena
period set with Setting [Sampling Rate] in 50Hz sys. Setting [Sampling Rate] in 60Hz sys.
[Record Time] 7.5º 15º 7.5º 15º
1 sec 204 255 255 255
3 sec 78 146 93 170
5 sec 46 93 56 102
8.3.3 Number of analog quantities and logical signals for disturbance recorder
Logical signals (i.e., 256) are recorded as disturbance phenomena.
Disturbance Record
10:48 1/2
_Record List >
Number of items
5/77
Clear Records +
Max. recording number for Disturbance phenomena
Operating counter
Figure 8.3-2 Running counter and Max number in the disturbance recorder
Disturbance Record
10:48 1/5
#1 2012-07-25 ○
a Disturbance record#1
10:48:21.223
#2 2012-07-21 ○
b Disturbance record#2
01:15:55.018
#3 2012/07/21 ○
c Disturbance record#3
Screen scroll down 13:11:29.621
#4 2012-07-02 ○
d Disturbance record#4
23:32:09.015
#5 2012-06-20 ○
e Disturbance record#5
09:37:48.915
8.3.6 Setting
Setting of DISTURB_REC(Function ID: 200401)
Uni Default
Setting item Range Contents Notes
ts setting value
8.3.7 Signal
Signal monitoring point
DISTURB_REC (Function ID: 200401)
Element ID Name Description
30A0001001 DSTR_CLR Data erased
9 Monitoring function
Contents Pages Pages
Accumulated time 545 Signal and Measurand 549
-Monitoring results 549
Counter features – -Software 31 measurands 549
-Information in GCNT 544
Total time measurements –
Dead band features – -Information in TOTALTIM 546
-V, I, Frequency. 542
-Phase 542
-GCNT 544
-TOTALTIM 546
Metering features –
-Information 542
-Information on the screen 542
Outline
The monitoring function is provided to measure the number of power quantities and statistics
data obtained on the VCT and BI circuits†. When the measuring instruments start measures
quantities, mathematical means is applied to the quantities from the circuits so that the actual
data (i.e., secondary value) is shown accurately on the IED screen.
†Note:The VCT and BIO structures and their features are discussed in Chapter
Technical description.
Metering
10:48 1/4
Ida
12.345A
Idb
12.345A
Idc
12.345A
when the entering current is out of the upper and lower limits again (i.e., Time=d). Then, at
Time=e, the value of the entering current will be sent to the network, because the repeated
number is incremented. After that, the repeated number will be set zero (0); the new positon
for the SD feature is set (i.e., from Time=e).
Lower limit
Repeat number
4
3
2
1
0 Time
a b c d e f g h i j k
…. …. ….
†Note:See Chapter General control function: Counter function for the general (GCNT).
Accumulated Time
10:48 1/1
ACT_TIME +
***d **h **m
…. …. ….
Total Time
10:48 1/12
TOTAL TIME 1 +
****d **h **m
TOTAL TIME 2 +
****d **h **m
TOTAL TIME 3 +
****d **h **m
(ii) Communication
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Communication. The communication features about the LAN port is discussed in
Chapter Communication protocol: LAN communication. The hardware information is
discussed in Chapter Technical description: Signal processing and communication module).
(iii) Binary IO
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Binary I/O. The structure and its operation is discussed in Chapter Technical
description: Binary IO module).
(v) Diagnostics
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Diagnostics sub-menu. The information about the diagnostics is discussed in Chapter
Automatic supervision).
Setting
Metering settings in MES (Function ID: 710001)
Unit Default
Setting item Range Contents Notes
s setting value
PeriodSD 0-4 – Period of Sending Dead band 0
10 Automatic supervision
Contents Pages Pages
Aux. contacts monitoring 581 Interruption 563
BIO module#1 error 568 LAN pinging error 576
BIO module#2 error 569 LRE error 577
BIO module#3 error 570 MRAM memory error 559
Check-sum error 556 PLC Data error 573
Clock error 566 Power supply failure 572
ECC memory error 558 Program code error 561
Error detection of differential current 583 RAM error 557
FPGA problem 560 ROM and RAM mismatch 555
GOOSE publishing error 580 Sampling error 564
HMI malfunction 571 Setting error 565
Supervision of communication setting 578
Tips: The alarms can be blocked when Off is set for the switch [A.M.F]. The switch can
be used to remove alarms during testing. See Chapter User interface: Test sub-
menu for more information.
The user can see a current error information in Monitoring sub-menu† on the LCD screen†
(see Figure 10.1-1); Table 10.1-3 shows the six detail information, which the user can examine
carefully using the hexadecimal number. When two or more errors occur at the same time, an
error code is given by the summation of the error codes. That is, when X and Y errors (e.g., X-
error-code ‘00000002’ and Y-error-code ‘00000004’) occur, the sum value ‘00000006’ is screened.
CP1M(ROM/RAM) error 1/1 C u r r e n t e r r o r i n d i c a te d b y S u p e r v i s i o n
10:48 C u r r e n t l o c a l ti m e ( N o t E r r o r o c c u r r i n g ti m e )
[Serious error] E rro r d e g re e (le ve l) d is p la ye d
D e ta i l e d i n f o r m a ti o n i n H e x a d e c i m a l d u m p
[00000011] [01234567] 7 6 5 4 3 2 1 0
[01234567]
[01234567]
[01234567]
[00000000] [ “Top left” ][ “Top right” ]
[ “Middle left” ][ “Middle right” ]
[ “Bottom left” ][ “Bottom right” ]
Figure 10.1-1 Example error codes and detailed information on Diagnostics sub-menu
†Note:See Chapter User interface: Monitoring sub-menu: Diagnostics. It will not be
updated automatically. If new information is required, refresh LED screen again.
Table 10.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display Meaning of the detailed information
area Left column Right column
00000001: ROM read error
Top row ROM address
00000002: ROM RAM mismatch
Middle row RAM address ROM value
Bottom row RAM value (No information displayed)
Middle
RAM address ROM value
row
Bottom
RAM value (No information displayed)
row
1For more information about the task and its kind, see Chapter PLC editing in PLC editor
(6F2S1904) separately.
Data(cmmslv) error
10:48 1/1
[Minor error]
[00010004] [51200131]
[03011001] [4747494F]
[32245354] [7456616C]
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row
Middle
00000002: DIF-SV-B 00000004: DIF-SV-C
row
Bottom
00000001: REF-SV (No message displayed)
row
10.2.27 Setting
Setting of CHK_SAMPLING (Function ID: 220701)
Setting item Range Contents Default setting value Notes
10.2.28 Signal
Signal monitoring point
MNT_LOGIC (Function ID: 220001)
Element ID Name Description
3211001001 ACT_TIME System active time in minutes
3210111001 CHECKSUMC
32E0001001 CHK_POINT
3210201001 LOADERSUM
3210121001 PROG_SIZE
… … …
Displaying error message founded by the TCS function is shown in Table 10.3-1; the error
is cleared when recovered
Table 10.3-1 Supervision items and error levels for Trip supervision
Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.3.1 Trip circuit error (TC error) N/A 3 On
8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s
8000011BB2
800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
TCS1-EN
On
8100021B60
8200031B60
8300041B60
8400051B60
8500061B60
≥1
8F00001B60
TC_FAIL
(ii) Applications
Example1
Figure 10.3-2 provides an application example of the TCS function. Two binary-input signals
are assigned to PLC connection points “TC1_FAIL_SIGNAL1” and “TC1_FAIL_SIGNAL2”.
When the trip circuit is healthy, a small current will flow in the BI circuits, the CB auxiliary
contacts, and the trip coil. This small current can be observed to flow in both the CB-open
condition and the CB-closed condition. If the small current supplied to the trip circuit is lost,
or if the connections between the trip circuit and the BI circuits become open circuit, a signal
"TC1_FAIL" is generated; then, the TCS1 logic will issue a Trip Circuit Fail alarm.
Note: A threshold setting voltage is required for the BI circuits. The user should set the
threshold to one-half of the value of the trip supply voltage. This is because in this
scheme there are two BI circuits connected in series. The supply voltage across the
BI circuit will be divided by two when the 52 contact is closed and the 52b contact
is open. Thus, the BI circuit may fail to operate if the BI sensitivity is only set in
response to the supply voltage. For example, the BI threshold voltage should be
set below 55V when a trip supply voltage of 110V is applied. For the TCS function,
the user should select two BI circuits from the BI2A module, because the BI
circuits of both of these modules can have lower threshold voltages than the BI
circuits that are available in other modules.
Trip circuit
()
Protection
8000011BB0
relay R
BI1 Binary input 800001EBB0 TC1_FAIL_SIGNAL1 1
circuit &
8000011B60
R 8000011BB1 t 0 0 t TC1_FAIL
Trip coil
()
LCP & GIS
Example2
In Example2 a binary input signal is assigned to PLC connection point “TC1_FAIL_SIGNAL1”.
With this arrangement if the CB is open, the small monitoring current will not be able to flow
in the BI circuit. Therefore, it is recommended that setting OPT-On is selected for the scheme
switch [TCS1-EN] and that a CB-closed-status signal is applied to PLC connection point
“TC1_FAIL_COND”. Monitoring is only enabled while the CB is in the closed position when
using this setting. This setting avoids unnecessary monitoring when the circuit breaker is open
when using this scheme.
Trip circuit
()
Protection
8000011BB0
relay R
8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s
52a
8000011BB2
800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
CB closed TCS1-EN On
status signal
Trip coil
()
LCP & GIS
10.3.3 Setting
Setting of TCS(Function ID: 482001)
Note
Setting item Range Units Contents Default setting value
s
TCS1(Trip Circuit Supervision 1)
TCS1-EN Off / On / OPT-On — Off
enable
TCS2(Trip Circuit Supervision 2)
TCS2-EN Off / On / OPT-On — Off
enable
TCS3(Trip Circuit Supervision 3)
TCS3-EN Off / On / OPT-On — Off
enable
TCS4(Trip Circuit Supervision 4)
TCS4-EN Off / On / OPT-On — Off
enable
TCS5(Trip Circuit Supervision 5)
TCS5-EN Off / On / OPT-On — Off
enable
TCS6(Trip Circuit Supervision 6)
TCS6-EN Off / On / OPT-On — Off
enable
…. …. …. ….
11 Communication protocol
Contents Pages Pages
IEC 60870-5-103 operation – LAN operation –
-Interface 675 -IP address 604
-Interoperability 678 -Hot standby operation 605
-Operation 699 -PRP/HSR operation 613
IEC 61850 operation 625 -RSTP operation 617
-About protocol 625 -Monitoring (Hot standby) 607
-Communication service 628 -Monitoring (PRP/HSR) 615
-Engineering work 631 Selection of slave protocol 603
-Goose monitoring status 655 RS485operation 704
-Protocol selection 652 USB operation 703
-Quality signal 653
-Setting 650
-Supervise 652
-61850 Editon1 option 627
-61850 Editon2 627
─────────────────────────────────────────────────────────────────
Note: The implementation of such protocols depends on the selection of protocols. Several
IED models do not have the protocols. To determine whether the protocols are implemented in
the IED, locate IED ordering codes, and check them at the “U and G&T” positions referring to
the comparison table below. For more information, see Appendix: Ordering.
Table Comparative table in respective ordering codes
Ordering codes
Sec.
Position “U” 1 2
Figure 11.1-1 illustrates the IED has both IEC61850 and IEC103, and the user can select one
of two using SLAVE PROTOCOL setting of Communication sub-menu. IEC61850 and IEC103
have their own settings. For example, an IED has IEC61850 settings, such as [GOINT],
whereas it has IEC103 settings, such as [103ADDR].
LAN operation
11.2.1 LAN address (IP address)
When LAN module(s) are provided, the IED can communicate using the “Transmission Control
Protocol/Internet Protocol (TCP/IP)”. The user can set the information about IP addresses and
other TCP/IP. Table 11.2-1 shows the setting items provided for the LAN†.
These setting values have been included in the CID file of the IEC61850. When the IED starts
up and if values except for the 0.0.0.0 values or default are set in the CID file, the CID
information is taken into the IED.
As the setting values have been included in the CID file, the user can define these values with
the engineering tool (GR-TIEMS). If the user wishes to modify those and the IEC61850 is used
to communicate, the user can change those with the GR-TIEMS. The user is required to write
both of setting values and IEC61850-CID file into the IED.
When wishing to change addresses, the user has to use the setting menu. Figure 11.2-1 shows
the setting menu provided to change the addresses‡.
LAN
10:48 1/6
IPADDRESS1 +
192. 168. 1. 11
SUBNETMASK1 +
255. 255. 255. 1
GATEWAY1 +
192. 168. 1. 1
†Note: When the user wishes not to operate Hot-standby, or the network is not ready for
the redundant, set Fixed for the [RedundantMode]. Port B (located at C12 if
provided) can only operate for the connection with the engineering tool (GR-
TIEMS®) or the PLC editor (MULTIPLOG®).
‡Note: See Chapter Technical description: Signal processing and communication
module.
(i) Overview
For the Hot-standby communication, the first communication module for Network is used as
the primary port, (i.e. Port A at C11) while a second communication module for Network, (i.e.
Port B at C12) is used as the secondary port; the IED will communicate using Port A for normal
operation. If a communications failure occurs at Port A, the IED can automatically switch
communication from Port A to Port B.
When the IED detects the occurrence of a communications failure, for which the LAN
module is unable to respond to the IED (i.e. a communications link is down), the IED starts a
timer. When the timer exceeds a setting [DownTime], the IED will switch ports. Thus, Port B
is then used for communications. (Note that Port A can be determined to be the secondary port
on the occurrence of the failure. If Port B is unable to continue to operate, then Port A will be
re-switched to run after a predetermined setting [UpTime]. Then, Port B will be discriminated
as the secondary port.)
used as the primary port. For example, provided that both Port A and Port B are physically
connected to the LAN, when the user wishes to use Port B as the primary port, the user should
set Port2(i.e., Port B) for the [PrimaryPort]. If the user wishes not to select the primary port,
set None for the [PrimaryPort].
The user should be aware of the following three facts prior to the Hot-standby operation:
1 The IED uses the IP/MAC address of Port A for the Hot-standby operation. The
IP/MAC address of Port B is not used even if communication is carried out on Port
B.
2 The user should ensure that an optical fiber is correctly connected when a 100Base-
FX module is used, otherwise a repeat communication failure (link-down) will be
experienced continuously. If the period for which the link-down is shorter than the
setting [DownTime], another port cannot be switched as the primary port. Thus,
the user should determine the setting value to be applied for [DownTime] on the
basis of the system requirement. It is allowable for the user to apply a setting of
zero for [DownTime] so that the switching of the ports will be performed
immediately; conversely, the user can set any value less than 3000ms in order that
the system need not experience chattering failures if the optical fiber were not
connected securely. Switching between the primary and the secondary ports is not
carried out during a value is setting for the [DownTime]. The user should consider
the setting approach for [UpTime] in the same manner as when setting [DownTime].
3 The auto-negotiation function is executed when the 100Base-TX modules establish
communication over the communications network. The auto-negotiation function
selects a mode for communication; the auto-negotiation function adjusts the
communication speed. In the case of a link-down condition, the auto-negotiation
function will run again immediately. The link-down condition continues until auto-
negotiation has been completed (it may continue for 1 or 2 seconds). The user can
apply a setting for [DownTime] for any value of time less than that required by the
auto-negotiation function in response to the system requirement (i.e. the user can
set [DownTime] to be zero milliseconds). In this case, switching between the
primary and secondary ports is performed immediately i.e. prior to the auto-
negotiation function running. If switching between ports is not required before the
completion of the auto-negotiation function, the user can set the setting
[DownTime] longer than the time required by the auto-negotiation function. The
user can consider the setting for [UpTime] in the same manner as when setting
[DownTime].
(vi) Monitor
LCD screen: The user can examine the statuses about the communion modules by
the monitoring function. Figure 11.2-2 shows the port status about the modules; terms
‘Up’ and ‘Down’ mean running and stopping, respectively. For menus operations, see
Chapter User interface: Monitoring sub-menu.
PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP
Port 1 (i.e., Port A) is connected. Ports 1&2 (i.e., Port A&B) are connected.
Port 2 (i.e., Port B) is not connected.
Status signals for Port A and Port B: The user can also examine the LAN status
using PLC signal monitoring points ‘Port1_Link (3100061001)’ and ‘Port2_Link
(3100061001)’ of the HOTST function. For example, when the user wishes to monitor
the status of the Prot1_Link, use the ‘Port1_Link’. Consequently, the user can get the
physical information about the Port A: the value ‘1’ is issued when the communication
is made (Linkup), whereas value ‘0’ is issued when the communication is not made
(Linkdown).
When Hot_Standby is set for the [RedundantMode], the user can find a running port
using the PLC signal monitoring point ‘Using_CH (3100081001)’ of the HOTST
function. Value ‘1’ is provided when the Port A is running, whereas value ‘2’ is
provided when the Port B is running.
Monitor setting: The Hot-standby (HOTST) function can send PING packets to
remote devices thus enabling the Hot-standby function to monitor the state of the
network. The Hot-standby function checks for a response signal from the remote
device. If the Hot-standby function does not receive a response signal, the Hot-
standby function will switch to the other port. The operation is performed when
the user sets the [RedundantMode]= Hot_Standby and [NetMonitor_EN] = On.
Settings [Ping_IP1] to [Ping_IP12] are provided in the Hot-standby function for the
monitoring of remote devices on the network. When the user sets plural remote IP
addresses for the settings [Ping_IP*], and if the Hot-standby function does not receive
a response from any one of these remote devices, the Hot-standby function determines
that a communication failure has occurred. Table 11.2-3 shows the network
monitoring settings for Hot-standby operation.
The user should note that the use of network monitoring could increase the burden
on the network. This is because a number of PING packets are repeatedly transmitted
over the network. Thus, the user should choose the setting values carefully in
accordance with the network capacity, the burden, and the required time. Examples
1 and 2 below show the respective results using the network monitoring function with
for different settings.
Example1: There is a remote device on the network with the address Ping_IP1.
The Hot-standby function sends ping packets to the remote device every five
seconds; then the Hot-standby function waits for one second until the Hot-
standby function receives a response signal from the remote device. The Hot-
standby function will determine that a communication failure has occurred if two
sequential response signals are not received from the remote device. Subsequently,
the Hot-Standby function will switch from one port to the other port (See Figure
11.2-3). The following settings are required in this example 1:
・ The IP address of the remote device1 is set for setting [Ping_IP1]. (the setting of
IP addresses in the other remote devices is not required.)
・ One second is set for setting [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “2” is set for [Check_Count].
5sec
NG: due to no response
Switching LAN ports is
performed if a response signal is
Sending Ping Packet for Ping_IP1.
not received for setting
[Chk_Count]. 1sec
5sec
Example2: It is assumed that there are three remote devices on the network:
Ping_IP1, Ping_IP2, and Ping_IP3. The Hot-standby function sends a Ping packet to
every remote device every 10 second (i.e., the IED sends a ping packet to a remote
device every 30 second). Suppose that “1” is set for [Check_Count]. The Hot-standby
function can determine a communication failure after 30 seconds if one of the remote
devices is unable to send a response. Figure 11.2-4 shows the operation. Switching is
not executed, because the IED cannot confirm all no-responses from the remote
addresses in the milled of the figure. Switching is performed after no-response is
confirmed from all remote devices.
・ The IP addresses of the remote devices are set for [Ping_IP1] to [Ping_IP3].
(Setting IP addresses for other remote devices is not required.)
・ 10seconds is set for [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “1” is set for [Check_Count].
5sec
5sec
10sec
NG: due to no response
LAN switching is not performed because the IED has not confirmed a response from the IP3.
Sending Ping Packet for Ping_IP1.
LAN switching is performed because the IED has not confirmed all response.
IP address at
Not applicable 192.168.1.12‡ 192.168.1.12§
Port B
IP address at
Not applicable Not applicable 192.168.1.13§
for Local PC
†Note:Address ‘192.168.1.11’ is set as default.
‡Note: An address can be set for SNTP, but it should not operate Time synchronization
with Port A and Port B, which have different IP addresses.
§Note: ‘192.168.1.13’ can be set for the local PC, if LAN for Local PC is ready at C13.
(i) Overview
‘Parallel redundancy protocol (PRP)’ is designed for double LAN networks in order to construct
high availability automation networks. Figure 11.2-5 shows an IED (i.e., Source, IED1 with
Port A and Port B†) and a server (i.e., Destination, Substation computer with Port A and Port
B). They are connected through LAN_A and LAN_B. For duplicating data, the IED have Link
redundancy entity (LRE) so that the IED can transfer data with A-Frame packet and B-Frame
packet at the same time. At the destination, either frames being arrived later is removed.
Substation computer
CPU
Operator
workstation
Data
Port A Port B
Rx Tx Rx Tx
Destination RedBox‡
A-Frame
LAN_A
B-Frame
LAN_B
TOSHIBA
IN SER VICE
ER R OR
Tx Rx Tx Rx
RedBox‡
Port A Port B TOSHIBA
IN SER VICE
LAN module LAN module Rx Rx
ER R OR
(C11) (C12) Tx Tx
Port A Port B
TOSHIBA
LAN module LAN module IN SER VICE
Data (C11) (C12) Rx
ER R OR
Tx
I Port A
R Data LAN module
L (C11)
CPU I
O Help Cancel ENTER
R
IED1 F1 F2 F3 F4 F5 F6 F7 L Data
CPU
Source O Help Cancel ENTER
I
IED2 F1 F2 F3 F4 F5 F6 F7
R
L
CPU
O Help Cancel ENTER
F3
IED3 F1 F2 F4 F5 F6 F7
Figure 11.2-5 PRP example for redundant LAN_A and LAN_B with DANP
†Note:For the locations about the LAN module, see Chapter Technical description:
Signal processing and communication modules.
‡Note: IED3 and Operator workstation (connected with singly attached node) can join
the network with Redundancy boxes (RedBox).
‘High-availability Seamless redundancy (HSR)’, for the ring topology, is designed to achieve
high reliability communication. Figure 11.2-6 illustrates IEDs connected over the ring LAN.
As doubly ports (Port A and Port B) are embedded in an IED, the IED can transfer the data
packet (A-Frame and B-Frame) for the destination over the ring LAN.
Source Destination
TOSHIBA
IED1 IN SE R VICE
E R R OR Substation Computer Operator Workstation
CPU CPU
CPU
Data Data
Data
I Port B Port A Port B Port A
R
L Rx Tx Rx Tx Rx Tx Rx Tx
Port B Port A
O Help Cancel ENTER
Rx Tx Rx Tx
F1 F2 F3 F4 F5 F6 F7
B-Frame B-Frame
A-Frame A-Frame A-Frame
Ring LAN1
A-Frame A-Frame
B-Frame B-Frame B-Frame
TOSHIBA TOSHIBA
IN SE R VICE
IN SE R VICE
E R R OR
E R R OR
Tx Rx Tx Rx Tx
Rx
Tx
Rx
Port A Port B QuadBox QuadBox Port A Port B
LAN module LAN module LAN module LAN module
(C11) (C12) (C11) (C12)
Data Data
I I
R R
L Ring LAN2 L
CPU CPU
O Help Cancel ENTER
O Help Cancel ENTER
IED2 F1 F2 F3 F4 F5 F6 F7 IED4 F1 F2 F3 F4 F5 F6 F7
A-Frame
B-Frame
TOSHIBA
IN SE R VICE
E R R OR
Tx Rx Tx Rx
Port A Port B
LAN module LAN module
(C11) (C12)
Data
R
L
CPU
O Help Cancel ENTER
IED3 F1 F2 F3 F4 F5 F6 F7
For Figure 11.2-5 example, the IED1 (Source) duplicates data by the LRE. The duplicated
data (in A and B-Frames) are transferred simultaneously over the LAN_A and LAN_B. In the
meantime, both frames cannot arrive at Substation computer (Destination). If the duplicated
frame is older than the setting [EntryForgetTime], the duplicated frame will be removed.
The [EntryForgetTime] has default 400ms setting, but the user can change it for an
appropriate value among 100 to 10,000ms. The setting value should be taken account of the
time after the entry removed from the duplicate table. The setting value also should be taken
account of the differences of the communication speeds between LANs.
(iv) Supervision
The communication supervisor function is available in PRP and HSR. The user can have
following settings:
Setting [LineCheckInterval]: is the setting of the interval time to send supervision frames
cyclically. The user is able to choice the time among 100ms to 100,000ms, but the
setting has default 2000ms values.
Setting [SV_Dst_MACAddr]: is for a reserved multicast address ’01-15-4E-00-01-xx’. By
default, ‘00’ is set for the ‘xx’. However, if conflict arises, the use can configure to
set any value between 0x00 and 0xFF for the ‘xx’.
Setting [SV_VLAN_EN]: can have On setting when the supervision frame is used in VLAN.
Additionally, the user can set identification specifying the VLAN to which the
supervision frame belongs and the priority of the supervision frame. Use the
settings [SV_VLAN_ID] and [SV_VLAN_Priority]. By default, Off is set for the
[SV_LAN_EN].
(v) Monitor
It is possible for the user to watch the communion statuses about Port A and Port B. Figure
11.2-7 shows the numbers of transferred packets via ports.
RedundantPacketNum
10:48 1/6
PortA_Send 12345
PortA_Recv 12345
PortA_ErrLANID 12345
PortB_Send 12345
PortB_Recv 12345
PortB_ErrLANID 12345
(i) Overview
‘Rapid Spanning Tree Protocol (RSTP)’ is designed to achieve LAN bridge connections in stable.
The RSTP choose one of bridges as the root and BPDU data (called ‘Bridge Protocol Data Unit)
is exchanged periodically over RPST network. Each bridge can listen and learn the BPDU data
so that all bridges in the network can find the shortest path for the root location (we call it
“Path-cost”). Consequently, the RTSP operation clear and recover the network failure if
occurred; no temporary loop will not occur in the network (that is, all terminals can have loop-
free LAN).
(ii) Parameters
When RSTP is set for the [RedundantMode], the user should enter several PSTP parameters
so that the IED is able to enjoy the Spanning Tree topology by the RSTP:
Setting [BridgeHelloTime]: is used to set a BPDU transferring cycle for other terminals
(i.e., BPDU sending interval; they are sent for IEDs, Network bridges, etc.)
Setting [BridgeMaxAge]: instructs the terminal (IED) to listen to a BPDU cyclically. When
a terminal (IED) cannot listen to BPDUs within the setting, the terminal (IED) starts the
computation to make new spanning tree.
Setting [BridgePrioriy]: is allowed for the user to make priority tables in the IEDs. When
a terminal has the smallest number, the terminal can become the root bridge with high
possibility Note that a number can be set in 4096 steps.
Note: the user shall take the above settings based on the IEEE 802.1D equations below:
Setting [PortA_PathCost]: is used to set the distance for the root bridge (path cost), when
the port is used in the LAN network, actually. As a rule, the setting value depends on the
communication bandwidth.
Setting [PortA_Priority]: is set a priority value for the port. Similar to the setting
[BridgePrioriy], a port having the smallest number can have the highest priority. Note
that a number can be set in 16 steps
†Note: Port A (connection for LAN_A) is located at C11 of IED. The second Port B
(connection for Port B) is located at C12 and has similar settings. See Table 11.2-6
for the IP addresses examples. The user can find the contents about LAN
communication module in Chapter Technical description: Signal processing and
communication module.
11.2.5 Settings
Setting of TCPIP_DRV (Function ID: 230201)
Un Default setting
Setting item Range Contents Notes
its value
IPADDRESS1 0 – 255 – First IP address 192.168. 1. 11
LAN1
SUBNETMASK1 0 – 255 – Subnet mask 255.255.255. 0
(Port A)
GATEWAY1 0 – 255 – Gateway 192.168. 1. 1
IPADDRESS2 0 – 255 – Second IP address 192.168. 1. 12
LAN2
SUBNETMASK2 0 – 255 – Subnet mask 255.255.255. 0
(Port B)
GATEWAY2 0 – 255 – Gateway 192.168. 1. 1
IPADDRESS3 0 – 255 – IP address provided for the engineering PC 192.168. 1. 13
LAN3 for
SUBNETMASK3 0 – 255 – Subnet mask 255.255.255. 0
Local PC
GATEWAY3 0 – 255 – Gateway 192.168. 1. 1
3111101001 RX2_CNT
3111111001 RX2ER_CNT
3111201001 TX2_CNT
3111211001 TX2ER_CNT
3211021001 PortB_Send frames sent over B(only HSR tagged or with PRP RCT)
3211071001 PortB_Recv frames received over Port B(only HSR tagged or with PRP RCT)
Remote
Monitoring
GPS
Communication Substation
Operator Network
Workstation Computer
Engineering
Workstation Printer Router/
Modem
GBU GRT GRG GBU GRL GRB GBU GRG GRZ GBU GRT GRL
GOOSE
†Note:When applying IEC 61850 communications, the user should map application
signals with the required logical-nodes (LNs) within the IED. In this manual, we
show the application signals as Data IDs; hence, the user is able to connect the
Data IDs with the required LNs using the engineering tool (GR-TIEMS) provided
by Toshiba. For the GR-TIEMS, see Chapter Engineering tool.
‡Note:Before using the IEC 61850 communications feature provided within the IED, the
user should verify its IEC 61850 capability by reviewing both the protocol-
implementation-conformance-statement (PICS) and the model-implementation-
conformance-statement (MICS). The MICS provides the user with information for
the LNs provided within the IED; the PICS provides the user with information to
enable the IED to communicate with both SAS and other devices. See
Appendix:IEC61850 MICS, PICS, PIXIT and TICS. It explains how the user can
obtain this information.
When TCP/IP operates, the IEDs can communicate with SAS computer, operator
workstation (OWS), engineering workstation (EWS), remote monitoring system, SNTP server.
In the SAS, the communication is served with the method of data transfer:
Report method of sending event messages like measurement, status, alarm and so on
GOOSE (Generic Object Oriented Substation Event) method of communication
between IEDs like interlock
Control method like controlling the circuit breaker (CB), the disconnector (DS), the
selector device (43), the transformer tap (TAP) and so on
For the IEC 61850 communication, the IED consists of multiple logical devices and logical
nodes. The user should configure the 61850 Data Model to perform a required function for the
protection and control.
Modular approach achieves data transfer between devices in the IEC 61850 standard. All
function in the IEC 61850 network are grouped into smaller objects called Logical Nodes (LNs),
which contains process objects related data and attributes of a logical device protection and
control function. Logical Node Zero (LLN0) represents specific information of the logical device.
Logical Node Physical Device (LPHD) represents specific information of a physical device. A
generic device is called Physical device (PD). The LPHD contains the properties of the PD. A
specific function in the IED is represented as domain specific LN. The domain specific LN
contains the essential function for target devices in the IEC 61850 network.
LN data model defines the abstract syntax and semantics of the information exchanged
between PDs. The relation between data object classes, data types, data attributes and
abstract data objects are provided in the LN data model. The LN data model is mapped to
Manufacturing Message Specification (MMS) and Generic Object Oriented Substation Event
(GOOSE) functions. Table 11.3-1shows the description of LNs.
All LN classes (LLN0 and domain specific LN) receive the mandatory data of the common LN
except LPHD. Table 11.3-2 exemplifies Function, Logical node and Communication service
used in the IEC 61850 communication.
Harmonics
measurement
Measuring
Control / Monitoring Protection function
Physical Model
“Logical Node” “Communication Service”
IEC 61850 Model Physical Device
LN Physical Device
LN LPHD LN
GOOSE
CB XCBR CALH
LN Enhanced-security Control
LN
CSWI
IHMI
LN Buffered Report
LN
CT PTOC
LN IARC
GOOSE
PTRC
LN
Buffered Report
VT PTUV
LN Unbuffered Report
MHAI
LN GOOSE
Binary
SIMG
Input
Figure 11.3-2 Example of Physical model and its equivalent IEC 61850 model
The user can handle LGOS with signals shown in Table 11.3-3. The signals are provided for
mapping in the 61850 Editon2. Figure 11.3-3 shows an example that they are mapped for the
LGOS.
The LN contains data list with their attributes based on their functionality in SAS. A
data has a well-defined structure and information of SAS. The data and attributes of the LN
in a logical device are exchanged by the communication services according to IEC 61850
protocol. The communication services are implemented by SCSM using Ethernet TCP/IP
protocol.
The data structures of the GOOSE are illustrated in Table 11.3-4; they are grouped for
the system (say, SAS) and other logical devices (say, a relay); they are used in the applications
in the SAS and the IED.
(iii) System
The data model in the LN named “System” is not allowed to modify (that is, a data model is
fixed; other LN data models are configurable to meet the system requirement). Mapping
signals to the GGIO1 is required when the GOOSE should send data faster.
IED
*IEC 61850-7-4
Logical device1 CONTROL
Logical Node
Current
Application
Data Logical device2
BIO ・・・ GOOSE GOOSE
DataSet
Binary
Control Block (outgoing)
Logical Node
Input
Binary
Input
2. Mapping 1. icd(cid)
data
GOOSE
GOOSE subscribe function
(incoming)
3. GOOSE subscribe
Add Substation, Voltage level, Bay and IED to the project tree
(→cf. sec. 11.3.3(i))
Selection of IED
When user’s project has been created or is opened, the user can add new IEDs.
Figure 11.3-7 illustrates new IED has been added on the project tree.
Edition list
Edition 1
Edition1 display
Edition 1-Opetion
Edition1_Option display
Edition 2
Edition2 display
Import CID/ICD
Export CID
Export ICD
should check whether the required signals are mapped in the default
configuration.
To verify the signals configured for the IEC 61850 protocol, the user should check
the mapped data, Dataset or Report Control list. If they have existed, the signals
in the signal list should be matched with the attributes of LNs.
Figure 11.3-11 shows an example to check if the signals are mapped in default
configuration. For example, to check for mapping of the primary element signal
in earth fault protection (EF1), follow the steps below:
1. To check if the EF1 signal is already mapped in the LN, key ‘EF1’ under Signal
Name in the Signal List screen.
Mapped data
3. To check, if the DataSet is already assigned to RCB, Right click on “LLN0” and
select Edit Report Control, then Report Control List screen appears as shown in
Figure 11.3-13.
Mapped data
Drop
Drag
Signals
Edit DataSet
Dataset can be edited or a new dataset can be added for the LNs as shown in
Figure 11.3-17. For editing the DataSet, follow the steps below:
1. Right click LLNO and select Edit DataSet, DataSet List window appears as
shown in Figure 11.3-17.
2. Choose the variables to be added to the DataSet and click OK.
*Note: 100 DataSets can be added in the DataSet List and each DataSet can have
maximum of 32 elements.
If the user wishes to assign the DataID for GOOSE operation, follow the steps
below:
1. Click GGIO1 and select Ind1 as shown in Figure 11.3-19.
2. Drag and Drop the required signals to be sent by GOOSE.
Note: The user can assign any signal to GGIO1->Ind1~16 for high-speed GOOSE, as
required.
Drop
Drag
Figure 11.3-20 shows the GOOSE Publish screen, where “System” is fixed and is
not configurable for GGIO1, whereas “Ctrl” (Control) and “Prot” (Protection) are
configurable. The user can add new variables from the “Logical Node” screen to
the GOOSE Publish screen using drag & drop* method. Figure 11.3-20 shows an
example for GOOSE Publish, where “System/GGIO2$Ind1$stVal” is added to the
GOOSE Publish screen.
*Note: Only “stVal” and “q” variables can be added to GOOSE Publish screen.
Drag
Fixed
Drop
In the example shown below, select the required variable and click Add. Similarly,
the user can delete the variables.
When the user adds a signal to the GOOSE subscribe list from the other IED,
then the same signal is automatically added in the Signal List of the current
IED.
List 2
List 1 List 2
For example, to let a device execute “Select”, “Operate” and “Cancel” commands
from the sever through “CSWI4” and transmit the information to an IED, the user
should map an input point (Data ID) to several variables of “CSWI4” (See Figure
11.3-22). Mapping period for Control shall be 100.
*Note: For more information of the input points, see chapter General control function or
Control and monitoring application, if available.
SBOW
Oper
DE V01_ CONTROL_ RE Q
Cancel
†Note:For more information for the BI, BO, see Chapter Technical description: Binary IO
module.
Note: The user can check the edition number through on the LCD screen. Therefore, the
user should confirm the edition number written in the IED too. See sec. 11.3.3(vi)
to show the LCD screen.
Scroll downward
The setting values have been included in the CID file of the IEC 61850. The IED uses the
information of the CID file when the IED starts up. As the setting values have been included
in the CID file, the user can modify this setting value with the GR-TIEMS. The user is required
to write both of the setting values and the IEC61850-CID file into the IED.
†Note:For example, Figure 11.3-27 shows the signal flow between a substation computer
(SC), an IED and a target device (e.g. CB). If the requirement is to close the CB on
request of the SC, the SC will send the operation command “Operate” to the IED;
the time information (T) is also sent along with the operation command. When
receiving the operation command and observing that the CB has closed, the IED
will send a response signal “CommTerm” to the SC along with the time
information. However, this time information is not the actual operation time of the
CB, but the same time information originally sent with the operation command.
The IEC 61850 standard defines this rule; hence, general operations in the IEC
61850 standard are subject to this rule. However, the server communication
provided by Toshiba is able to accept the actual operation time; hence, the setting
‘CommTerm’ is required in the Toshiba communication. The user should also note
that Off is set for the scheme switch [TCMD] as the default setting.
Command Open
Response
Process Closed
CommTerm+(T) Response
†Note:The user may wish to perform bad reception tests from a remote terminal using
the GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid the influence, we recommend the user to test bad receptions for a particular
IED using the GOSUBBLK function. As a result, testing will only affect the
particular IED under test i.e. all other terminals will not be influenced by the
tests.
Qual_Validity
M/ Default
Attribute Name Attribute value O/
C1 value
(i) Qual_validity
Qual_validity (61850: Signal No. 301001 3110041005) is a signal provided for a common quality
information. It can be useful if some ‘q’ attributes (it’s defined in Quality type) should belong
to a common quality. Both severe and non-severe errors are included; therefore, that signal
value will be changed whenever errors (including alarm and warning incidents) are detected.
In this quality signal, the Detail quality information—defined in the standard—is not set at
all.
Detail quality
Kinds of Value
operatorblocked
Validity
badReference
Good 00
outOfRange
inconsistent
Validity
inaccurate
Invalid 01
oscillatory
overflow
Kinds of
Questionable 11
oldData
source
failure
test
301001 3110041005
0 0 0 0 0 0 0 0 0 0 0 Qual_Validity
220001 3110111001
SERI_ERR
≥1
220001 3110121001
MINR_ERR
201301 3100001190
Test Mode
On the LCD screen, the user can find either OK or NG message regarding other IEDs. The
OK/NG message is generated with the information of the GOOSE packet received. Table 11.3-7
illustrates the messages displayed on LCD screen and GR-TIEMS screen.
When the user wishes to see GOOSE outputs†, the user can see them by user’s PLC logic, but
the user should build its logic using the PLC function. Table 11.3-8 shows the GOOSE signals,
which the user can select. For example, in order to get the GRL200_Bay1_4 information, the
user should take the GOOSE content using SUB_QUAL#3 output.
Note: The option1 is designed to transfer the metering values during the fault on the
IEC61850 Edition1.
11.3.10 Setting
Setting of 61850(Function ID: 301001)
Unit Default setting
Setting item Range Contents Notes
s value
11.4.1 Overview
For the communication in the IEC 60870-5-103 standard, the user should create the data with
regard the protocol, which is grouped into a slave and a master. The user can edit the slave
Data or the master Data using the GR-TIEMS.
(i) Management
As cited earlier, the IEC 60870-5-103 standard is grouped into the slave and the master. In an
IED the user should select either the master mode or the slave mode; the user should edit
either the master data or the slave Data. The both modes can provide the same functions
equally. The GR-TIEMS can provide the user the management means for the following data.
Data management
Import data are provided in the CSV file. The data are categorized as “adding items”,
“editing items”, “deleting items”, and “arranging items”.
Process management
Creation of the new data
Registration, clear, and change name of a slave IED
Registration and clear of signals
Edition of the dialog prototype
External Interfaces
Logging and Access Security
(ii) Configuration†
Table 11.4-1 and Table 11.4-2 show that the items should be programmed using the GR-TIEMS.
We shall see how to set and edit data of the IEC 60870-5-103 configuration in section 11.4.5
Data request
Data request
Response frame
Figure 11.4-1 Ping cycles between the master station and the IED
11.4.3 Interoperability
The IEC 60870-5-103 protocol provides a physical layer and an application layer for the
communication to secure the interoperability.
Optic interface
Several optic communication modules are available
(iv) Commands2
The user can customize the supported commands. The IED can replay for unsupported
commands using the cause of transmission (COT) negative acknowledgement of a command.
1Note: With regard to the GI list, see Appendix IEC 60870-5-103 interoperability. When
the user wishes to understand the details, refer to the section 7.4.3 of the IEC
60870-5-103 standard.
2Note: For details, refer to the section 7.4.4 of the IEC 60870-5-103 standard.
3Note: For details, refer to the section 7.4.5 of the IEC 60870-5-103 standard.
4Note: For details, refer to the section 7.4.6 of the IEC 60870-5-103 standard.
Measurand period
This setting is used to set the transmission cycle (s) of Measurand frame. The setting range
is 0 to 60s. If no Measurand frame is provided by measurand setting, this setting is disabled.
The test mode in the IEC 60870-5-103 standard is enabled by the operation on the IED
screen or the GR-TIEMS. When the set signal changes “ON” and Time-tagged message or
Time-tagged measured of spontaneous cause (COT=1) or measurand frame or cyclic
transmission (Type ID=3 or 9) occurs, its COT shifts COT=7 (Test mode).
The time (ms), which is from the establishment of a set signal to the detection of a
status change, is added the set frame as RET value. FAN (Fault number), attached the
frame of Type ID=2 or 4, has the same number during the set signal ON. (Whenever the set
signal is ON, the FAN increases.) When setting to “0”, RET value is always “0” (RET=0).
The default setting is set to the OR signal of elements operation. When Type ID=2 frame is
provided with OC trip as send condition, for example, the time from OC element operation
to OC tripping is attached to the frame as RET. Though, the RET of GI frame is always “0”
in spite of this setting.
T1
T2
T3 t
Signal “ON” Type ID=2 Type ID=4 Signal “OFF” Type ID=2
i occurs ii occurs iii occurs
Figure 11.4-4 Occurrences after the signal “ON”
When the “Time-tagged message” tab is selected, the “Time-tagged message” setting
screen is displayed on the start screen.
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative
time) can be set in this screen. In one frame of Time-tagged message, the Type ID, INF,
FUN, DPI and COT must be set and the maximum 256 frames of Time-tagged message can
be set. The information number of the frame is determined by the INF setting. The most
left item “No.” is only serial number and can be skipped.
Common address is linked with the address setting† in the IEC 60870-5-103 standard.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.
In the transmission format of Type ID=1 (Time-tagged message) and Type ID=2 (Time-
tagged message with relative time), customized items are shown in Table 11.4-3 and Table
11.4-4.
Table 11.4-3 Time-tagged message (Type ID=1)
Oct. Item Value Remarks
1 Start 68H
2 Length 14
3 Length 14
4 Start 68H
5 Control field 08H+ACD+D
FC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 1 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 1/9/11/12 Customized by GR-TIEMS
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of IEC 60870-5-103 communication.
relay. If the setting value (signal No.) is “0”, all setting items related events are disable and
the frame is not provided.
†Note:A relevant Data ID is required to select; the description is obtained
automatically.
Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-5 and the
Appendix†.
Table 11.4-5 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 Status
32 to 47 Supervision
48 to 63 earth fault
64 to 127 short circuit
128 to 143 auto-reclosure
144 to 159 Measurands
160 to 239 not used
240 to 255 generic functions
†Note:See Appendix: IEC 60870-5-103 interoperability: Semantics of Information
number.
FUN
Function type (FUN) is set referring to Table 11.4-6. The FUN can be set to 0 to 255. When
clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 11.4-6 Semantics of Function type
0 - 127 private range
128 distance protection
129 not used
144 not used
145 not used
160 overcurrent protection
161 not used
176 transformer differential protection
177 not used
192 Line differential protection
DPI/Off, DPI/On
Double-point information (DPI) is set using the menu as follows:
DPI/Off: The frame is transmitted when the DPI/Sig.No. signal is OFF.
DPI/On: The frame is transmitted when the DPI/Sig.No. signal is ON.
Note: If selecting “-”(=don’t care), the frame is not transmitted even though the
DPI/Sig.No. signal set change to the set status. In general, the frames related
to tripping such as “Time-tagged message” and Time-tagged measurand”, etc.,
which are not an object of GI (General Interrogation), are not transmitted
when the DPI changes “On” to “Off”. In this case, set the “DPI/Off” to “-”(=don’t
care).
Note: When selecting “DP” for both “DPI/Off” and “DPI/On”, the DPI number is
transmitted as the number (=0/1/2/3) using the same information number
(INF). Regarding the frame related to a device control, the “undefined/failed”
status may be required in addition to the “close/open” status for the extension.
When selecting “DP”, “undefined(00)/close(01)/open(10)/failed(11)” status is
applied in the same information number (INF).
COT
Cause of Transmission (COT) of the frame is set. Not only one COT but also two or more
COT can be selected each No. (frame). COT setting pattern and COT supplemented the
frame are as follows:
(1) If two or all of COT=1, 11 and 12 are checked per No., each frame of the No. become
the following conditions.
Table 11.4-7 COT
COT Conditions
COT=12
TR[ms] after receiving any command of the IEC 60870-5-1031
(remote operation)
COT=11
TL[ms] after Key operation on the relay front panel1
(local operation)
COT=1 Conditions except above COT=11 and 12
(spontaneous) The relay is in test mode2, the COT=1(Spontaneous) is shifted to 7(Test mode)
1Note: TR and TL are set in Common setting.
2Note: Settings of the test mode is described later.
(2) If one of COT is specified per No., the frame is always supplemented with the
Table 11.4-8 shows the summary of (1), (2) and (3) above.
Table 11.4-8 COT setting pattern and COT supplemented frame
COT setting
pattern COT supplemented frame when status changes GI
1 9 11 12
Always “1” No
Events don’t occur. Yes
Always “11” No
Always “12” No
Always “1” Yes
“11” (cause at local) or “1” (other causes) No
“12” (cause at remote) or “1” (other causes) No
Always “11” Yes
Always “12” Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) No
“11” (cause at local) or “1” (other causes) Yes
“12” (cause at remote) or “1” (other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) No
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) Yes
Always “1” in spite of cause of event occurrence No
Note: When being in the test mode, the COT=1(Spontaneous) is shifted to 7(Test
mode)
When the “Time-tagged measurand” item is selected on the GR-TIEMS, the setting
screen is displayed.
Type ID=4 (Time-tagged measurand with relative time) can be set in this screen. In
one frame of Time-tagged measurand, the INF, FUN, Sig No., Rev, COT and SCL must be
set and the maximum eight frames of Time-tagged measurand can be set. The information
number of the frame is determined by the INF setting. The most left item “No.” is only serial
number and can be skipped.
In the transmission format of Type ID=4 (Time-tagged measurand with relative time),
customized items are shown in Table 11.4-9.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
The frame cannot be set to the object of GI and cannot be transmitted even though the
status of set signal changes from ON to OFF. If the metering values at the newest fault
record are transmitted as the status change frame, select the Data ID of “F.Record_DONE”
or “FAULT RECORD DONE” in the signal list of the relay.
†Note:A relevant Data ID is required to select in the signal list. The description of the
Data ID is obtained automatically on the setting.
Inverse
This setting is used to invert the logic of the signal assigned to the Data ID above. If the
frame is transmitted when the signal assigned to the Data ID is ON, leave the Inverse check
box blank. If the frame is transmitted when the signal is OFF, click the inverse check box
to be marked with “”.
Type ID
Type ID=4 (Time-tagged measurand with Relative time) is fixed. In Type ID=4, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the fame
out of the standard is provided, the INF should be set referring Table 11.4-3 and the
Appendix†.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.
FUN
Function type (FUN) is set referring to the Table 11.4-4. The FUN can be set to 0 to 255.
When clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed
to the setting values at Common setting.
COT
Cause of Transmission (COT) of the frame is set. Not only one COT but two or more COT
can be selected each No. (frame). COT setting pattern and COT supplemented the frame
are according to Table 11.4-6. Though, the COT=9 (General Interrogation) cannot be
selected.
Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The SCL is a value which the power system quantity specified as above is
multiplied by this setting value.
When the “General command” item is selected on the GR-TIEMS, the setting screen
is displayed.
The frame of Type ID=20 (General command) and Command ACK/NACK can be set
in this screen. In one command of General command, the INF, FUN and DCO must be set.
The Command ACK/NACK is for detail setting and must not be set usually. (If do not check
the Ext check box, the setting of Command ACK/NACK is disabled and the Command ACK
and Command NACK respond according to the default response.)
The maximum 32 frames of General command and Command ACK/NACK can be set.
The information number of the frame is determined by the INF setting. The most left item
“No.” is only serial number and can be skipped.
In this setting screen, if a Data ID except “0” is set to “Sig Off” and “Sig On”, the
command at INF setting value is provided and Command ACK or Command NACK is sent
back when receiving the command from upper station. If both “Sig Off” and “Sig On” have
“0”, the fixed length NACK is always sent back then and the command is not provided.
Though the command is provided, however, Command NACK is always sent back and
no control is performed in the following cases:
(1): When receiving any General command from the upper station before Command
ACK/NACK is sending back from the relay.
(2): Under Monitor direction block condition (“IECBLK” setting is “blocked”.) when
receiving General command.
(3): When receiving an incorrect value of DCO of General command, that is DCO is neither
“1” nor “2”.
Primary Secondary
station station
General
Command
ACK
Class 1
Command
ACK/NACK
In the transmission format of General command (Type ID=20), customized items are
shown in Table 11.4-10.
Any comment with maximum 16 characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Type ID
Type ID=20 (General command) is fixed.
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-12 and the
appendix†.
Table 11.4-12 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 status
32 to 239 not used
240 to 255 generic functions
FUN
Function type (FUN) applied to a command response frame is set referring to Table 11.4-13.
The FUN can be set to 0 to 255. When clicking the “Change all FUNs” on the Common
setting screen, all FUNs are changed to the setting values at Common setting.
DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
“Sig off” and “Sig On” are used to set the Data ID of control object in General command.
(Hereafter, these are described as “command output signal”.) “Inverse” is used to reverse
the logic when controlling the command output signal.
When the command output signal is treated as two signals (Sig Off Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.
For example, when the DCO=Off command is received under “Inverse” no-checked,
the command output signal of “Sig Off” is controlled to “1”. “Sig On” is not controlled.
Table 11.4-13 Control Scheme of Command Output Signal (Sig Off Sig On)
“Inverse” checked Checked No-checked
Control object
Signal specified Signal specified Signal specified Signal specified to
Receiving
to Sig.off to Sig.on to Sig.off Sig.on
command DCO
When the command output signal is treated as one signal (Sig Off Sig On), the
control scheme is shown in Table 11.4-14. For example, when the DCO=On command is
received under “Inverse” checked, the command output signals of “Sig On” and “Sig Off” are
controlled to “0”. “Sig On” is not controlled.
Table 11.4-14 Control Scheme of Command Output Signal (Sig Off = Sig On)
“Inverse” checked Checked No-checked
Control object
Signal specified Signal specified Signal specified Signal specified
Receiving
to Sig.off to Sig.on to Sig.off to Sig.on
command DCO
When setting the “Sig Off”, “Sig On” and “Inverse”, check the specifications of the
command output signals of communication and others, and then set them.
Valid time
Valid time is used to set the time (ms) to control the command output signal. The command
output signal is controlled based on the control scheme described in section 11.4.5(iv)-5 for
the setting time after receiving General command, and is reset by communication side after
the set time. However, if the time is set to “0”, the control is not reset and is continued. Set
the time with a margin for interface of other applications.
ACK/NACK / Ext
This setting is used to enable the extension setting of Command ACK/NACK response
scheme or not. If “Ext” is not specified (Ext check box is not checked.), Command NACK (in
cases of (1)–(3) of the section 11.4.5(iii) and Command ACK (in case of others) respond
according to the default response. If “Ext” is specified, the setting of Command ACK/NACK
described later is enabled and the response scheme can be customized. When required the
stricter handshake by using Command ACK/NACK, it is better to specify the “Ext”. This
setting is not influenced by the control scheme of the command output signal.
When the command response signal is treated as two signals (ACK Sig NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is when (1), (2), (3) or (4) in Table
11.4-15 is established. If the neither (1), (2), (3) nor (4) is established (that is ACK sig =
NACK Sig = 1 or ACK sig = NACK Sig = 0) for the period from the command receiving to
the timeout setting time, Command NACK responds at that time.
For example, when the DCO=On command is received under “Inverse” no-checked,
Command ACK responds in case of “ACK Sig = 0” and NACK Sig = 1”.
Table 11.4-15 Judgment Scheme of Command Response (ACK Sig NACK Sig)
“Inverse” checked No-checked Checked
When the command response signal is treated as one signal (ACK Sig = NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is after the timeout setting time
For example, when the DCO=On command is received under “Inverse” checked,
Command ACK responds in case of “ACK Sig = NACK Sig = 1” after the timeout setting
time.
Table 11.4-16 Judgment Scheme of Command Response (ACK Sig = NACK Sig)
“Inverse” checked No-checked Checked
When the “Measurands” item is selected on the start screen of the GR-TIEMS, the
setting screen is displayed.
In one frame of Measurand, the Type ID, INF, FUN settings, and its position setting
(Measurement Name/Measurement Description/Lower Limit/Upper Limit/Coefficient)
must be set. “No.” shows the position of power system quantity. (For details, describe later.)
The maximum 16 items of Measurands and the maximum 32 power system quantities per
one frame can be set.
In the transmission format of Measurand I (Type ID=3) and Measurand II (Type ID=9),
customized items are shown in Table 11.4-17.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of the IEC 60870-5-103 communication.
Type ID
Type ID=3 (Measurands I) or Type ID=9 (Measurands II) can be selected to set the frame
type of Measurand frame. In general, the maximum MEA number of Type ID=3 uses 1 or 2
or 4 and that of Type ID=9 uses 9. (However, the maximum MEA number of both types can
extend up to 32 in the GR-TIEMS. In this case, there are no difference between the
transmission format of Type ID=3 and that of Type ID=9.)
INF
Information number (INF) of the Measurand frame is set. The INF can be set to 0 to 255.
When the standard frame† is provided, the INF according to the standard is recommended.
If the fame out of standard is provided, the INF should be set referring Table 11.4-3
and the appendix†.
FUN
Function type (FUN) of the Measurand frame is set referring to the Table 11.4-4. The FUN
can be set to 0 to 255. If click the “Change all FUNs” on the Common setting screen, all
FUNs are changed to the setting values at Common setting.
Name
Any comment with maximum eight characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
If MEA value exceeds the full scale (if the value expressed as B1 to B12 is less than
4096 or more than 4095), the MEA is clamped at 4096 or 4095 and OV flag is established.
However, if IV flag is established, OV flag is not established.
Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The MEA is a value which the power system quantity specified as above is
multiplied by this setting value.
Figure 11.4-11 Slave protection for the IEC103 protocol (on IED setting menu)
Note: This sample menu illustrates how to select the IEC103, so that we do not discuss
the inclusion of IEC61850, DNP3.0, and Modbus and the selection of those
protocols here. See Figure 11.1-1 to check the inclusion of the protocols in the IED.
Figure 11.4-12 shows the editing screen of the GR-TIEMS; the screen has a remark field
concerning to the IEC 60870-5-103 communication. Note the available length of the remark
field is up to 12 in the one-byte character. The remark field is utilized for the control of the
setting data.
11.4.8 Setting
Setting of 103_SLAVE (Function ID: 304001)
Unit Default setting
Setting item Range Contents Notes
s value
USB communication
The IED front panel has an USB receptacle in a B-type to connect with a local PC for
engineering. The user can select a transmission speed, which is shown below, by the operation
of the setting menu, as shown in Figure 11.5-1.
USBCOM
10:48 1/1
USBCOM_BRATE_SW +
921.6kbps
USBCOM_BRATE_SW 115.2 / 921.6 kbps Baud rate Switch for USB Com port 921.6
RS485 communication
When the IED has an RS485 module for the communication, the user can select and set its
transmission and error check parity codes. Figure 11.6-1 shows the setting screen when the
RS485 module (#1) operates.
RS485
10:48 1/2
RS485_1_BRATE_SW +
19.2kbps
RS485_1_BRATE_SW +
NONE
Module RS485_1_BRATE_SW 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbps Transmission speed 19.2
#1 RS485_1_PAR_SW NONE / ODD /EVEN – Parity check code NONE
12 User interface
Contents Pages Pages
Outline 706 Time sub-menu 745
-Front panel 706 -Clock 745
-LCD screen 706 -Time zone 746
-LEDs 706 -Time synchronization 747
-Function Keys 707 -Display format 749
-Operation Keys 708 -Summer time(DST) 751
HMI operation 709 Test sub-menu 753
-General operation 709 -Test screen 753
-Main-menu and sub-menu 709 -Test mode screen 753
Record sub-menu 712 -Test flag enabling screen 757
-Fault record 712 -Mode change screen 758
-Event record 715 -Signal monitoring screen 758
-Disturbance record 717 Information sub-menu 759
Monitoring sub-menu 719 Security setting sub-menu 760
-Metering 719 Control sub-menu 761
-Binary I/O 719 -DPOS operation 761
-Communication 720
-Relay elements 722
-Statistics 723
-Goose monitoring 724
-Diagnostics 725
Setting sub-menu 726
-Setting method 726
-Confirmation dialog 730
-On/Off 733
- Group setting 733
-Function key 735
I/O setting 739
-Binary input 739
-Binary output 740
-LED 743
Outline
Users can perform maintenance on the IED from the front panel. Monitoring is also possible
locally by using a PC connected through the USB cable. This section discusses the
configuration of the front panel and the basic configuration of the screen-menu hierarchy of
the Human Machine Interface (HMI).
LEDs
LCD screen
Operation keys
Function keys
with LEDs
(iii) LEDs
As shown in Table 12.1-1, 26 LEDs, each having signal labels and colors, are defined:
. N/A N/A ✔ .
. . . . .
. . . . .
. . . . .
26 N/A N/A ✔
1Note: LED3 to LED26 are user-configurable. Users can use them with or without latch
function.
2Note: For setting LEDs, see section 12.6(iii).
†Note: The user can program to light the LEDs by itself. Setting are similar to the ones
of the Table 12.1-1 (For setting, see section 12.6(iii)). Note the manufacture
programs to light the respective LEDs in default prior to shipping.
ENTER Enter edit mode, if item is active / Executive operation / Accept alarm
message.
CLEAR Clear all latched LEDs (Except [In service] and [Error] LEDs).
HELP Display the help message, for cases where the active item has a help
function.
L
R
Switch between Local mode and Remote mode.
MENU Switch for using MIMIC2 mode or for returning back to the menu screen.
MIMIC
This key is not provided for standard LCD screen2.
1Note: To scroll up or scroll down quickly, press keys ▲ or ▼ respectively along with key
►.
2Note: The MIMIC key is only available when Large LCD screen is mounted on the front
panel. The pixel resolution (dot) is 240(W) × 320(H). Note that this mode is only
provided when the user programmed the feature using GR-TIEMS engineering
tool. See chapter Engineering tool: MIMIC configuration tool.
HMI operation
By using the LCD screen, the operation keys and the function keys, the user can access
functions such as recording, monitoring, relay setting and testing.
Note: The operation of the LCD screen is more or less common in all IED models.
However, the contents of the LCD screen depend upon the IED model.
Sub-menu
An example of setting the sub-menu screen is shown in the right of Figure 12.2-1. By
using the key ▼ and the key ▲, the user can move the cursor downward or upward
to view all of the items. By using the keys ◄ ►, the user can return to a previous
level of hierarchy or go to the next level of hierarchy.
Screen structure
The screen is composed of a title area and a data area. The title area is fixed on the
top two lines. The first line displays the screen title. The second line on the left-hand
side displays local time, whereas the right-hand side displays either the current line
number, cursor position number and the maximum page number, or the item number.
For example, the display “2/4” means the current cursor position, which is at the
second item of a maximum of four items.
Figure 12.2-2 shows the menu hierarchy. The menu consists of a Main-Menu and several
Sub-menus. Table 12.2-1 shows the configuration of Main-Menu.
Main Menu Sub-menu Sub-menu Sub-menu Main Menu Sub-menu Sub-menu Sub-menu
Main Menu Record Record List
Main Menu
Fault Record
Clear Records
Event Record1 Record List
Clear Records Setting
Event Record2 Record List
Clear Records Statistics Counter(GCNT01~)
Event Record3 Record List
Clear Records Function Key F1 Key ~ F7 Key
Disturbance Record Record List
Clear Records Diagnostics Detail
Clear All Records
Control
Statistics
Interlock Time Clock ActiveSyncSrc
Total Time
Summer Time
Signal monitoring
Setting Record Fault Record
Event Record
Metering Disturbance Record
Communication LAN
Information
USBCOM
RS485
SLAVE PROTOCOL IEC61850 Security Setting Change Password
IEC61850 IEC103
IEC103 SLV
Security
Record sub-menu
The Record sub-menu is composed of several sub-menus: fault record, event record,
disturbance record, and clearance of all records. In each sub-menu, the user can clear records
separately.
Record
10:48 1/6
_Fault Record >
Event Record1 >
Event Record2 >
Event Record3 >
Disturbance Record >
Clear All Records +
Record
1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Fault Record
2). Fault Record screen is displayed. Press ► at the Record List sub
10:48 1/2 menu.
_Record List >
Clear Records +
Fault Record
3). Fault record list in the Fault Record screen is displayed. Move
10:48 1/6 cursor to a desired item by ▲ or ▼ and press ►.
#1 2012-07-25 >
10:48:21.223
#2 2012-07-21 >
01:15:55.018
#3 2012/07/20 >
13:11:29.621
Fault Record#2
4). Press ▲ or ▼ to move display items.
10:48 1/222
2012-07-21
01:15:55.018
DIFZA
Record
1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Fault Record
2). Move cursor to Clear Records and press ENTER.
10:48 1/2
Record List >
_Clear Records +
Fault Record
3). Clear records if ENTER is pressed. Back to display of “Fault Record”
directly if CANCEL is pressed.
Clear records?
ENTER=Yes CANCEL=No
Record
1). Move cursor to the Clear all Records sub menu and press ENTER.
10:48 1/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
_Clear all Records +
Clear Records
2). Clear all records if ENTER is pressed. Back to display of “Record”
directly if CANCEL is pressed.
Clear All records?
ENTER=Yes CANCEL=No
Event record1
10:48 1/3
#1 2012-07-25
10:48:21.223
Set.Group change
2
#2 2012-07-25
10:20:21.021
Record
1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
10:48 2/6
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Event Record1
2). Event Record screen is displayed. Press ► at the Record List sub
10:48 1/2 menu.
_Record List >
Clear Records +
Event Record1
3). Press ▲ or ▼ to move display items.
10:48 1/3
#1 2012-07-25
10:48:21.223
Set. Group change
2
#2 2012-07-25
10:20:11.021
Record
1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
10:48 2/6
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Event Record1
2). Event Record screen is displayed. Press ENTER at the Clear
10:48 1/2 Records sub menu.
Record List >
_Clear Records +
Event Record1
3). Clear all Event records if ENTER is pressed. Back to display of
Event Record directly if CANCEL is pressed.
Clear records?
ENTER=Yes CANCEL=No
Disturbance record
10:48 1/6
#1 2012-07-25
10:48:04.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621
Record
1). Move cursor to Disturbance Record sub menu and press ►.
10:48 2/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +
Disturbance Record
2). Disturbance Record screen is displayed. Press ► at the Record List
10:48 1/2 sub menu.
_Record List >
Clear Records +
Disturbance Record
3). Press ▲ or ▼ to move display items.
10:48 1/6
#1 2012-07-25
10:48:21.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621
Record
1). Move cursor to Disturbance Record sub menu and press ►.
10:48 2/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +
Disturbance Record
2). Disturbance Record screen is displayed. Press ENTER at the
10:48 1/2 Clear Records sub menu.
Record List >
_Clear Records +
Disturbance Record
3). Clear all Disturbance records if ENTER is pressed. Back to
display of “Disturbance Record” directly if CANCEL is pressed.
Clear records?
ENTER=Yes CANCEL=No
Monitoring sub-menu
“Monitoring” sub-menu is used to display the current status of the IED. The data is updated
every second on the LCD screen. The user can view the following functions from the Monitoring
sub-menu:
i. Metering sub-menu
ii. Binary I/O sub-menu
iii. Communication sub-menu
iv. Relay Elements sub-menu
v. Statistics sub-menu
vi. GOOSE Monitoring sub-menu
vii. Diagnostics sub-menu
(i) Metering
The value and direction of current, voltage etc. can be displayed. The user can change the units
as required by using the appropriate setting. Figure 12.4-1 shows an example of the Metering
sub-menu.
Metering
10:48 1/4
Ida
12.234A
Idb
12.234A
Idc
12.235A
Slot#1
10:48 1/12
BI1 0 CB1 contact
BI2 0 DC power sup.
BI3 0 Trans-T Comm1
BI3 0 Trans-T Comm2
BI4 0 ARC-Block1
BI5 0 Indi. Reset
Figure 12.4-3 shows the steps required to display the status of the binary inputs and outputs.
► ◄
Slot#1 Slot#1
10:48 2/12 10:48 1/12
BI1 0 CB1 contact ▲ BI1 0 CB1 contact
BI2 0 DC power sup. BI2 0 DC power sup.
BI3 0 Trans-T Comm1 BI3 0 Trans-T Comm1
▼
BI3 0 Trans-T Comm2 BI3 0 Trans-T Comm2
BI4 0 ARC-Block1 BI4 0 ARC-Block1
BI5 0 Indi. Reset BI5 0 Indi. Reset
(iii) Communication
The “Communication” sub-menu provides several sub-menus as shown in Figure 12.4-4.
61580STAT
LAN sub-menu: the communication port name and status are shown in a line.
When the IED has single communication module, or when the IED has
communication modules but a communication module is allowed to operate in
the IED, an operation status of the communication ports is shown, as shown
in Figure 12.4-5.
LAN
10:48 1/2
PortStatus >
NetMonitor Inactive
The following two sub-menus are displayed to show the communication status
when the IED has dual LAN communication modules.
PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP
61850STAT
10:48 1/6
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
DIFHZ
10:48 1/12
DIF1-A 0
DIF1-B 0
DIF1-C 0
DIF2-A 0
DIF2-B 0
DIF2-C 0
► ◄
DIFHZ
10:48 1/12
DIF1-A 0
DIF1-B 0
DIF1-C 0
DIF2-A 0
DIF2-B 0
DIF2-C 0
(v) Statistics
“Statistics” sub-menu has several sub-menus.
Operation Counter
Total Time
Counter sub-menu: the name and number of statistical items are shown in
two lines. When an item is revised, a [+] mark is shown at the end of the first
line.
Counter
10:48 1/32
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0
► ◄
CANCEL Counter
ENTER 10:48 1/32
Count1(No Assign) +
0
COUNT2 (No Assign) +
The data has been revised. 1
COUNT3 (No Assign) +
0
Accumulated Time sub-menu: Total time for which the IED has been running
is shown in “d (date) h (hour) m (minute)” format. The user can clear the total
time value by clear operation (reset), which is shown in Figure 12.4-13.
ENTER
GOOSE Monitoring
10:48 1/3
GRx200-11-603 OK
GRx200-21-603 OK
GRx200-31-603 NG
(vii) Diagnostics
Error message will be published in Automatic supervision. If there are no errors, an error
message is not displayed.
Diagnostics
10:48 1/2
PLC data error
>
Data(commslv) error >
Setting sub-menu
"Setting" sub-menu is used to view and change settings for the following functions: Recording,
Metering, Communication interface, Relay application, and Monitoring. In this section, we
show the “Setting method for elements, switches, and list selection”, “Protection setting”, and
others. Furthermore, this section describes the confirmation of setting, and the “On/Off”
function that is used to hide some unnecessary settings.
Note: The meaning of settings and their setting process are beyond the scope of this
section. The figures in this chapter are examples only. The user should confirm
setting values after their values are changed.
Element Setting Mode: The “Element Setting Mode” is used for setting
numerical values. For each setting, the setting name, setting value and the
unit are displayed in two lines. Figure 12.5-1 provides an example of the
element setting mode.
OC1 OC1
10:48 2/8 10:48 2/8
_OC1-b + *OC1-b +
123.00000 124.00000
OC1-c + OC1-c +
1.00000 1.00000
OC1-angle + OC1-angle +
45 deg 45 deg
To begin the setting process, press the key ENTER. Once the setting has been
changed, the [*] mark will appear alongside the name of the setting. Once the
change is canceled or confirmed, the [*] mark will disappear automatically. For
the setting of a value, follow the steps as shown in Figure 12.5-21:
[▲] [▼]
[CANCEL] [CANCEL]
OC1 OC1
OC1
10:48 2/8 10:48 2/8
10:48 2/8
*OC1-b + [▼] *OC1-b + [ENTER] *OC1-b +
124.00000 124.00000
124.00000
_OC1-c + [▲] OC1-c +
OC1-c +
1.00000 1.00000 [ENTER] 1.00000
OC1-angle + OC1-angle +
OC1-angle +
45 deg 45 deg
45 deg
Table 12.5-1 Operation example when the operation keys are pressed.
Before Key After
1 2 6 7 9
1 2 6 8 0
[▲]
9 1 7 1 0 1 7
9 1 7 [▼] 1 0 9 1 7
9 . 1 1 0 9 . 1
6 7 5 6 7 5
[◄]
1 . 7 5 1 . 7 5
2 1 : 2 3 [►] 2 1 : 2 3
Switch Setting Mode: The “Switch Setting Mode” is a setting used for the
selection of two modes. Figure 12.5-3 provides an example of the switch
setting mode. For each setting, the setting name and the selected item are
OC1 OC1
10:48 24/56 10:48 24/56
_OC1-VTFBlk + *OC1-VTFBlk +
Non Block
OC1-UseFor + OC1-UseFor +
Trip Trip
OC1-OPMD + OC1-OPMD +
3POR 3POR
To begin the setting process, press the key ENTER. Once the setting is changed,
the [*] mark will appear alongside the name of the setting. When the change is
canceled or confirmed, the [*] mark will disappear automatically. Figure 12.5-4
shows the operation of the switch setting mode.
[CANCEL]
[ENTER] [ENTER]
OC1 OC1
10:48 24/56 10:48 24/56
*OC1-2fBlk + *OC1-2fBlk +
[▼] Block
Block
_OC1-UseFor + OC1-UseFor +
Trip [▲] Trip
OC1-OPMD + OC1-OPMD +
3POR 3POR
setting-screen, the setting name and the selected item are displayed. Press
the key ENTER to begin the setting process; the screen for selection list will
appear. Once a setting has been changed, the [*] mark will appear alongside
the name of the setting. When the change is canceled or confirmed, the [*]
mark will disappear automatically.
[CANCEL] [ENTER]
OC1 OC1
10:48 23/56 10:48 23/56
*OC1-2fBlk + [▼] *OC1-2fBlk +
Block-3P Block-3P
_OC1-VTFBlk + OC1-VTFBlk +
Non [▲] Non
OC1-UseFor + OC1-UseFor +
Trip Trip
Signal Selection Mode: Figure 12.5-6 shows the steps to select a signal.
[CANCEL] [ENTER]
F1 Key
10:48 1/2
*Signal +
423100 AF00001001
Logic +
Toggle
[►] [◄]
OC OC Trip
10:48 1/4 10:48 1/4 10:48 1/12
*OC1EN +> [ENTER] *OC1EN + [►] *OC >
On On UV >
OC2EN + OC2EN + ZS >
Off [CANCEL] Off [◄] ZG >
OC3EN + OC3EN + EF >
Off Off DIFF >
OC [CANCEL] OC Group1
10:48 1/4 10:48 1/4 10:48 2/3
*OC1EN +> *OC1EN +> [◄] x 2 Telecommunication >
Off Off *Trip >
OC2EN + [ENTER] OC2EN + Autoreclose >
Off Off
[►] x 2
OC3EN + OC3EN +
Off Off
[◄]
Protection Protection
[ENTER]
10:48 3/10 The changed Setting
Active group > Change setting?
is confirmed. ENTER=Yes CANCEL=No
Copy gr.(A->B) >
_Group 1 >
Group 2 > The changed Setting
Group 3 > [CANCEL]
Group 4 >
is canceled.
[►] [◄]
[ENTER] [CANCEL]
IEC61850 Setting
Communication
10:48 1/6 10:48 2/5
*850BLK + [◄] [◄] Change setting?
LAN >
Block ENTER=Yes CANCEL=No
*IEC61850† >
GSECHK + IEC103† >
ON Modbus† >
[►]
SI1-1 + DNP† >
254
Setting [ENTER]
The changed setting is
10:48 3/7
Record > confirmed.
Metering >
_Communication >
Protection > The changed setting is
[CANCEL]
Counter > canceled.
Function key >
“On” indicates that the setting is enabled; the mark [>] will appear. More detail of the
settings provided within the hierarchy are described later.
“Off” indicates that the setting is disabled; the detailed settings are hidden, the mark [>]
is not indicated. The following figure shows the usage of On/Off function.
OC OC OC
10:48 1/4 10:48 1/4
[►] / [◄] /
10:48 1/4
*OC1EN +> [ENTER] *OC1EN +>
[▲] / [▼]
*OC1EN +
On On Off
OC2EN + OC2EN + OC2EN +
Off [CANCEL] Off [►] / [◄] / Off
OC3EN + OC3EN + [▲] / [▼] OC3EN +
Off Off Off
[ENTER]
Protection OC
10:48 1/4
[ENTER] Change setting? *OC1EN +
The changed ENTER=Yes CANCEL=No Off
setting is confirmed. [◄] x 3
OC2EN +
Off
OC3EN +
Off
Protection OC
10:48 3/10 10:48 1/4
Active group > *OC1EN +
Copy gr.(A->B) >
Return to the “OC” Off
_Group 1 > setting screen. OC2EN +
Group 2 > Off
Group 3 > OC3EN +
Group 4 > Off
operation of the power system. In the “Protection” sub-menu, the user can change the active
group and can copy the group settings. Jump to the “Element Setting Menu” if a relay setting
is required.
Change active group: An example for changing the active group is shown in
the following figure.
[▲] x 2 [▼] x 2
Protection
Protection
10:48 5/11
Common
Change Setting? [ENTER]
ENTER=Yes CANCEL=No Active Group +
1
Copy Group (A->B) >
Group 1 >
Group 2 >
[ENTER]
Protection
10:48 1/10
Common
The changed [►]
Active Group >
setting is confirmed. Copy Group(A->B) >
Group 1 >
Group 2 >
Group 3 >
Copy group setting: The user can copy an active setting from one group to
another group. As an example, in the following figure “Group3” will be copied
to “Group2”, as shown in Figure 12.5-12.
Note: In the “Copy Group (A->B)” screen, the number displayed at A is the current active
group number.
[ENTER]
[◄]
Protection
Protection
10:48 1/11
Common
Active Group >
1
Copy Group(A->B) >
Group 1 >
Group 2 >
Change group settings: Upon shipment from the factory, the default settings
are set. Therefore, in each group, the user can change the settings of the
protection functions and other features. To change the settings in each group,
refer to the setting method discussed in section 12.5(i).
programmed using settings. Six screens are configured for six of the function keys (F1 to F6),
respectively, as the default settings shown in Table 5.6-3.
Screen jump function: To configure the screen jump function, follow the steps
as shown in the figure below.
Function Key F1 Key F1 Key Function
10:48 1/7 10:48 1/3 10:48 3/3
F1 Key > [►] *Function + [ENTER] Screen Jump
F2 Key > No Assign Assign Signal
F3 Key > Signal + _No Assign
[◄] [CANCEL]
F4 Key > No Assign
F5 Key > Logic
F6 Key > Instant +
[ ]x2 [▼] x 2
[ENTER]
[An Example]
OC F1 Key
The “Screen Jump”
10:48 1/4 Push [F1]
setting is _OC1EN +> for 3s. Register this screen
On to F1 Key?
confirmed. Do the
OC2EN +> ENTER=Yes CANCEL=No
next step to select On
OC3EN +
a screen.
Off
[ENTER]
The selected screen is assigned to [F1].
On any screen, press the screen-jump function key to display a screen, refer to the
following figure:
Main Menu OC
10:48 2/8 10:48 1/4
Record > [F1] _OC1EN +>
_Monitoring > On
Setting > OC2EN +>
IO setting >
[F1] On
Time > OC3EN +
Test > Off
To cancel the screen-jump function, follow the procedure provided in Figure 12.5-15.
Note: 1) Once a screen is configured to a function key, it will not be deleted until a new
screen is configured for the same function key.
2) If a configured screen is disabled by “On/Off Function” setting (refer to section
12.5(iii)), the screen jump function is also disabled for the function key.
[▼] x 2 [▲] x 2
[ENTER]
The “Screen Jump” function is
canceled on F1 key.
Signal control function: To assign a test signal to a function key, follow the
steps as shown in Figure 12.5-16.
[▲] [▼]
[ENTER]
[ENTER]
Setting F1 Key
[ENTER] [◄] x 2 10:48 1/3
The changed Change Setting? *Signal +
ENTER=Yes CANCEL=No
setting is confirmed. 123101AF00003001
Logic +
Instant
The user can activate or turn off the above timers and switches using the setting function.
To configure the binary input circuits, the user should follow the procedure in steps ((i)-1 and
(i)-2)
Selection of binary input circuit: For example, Figure 12.6-1 illustrates the
selection of a binary input circuit on a binary IO module. Move the cursor by
pressing keys ▲ and ▼. Then, press key ►to go to the next hierarchy.
Common
10:48 1/2
Thres_Level +
Low
Cmp_Num +
4
For example, Figure 12.6-3 shows the CPL setting for binary input circuit (BI1).
The timer and the inverse switch can be activated when On is set for setting
[BI1_CPL]. Press key ENTER to commence the setting of a switch or parameter.
BI1
10:48 1/2
BI1_CPL +
Off
On Delay Timer +
0.000 s
Off Delay Timer +
0.000 s
SW
Inverse-SW +
Normal
Selection of binary output circuit: For example, Figure 12.6-4 illustrates the
selection of a binary output circuit on a binary IO module. Move the cursor by
pressing keys ▲ and ▼. Press key ► to go to the next level in the hierarchy.
CPL Setting: For example, Figure 12.6-5 illustrates the setting of a binary
output circuit (BO1). Using setting [BI1_CPL] On, the CPL logic in BO1 is
available. Similarly, assigned signals, timers and switches can be set in this
menu. Note that detailed setting items are shown when On is keyed into
setting [BI*_CPL].
BO1
10:48 1/17
BO1_CPL +
Off
Input signal1 +
No Assign
Input Signal2 +
No Assign
Input Signal3 +
No Assign
Signal8 +
No Assign
LOGIC-SW
AND
On Delay Timer +
0.000 s
Off Delay Timer +
0.000 s
INVERSE-SW +
Normal
TIMER-SW +
Off
Logic Timer +
0.000 s
FF-SW +
Off
Reset Signal +
No Assign
[►] [CANCEL]
Select Element
10:48 2/155
No Assign
_CO-OC-A 8000001B60
CO-OC-B 8100001B61
CO-OC-C 8200001B62
CO-EF 8300001B63
EXT.ARC_S 8300001B64
Selection of LED: Figure 12.6-7 shows the LED selection screen; the user can
select a setting item by pressing keys ▲ and ▼. Press key ► to go to the next
level in the hierarchy.
LED
10:48 1/31
_LED3 >
LED4 >
LED5 >
LED6 >
LED7 >
LED8 >
LED26 >
F1 Key >
F2 Key >
:
Figure 12.6-7 LED selecting screen
LED Setting: As shown in Figure 12.6-8, the user can set the logical gate, timer,
color of LED and assign signals in this screen.
LED3
10:48 1/16
Color >
RED
Input signal1 +
No assign
Input signal 2 +
No assign
Input signal 8 +
No assign
Reset signal +
No assign
LOGIC-SW +
AND
INVERSE-SW +
Normal
TIMER-SW +
Off
On Delay Timer +
0.00 s
Off Delay Timer +
0.00 s
Logic Timer +
0.00 s
Color +
Figure 12.6-8 LED setting screen
Time sub-menu
In Time sub-menu, the user can change settings of Clock function, such as time zone, time
synchronizing source, format of time displaying and so on. Figure below shows the Time sub-
menu. (For more information, see Chapter Technical description: Clock function)
Time
10:48 1/5
Clock >
Time Zone >
Time Sync >
Display Format >
Summer Time >
Time menu
(1) Move cursor to the Time menu and press ENTER.
Clock
10:00 1/2
_[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] >
SNTP
ActiveSyncSrc menu
ActiveSyncSrc can be shown by the following procedure.
(1) Move cursor to the [ActiveSyncSrc] menu and press ►.
Clock
10:00 1/2 *Note: When the active synchronizing source is not SNTP, the > is
[Time] +
2012-11-21 10:00:05 not shown in the screen.
[Format]
YYYY-MM-DD HH:mm:ss
_[ActiveSyncSrc] >
SNTP
Time Zone
10:48 1/1
Time zone +
0.00hour
(1) Move cursor to the Time zone menu and press ENTER.
Time Zone
10:48 1/1 Time zone can be set by 0.25 hour. The user has to fill the Time zone
_Time zone +
0.00hour in accordance with UTC (Coordinate Universal Time).
Time Sync
10:48 1/3
TimeSyncSrc +
SNTP
SNTP +>
On
BI SYNC +>
Off
IRIG SYNC +>
Off
TimeSyncSrc menu
Time SyncSrc (Time Synchronization Source) can be changed by the following procedure.
Time Sync
10:48 1/3 (1) Move cursor to the TimeSyncSrc menu and press ENTER.
_TimeSyncSrc +
SNTP
SNTP +>
On
BI SYNC +>
Off
By using time synchronization via Ethernet with a SNTP server, the user can connect up
to a maximum of four SNTP servers. If more than one SNTP is used, the priority of the servers
can be decided in ascending order of synchronized stratum value (in order of higher-accuracy)
and select the server with the smallest value.
SNTP menu
IP address of SNTP server can be set by the following procedure.
(1) Confirm that the SNTP synchronization function has been set for
Time Sync
10:48 1/3 On. Subsequently move cursor to the SNTP menu and press ►.
TimeSyncSrc +
SNTP
_SNTP +>
On
BI SYNC +>
Off
SNTP (2) Move cursor to desired server number and press ENTER.
10:48 1/4
_Server1 +
0. 0. 0. 0
Server2 +
0. 0. 0. 0
Server3 +
0. 0. 0. 0
SNTP (3) The user can set IP address using ▲ or ▼ by each digit.
10:48 1/4 When the user has finished setting IP address of the server, press
Server1 +
0. 0. 0.176 ENTER.
Server2 +
0. 0. 0. 0
Server3 +
0. 0. 0. 0
BI SYNC menu
When the “BI SYNC” is set to On in Time Sync menu, the user can choose a binary input circuit
(BI) as a synchronization standard. Adjustment setting ‘SYNC_ADJ’ is provided.
Binary synchronization function can be set by the following procedure.
Display Format
10:48 1/4
Date_fmt +
YYYYMMDD
Date_delimiter +
-
Time_delimiter +
:
Date_delimiter
10:48 1/3 (2) Date delimiter can be selected by moving cursor to the desired
_-
/ format type.
.
Display Format
10:48 3/4 (2) The time delimiter mark is switched.
Date_fmt +
YYYYMMDD
Date_delimiter +
-
_Time_delimiter +
.
Summer Time
10:48 1/13
Summer time +
Off
Summer Time (1) Move cursor to the [Summer time] menu and press ENTER.
10:48 1/13 Summer time mode can be switched On/Off by pressing ► or ◄.
_Summer time +
Off After Summer time mode is set to On, the user can set summer time
in detail.
Summer Time (2) In this screen, details of summer time setting can be set.
10:48 1/9
IS_UTC_base +
On
Start_Month +
3
Start_Week +
5
The user can set the starting date and ending of summer time. The following procedure is a
case of starting weekday setting.
Summer Time (1) Move cursor to the [Start_Wday] menu and press ►.
10:48 4/9
Start_Month +
3
Start_Week +
5
_Start_Wday +
Sun
Start_SM(Wday)
(2) Move cursor to the desired weekday and press ENTER.
10:48
1/8
---
_Sun
Mon
Tue
Wed
Test sub-menu
Test functions can be operated from the test screen available on the front panel of the IED.
(i) Test screen
The Test screen has functions such as Test Mode, Test Flag, Mode Change and Signal
Monitoring. The user can select any of these test functions using the following test screen.
Test
10:48 1/4
Test Mode +
Off
TestFlag-EN +
On
Mode Change >
Single Monitoring >
Test Mode
10:48 1/4
Test Option >
Function Test >
Binary Input >
Binary Output >
Test Option
10:48 1/65
S-TestFlagCancel +
Off
GOSNDBLK +
Off
GOSUBBLK +
Off
Note: The user may perform bad reception tests from a remote terminal using the
GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid that the user can simulate bad reception tests for a particular IED using the
GOSUBBLK function. As a result, testing will only affect the particular IED
under test i.e. all other terminals will not be influenced by the tests.
Function test screen: Function test screen is provided for testing; the use can
program test operations, which can be implemented in protection and control
functions. Figure 12.8-4 exemplifies the Test screen. Automatic supervision
will stop when the user sets Off for A.M.F (for more information about the
automatic supervision, see Chapter Automatic supervision). The function of
the cold load protection will operate for the test if either CL or Non-CL is set
for CL-TEST (for more information, see Chapter Relay application).
Function Test
10:48 1/2
A.M.F. +
On
CL-TEST +
Off
Binary input test screen: The user can have a virtual signal to a binary input
circuit using the binary input test screen. Figure 12.8-5 shows an example;
the user can select IO#1 or IO#3. (Actually, the content displayed will differ
depending upon the binary IO module inserted. Refer to Chapter Technical
description: Binary IO Module)
Binary Input
10:48 1/2
Slot#1 >
Slot#3 >
Slot#3
10:48 1/19
BIF OP +
Slot3-BIO1-SET +
Normal
Slot3-BIO2-SET +
Normal
Slot3-BI03-SET +
Slot3-BIO1-SET
10:48 1/3
Normal
Off
On
The user can then make the following selections on the screen and configure the
items required for simulation.
ON: BI1 output is set forcibly to ON(Logic level=high(1)) regardless of
the actual input signal.
OFF: BI1 output is set forcibly to OFF(Logic level=low(0)) regardless of
the actual input signal.
Normal: Actual inputs are applied.
Use the screen shown in Figure 12.8-7 only to configure the BI signals for the
simulation test. This does not start the simulation.
The setting menu is shown in the manner of the screen illustrated in Figure 12.8-7,
if the user needs to configure an Input Circuit other than BI01 (BI02 to BI18 in the
screen shown in Figure 12.8-6); the user can configure each BI signal in a manner
similar to that described for BI01.
After selecting OP in Figure 12.8-6, use the following screen to start the simulation
test.
Slot#3
10:48
Press and hold ENTER
to operate
Press <- to return
To previous page
Slot#3
10:48
Press and hold ENTER
to operate
Operating..
Binary output test screen: The user is able to test a binary output circuit.
Figure 12.8-10 is an example of how to select a binary output from the Test
Mode screen.
Binary Output
10:48 1/2
Slot#2 >
Slot#3 >
Slot#2
10:48 1/19
BO2F OP +
SLOT2-BO01-SET +
Normal
SLOT2-BO02-SET +
Normal
SLOT2-BO02-SET +
Figure 12.8-12 shows the Output Circuit configuration of BO01 at IO#2 (Slot#2).
The procedure for operation is similar to the operation of the binary input circuit.
(Refer to Figure 12.8-7 to Figure 12.8-9)
SLOT2-BO01-SET
10:48 1/3
Normal
Off
On
The user can configure the required settings for the simulation test of the binary
output circuit.
ON: Output signal for simulation test is ON
OFF: Output signal for simulation test is OFF
Normal: Actual inputs are applied.
Mode Change
10:48 1/3
MDCTRL-EN +
Off
MDCTRL-SELRST +
30 s
MDCTRL-EXERST +
30 s
Signal Monitoring
10:48 1/3
Term A +
No Assign
Term B +
No Assign
Term C +
No Assign
When the user wishes to use monitoring jack A to monitor a signal-monitoring point,
select “Term A” in the signal monitoring sub-menu (Figure 12.8-15). The user can then assign
the signal monitoring point for Term A.
10:48 1/3
Input signal +
No Assign
Information sub-menu
In the information sub-menu, the user can see the information about the IED. Those of the
information are set in a factory. Figure 12.9-1 shows the Information sub-menu. Table 12.9-1
shows detail of information that is displayed in this screen.
Information
10:48 1/9
[IED TYPE]
GRH200 __-11-111-22-33-
44-555
__-6666-777-88
[Serial No.]
View ✔ ✔ ✔ ✔ ✔
to operate F2 ✔ ✔ ✔ ✔ ✔
F3 ✔ ✔ ✔ ✔ ✔
F4 ✔ ✔ ✔ ✔ ✔
F5 ✔ ✔ ✔ ✔ ✔
F6 ✔ ✔ ✔ ✔ ✔
F7 ✔ ✔ ✔ ✔ ✔
Note: Sign “✔” shows that the user can operate the function. Sign “N.A” shows that the user
cannot operate the function. Password can be changed in Change-Password sub-menu in
Control sub-menu
The user can control external devices using the IED front panel. Control sub-menus are
provided to operate; the user can operate the devices by pressing Operation keys. Note that
Control sub-menus are only available when the IED is in “LOCAL” mode†. When the IED is in
“REMOTE” mode, an error message will be shown on the screen. Remember that the IED will
change to “REMOTE” mode if there is no operation for a while; then the IED can be monitored
remotely. Figure 12.11-1 shows “Control” sub-menu.
Control
10:48 1/5
_SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
Table 12.11-1 shows how to operate by the IED front panel. The IED can have several
control functions, which are dependent on the ordering code. For more information, see
Chapter Control and monitoring application or Appendix: Ordering for more information).
Control
10:48 1/5
_SPOS >
Double DIR mode
DPOS >
TPOS >
responses?
Software Switch >
Auto Sequence > SBO mode
Executing screen
[ ] [ ] [ ] [ ] [ ]
─────────────────────────────────────────────────────────────────
For rack mounting, cable and electrical wiring, see a separate service manual entitled
Installation handbook for rack mounting, cable work, etc. (Document No. 6F2S1954).
See a service manual entitled Guide for replacement of inner modules depending on the
situation. (Document No. 6F2S1955 or 6F2S1956).
Handling precautions
Modules of the IED should be handled in the electro static charge free environment. That is,
the user shall use an anti-electrostatic-wrist-band; and it is grounded.
CAUTION
Before removing a module, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
Handle the module by its front plate, frame or edges of the printed circuit board. Avoid
touching the electronic components, printed circuit board or connectors.
Place the module on an anti-static surface, or on a conducting surface connected to
the earth.
You have to check carefully the electronic circuitry for your handling area, which is defined in
the IEC 60747 standard.
Ordering positions
7 8 9 A B C D E F G H J K L
- 9 1 - 2 1 3 - 0 0 - 9 T - 3 0 - 11 0
Ordering positions
7 8 9 A B C D E F G H J K L
- 9 1 - 2 1 3 - 0 0 - 9 T - 3 0 - 1 1 0
VCT39B
System
frequency (fn) = 50Hz
AC rating (In) = 1A
The user can check the layout of the binary input and output modules (BI, BO, or BIO)
using the ordering codes. For example, the user can find a BIO3A module in the IED when the
ordering cord “13” is printed at Positions A&B. The user can the IO configuration label
depending on the “13”. The user can check terminal block types by seeing a code at Positon ‘H’.
- 9 1 - 2 1 3 - 0 0 - 9 T - 3 0 - 1 1 0
Positions
7 S G T E F U 9 V
- 9 0 3 1 - 9 T 2 - 1 E
GRH200- --
Selected language
Selected protocol
Selected software
Flange covers
Rack mounting type: flanges have to be screwed and fixed on the case, and countersunk screws
are provided for them. When wishing to place the IED case in a 19-inch rack, put white-
plastics-sheets on the countersunk screws to cover up (see Figure 13.3-6); they are bundled in
its package. Detach the flange from the case if combining cases is required with a mounting
kit. Remind that the user needs to put the white-plastic-sheet over the countersunk screws on
each side.
Left silver-flange Right silver-flange
White White
plastic Countersunk plastic
sheet Relay case sheet
screws
Figure 13.3-6 Covering the screw holes with white plastic sheets
Note: For more information about how to mount a case in a rack, see Installation
handbook for rack mounting, cable work, etc. (6F2S1954). The user can get a
mounting kit by ordering (see Appendix: Ordering).
Flush-mounting type: flanges are integrated at the both sides of the case. Thus, the white-
plastics-sheets are not bundled.
- x 1 - x x x - x x - x x - x x - x x x
CAUTION
Note: A short-wire is connected between terminal screws No. 35–37 ( No.35–36 for type
using the ring terminal). It is done by the manufacturer. The user shall remove
that when the user undertakes the dielectric voltage test for the IED; and the user
shall connect again the terminals with that after the test (See Appendix: Notes for
the dielectric voltage test).
29 28
27
30
29 30
31
32 31 32
33
33 34
Short wire 34
35 35 36
36 38
FG
37
38
39
40 Short wire
FG FG
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by monitoring
which circuits functions when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests
These tests are performed for the following functions that are fully software-based. Tests of the
protection schemes and fault locator require a dynamic test set.
Measuring elements
Timers
Protection schemes
Metering and recording
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment,
telecommunication equipment and other external equipment.
The following tests are included in these tests:
On load test: phase sequence check and polarity check
Signaling circuit test
Cautions
(i) Safety Precautions
CAUTION
The IED rack is provided with a grounding terminal.
Before starting the work, always make sure the IED rack is grounded.
When connecting the cable to the back of the IED, firmly fix it to the terminal block
and attach the cover provided on top of it.
Before checking the interior of the IED, be sure to turn off the power.
Class 1 laser.
Failure to observe any of the precautions above may cause electric shock or malfunction.
Failure to observe any of the precautions above may cause damage or malfunction of the relay.
Before mounting/dismounting the PCB, take antistatic measures such as wearing an earthed
wristband.
Preparations
Test equipment
The following test equipment is required for the commissioning tests.
2 Single-phase current sources
1 Dynamic three-phase test set (for protection scheme test)
1 DC power supply
3 DC voltmeters
3 AC voltmeters
3 Phase angle meters
2 AC ammeters
1 Time counter, precision timer
1 PC (not essential)
Relay settings
Before starting the tests, it must be specified whether the tests will use the user’s settings or
the default settings.
Visual inspection
After unpacking the product, check for any damage to the IED case. If there is any damage,
the internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the IED conform to the user’s
specification. The items are: relay type and model, AC current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC
To examine the IED with a PC locally, connect the PC with the IED using a USB cable. The
GR-TIEMS software is required to install in the PC.
During commissioning and maintenance, check wire connection and observe relay output
signals. The user can see the signals whether the relay operations are appropriate or not.
Test operations
The user can change IED to for Test mode by the operations on the IED front panel with
Main/Sub menus, as shown in Figure 14.4-1.
Information
Security Setting
Login/Logout
Setting
Setting of TEST (Function ID: 201301)
Setting items Range Unit Contents Default Note
CL-TEST Off / CL / Non-CL Forcibly establishing the cold load condition Off
Signal
Signal monitoring point
TEST (Function ID: 201301)
Element ID Name Description
3100051197 SIM FAULT OUTPUT for Sim.Fault Display
C100_S8 2000641120 Constant value 100 expressed with signed integer in 8 bit
C100_S16 2100641121 Constant value 100 expressed with signed integer in 16 bit
C100_U16 3100641125 Constant value 100 expressed with unsigned integer in 16 bit
C100_U32 3200641126 Constant value 100 expressed with unsigned integer in 32 bit
229.3
265.9
260.7
190.5
260.7
242 229.3 (64.4)
255 256.3
† The (64.4) means the height of
the tallest ring type terminal.
Unit: mm
Unit: mm
Panel cutout
Unit: mm
1.1. 1/2 case size for type using compression terminal (BIO3A × 2 plus RS485 and IRIG-B)
23 23
BO2(F)
24
BO2(F)
24
C14
25 25
BO3(F) BO3(F)
26 26
27 27
BO4(F) BO4(F)
28 28
(+) 29
29 29
30
DC/DC BO5(F) BO5(F)
30 30
(-) 31 31 31 C15
32 BO6(F) BO6(F) IRIG-B000
32 32 30
A1
35
33 33 B1
SIG
36
BO7 BO7 A2
34 34 DISUSE
37 B2
DISUSE
38 35 35
A3
37 37
B3
GND
36 36
BO8 BO8
38 38
GRH-A (0.1)
1.2. 1/2 case size for type using ring terminal (BIO3A+BO1A plus RS485 and IRIG-B)
(-) 16
BI8 BO8
16 16
Ide
17
BO9
18
21 21
BO1(F) BO10
22 22
23 23
BO2(F)
24
BO11
24
C14
Remote
25 25 communication
BO3(F) BO12
26 26
27 27
BO4(F) BO13
28 28
(+) 29 TX
29 29
30
DC/DC BO5(F) BO14
30 30
(-) 31 31 31 C15
32 BO6(F) BO15 IRIG-B000
32 32 30
A1
35
33 33 B1
36 SIG
BO7 BO16 A2
34 34 DISUSE
37
B2
DISUSE
38 35 35
A3
37 BO17
36 B3
GND
36
BO8 37
38 BO18
38
GRH-A (0.1)
1.3 Example for three phases protection regarding the busbar protection
(GRH200-91-213-00-9T-30-110)
Busbar
A
B
C
BIO3A
21
BO1(F) Trip comand1
22
23
Trip1~3 Varistor units VCT39B
BO2(F) Trip comand2
VCT1-9 24
CT
10 I 25
da Trip comand3
BO3(F)
26
(F)
27
11 BO4(F) 28
12 I
db 29
BO5(F) 30
(F)
13 31
14 I BO6(F)
dc 32
33
Line1 Line2 Line3 BO7 34
I
de
35
BIO3A
36
1 37
BO8
Programmable BI 2 BI1
3 38
4 BI2
5
Ethernet LAN I/F
6 BI3
7
8 BI4
9
Remote Comm
10 BI5 (IEC103)
11
COM
12 BI6
13
14 BI7 SIG A1
B1
15 DISUSE A2
B2 IRIG-B
16 BI8 A3
GND B3
PWS1
A
RELAY 2
1
FAIL.
DD FAIL. 4
DC (+) 29
30 +5Vdc 3
SUPPLY FAIL
31 Fail1
(-) 32 DC-DC 1
0V
8
35
36 10
37
Note: A dashed line is added when 9
38 FAIL Fail2
DC rated voltage is 24-60Vdc.
FG 7
E
Figure 3-1 External connection using VCT39B (Ch5,6,7), BIO3A for Type using compression
terminals
1.4 Example of single phase protection regarding the restricted earth fault protection
(GRH200-91-213-00-9T-30-110)
BIO3A
Trip1 ~ 3
VCT39B 21
Transformer BO1(F) Trip comand1
22
A VCT
23
9 Trip comand2
BO2(F)
B 10 I 24
da
11 25
I BO3(F) Trip comand3
C 12 db 26
13 (F)
I 27
14 dc BO4(F) 28
Varistor units
15 29
16 I BO5(F) 30
de
(F)
31
BO6(F) 32
33
BO7 34
BIO3A 35
36
1 37
BO8
Programmable BI 2 BI1
3 38
4 BI2
5
Ethernet LAN I/F
6 BI3
7
8 BI4
9
Remote Comm
10 BI5 (IEC103)
11
COM
12 BI6
13
14 BI7 SIG A1
B1
15 DISUSE A2
B2 IRIG-B
16 BI8 A3
GND B3
PWS1
A
RELAY 2
1
FAIL.
DD FAIL. 4
DC (+) 29
30 +5Vdc 3
SUPPLY FAIL
31 Fail1
(-) 32 DC-DC 1
0V
8
35
36 10
37
Note: A dash line is added when 9
38 FAIL Fail2
the rated voltage is 24-60Vdc.
FG 7
E
Figure 3-2 External connection using VCT39B (Ch8), BIO3A for Type using compression
terminals
(MICS Edition 1)
(MICS Ed.1)
The GRH200 with communication firmware G2M850-01 series version upper than E(G2M850-01-E) supports IEC
61850 logical nodes and common data classes as indicated in the following tables.
Logical nodes in IEC 61850-7-4
Logical Nodes GRH200 Nodes GRH200
L: System Logical Nodes GGIO_GOOSE Yes
LPHD Yes GSAL ---
Common Logical Node Yes I: Logical Nodes for Interfacing and archiving
LLN0 Yes IARC ---
P: Logical Nodes for Protection functions IHMI ---
PDIF Yes ITCI ---
PDIR --- ITMI ---
PDIS --- A: Logical Nodes for Automatic control
PDOP --- ANCR ---
PDUP --- ARCO ---
PFRC --- ATCC ---
PHAR --- AVCO ---
PHIZ --- M: Logical Nodes for Metering and measurement
PIOC --- MDIF ---
PMRI --- MHAI ---
PMSS --- MHAN ---
POPE --- MMTR ---
PPAM --- MMXN ---
PSCH --- MMXU ---
PSDE --- MSQI ---
PTEF --- MSTA ---
PTOC --- S: Logical Nodes for Sensors and monitoring
PTOF --- SARC ---
PTOV --- SIMG ---
PTRC Yes SIML ---
PTTR --- SPDC ---
PTUC --- X: Logical Nodes for Switchgear
PTUV --- XCBR ---
PUPF --- XSWI ---
PTUF --- T: Logical Nodes for Instrument transformers
PVOC --- TCTR ---
PVPH --- TVTR ---
PZSU --- Y: Logical Nodes for Power transformers
R: Logical Nodes for protection related functions YEFN ---
RDRE --- YLTC ---
RADR --- YPSH ---
RBDR --- YPTR ---
RDRS --- Z: Logical Nodes for Further power system equipment
RBRF --- ZAXN ---
RDIR --- ZBAT ---
RFLO --- ZCAB ---
RPSB --- ZCAP ---
RREC --- ZCON ---
RSYN --- ZGEN ---
C: Logical Nodes for Control ZGIL ---
CALH --- ZLIN ---
CCGR --- ZMOT ---
CILO --- ZREA ---
CPOW --- ZRRC ---
CSWI --- ZSAR ---
G: Logical Nodes for Generic references ZTCF ---
GAPC --- ZTCR ---
GGIO Yes
(MICS Ed.1)
Common data classes in IEC61850-7-3
Common data classes GRH200
Status information
SPS Yes
DPS ---
INS Yes
ACT ---
ACT_ABC Yes
ACD ---
ACD_ABC Yes
SEC ---
BCR ---
Measured information
MV ---
CMV ---
SAV ---
WYE ---
WYE_ABCN Yes
DEL ---
SEQ Yes
HMV ---
HWYE ---
HDEL ---
Controllable status information
SPC Yes
DPC ---
INC Yes
BSC ---
ISC ---
Controllable analogue information
APC ---
Status settings
SPG ---
ING Yes
Analogue settings
ASG Yes
CURVE ---
Description information
DPL Yes
LPL Yes
CSD ---
(MICS Ed.1)
LPHD class
Attribute Name Attr. Type Explanation T M/O GRH200
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
PhyName DPL Physical device name plate M Y
PhyHealth INS Physical device health M Y
OutOv SPS Output communications buffer overflow O N
Proxy SPS Indicates if this LN is a proxy M Y
InOv SPS Input communications buffer overflow O N
NumPwrUp INS Number of Power ups O N
WrmStr INS Number of Warm Starts O N
WacTrg INS Number of watchdog device resets detected O N
PwrUp SPS Power Up detected O N
PwrDn SPS Power Down detected O N
PwrSupAlm SPS External power supply alarm O N
RsStat SPC Reset device statistics T O N
LLNO class
Attribute Name Attr. Type Explanation T M/O GRH200
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation for complete logical device O Y
OpTmh INS Operation time O N
Controls
Diag SPC Run Diagnostics O Y
LEDRs SPC LED reset T O Y
(MICS Ed.1)
GGIO class
Attribute Name Attr. Type Explanation T M/O GRH200
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind01 SPS General indication (binary input) O Y
Ind02 SPS General indication (binary input) O Y
Ind03 SPS General indication (binary input) O Y
Ind04 SPS General indication (binary input) O Y
Ind05 SPS General indication (binary input) O Y
Ind06 SPS General indication (binary input) O Y
Ind07 SPS General indication (binary input) O Y
Ind08 SPS General indication (binary input) O Y
Ind09 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
:
:
:
Ind64 SPS General indication (binary input) O Y
(MICS Ed.1)
GGIO_GOOSE class
Attribute Name Attr. Type Explanation T M/O GRH200
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind01 SPS General indication (binary input) O Y
Ind02 SPS General indication (binary input) O Y
Ind03 SPS General indication (binary input) O Y
Ind04 SPS General indication (binary input) O Y
Ind05 SPS General indication (binary input) O Y
Ind06 SPS General indication (binary input) O Y
Ind07 SPS General indication (binary input) O Y
Ind08 SPS General indication (binary input) O Y
Ind09 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
Ind11 SPS General indication (binary input) O Y
Ind12 SPS General indication (binary input) O Y
Ind13 SPS General indication (binary input) O Y
Ind14 SPS General indication (binary input) O Y
Ind15 SPS General indication (binary input) O Y
Ind16 SPS General indication (binary input) O Y
(MICS Ed.1)
SPS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal BOOLEAN ST dchg TRUE | FALSE M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV TRUE | FALSE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
INS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal INT32 ST dchg M Y(*1)
q Quality ST qchg M Y
t TimeStamp ST M Y
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
(MICS Ed.1)
ACT_ABC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
phsA BOOLEAN ST dchg O Y
phsB BOOLEAN ST dchg O Y
phsC BOOLEAN ST dchg O Y
neut BOOLEAN ST dchg O N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
operTm TimeStamp CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
ACD_ABC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
dirGeneral ENUMERATED ST dchg unknown | forward | backward | both M Y
phsA BOOLEAN ST dchg GC_2 (1) Y
dirPhsA ENUMERATED ST dchg unknown | forward | backward GC_2 (1) Y
phsB BOOLEAN ST dchg GC_2 (2) Y
dirPhsB ENUMERATED ST dchg unknown | forward | backward GC_2 (2) Y
phsC BOOLEAN ST dchg GC_2 (3) Y
dirPhsC ENUMERATED ST dchg unknown | forward | backward GC_2 (3) Y
neut BOOLEAN ST dchg GC_2 (4) N
dirNeut ENUMERATED ST dchg unknown | forward | backward GC_2 (4) N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
(MICS Ed.1)
WYE_ABCN class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsA CMV GC_1 Y
phsB CMV GC_1 Y
phsC CMV GC_1 Y
neut CMV GC_1 Y
net CMV GC_1 N
res CMV GC_1 N
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | Vbc | Vca | O N
Vother | Aother
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
SEQ class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
c1 CMV M Y
c2 CMV M Y
c3 CMV M Y
DataAttribute
measured attributes
seqT ENUMERATED MX pos-neg-zero | dir-quad-zero M Y
configuration, description and extension
phsRef ENUMERATED CF A|B|C|… O N
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
(MICS Ed.1)
SPC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator_RO CO, ST AC_CO_O Y
ctlNum INT8U_RO CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_M N
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
stVal BOOLEAN ST dchg FALSE | TRUE AC_ST Y
Q Quality ST qchg AC_ST Y
T TimeStamp ST AC_ST Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31
(MICS Ed.1)
INC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal INT32 CO AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O N
ctlNum INT8U CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M N
Cancel Cancel CO AC_CO_SBO_N_M N
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
stVal INT32 ST dchg M Y
Q Quality ST qchg M Y
T TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31
(MICS Ed.1)
ING class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setVal INT32 SP AC_NSG_M Y(*3)
setVal INT32 SG, SE AC_SG_M N
configuration, description and extension
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 39
(*3): “ENUM” type is also used.
ASG class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setMag AnalogueValue SP AC_NSG_M Y
setMag AnalogueValue SG, SE AC_SG_M N
configuration, description and extension
units Unit CF see Annex A O Y
sVC ScaledValueConfig CF AC_SCAV Y
minVal AnalogueValue CF O N
maxVal AnalogueValue CF O N
stepSize AnalogueValue CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 42
(MICS Ed.1)
DPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
hwRev VISIBLE STRING255 DC O N
swRev VISIBLE STRING255 DC O Y
serNum VISIBLE STRING255 DC O N
model VISIBLE STRING255 DC O Y
location VISIBLE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45
LPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRH200
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
swRev VISIBLE STRING255 DC M Y
d VISIBLE STRING255 DC M Y
dU UNICODE STRING255 DC O N
configRev VISIBLE STRING255 DC AC_LN0_M Y
ldNs VISIBLE STRING255 EX shall be included in LLN0 only; AC_LN0_EX N
for example "IEC 61850-7-4:2003"
lnNs VISIBLE STRING255 EX AC_DLD_M N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45
(PICS Ed.1&Ed.2)
Introduction
The template of this document is “Protocol Implementation Conformance Statement for the
IEC 61850 interface in <device>” version 1.6 published by UCA International Users Group in
Nov 19, 2015.
This document specifies the Protocol Implementation Conformance Statement (PICS) of the
IEC 61850 interface in G2 series IED with communication firmware G2M850-01 series version
equal to or upper than F (G2M850-01-F). Each tables of this document is specified in IEC 61850-
7-2 Annex A.3 “ACSI models conformance statement”.
— ASCI basic conformance statement,
— ACSI models conformance statement,
— ACSI service conformance statement
Together with the MICS and the PIXIT, the PICS forms the basis for a conformance test
according to IEC 61850-10.
Note: Term “Ed” is mentioning the edition number of IEC 61850. Editon2 (Ed2) provides
backward compatibility for legacy Edition 1 (Ed1).
(PICS Ed.1&Ed.2)
ASCI basic conformance statement
The basic conformance statement is defined in Table A.1.
Table A.1 – Basic conformance statement
Client/ Server/ Value/
Subscriber Publisher Comments
Client-Server roles
Server side (of TWO-PARTY-APPLICATION-
B11 Y
ASSOCIATION)
Client side of (TWO-PARTY-APPLICATION-
B12 N
ASSOCIATION)
SCSMs supported
Client/Subscrib
er side is only
B21 SCSM: IEC 61850-8-1 used Y Y
GOOSE and
SNTP.
Deprecated
B22 SCSM: IEC 61850-9-1 used
Ed2
B23 SCSM: IEC 61850-9-2 used
B24 SCSM: other
(PICS Ed.1&Ed.2)
ACSI models conformance statement
The ACSI models conformance statement is defined in Table A.2.
Table A.2 – ACSI models conformance statement
Client/ Server/ Value/
Subscriber Publisher Comments
If Server or Client side (B11/12) supported
M1 Logical device N Y
M2 Logical node N Y
M3 Data N Y
M4 Data set N Y
M5 Substitution N N
M6 Setting group control N Y
Reporting
M7 Buffered report control N Y
M7-1 sequence-number N Y
M7-2 report-time-stamp N Y
M7-3 reason-for-inclusion N Y
M7-4 data-set-name N Y
M7-5 data-reference N Y
M7-6 buffer-overflow N Y
M7-7 entryID N Y
M7-8 BufTm N Y
M7-9 IntgPd N Y
M7-10 GI N Y
M7-11 conf-revision N Y
M8 Unbuffered report control N Y
M8-1 sequence-number N Y
M8-2 report-time-stamp N Y
M8-3 reason-for-inclusion N Y
M8-4 data-set-name N Y
M8-5 data-reference N Y
M8-6 BufTm N Y
M8-7 IntgPd N Y
M8-8 GI N Y
M8-8 conf-revision N Y
Logging N N
M9 Log control N N
M9-1 IntgPd N N
M10 Log N N
M11 Control N Y
M17 File Transfer N Y
M18 Application Association N Y
M19 GOOSE Control Block N Y
M20 Sampled Value Control Block N N
If GSE (B31/32) is supported
M12 GOOSE Y Y
M13 GSSE N N Deprecated Ed2
If SVC (41/42) is supported
M14 Multicast SVC N N
M15 Unicast SVC N N
For all IEDs
SNTP client functions
M16 Time Y N
are supported.
Y = service is supported
N or empty = service is not supported
(PICS Ed.1&Ed.2)
ACSI service conformance statement
The ACSI service conformance statement is defined in Table A.3 (depending on the statements
in Table A.1).
Table A.3 – ACSI service Conformance statement(1/3)
Ed Services AA: Client Server Comments
TP/MC (C) (S)
Server
S1 1 GetServerDirectory (LOGICAL-DEVICE) TP N Y
Application association
S2 1 Associate TP N Y
S3 1 Abort TP N Y
S4 1 Release TP N Y
Logical device
S5 1 GetLogicalDeviceDirectory TP N Y
Logical node
S6 1 GetLogicalNodeDirectory TP N Y
S7 1 GetAllDataValues TP N Y
Data
S8 1 GetDataValues TP N Y
S9 1 SetDataValues TP N Y
S10 1 GetDataDirectory TP N Y
S11 1 GetDataDefinition TP N Y
Data set
S12 1 GetDataSetValues TP N Y
S13 1 SetDataSetValues TP N N
S14 1 CreateDataSet TP N N
S15 1 DeleteDataSet TP N N
S16 1 GetDataSetDirectory TP N Y
Substitution
S17 1 SetDataValues TP N N
(PICS Ed.1&Ed.2)
Logging
Log control block
S30 1 GetLCBValues TP N N
S31 1 SetLCBValues TP N N
Log
S32 1 QueryLogByTime TP N N
S33 1 QueryLogAfter TP N N
S34 1 GetLogStatusValues TP N N
(PICS Ed.1&Ed.2)
Control
S51 1 Select N Y
S52 1 SelectWithValue TP N Y
S53 1 Cancel TP N Y
S54 1 Operate TP N Y
S55 1 CommandTermination TP N Y
S56 1 TimeActivatedOperate TP N N
File transfer
S57 1 GetFile TP N Y
S58 1 SetFile TP N N
S59 1 DeleteFile TP N N
S60 1 GetFileAttributeValues TP N Y
S61 1 GetServerDirectory (FILE-SYSTEM) TP N Y
Time
T1 1 Time resolution of internal clock 10 nearest negative power of 2 in
(1ms) seconds
T2 1 Time accuracy of internal clock T1 T0 (10ms)
T1 (1ms)
T2 (100µs)
T3 (25µs)
T4 (4µs)
T5 (1µs)
T3 1 Supported TimeStamp resolution 10 nearest negative power of 2 in
(1ms) seconds
(PIXIT Edition1&2)
Note: The template of this document is “PIXIT template extracted from server test
procedures version 1.0 and updated according to TPCL version 1.2.6” published by
UCA International Using Group.
(Original document#: 6F2S1875 Ver. 0.11)
(PIXIT Ed.1&Ed.2)
1. Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of
the IEC 61850 interface in G2 Series IED with communication firmware G2M850-02 series
version equal & upper than A(G2M850-02-A).
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test
according to IEC 61850-10. The PIXIT entries contain information which is not available in the
PICS, MICS, TICS documents or SCL file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-
10.
Note: Term “Ed” mentions the edition number of the IEC 61850. The editon2 (Ed2)
provides backward compatibility for legacy the Edition 1 (Ed1).
(PIXIT Ed.1&Ed.2)
4. PIXIT FOR ASSOCIATION MODEL
ID Ed Description Value / Clarification
Maximum number of clients that can set-up an
As1 1 6
association simultaneously
From 10 to 30 seconds
As3 1,2 Lost connection detection time
(TCP_KEEPALIVE + 10sec.)
Transport selector N
Session selector N
What association parameters are necessary for
As5 1,2 Presentation selector N
successful association
AP Title N
AE Qualifier N
(PIXIT Ed.1&Ed.2)
5. PIXIT FOR SERVER MODEL
ID Ed Description Value / Clarification
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
Y* Overflow
Y* OutofRange
N BadReference
N Oscillatory
Which analogue value (MX) quality bits are
Sr1 1,2 Y* Failure
supported (can be set by server)
N OldData
Y* Inconsistent
N Inaccurate (OnlyHz)
Source:
Y Process
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
N BadReference
Y Oscillatory
Which status value (ST) quality bits are
Y Failure
Sr2 1,2 supported
Y OldData
(can be set by server)
Y Inconsistent
N Inaccurate
Source:
N Substituted
Y Test
N OperatorBlocked
(PIXIT Ed.1&Ed.2)
6. PIXIT for Data set model
ID Ed Description Value / Clarification
Not limited by an internal
configuration parameter.
(PIXIT Ed.1&Ed.2)
size)
$14.2.2.9)
(PIXIT Ed.1&Ed.2)
9. PIXIT for Reporting model (continued)
ID Ed Description Value / Clarification
What is the buffer size for each BRCB or how For example, LLN0$ST$Health
many reports can be buffered can be stored 408 events.
Rp7 1,2
What is the scan cycle for binary events More than 1.6 milliseconds
Rp10 1,2
Is this fixed, configurable Configurable
Does the device support to pre-assign a RCB to a
Rp11 1 specific client in the SCL N
After restart of the server is the value of ConfRev Restored from original
restored from the original configuration or configuration
Rp12 2 retained prior to restart
Rp14 2 Or
<additional items>
Is it supported to change LLN0.Mod online? N
Not applicable
(PIXIT Ed.1&Ed.2)
11. PIXIT FOR GOOSE PUBLISH MODEL
ID Ed Description Value / Clarification
Can the test (Ed1) / simulation (Ed2) flag in the
Gp1 1,2 N
published GOOSE be set
What is the behaviour when the GOOSE publish If the configuration is incorrect,
Gp2 1
configuration is incorrect the GOOSE isn’t published.
Published FCD supported common data classes All CDC/data types can be
Gp3 1,2
are published.
Y
Does Server or ICT refuse GOOSE payload
Gp9 1,2 Server Refuses the
dataset length greater than SCSM supports?
Configuration.
<additional items>
1,2 Is the DUT a test equipment N
(PIXIT Ed.1&Ed.2)
12. PIXIT FOR GOOSE SUBSCRIBE MODEL
ID Ed Description Value / Clarification
What elements of a subscribed GOOSE Y destination MAC address
message are checked to decide the message is = as configured
valid and the allData values are accepted? If Y APPID
yes, describe the conditions. Y gocbRef
N timeAllowedtoLive
Notes: N datSet
the VLAN tag may be removed by a Y goID
ethernet switch and shall not be =as configured
Gs1 1,2 checked N t
the simulation flag shall always be N stNum
checked (Ed2) Y sqNum
Y simulation / test
N confRev
Y ndsCom
N numDatSetEntries
N out-of-order dataset
members
When is a subscribed GOOSE marked as lost [message does not arrive prior to
(TAL = time allowed to live value from the last TAL]
received GOOSE message) GOOSE subscribe quality
information will become
QUESTIONABLE (=1100 0000
0000 0).
N Substituted
Y Test
N OperatorBlocked
(PIXIT Ed.1&Ed.2)
12. PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
ID Ed Description Value / Clarification
What is the behavior when a subscribed Refer to Gs3
Gs4 1,2 GOOSE message is out-of-order
(NOTE)
But each data size shall be less
than 32 bits.
Dataset including measurand
CDC listed above cannot be
subscribed.
(PIXIT Ed.1&Ed.2)
12. PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
ID Ed Description Value / Clarification
<additional items>
Are subscribed GOOSE with ndsCom=T GOOSE subscribe quality
Accepted. information will become
QUESTIONABLE |
INACCURATE (=1100 0000 0100 0).
1,2
GOOSE status change is ignored.
The behavior can be changed by
modifying PLC logic.
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL
ID Ed Description Value / Clarification
What control models are supported DOns: Y
(compare ICD file enums for Ed2) SBOns: Y
Ct1 - DOes: Y
SBOes: Y
Is the control model fixed, configurable and/or Fixed
Ct2 1,2 dynamic
Is TimeActivatedOperate supported (compare Deprecated
Ct3 - PICS or SCL)
Is “operate-many” supported (compare Deprecated
Ct4 - sboClass)
Will the DUT activate the control output when Y
the test attribute is set in the SelectWithValue
Ct5 1 and/or Operate request (when N test procedure
Ctl2 is applicable)
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
ID Ed Description Value / Clarification
Which additional cause diagnosis are Y Unknown
supported Y Not-supported
Y Blocked-by-switching-hierarchy
Y Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
Y Blocked-by-Mode
N Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
Y Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
Y Time-limit-over
Y Abortion-by-trip (only for BCPU)
Y Object-not-selected
Ct9 1,2
Edition 1 specific values:
Y Parameter-change-in-execution
How to force a “test-not-ok” respond with Set orCat with unsupported value.
SelectWithValue request See below “Which origin categories
Ct10 1,2
are supported?”
How to force a “test-not-ok” respond with Send SELECT request to the control
Ct11 1,2 Select request object which is not mapped to
control application.
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
ID Ed Description Value / Clarification
How to force a “test-not-ok” respond with DOns, SBOns, DOes:
Operate request [Example1]
Set orCat as unsupported value
-> Cause AddCause as “Not-
supported(1)”
[Example2]
Set ctlCat same as stVal
-> Cause AddCause as “Position-
reached(5)”
Ct12 1,2
SBOes: (Only Ed1)
Same as above. Or,
[Example3]
Set Oper parameters as different
parameter from the parameter of
SelectWithVal
-> Cause AddCause as “Parameter-
change-in-execution (6)”
maintenance (7): N
process (8): N
What happens if the orCat value is not DOns, SBOns, DOes, SBOes:
Ct14 1,2 supported or invalid “test-not-ok” IED respond
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
ID Ed Description Value / Clarification
Does the IED accept a Select/SelectWithValue SBOns: N
from the same client when the control object is SBOes: N
Ct17 1 already selected (Tissue #334)
Is for SBOes the internal validation performed Yes for both SelectWithValue and
Ct18 1,2 during the SelectWithValue and/or Operate Operate
step
Name a DOes point (if any) with a finite The timeout time is setting.
operate timeout and specify the timeout One example,
Ct26 1,2 (in milliseconds) DPSY01-RST
Default value is 300[ms]
(10[ms]-1000[ms])
Does the IED support control objects with DOns: N
external signals? SBOns: N
Ct27 2 DOes: N
SBOes: N
(PIXIT Ed.1&Ed.2)
15. PIXIT FOR TIME AND TIME SYNCHONISATION MODEL
ID Ed Description Value / Clarification
What time quality bits are supported (may be Y LeapSecondsKnown
set by the IED) N ClockFailure
Tm1 1 Y ClockNotSynchronized
Describe the behavior when the time server(s) On one time server: IED tries to
ceases to respond synchronize with another time
server.
What is the time server lost detection time The lost detection time depends on
the network condition.
How long does it take to take over the new time 10 seconds
Tm3 1,2 from time server
Tm4 1,2 When is the time quality bit “ClockFailure” set RTC is out-of-order
When is the time quality bit “Clock not It depends on the condition of
Tm5 1,2 Synchronized” set synchronization. Typically from 1 to
10 minutes.
Is the timestamp of a binary event adjusted to Deprecated
Tm6 - the configured scan cycle
Does the device support time zone and daylight Yes for both.
Tm7 1
saving
Which attributes of the SNTP response packet Y Leap indicator not equal
are validated to 3?
N Mode is equal to SERVER
N OriginateTimestamp is
equal to value sent by the
SNTP client as Transmit
Tm8 1,2 Timestamp
Y RX/TX timestamp fields
are checked for
reasonableness
Y SNTP version 3 and/or 4
N other (describe)
Do the COMTRADE files have local time or UTC
Tm9 1,2 UTC time and is this configurable Not Configurable
(PIXIT Ed.1&Ed.2)
16. PIXIT FOR FILE TRANSFER MODEL
(NOTE)
Ft1 1 At root directory in IED, the
directory “/COMTRADE/” is
Hidden. Therefore a client
shall directly access this
directory.
Are comtrade files zipped and what files are Not zipped
included in each zip file
Directory names are separated from the file
Ft2 1,2 name by “/”
The maximum file name size including path
Ft3 1 (recommended 64 chars) 64 chars
(TICS Edition2)
Note: The template of this document is “Test Procedures Change List (TPCL) version
1.2.6 for IEC 61850 Edition 2 server test procedures revision 1.0” published by
UCA International Users Group Testing Sub Committee in April 3, 2018.
(Original document#: 6F2S1920 Ver. 0.1)
(TICS Ed.2)
1. Introduction
This document provides a template for the Tissues conformance statement. According to the
UCA IUG QAP the Tissue conformance statement is required to perform a conformance test
and is referenced on the certificate.
This document is applicable for G2 series IED with communication firmware G2M850-02 series
version equal & upper than A (G2M850-02-A).
Note: Term “Ed” is mentioning the edition number of IEC 61850. Editon2 (Ed2) provides
backward compatibility for legacy Edition 1 (Ed1).
(TICS Ed.2)
2. Mandatory Edition2 Tissues
Below tables give an overview of the applicable mandatory Tissues.
Part 6 Implemented
Description
Tissue Y/na
658 Tracking related features na
FCDA element cannot be a "functionally constrained
663 Y
logical node"
668 Autotransformer modeling na
687 SGCB ResvTms na
719 ConfDataSet - maxAttributes definition is confusing na
721 Log element name na
768 bType VisString65 is missing Y
779 object references na
788 SICS S56 from optional to mandatory na
789 ConfLdName as services applies to both server and client na
804 valKind and IED versus System configuration na
806 Max length of log name inconsistent between -6 and -7-2 na
807 Need a way to indicate if "Owner" present in RCB na
(TICS Ed.2)
2. Mandatory Edition2 Tissues (continued)
Part 7-1 Implemented
Description
Tissue Y/na
828 Data model namespace revision IEC 61850-7-4:2007[A] na
simulated GOOSE disappears after 1st appearance when
1151 na
LPHD.Sim = TRUE
(TICS Ed.2)
2. Mandatory Edition2 Tissues (continued)
Part 7-4 Implemented
Description
Tissue Y/na
671 mistake in definition of Mod & Beh Y
674 CDC of ZRRC.LocSta is wrong na
676 Same data object name used with different CDC na
677 MotStr is used with different CDC in PMMS and SOPM LN classes na
679 Remove CycTrMod Enum na
680 SI unit for MHYD.Cndct na
681 Enum PIDAlg na
682 ANCR.ParColMod na
683 Enum QVVR.IntrDetMth na
685 Enum ParTraMod na
686 New annex H - enums types in XML na
694 Data object CmdBlk na
696 LSVS.St (Status of subscription) na
712 interpretation of quality operatorBlocked na
713 DO Naming of time constants in FFIL na
724 ANCR.Auto na
725 Loc in LN A-group na
734 LLN0.OpTmh vs. LPHD.OpTmh na
736 PFSign na
742 GAPC.Str, GAPC.Op and GAPC.StrVal na
743 CCGR.PmpCtl and CCGR.FanCtl na
744 LN STMP, EEHealth and EEName na
773 Loc, LocKey and LocSta YPSH and YLTC na
774 ITCI.LocKey na
800 Misspelling in CSYN na
802 CCGR and Harmonized control authority na
808 Presence condition of ZMoT.DExt and new DOs na
831 Setting of ConfRevNum in LGOS na
838 Testing in Beh=Blocked na
844 MFLK.PhPiMax, MFLK.PhPiLoFil, MFLK.PhPiRoot DEL->WYE na
Presence conditions re-assessing in case of derived
849 statistical calculation na
877 QVUB -settings should be optional na
909 Remove ANCR.ColOpR and ColOpL na
920 Resetable Counter is NOT resetable na
932 Rename AVCO.SptVol to AVCO.VolSpt na
939 Change CDC for ANCR.FixCol na
991 LGOS: GoCBRef (as well as LSVS.SvCBRef) should be mandatory Y
1007 PTRC as fault indicator - Update of description required na
1044 TapChg in AVCO na
1077 Rename DOnames within LTIM na
Note: Tissues 675, 735, 772, 775, 776, 878 are not relevant for conformance testing
(TICS Ed.2)
2. Mandatory Edition2 Tissues (continued)
Part 8-1 Implemented
Description
Tissue Y/na
784 Tracking of control (CTS) na
817 Fixed-length GOOSE float encoding Y
834 File dir name length 64 Y
951 Encoding of Owner attribute Y
1040 More associate error codes Y
1178 Select Response+ is non-null value Y
Appendix 5 Ordering
Positions
[Hardware selection](1/2) 7 8 - 9 A B - C D - E F - G H - J K L
Configuration G R H 2 0 0 - 9 - - 0 0 - - 3 - 1 0
DC rated voltage
110-250 Vdc (or 100-220 Vac †1) 1
24-60 Vdc 3
System Frequency
50Hz 1
60Hz 2
AC rated current
1A 1
Outlines
Standard LCD, 1/2 size case; flush mounting type 2
Large LCD, 1/2 size case; flush mounting type 6
Standard LCD, 1/2 size case; rack mounting type†2 F
Large LCD, 1/2 size case; rack mounting type†2 J
1† The operation of BI modules is intended to use while DC power source is being supplied to the
IED, and the operation of power supply module (PWS) of the IED is only guaranteed for DC
power source. Thus, the user should disable the PWS supervision function when AC power is
supplied to the IED so that the IED does not issue spurious alarms (see p. 456).
2† Mounting kits (for 19” rack) are provided if EP-204/205 accessories are ordered (see p. 849).
Tips: The user can find out the ordering number from the information menu on the LCD (see
Chapter User interface: Information sub-menu).
Positions
[Hardware selection](2/2) 7 8 - 9 A B - C D - E F - G H - J K L
Configurations G R H 2 0 0 - 9 - - 0 0 - - 3 - 1 0
(…continued from the previous page)
Positions
[Software selection](1/1) 7 S G T E F U 9 V
Configurations G R H 2 0 0 - 9 0 3 1 - -
Function block
See Function table (see p. 845) 1
Network / Time Sync. modules
Assignment at ‘E’ position (see pp. 841—843)
Assignment at ‘F’ position (see pp. 841—843)
Protocol†1
IEC60870-5-103 or IEC 61850 1
IEC 61850 2
Outline
Assignment at ‘9’ position (see p. 840)
Language
English E
1† One of the codes (i.e., 1 or 2 at positons U) has to be selected to be relevant for the user’s purpose:
IEC 60870-5-
30 ✓ NA
103†3
✓: Valid NA: Not applicable
2† Duplicated LAN modules are required for the hot-standby. For the PRP/HSR/RSTP, choose LAN modules
[Number of BI/BO]
Selction of 1xBIO module, a slot is assigned in the IED case.
Number of circuits on a module
Binary input circuits (BI) Independent type & variable thresholds Binary output circuits (BO)
Hybrid type
No.†1 Selections of a BIO module
- - - - - - - (N/A) -
- - - - - - - (N/A) -
8 - - 6 - 2 - 13 1xBIO3A
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
Note
†1 The code selected is set for A & B positions of ‘Hardware selection’.
Selction of 2xBIO modules, two slots are assigned in the IED case.
Number of circuits on a module
Binary input circuits (BI) Binary output circuits (BO)
Hybrid type
No.†1 Selections of BIO module combination
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
16 - - 12 - 4 - 2A 2xBIO3A
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
8 12 - 6 - 2 - 2G 1xBI2A+1xBIO3A
Note
†1 The code selected is set for A & B positions of ‘Hardware selection’.
Selction of 3xBIO modules; three slots are assigned in the IED case.
Number of circuits on a module
Binary input circuits (BI) Binary output circuits (BO)
Hybrid type
No.†1 Selections of BIO module combination
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
24 - - 18 - 6 - 36 3xBIO3A
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
16 12 - 12 - 4 - 3S 1xBI2A+2xBIO3A
- - - - - - - (N/A) -
- - - - - - - (N/A) -
- - - - - - - (N/A) -
Note
†1 Selection of a BIO code depends on a size of the IED case.
[Optional accessories]
[Label sheet]
Accessory names Quantity per order Codes
Pocket sheet label for LEDs(White) 10 EP-211-00
Pocket sheet label for function keys(White) 10 EP-212-00
[Rating jumpers]
Accessory names Quantity per order Codes
Jumpers to change rated current 20 EP-221
[Monitoring plugs]
Accessory names Quantity per order Codes
Plugs for monitoring jacks on the front 4 EP-222
[Engineering tools]
Accessory names Quantity per order Codes
GR-TIEMS 1 license EP-251
PLC-EDITOR 1 license EP-261
Technical data
Analog Inputs
Rated current In 1A
Rated Frequency Either 50Hz or 60Hz (specified when the ordering)
Overload Rating
Current inputs 4 times rated current continuous
5 times rated current for 3 minutes
6 times rated current for 2 minutes
30 times rated current for 10 seconds
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
Burden
Phase current inputs 0.1VA at In = 1A, 0.2VA at In = 5A
Power Supply
Rated auxiliary voltage 24/48/60Vdc (Operative range: 19.2 – 72.0Vdc)
48/125Vdc (Operative range: 38.4 – 150.0Vdc)
110/250Vdc (Operative range: 88.0 – 300.0Vdc)
Superimposed AC ripple on DC supply 15%
Power Supply Interruption Withstand Period 110/250Vdc rating : 50ms
(IEC60255-11)
Power consumption 15W (quiescent)
25W (maximum)
Binary Inputs
Input circuit DC voltage 24/48/60Vdc (Operating range: 19.2 – 72Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Capacitive discharge immunity 10μF charged to maximum supply voltage and discharged
into the input terminals, according to ENA TS 48-4 with an
external resistor
Maximum permitted voltage 72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
Power consumption 0.5W per input at 220Vdc
Binary Outputs
Fast operating contacts
Make and carry 5A continuously
30A, 290Vdc for 0.2s (L/R=5ms)
Break 0.15A, 290Vdc (L/R=40ms)
Operating time Typically 3 ms
Auxiliary contacts
Make and carry 8A continuously
30A, 240Vdc for 1s (L/R=5ms)
Break 0.1A at 250Vdc (L/R=40ms)
0.2A at 125Vdc (L/R=40ms)
Operating time Typically 8 ms
Durability ≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
Mechanical Design
Installation Flush mounting
Weight Approx. 12kg (1/2 size)
Case color 2.5Y7.5/1 (approximation to Munsell value)
LED
Number 26 (Fixed for “In service” and “ERROR”)
Color Red / Yellow / Green (configurable) except In service (green)
and Error (red)
Function keys
Number 7
Local PC Interface (front port)
USB Type B
Maximum cable length 2 meters (less than)
Terminal block structure
VCT Ring type terminal
Wire thickness: 2.5mm2 through 5.5 mm2
Termination: M3.5 ring tongue insulated
Environmental performance
Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range:–25C to +55C.
IEC 60068-2-14 Storage / Transit:–25C to +70C.
Cyclic temperature test as per IEC 60068-2-
14
Humidity IEC 60068-2-30 56 days at 40C and 93% relative humidity.
IEC 60068-2-78 Cyclic temperature with humidity test as per
IEC 60068-2-30
Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof
IP20 for rear panel
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between all terminals
and earth.
2kVrms for 1 minute between independent
circuits.
1kVrms for 1 minute across normally open
contacts.
High Voltage Impulse IEC 60255-27 Three positive and three negative impulses of
IEEE C37.90 5kV(peak), 1.2/50s, 0.5J between all
terminals and between all terminals and
earth.
Voltage Dips, IEC 60255-11, 1. Voltage dips:
Interruptions, IEC 61000-4-29, 0 % residual voltage for 20 ms
Variations and Ripple IEC 61000-4-17 40 % residual voltage for 200 ms
on DC supply IEC 60255-26 Ed 3 70 % residual voltage for 500 ms
2. Voltage interruptions:
0 % residual voltage for 5 s
3. Ripple:
15 % of rated d.c. value, 100 / 120 Hz
4. Gradual shut-down / start-up:
60 s shut-down ramp, 5 min power off, 60s
start-up ramp
5. Reversal of d.c. power supply polarity:
1 min
Capacitive Discharge ENA TS 48-4 10μF charged to maximum supply voltage
and discharged into the input terminals with
an external resistance
Environmental performance
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1 MHz burst in common / differential modes
Disturbance / IEC 61000-4-18 Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Damped Oscillatory IEC 60255-26 Ed 3 Communications ports: 1 kV / 0 kV
Wave
Electrostatic IEC 60255-22-2 Class 4, Contact: 2, 4, 6, 8kV
Discharge IEC 61000-4-2 Air: 2, 4, 8, 15kV
IEEE C37.90.3-2001
IEC 60255-26 Ed 3
Radiated RF IEC 60255-22-3, Sweep test ranges: 80 MHz to 1 GHz and 1.4
Electromagnetic GHz to 2.7 GHz.
Disturbance IEC 61000-4-3 Level 3 Spot tests at 80, 160, 380, 450, 900, 1850 and
IEC 60255-26 Ed 3 2150 MHz.
Field strength: 10 V/m
IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of
25MHz to 1GHz.
Fast Transient IEC 60255-22-4 5 kHz, 5/50ns disturbance
Disturbance IEC 61000-4-4 Auxiliary supply and input / output ports: 4 kV
IEC 60255-26 Ed 3 Communications ports: 2 kV
Surge Immunity IEC 60255-22-5 1.2/50µms surge in common/differential
IEC 61000-4-5 modes:
IEC 60255-26 Ed 3 Auxiliary supply and input / output ports: 4, 2,
1, 0.5 kV / 1, 0.5 kV
Communications ports: up to 1, 0.5 kV / 0 kV
Surge Withstand IEEE C37.90.1-2002 3kV, 1MHZ damped oscillatory wave
4kV, 5/50ns fast transient
Conducted RF IEC 60255-22-6 Sweep test range: 150 kHz to 80MHz
Electromagnetic IEC 61000-4-6 Spot tests at 27 and 68 MHz.
Disturbance IEC 60255-26 Ed 3 Voltage level: 10 V r.m.s
Power Frequency IEC 60255-22-7 50/60 Hz disturbance for 10 s in common /
Disturbance IEC 61000-4-16 differential modes†
IEC 60255-26 Ed 3 Binary input ports: 300 V / 150 V
Power Frequency IEC 61000-4-8 Class 4 Field applied at 50/60Hz with strengths of:
Magnetic Field IEC 60255-26 Ed 3 30A/m continuously,
300A/m for 1 second.
Conducted and IEC 60255-25 Conducted emissions:
Radiated Emissions EN 55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB
EN 61000-6-4 (mean)
IEC 60255-26 Ed 3 0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions
30 to 230 MHz: < 40 dB(uV/m)
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m
†For differential mode, ‘CMP_NUM’ setting utilized.
REF (restrict earth fault overcurrent): 0.020 - 2.000A in 0.001A steps (1A rating)
Accuracy
Overcurrent Pick-ups: Setting value 5%
Metering Function
AC current Accuracy 0.5% (at rating)
DC current Accuracy 0.5% (within the range)
Cabling
The table below shows the recommended cables in the cross-section and rated-voltage for the
connection with the transformer module (VCT), the binary IO module (BI, BO, and BIO), and
the power supply module (PWS). Rated-voltage required for the cable is 600Vac.
Table Cables for the connection with module
Fuses
The table below shows the required fuse in the PWS. DO NOT change the fuse by the user.
The fuse is complies with IEC60127-2 Sheet 5.
Table Fuse specification in PWS
Specification Description
Rated current 3.15A
Rated voltage 500Vac & 400Vdc
Cutoff velocity Type “T”
Manufacture Littelfuse, Inc.
Type 04773.15XP
2 ERROR Red Red LED turns on when failures are detected in IED.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
High voltage on the differential circuit will be developed by the excitation of the current
transformer under internal fault conditions. Varistors (non-linear resistors) have to be
connected in parallel to the relay in order that the overvoltage will be limited, accordingly.
Figure-8.A shows the varistor V-I characteristic used in EB-101 and EB-201. Figure-8.B shows
the internal circuits of them.
2000
1800
1600
1400
Voltage
(V) 1200
1000
800
600
400
200
EB-101 EB-102
2kΩ 2kΩ
TB1- TB2- TB1- TB2-
1 2kΩ 1 1 2kΩ 1
2kΩ 2kΩ
11Ω 11Ω for A phase
Varisor Varisor
2 2 2 2
Earth 8
2kΩ
3 2kΩ 3
2kΩ
11Ω for B phase
Varisor
4 4
2kΩ
5 2kΩ 5
2kΩ
11Ω for C phase
Varisor
6 6
Earth 8
110-250 Vdc ✓ ✓
DC rated voltage
24-60 Vdc ✓ ✓
Page 866 867 868 869
Dielectric voltage testing shall be carried out after reading the below notices carefully.
Cable connections
1-1. Type using compression terminals and 110-250 Vdc
✓ Type using compression terminals
IED case structure
Type using ring terminals
✓ 110-250 Vdc
DC rated voltage
24-60 Vdc
Figure-9.A illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, two short-wires attached on the PSW shall be carefully handled; follow the below
instructions (1) and (2).
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(1) (+) 29
30
DC/DC
(-) 31
32
35
36
37
y
38
(2)
FG
Figure-9.A Short-wires, around the PWS, for Type using compression terminals and 110-250Vdc
Figure-9.B illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, three short-wires attached on the PSW shall be carefully handled; follow the below
instructions (1), (2) and (3).
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(1) (+) 29
30
DC/DC
(-) 31
32
35
36
37
y
38
(2)
(3)
FG
Figure-9.B A Short-wires, around the PWS, for Type using compression terminals and 24-60Vdc
✓ 110-250 Vdc
DC rated voltage
24-60 Vdc
Figure-9.C illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, a short-wire and a short-bar attached on the PSW shall be carefully handled; follow
the below instructions (1) and (2).
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(1)
(+) 29
30
DC/DC
(-) 31
32
35
36
37
y
38
(2)
FG
Figure-9.C A short-wire and a short-bar, around the PWS, for Type using ring terminals and 110-250Vdc
Figure-9.D illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, short-wires and a short-bar attached on the PSW shall be carefully handled; follow
the below instructions (1), (2) and (3).
2
4
3
FAIL1
1
8
10
9
FAIL2
7
(1)
(+) 29
30
DC/DC
(-) 31
32
35
36
37
y
38
(2)
(3) FG
Figure-9.D Short-wires and a short-bar, around the PWS, for Type using ring terminals and 24-60Vdc