- Lenght of Column P2 = 247.

18 mm

- Width of Column L2 = 247.18 mm

- Distance Chimney to edge of Foundation P3 = (P-P2)/2 = 376.41 mm


L3 = (L-L2)/2 = 376.41 mm

2.3 Weight of Foundation

- Selfweight of foundation slab Vslab = P * L * h2 * γ concr = 7.20 kN

- Soil weight Vsoil = [(P * L) - (P2 * L2)] * h1 * γ soil = 18.03 kN

- Total weight Vfounf = Vslab + Vsoil = 25.23 kN

2.4 Loading from Upper Structure

Service Load Combinations


TABLE: Joint Reactions
Joint OutputCase CaseType F1 F2 F3 M1 M2 M3
Text Text Text KN KN KN KN-m KN-m KN-m
68 CS-GEMPA13 Combination -0.315 -3.779 -20.493 0 0 0
68 CS-GEMPA20 Combination 1.501 4.12 82.54 0 0 0

Ultimate Load Combinations


TABLE: Joint Reactions
Joint OutputCase CaseType F1 F2 F3 M1 M2 M3
Text Text Text KN KN KN KN-m KN-m KN-m
68 CU-GEMPA08 Combination 1.784 5.758 108.266 0 0 0
68 CU-GEMPA13 Combination -0.418 -5.389 -27.613 0 0 0
68 CU-GEMPA16 Combination 1.753 5.773 97.416 0 0 0

3. Check Stability

3.1. Check Bearing Capacity

Reaction on bottom of pad

- Axial force = Vfound + Vreaction chimney P = 107.77 kN

- Moment force (x-x) Mx-x = M1 = 0.00 kN.m

- Moment force (y-y) My-y = M2 = 0.00 kN.m

Excentricity Check

- Width of pad B = 1.00 m

- Limitation B/6 = 0.17 m

- Check excentricity x-x direction ex-x = Mx-x / P = 0.00 m

Check excentricity x-x = ex-x < B / 6 excentricity OK

- Check excentricity y-y direction ey-y = My-y / P = 0.00 m

Check excentricity y-y = ey-y < B / 6 excentricity OK

Check Bearing Capacity

- Bearing capacity of soil qall = 120.00 kN/m2

- Bearing pressure of soil

σ max = P / B² + Mx-x / (1/6 B³) + My-y / (1/6 B³) = 107.77 kN/m2

σ max = P / B² - Mx-x / (1/6 B³) - My-y / (1/6 B³) = 107.77 kN/m2

Check Bearing Capacity = σ max < qall, Bearing Capacity OK