M ED I U M VO LTAG E PR O D U C T S
VD4G
Medium voltage vacuum circuit-breakers
15 kV - 2000...3150 A - 25...50 kA
2 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
Vacuum circuit breakers for
generator switching applications.
A complete product line compliant
with the latest Global Dual Logo
IEC/IEEE 62271-37-013 Standard,
featuring the familiar VD4 design
for easy integration into existing
installations.
M E D I U M V O LTA G E P R O D U C T S 3
—
Index
—
1. ABB strength, Your benefit
Efficiency
...Product Optimized
features …Compliant with
investments
the familiar the global dual
Reliability logo standard
VD4 design...
Protects
your assests
Productivity
Maximizes
your output
A full range...
M E D I U M V O LTA G E P R O D U C T S 5
—
2. Description
Thus the vacuum interrupter restores the VD4G circuit-breakers use a mechanical operating
insulating capacity and the ability to sustain the mechanism, with stored energy and free trip.
transient recovery voltage, thereby definitively These characteristics allow opening and closing
extinguishing the arc. operations to be performed independent of the
Since high dielectric strength can be reached in operator. The simply designed, user-friendly
the vacuum even with minimum distances, circuit operating mechanism can be customized with a
breaking is also guaranteed when the contacts wide range of easily and rapidly installed
separate a few milliseconds before natural zero accessories. Since it is so simple, the apparatus is
crossing. more reliable.
The special shape of the contacts and material
used, combined with the brief arcing time and Structure
low arc voltage guarantee long-lasting contacts The operating mechanism and poles are fixed to a
with a minimum amount of wear. The vacuum also metal frame, which also acts as the support for
prevents the contacts from tarnishing and the fixed version of the circuit-breaker. The
becoming contaminated. compact structure is sturdy and ensures
mechanical reliability.
Operating mechanism Apart from the isolating contacts and cord with
Along with short travel and low weight, the low plug for connecting the auxiliary circuits, the
speed of the contacts limits the energy required withdrawable version has a truck for racking it
for operation, thus guaranteeing extremely into and out of the switchgear or enclosure with
limited wear in the system. the door closed.
This ensures that the circuit-breaker also requires
very little maintenance.
8 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
2. Description
Vacuum interrupter
The spiral contacts of ABB vacuum interrupters contacts, this makes contact erosion negligible
Thanks to their special shape, spiral contacts and above all, allows the interruption process to
generate a radial magnetic field in all areas of the be controlled even with very high short-circuits.
arc column, which concentrates over the contact ABB vacuum interrupters interrupt at the natural
circumferences. zero crossing, thereby preventing the arc from
A self-generated electromagnetic force acts restriking after that event.
tangentially, causing the arc to rapidly rotate A rapidly reduced current charge and rapid
around the contact axis. condensation of the metal vapors at the same
The arc is forced to rotate and involve a wider time as zero crossing, allows maximum dielectric
surface than that of a fixed contracted arc. strength to be restored between the interrupter
Besides minimizing thermal stress on the contacts within microseconds.
Short-circuit
current
Current, Voltage
Arc voltage
Voltage of
the system
Short-circuit current
interruption
Time
Contact
separation
Recovery voltage
(frequency of the system)
—
2. Description
Vacuum circuit breakers for generator
switching applications
A B
Generator
Generator Transformer Grid
circuit-breaker
40 40
Short-circuit current [kA]
20 20
0 0
-20 -20
-40 -40
-60 -60
0 25 50 75 100 125 150 175 200 225 250 0 25 50 75 100 125 150 175 200 225 250
Time [ms] Time [ms]
IR(t) [kA] IS(t) [kA] IT(t) [kA] IR(t) [kA] IS(t) [kA] IT(t) [kA]
—
3. Selection and ordering
Fixed circuit-breakers
Circuit-breaker VD4G-25/16
Standards IEC/IEEE 62271-37-013 •
Rated voltage Ur [kV] 15
Rated insulation voltage Us [kV] 15
Withstand voltage at 50 Hz common value Ud (1 min) [kV] 38
Impulse withstand voltage common value Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated nominal current (40° C) Ir [A] 1250
Symmetrical short-circuit current IscSFF [kA] 25
Rated system-source
DC component of rated short-circuit breaking current * % 74
short-circuit breaking current
Asymmetrical system-source short-circuit current IascSFF [kA] 36.5
symmetrical short-circuit current Iscg Class G1 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 110
Rated generator-source current Class G1
short-circuit breaking current symmetrical short-circuit current Iscg Class G2 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 130
current Class G2
Rated breaking current under symmetrical short-circuit current IscOOP [kA] 12.5
out-of-phase conditions DC component of rated short-circuit breaking current % 74
Making current Ip [kA] 68.5
Rated operating sequence during short-circuit interruption CO-10 min-CO
Rated short-time withstand current (3s) Ik [kA] 25
Opening time [ms] 33...60
Maximum arcing time (generator-source fault - 130% DC component at contact separation) [ms] 40
Closing time [ms] 30...60
P P H [mm] 461
Maximum W [mm] 450
overall
H D [mm] 424
dimensions
W D Pole distance P [mm] 150
Weight [kg] 73
Standardized table of dimensions 1VCD003891
Operating temperature [°C] - 5 ... + 40
(1) 4000 A with forced ventilation
M E D I U M V O LTA G E P R O D U C T S 13
The circuit-breakers can be completed with the optional accessories indicated on the following pages.
VD4G-40/25 VD4G-50/50
• •
15 15
15 15
38 38
95 95
50-60 50-60
2000 2000 3150 4000(1) 3150 4000(1)
40 50
74 74
58.5 73
25 50
110 110
25 37
130 130
20 25
74 74
115 137
CO-10 min-CO CO-10 min-CO
40 50
33...60 <30
34 33
30...60 <55
610 610 636 636 636 636
600 750 750 750 750 750
459 459 459 459 459 459
210 275 275 275 275 275
146 158 177 177 210 210
1VCD000240 1VCD000241 1VCD000242
- 5 ... + 40 - 5 ... + 40
14 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
3. Selection and ordering
Withdrawable circuit-breakers
Withdrawable circuit-breakers
for Unigear ZS1 switchgear (15 kV)
Circuit-breaker VD4G-25/16
Standards IEC/IEEE 62271-37-013 •
Rated voltage Ur [kV] 15
Rated insulation voltage Us [kV] 15
Withstand voltage at 50 Hz common value Ud (1 min) [kV] 38
Impulse withstand voltage common value Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated nominal current (40° C) Ir [A] 1250
Symmetrical short-circuit current IscSFF [kA] 25
Rated system-source
DC component of rated short-circuit breaking current * % 74
short-circuit breaking current
Asymmetrical system-source short-circuit current IascSFF [kA] 36.5
symmetrical short-circuit current Iscg Class G1 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 110
Rated generator-source current Class G1
short-circuit breaking current symmetrical short-circuit current Iscg Class G2 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 130
current Class G2
Rated breaking current under symmetrical short-circuit current IscOOP [kA] 12.5
out-of-phase conditions DC component of rated short-circuit breaking current % 74
Making current Ip [kA] 68.5
Rated operating sequence during short-circuit interruption CO-10 min-CO
Rated short-time withstand current (3s) Ik [kA] 25
Opening time [ms] 33...60
Maximum arcing time (generator-source fault - 130% DC component at contact separation) [ms] 40
Closing time [ms] 30...60
P P H [mm] 632
Maximum W [mm] 503
overall
H D [mm] 664
dimensions
W D Pole distance P [mm] 150
Weight [kg] 116
Standardized table of dimensions 1VCD000233
Operating temperature [°C] - 5 ... + 40
(1) 4000 A with forced ventilation
M E D I U M V O LTA G E P R O D U C T S 15
The circuit-breakers can be completed with the optional accessories indicated on the following pages.
VD4G-40/25 VD4G-50/50
• •
15 15
15 15
38 38
95 95
50-60 50-60
2000 2000 3150 4000(1) 3150 4000(1)
40 50
74 74
58.5 73
25 50
110 110
25 37
130 130
20 25
74 74
115 137
CO-10 min-CO CO-10 min-CO
40 50
33...60 <30
34 33
30...60 <55
691 691 730 730 735 735
681 853 853 853 851 851
643 643 643 643 650 650
210 275 275 275 275 275
190 205 221 221 270 270
1VCD000234 1VCD000243 1VCD000244
- 5 ... + 40 - 5 ... + 40
16 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
3. Selection and ordering
Optional accessories
(*) The minimum current 1 Shunt opening release (-MBO1) 2 Additional shunt opening release (-MBO2)
that the relay with TCS
function (used for mon-
Allows opening command of apparatus to be Similarly to shunt opening release -MBO1, this
itoring coil continuity) enabled by remote control. allows the opening command of the apparatus
detects as a condition
denoting that the trip
This release is suitable for both instantaneous to be transmitted by remote control. It can be
circuit is operating and permanent duty. However, an auxiliary powered by the same circuit as main shunt
correctly (specified for
each relay in the relative
contact -BGB1 de-energizes it after circuit- opening release -MBO1 or by a circuit that is
manual), must be breaker has opened. In the case of completely separate from release -MBO1.
sensibly higher than the
current consumption of
instantaneous service, the current impulse This release is suitable for both instantaneous
the actual coil (~1.5 mA). must last at least 100 ms. and permanent duty. However, an auxiliary
If this fails to occur, al-
ways add, in parallel to
This release can be controlled by the following contact -BGB1 de-energizes it after the circuit-
the TCS, a circuit able devices: coil continuity control (CCC), opening breaker has opened.
to absorb sufficient
current to compensate
circuit supervision (TCS)(*) or the ABB STU To guarantee the release action, the current
the gap while prevent- functionality control device (see accessory 21, impulse must last at least 100 ms.
ing the total current
in the TCS circuit
supplied on request). Continuity functionality can be checked with a
from rising above the continuity control device (CCC), opening
maximum threshold
(Itcs <10 mA for High
circuit supervision (TCS)(*) or the STU
Characteristics
Voltage coils - from functionality control device (see accessory 21,
110V to 250V, and Itcs 24-30-48-60-110...132-
Un supplied on request).
<50 mA for Low Voltage 220...250 V DC
coils from 24 V to 60 V). 48-60-110...127-220...250 • MBO2 has the same electrical and operating
A simple resistor Un
can be sized for the
V AC 50-60 Hz characteristics as release -MBO1.
purpose, depending on Operating limits 65 … 120% Un
the parameters of the
Inrush power (Ps) 60...100 W / VA
TCS and the auxiliary
voltage range used. Continuous power
1.5 W
consumption (Pc)
Electronics self-consumption
(no coil supplied); value
1.5 mA
independent of voltage
applied
(*) The minimum current 3 Opening solenoid (-MO3) 4 Shunt closing release (-MC)
that the relay with TCS
function (used for mon-
The opening solenoid (-MO3) is a special Allows closing command of apparatus to be
itoring coil continuity) demagnetization release to be used in transmitted by remote control.
detects as a condition
denoting that the trip
conjunction with a self-supplied overcurrent This release is suitable for both instantaneous
circuit is operating protection relay. and permanent duty. An auxiliary contact that de-
correctly (specified for
each relay in the relative
It is situated in the operating mechanism (left- energizes it after the circuit-breaker has closed is
manual), must be hand side) and is not an alternative to the not envisaged.
sensibly higher than the
current consumption of
additional shunt opening release (-MO2). The permanently supplied release provides the
the actual coil (~1.5 mA). It is not available for 40 and 50 kA circuit- electrical anti-pumping function with both
If this fails to occur,
always add, in parallel
breakers. electrical opening and re-closing commands
to the TCS, a circuit able Should this accessory be required, it must be maintained. To guarantee the closing action, the
to absorb sufficient cur-
rent to compensate the
requested at the time of order since subsequent current impulse must last at least 100 ms.
gap while preventing the application by the customer is not possible. If there is the same supply voltage for shunt
total current in the TCS
circuit from rising above
Note: the compatible protection relays are listed closing release -MBC and under-voltage
the maximum threshold in document: Data sheet 1VCD600854. release -MBU and the circuit-breaker must
(Itcs < 10 mA for High
Voltage coils - from
The opening solenoid (-MBO3) is available in two close automatically when auxiliary voltage
110V to 250V, and Itcs < versions: returns, there must be a delay of at least 50 ms
50 mA for Low Voltage
coils from 24 V to 60 V).
– For DC (release by discharging energy stored in between under-voltage release energizing and
A simple resistor protection relay against self-supplied energizing of the shunt closing release to allow
can be sized for the
purpose, depending on
overcurrent) the closing operation to take place. Continuity
the parameters of the – For AC (release by means of the energy supplied functionality can be checked with a continuity
TCS and the auxiliary
voltage range used.
by an adder transformer on the secondaries of control device (CCC), opening circuit
the protection current transformers (CT is at supervision (TCS)(*) or the STU functionality
customer's charge) control device (see accessory 21, supplied on
request).
Characteristics
24-30-48-60-110...132-
Un
220...250V DC
48-60-110...127-220...250V
Un
AC 50-60Hz
Operating limits 65 … 120% Un
Inrush power (Ps) 60...100 W/VA
Continuous power
1.5 W
consumption (Pc)
Electronics self-consumption
(no coil supplied; value
1.5 mA
independent of voltage
applied
Opening time 33...60 ms
Insulation voltage 2000V 50Hz (for 1 min)
18 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
3. Selection and ordering
Optional accessories
5 Auxiliary contacts of the circuit-breaker • non-wired auxiliary contacts; wiring to the ter-
(-BGB1) for 12 to 24 kV versions minals of the contacts is at the customer's
Electrical signaling of circuit-breaker open/closed charge (photo below left; the terminal box to
can be obtained with a group of 10, 16 or 20 which the other electrical accessories are wired
auxiliary contacts for the fixed version and 10 or is at the top); ask for instructions 1VCD601204
16 auxiliary contacts for the withdrawable (available in the main languages) which describe
version. The standard equipment comprises 10 how to remove, wire the auxiliary contacts more
auxiliary contacts. easily and fit the auxiliary contacts unit back
into its housing;
Note • auxiliary contacts already wired to the terminal
The following are available using the standard box (see photo at top right)
group of ten auxiliary contacts and the maximum
number of electrical accessories:
• for fixed circuit-breakers: three closing contacts Consult circuit diagrams 1VCD400151 for fixed
"a" for signaling circuit-breaker open and five circuit-breakers and 1VCD400155 for
opening contacts "b" for signaling cir- withdrawable circuit-breakers.
cuit-breaker closed;
• for withdrawable circuit-breakers: three closing Note
contacts "a" for signaling circuit-breaker open The main shunt opening release and/or the
and four opening contacts "b" for signaling cir- additional shunt opening release use 1 and/or 2
cuit-breaker closed; closing contacts "a", thereby reducing the number
• Fixed circuit-breakers are available with two fin- of auxiliary contacts available. Always check the
ishing accessories (to be specified when order- maximum number of contacts available if the
ing): equipment is non-standard.
M E D I U M V O LTA G E P R O D U C T S 19
The new layouts can be interchanged with the Electrical characteristics (according to IEC 60947)
existing ones, with the following exceptions: Breaking capacity
Rated current Un
• diagram 1VCD400151 (substitutes 1VCD400046 (10000 interruptions)
and 1VCD400099) 220 V AC Cosj = 0.70 20 A
• fig. 34 on the previous diagrams is represented 220 V DC Cosj = 0.45 10 A
by fig. 31 + fig. 32 on the new diagram; 1 ms 12 A
• fig. 33 and fig. 35 on the previous diagrams are 24 V DC
15 ms 9A
not available with the new layout 50 ms 6A
• diagram 1VCD400155 (substitutes 1 ms 10 A
1VCD400047) 60 V DC
15 ms 6A
50 ms 4.6 A
Auxiliary contacts –BGB1 conform to the 1 ms 7A
following standards/regulations/directives: 110 V DC 15 ms 4.5 A
• IEC 62271-100
50 ms 3.5 A
• IEEE C37.54
1 ms 2A
• EN 61373 cat.1 class B / impact and vibration
220 V DC 15 ms 1.7 A
test
50 ms 1.5 A
• Germanish Loyd regulation / vibrations envis-
1 ms 2A
aged by the shipping registers
250 V DC 15 ms 1.4 A
• UL 508
50 ms 1.2 A
• EN 60947 (DC-21A DC-22A DC-23A AC-21A)
• RoHS Directive
—
3. Selection and ordering
Optional accessories
—
3. Selection and ordering
Optional accessories
10 Contact for signaling closing spring loaded/ 11 Locking magnet on operating mechanism
discharged (-BGS2) (-RLE1)
Consists of a microswitch which remotely Only allows activation of the command with the
signals the state of the closing spring of the supplied electromagnet.
circuit-breaker operating mechanism. The locking electromagnet in the operating
The following signals can be transmitted: mechanism has the same electrical
• contact open: signaling spring loaded characteristics as shunt closing release -MBC.
• contact closed: signaling spring discharged
The two signals must be used for circuits with the
same power supply voltage.
M E D I U M V O LTA G E P R O D U C T S 23
Characteristics
24 - 30 - 48 - 60 - 110 - 125 -
Un
127 - 132 - 220 - 240 V–
—
3. Selection and ordering
Characteristics
Un 24 - 30 - 48 - 60 - 110 - 220 V–
Operating limits 85 … 110% Un
Rated power (Pn) 40 W
M E D I U M V O LTA G E P R O D U C T S 25
16 STU Shunt Test Unit Two relays and a changeover contact are also
Owing to their construction, the functionality of available on the unit for remote signaling of the
the shunt closing (-MBC) and opening (-MBO1, following two events:
-MBO2) releases cannot be checked with • test failure (resetting occurs automatically
dedicated relays (e.g. TCS Test Control when the alarm stops)
Supervision, CCC Control Coil Continuity) or with • failure of three tests (resetting can only be per-
the REF control and protection unit. The only formed by means of the manual - RESET – but-
device able to check this functionality is the STU ton from the front of the unit).
Shunt Test Unit. Please contact us if you want to
check this functionality using devices other than There is also a manual - RESET – button on the
STU. front of the unit.
This device can be used in conjunction with shunt
opening release (-MBO1; -MBO2) or shunt closing Characteristics
release (-MBC) for the purpose of checking Un 24 ... 250 V AC/DC
functionality and continuity. Maximum interrupted current 6A
The Shunt Test Unit is used to check the Maximum interrupted voltage 250 V AC
continuity of releases with rated operating
voltage between 24 V and 250 V (AC and DC), as
well as the functionality of the electronic circuit
of the release.
Continuity is checked cyclically with an interval of
20 seconds between one test and the next.
LEDs on the front provide optical signals. The
following information is given:
• POWER ON: power supply present
• (-MO) TESTING: test in progress
• TEST FAILED: signal given if a test fails or in the
absence of auxiliary power supply
• ALARM: signal given after three failed tests.
26 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
4. Specific product characteristics
—
5. Overall dimensions
Fixed circuit-breakers
450
VD4G 248
52
95 32
TN 1VCD003891
Ur 15 kV
Ir 1250 A
205
IscSFF 25 kA
30
52
IscGFF 16 (G2)
475
16
451
435
IscOOP 12.5 kA
56
16
217,5
171
77,5
96
56
33 227,5 28,5
49 28,5
24 402 24 45 250 109
406
150 150
417,5 0,8
45
22
22
Fixed circuit-breakers
VD4G 600
323
TN 1VCD000240
210 210 130
Ur 15 kV
Ir 2000 A
119
IscSFF 40 kA 32
IscGFF 25 (G2)
IscOOP 20 kA
310
609
30
119
475
435
16
56
15
237,5
171
77,5
97
368 28,5
2,5
24
28,5
172 142 109
48 504 48
424
20 436 1
40
24
—
5. Overall dimensions
Fixed circuit-breakers
VD4G 750
396
TN 1VCD000241
275 275 119 99
Ur 15 kV
Ir 2000 A
119
IscSFF 40 kA
32
IscGFF 25 (G2)
IscOOP 20 kA
310
609
30
119
474
435
56
15
238
16
171
77,5
97
28,5
24
69 270 84
49 28,5
429 424
58 634
440 0,8
Fixed circuit-breakers
750
VD4G
398
TN 1VCD000242 375 454
275 275 240
Ur 15 kV
189 119
69
Ir 3150 A
IscSFF 40 kA
118
119
IscGFF 25 (G2)
32
IscOOP 20 kA
310
29,5
119
475
16
435
56
237,5
171
2,5
116 28,5
77,5
24
20 2xM10 deep 20
M E D I U M V O LTA G E P R O D U C T S 29
Fixed circuit-breakers
643 Transportbohrung
VD4G 750 beidseitig
459 transport boring
TN 1VCD000285 275 275 on both sides 194 98 166
130 125
Kabeleinführung
Ur 15 kV cable entry
88
Ir 3150 A
IscSFF 50 kA
310
IscGFF 50/37(G2)
40°
431,5
434
IscOOP 25 kA
80°
237,5
4xM12 M 42,5
24
77,5
545
25 700 25
39 274 72 80 M M
550
100
35 M12 / 30 tief
30
695 530 40 M12 / depth 30
750 670
40
Withdrawable circuit-breakers
123
VD4G
492 121
TN 1VCD000233 233 43 110 150 ±1 150 ±1
Ur 15 kV
100
10
Ir 1250 A
78
296
IscSFF 25 kA
IscGFF 16 (G2)
205 ±1
IscOOP 12.5 kA
627
626
619
64
29
260 ±1
78
154 ±1
23
19
341
4
21,5
503 14 25 468
34 302
37 492
531 320 500
382
437
610
662
30 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
5. Overall dimensions
Withdrawable circuit-breakers
314
VD4G 636
123
44,5 220 25 110 16
TN 1VCD000234
10
Ur 15 kV
119
Ir 2000 A
20
IscSFF 40 kA
310
IscGFF 25 (G2)
698
689
IscOOP 20 kA
119
281
11 23
165
12,5
19
76
26
21,5
19,5
605
4
4
302
14 653 14
25 320 37
359
650
382
640
626 590 52
550 642
210 210
29
590
359
302
Withdrawable circuit-breakers
331
VD4G 842
313
230 48 110
TN 1VCD000243
Ur 15 kV
Ir 2000 A
20
IscSFF 40 kA
310
IscGFF 25 (G2)
698
689
681
IscOOP 20 kA
29
280
89
164
19
19,5
880 34 302
320
374 359
275 275 416
590 52
144
695
750
806
836
M E D I U M V O LTA G E P R O D U C T S 31
Withdrawable circuit-breakers
331
VD4G 842
313
230 48 110
TN 1VCD000243
Ur 15 kV
Ir 2000 A
20
IscSFF 40 kA
310
IscGFF 25 (G2)
698
689
681
IscOOP 20 kA
29
280
89
164
19
19,5
853 13,5 123
4
21,5
880 34 302
320
374 359
275 275 416
590 52
144
695
750
806
836
Withdrawable circuit-breakers
124 122 144
VD4G 36
43
36 127 125 76
35
TN 1VBM700160
30 30
Ur 15 kV
158
Ir 3150 A
2)
IscSFF 50 kA
310
424
IscGFF 50/37(G2) 393
384
735
735
353
IscOOP 25 kA 325
307
175 Riegel
Bar
157
280
*)
165
76
22
0
25 320 4
22
383
383 53
735 389
752
294 303
843 **)
851
275 275
16
16
55
32 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
6. Electric circuit diagram
—
6. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 35
36 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
6. Electric circuit diagram
—
6. Electric circuit diagram
The circuit diagram given in this section refers to withdrawable circuit-breakers for UniGear switchgear.
See diagram 1VCD400156 for withdrawable circuit-breakers with motor-operated truck.
40 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
6. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 41
42 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
—
6. Electric circuit diagram
Fig. 26 = Electrical signaling of closing springs C) Check power of auxiliary circuit to find out
loaded and discharged. whether several motors for loading the closing
Fig. 30 = Auxiliary let-through contact of circuit- springs can be operated at the same time. To
breaker with momentary closing during prevent excessive power draw, the springs must
circuit-breaker opening. be loaded by hand before auxiliary circuit is
Fig. 31, ... , 34 = Available auxiliary contacts of powered.
circuit-breaker (see note E). D) The circuit for monitoring the continuity of the
Fig. 51 = Contacts for electrical signaling of release windings must only be used for that
circuit-breaker in racked-in and isolated purpose. The SOR Test Unit can be used for
positions located on circuit-breaker checking the continuity of the various different
truck (obligatory when fig. 31 or 32 are releases:
required). -MBO4 incompatible with -MBU.
Fig. 52 = Contacts for electrical signaling -MBO4 not available on Vmax and VD4 50kA.
of circuit-breaker in racked-in and E) When fig. 6 is required, contact -BGB1 (23-24) of
isolated positions located on circuit- fig. 32-34 is not available.
breaker truck (supplied on request when When fig. 7 is required, contact -BGB1 (3-4) of
fig. 33 or 34 are required). fig. 31-32-33-34 is not available.
Fig. 60 = Contact for electrical signaling When fig. 9 is required, contact -BGB1 (7-8) of
of undervoltage release de-energized. fig. 31-32-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB1
(31-32) of fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB1 (25-26)
Incompatibility of fig. 32 and 34 is not available.
The circuits indicated in the following figures
F) The contacts for electrical signaling of circuit-
cannot be supplied at the same time in the same
breaker in isolated and racked-in position
circuit-breaker:
(-BGT1 and BGT2) shown in fig. 51-52 are
3-4 3-33-34 4-31-32 5-6 10-11 installed on circuit-breaker truck (movable
31-32-33-34 31-32-52 33-34-51 51-52 part).
G) Fig. 3 is supplied when fig. 31 or 32 are required.
Fig. 4 is supplied when fig. 33 or 34 are required
(in this case, it is obligatory to supply –BGT3).
Notes H) Fig. 10 is only available for VD4 up to 31.5 kA and
A) Circuit-breaker is equipped solely with the Vmax.
applications specified in the order confirmation. Fig. 11 is only available for VD4 up to 31.5 kA.
Consult this catalog for information about how I) The energizing voltage must be the same for
to make out an order. both signals.
B) The undervoltage release can be supplied
for energizing with voltage derived from the
supply side of the circuit-breaker or from an
independent source.
Circuit-breaker closing is only enabled when the
release is energized (closing lock is obtained
mechanically). If there is the same power supply
for the shunt closing and under-voltage releases
and the circuit-breaker must close automatically
when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage
release's enabling instant and energizing of the
shunt closing release.
Incompatible with -MBO4.
44 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
M E D I U M V O LTA G E P R O D U C T S 45
—
Contact us
—
ABB S.p.A.
ABB SACE Division
Medium Voltage Products
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: info.mv@it.abb.com
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
D-40472 Ratingen
1VCP000671 - Rev. A, en - Technical catalog - 2017.04 (VD4-50 kA) (gs)