M ED I U M VO LTAG E PR O D U C T S

VD4G
Medium voltage vacuum circuit-breakers
15 kV - 2000...3150 A - 25...50 kA
2 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


Vacuum circuit breakers for
generator switching applications.
A complete product line compliant
with the latest Global Dual Logo
IEC/IEEE 62271-37-013 Standard,
featuring the familiar VD4 design
for easy integration into existing
installations.
M E D I U M V O LTA G E P R O D U C T S 3


Index

01 – 05 1. Values

06 – 11 2. Description

12 – 25 3. Selection and ordering

26 – 26 4. Specific product characteristics

27 – 31 5. Overall dimensions

32– 43 6. Electric circuit diagram


4 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


1. ABB strength, Your benefit

Efficiency
...Product Optimized
features …Compliant with
investments
the familiar the global dual
Reliability logo standard
VD4 design...
Protects
your assests
Productivity
Maximizes
your output

A full range...
M E D I U M V O LTA G E P R O D U C T S 5

VD4G: Small footprint, complete protection

Thanks to the VD4G family you can:

Offer standardized solutions for all


ratings, even when very low ratings
or generator breakers are required.

Comply with Specifications where


Dual Logo-tested generator breakers
are mandatory, thereby providing
liability risk-free solutions.

Offer solutions using the same


distribution panel, increasing benefit
while optimizing maintenance and
product know-how.
6 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


2. Description

The new VD4G family epitomizes ABB's Vacuum interruption technique


renowned technology and excellence in The vacuum circuit-breaker does not need a
designing and constructing vacuum breaking and insulating medium. Thus, the
interrupters embedded in poles and circuit- interrupter does not contain ionizable material.
breakers. The electric arc that generates when the contacts
VD4G medium voltage circuit-breakers use separate is merely formed by the fusion and
vacuum interrupters embedded in the poles. vaporization of the contact material.
This construction technique makes the Sustained by the external energy, the electric arc
circuit-breaker poles particularly sturdy and persists until the current is annulled near the
protects the interrupter from impact, dust natural zero crossing. In that instant, the
and humidity. The vacuum interrupter houses dielectric properties are very rapidly restored by
the contacts and forms the interrupting a sharp reduction in the density of the conveyed
chamber. charge and rapid condensation of the metallic
vapor.

• Vacuum interruption technique


• Vacuum contacts protected against oxidation
1
and contamination
• Vacuum interrupter embedded in the pole
• Interrupter protected against shocks, dust and
2
humidity
• Operation under different climatic conditions
3
• Limited switching energy
4 • Stored energy operating mechanism with an-
ti-pumping device supplied as standard equip-
ment
• Simple customization with a complete range of
5 accessories
• Fixed and withdrawable versions
6
• Compact dimensions
• Sealed-for-life poles
7 • Sturdy and reliable
• Limited maintenance
• Circuit-breaker racked in and out with the door
8 closed
• Incorrect and hazardous operations prevented
9 thanks to special locks in the operating mecha-
nism and truck
10
• High degree of environmental compatibility
ART
M E DI CL
IUME OR
V O LTA
CH AP
G ETP
ERR OTD
I TL
U CET S 7

Thus the vacuum interrupter restores the VD4G circuit-breakers use a mechanical operating
insulating capacity and the ability to sustain the mechanism, with stored energy and free trip.
transient recovery voltage, thereby definitively These characteristics allow opening and closing
extinguishing the arc. operations to be performed independent of the
Since high dielectric strength can be reached in operator. The simply designed, user-friendly
the vacuum even with minimum distances, circuit operating mechanism can be customized with a
breaking is also guaranteed when the contacts wide range of easily and rapidly installed
separate a few milliseconds before natural zero accessories. Since it is so simple, the apparatus is
crossing. more reliable.
The special shape of the contacts and material
used, combined with the brief arcing time and Structure
low arc voltage guarantee long-lasting contacts The operating mechanism and poles are fixed to a
with a minimum amount of wear. The vacuum also metal frame, which also acts as the support for
prevents the contacts from tarnishing and the fixed version of the circuit-breaker. The
becoming contaminated. compact structure is sturdy and ensures
mechanical reliability.
Operating mechanism Apart from the isolating contacts and cord with
Along with short travel and low weight, the low plug for connecting the auxiliary circuits, the
speed of the contacts limits the energy required withdrawable version has a truck for racking it
for operation, thus guaranteeing extremely into and out of the switchgear or enclosure with
limited wear in the system. the door closed.
This ensures that the circuit-breaker also requires
very little maintenance.
8 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


2. Description

Interruption principle of ABB interrupters

In a vacuum interrupter, an electric arc begins


the instant in which the contacts separate. It
persists until zero crossing is reached and can
be influenced by magnetic fields.

Diffuse or contracted arc in a vacuum


1
Individual points of fusion form on the surface of
2 the cathode following separation of the contacts.
This leads to the formation of metallic vapors
3
that support the arc itself.
4 The diffuse arcis characterized by expansion over
the contact surface itself and by evenly
5 distributed thermal stress.
The electric arc is always the diffuse type at the
interrupter's rated current value. The contact is
6
only eroded very slightly and the number of
7 interruptions is very high.
As the value of the interrupted current increases
8 (beyond rated value), the electric arc tends to
change from diffuse to contracted owing to the
9
Hall effect.
Starting out from the anode, the arc contracts
10 and tends to concentrate as the current rises.
There is a temperature rise on a level with the
affected area and the contact is consequently
subjected to thermal stress.
1 Stem/terminal 6 Ceramic insulator To prevent the contacts from overheating and
2 Protection 7 Shield
3 Bellows 8 Contacts becoming eroded, the arc is made to rotate. By
4 Interrupter housing 9 Terminal turning, the arc resembles a moving conductor
5 Shield 10 Interrupter housing
through which current passes.

Vacuum interrupter

Diffuse arc. Contraction Contraction on the


on the anode anode and cathode.

Diagram of transition from diffuse arc to contracted arc in a vacuum interrupter.


M E D I U M V O LTA G E P R O D U C T S 9

The spiral contacts of ABB vacuum interrupters contacts, this makes contact erosion negligible
Thanks to their special shape, spiral contacts and above all, allows the interruption process to
generate a radial magnetic field in all areas of the be controlled even with very high short-circuits.
arc column, which concentrates over the contact ABB vacuum interrupters interrupt at the natural
circumferences. zero crossing, thereby preventing the arc from
A self-generated electromagnetic force acts restriking after that event.
tangentially, causing the arc to rapidly rotate A rapidly reduced current charge and rapid
around the contact axis. condensation of the metal vapors at the same
The arc is forced to rotate and involve a wider time as zero crossing, allows maximum dielectric
surface than that of a fixed contracted arc. strength to be restored between the interrupter
Besides minimizing thermal stress on the contacts within microseconds.

Short-circuit
current
Current, Voltage

Arc voltage
Voltage of
the system
Short-circuit current
interruption

Time
Contact
separation

Recovery voltage
(frequency of the system)

Transient recovery voltage (TRV)


(high frequency)

Geometry of radial magnetic field


contact with a rotating vacuum arc. Current and voltage trend evolution in a single phase during vacuum interruption.
10 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


2. Description
Vacuum circuit breakers for generator
switching applications

A complete product line compliant with the


latest Global Dual Logo IEC/IEEE 62271-37-013
Standard, featuring the familiar VD4 design for
easy integration into existing installations.

The VD4G breaker family is the first complete


product line for generator switching applications
developed in accordance with the most recent
Dual Logo IEC/IEEE 62271-37-013 Standard.

Generator switching applications


The globally expanding energy demand is
increasingly covered by decentralized power
plants and small installations using renewable
resources. As the generated power is fed into the
grid by step-up transformers and MV distribution

A B

Generator
Generator Transformer Grid
circuit-breaker

Typical schematic of generator circuit-breaker application

System short-circuit current Generator short-circuit current


60 60

40 40
Short-circuit current [kA]

Short-circuit current [kA]

20 20

0 0

-20 -20

-40 -40

-60 -60
0 25 50 75 100 125 150 175 200 225 250 0 25 50 75 100 125 150 175 200 225 250
Time [ms] Time [ms]

IR(t) [kA] IS(t) [kA] IT(t) [kA] IR(t) [kA] IS(t) [kA] IT(t) [kA]

Failure location A: System-fed fault Failure location B: Generator-fed fault


Fast decaying DC component Slowly decaying and raised DC component results in delayed current zero.
M E D I U M V O LTA G E P R O D U C T S 11

boards, the VD4G family of vacuum circuit- Service safety


breakers offers a reliable and economical solution
Safe distribution switchgear can be created with
for protecting power plant assets.
VD4G circuit-breakers thanks to the complete
range of mechanical and electric locks available
The need to protect the grid as well as the
on request.
generator from failures makes generator circuit-
The locking devices have been designed to
breakers indispensable. The specific current
prevent incorrect operations and allow the
shapes in this kind of application require
installations to be inspected whilst guaranteeing
dedicated circuit-breakers tested for compliance
maximum operator safety.
with the specific duty defined by the latest Global
The key locks and padlocks enable opening and
Standard for Generator applications.
closing and/or racking in and out operations to
Each generator plant has specific technical
be performed.
characteristics. It is essential to perform a
The closed door racking-out device only allows
suitability analysis of the generator circuit-
the circuit-breaker to be racked into or out of the
breaker application for the purpose of selecting
switchgear with the door closed.
the solution most able to fully meet your needs
Anti-racking-in locks prevent circuit-breakers
and ensure plant safety.
with different rated currents from being racked
in, and racking-in and out operations with the
Versions available circuit-breaker closed.
VD4G circuit-breakers are available in fixed and
withdrawable versions with front operating • Complete product line fully compliant with the
mechanism. latest Global Dual Logo IEC/IEEE 62271-37-013
The withdrawable version is available for UniGear Standards
ZS1, switchgear enclosures. • Same familiar VD4 design for easy integration
into existing installations.
• Highly reliable operating mechanisms thanks to
Fields of application a low number of components manufactured by
VD4G circuit-breakers are used in power
mass production systems
generation systems for generation for the full
• Limited and simple maintenance
protection of power generation assets.
• Electrical accessories that can be easily and
quickly installed or replaced thanks to wiring
Standards pre-engineered with plug-socket connectors
VD4G circuit-breakers conform to IEC /IEEE • Mechanical anti-pumping device included in
62271-37-013 Standards. standard equipment
VD4G circuit-breakers undergo the tests • Built-in closing spring loading lever
indicated below and guarantee the safety and
reliability of the apparatus in service in any
installation.
Accessories
VD4G circuit-breakers are available with a full
• Type tests: temperature rise, power frequency
range of accessories to suit all installation
insulation withstand voltage, lightning impulse
requirements.
insulation withstand voltage, short-time and
The operating mechanism has a standardized
peak withstand current, mechanical life, short-
range of accessories and spare parts which are
circuit current making and breaking capacity.
easy to identify and order.
• Individual tests: insulation of the main
The accessories are installed conveniently from
circuits with voltage at power frequency,
the front of the circuit-breaker. Plug-socket
auxiliary circuit and operating mechanism
connectors are used for the electrical
insulation, measurement of the main circuit
connections.
resistance, mechanical and electrical
Operation and maintenance of the apparatus are
operation.
simple and require limited use of resources.
12 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering
Fixed circuit-breakers

Fixed VD4G circuit-breakers (15 kV)

Circuit-breaker VD4G-25/16
Standards IEC/IEEE 62271-37-013 •
Rated voltage Ur [kV] 15
Rated insulation voltage Us [kV] 15
Withstand voltage at 50 Hz common value Ud (1 min) [kV] 38
Impulse withstand voltage common value Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated nominal current (40° C) Ir [A] 1250
Symmetrical short-circuit current IscSFF [kA] 25
Rated system-source
DC component of rated short-circuit breaking current * % 74
short-circuit breaking current
Asymmetrical system-source short-circuit current IascSFF [kA] 36.5
symmetrical short-circuit current Iscg Class G1 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 110
Rated generator-source current Class G1
short-circuit breaking current symmetrical short-circuit current Iscg Class G2 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 130
current Class G2
Rated breaking current under symmetrical short-circuit current IscOOP [kA] 12.5
out-of-phase conditions DC component of rated short-circuit breaking current % 74
Making current Ip [kA] 68.5
Rated operating sequence during short-circuit interruption CO-10 min-CO
Rated short-time withstand current (3s) Ik [kA] 25
Opening time [ms] 33...60
Maximum arcing time (generator-source fault - 130% DC component at contact separation) [ms] 40
Closing time [ms] 30...60
P P H [mm] 461
Maximum W [mm] 450
overall
H D [mm] 424
dimensions
W D Pole distance P [mm] 150
Weight [kg] 73
Standardized table of dimensions 1VCD003891
Operating temperature [°C] - 5 ... + 40
(1) 4000 A with forced ventilation
M E D I U M V O LTA G E P R O D U C T S 13

Types of fixed circuit-breakers available

The circuit-breakers can be completed with the optional accessories indicated on the following pages.

Fixed VD4G circuit-breaker (15 kV)


W = Width of circuit-
Ur Isc Rated current (40 °C) [A] breaker.
D = Depth of circuit-
H = 461 H = 610 H = 636 H = 636 breaker.
D = 424 D = 459 D = 459 D = 459 Circuit-breaker type u/l = Distance between
kV kA bottom and
P = 150 P = 210 P = 275 P = 275 top terminal.
W = 450 W = 600 W = 750 W = 750 l/g = Distance between
bottom terminal
25 1250 VD4G-25 15.12.25 p150 and bearing
surface of
40 2000 VD4G-40 15.20.40 p210
circuit-breaker.
15 40 2000 VD4G-40 15.20.40 p275 P = Horizontal center
distance of pole.
40 3150 VD4G-40 15.32.40 p275
(1) 4000 A with forced
50 3150 VD4G-40 15.32.50 p275 ventilation

VD4G-40/25 VD4G-50/50
• •
15 15
15 15
38 38
95 95
50-60 50-60
2000 2000 3150 4000(1) 3150 4000(1)
40 50
74 74
58.5 73
25 50

110 110

25 37

130 130

20 25
74 74
115 137
CO-10 min-CO CO-10 min-CO
40 50
33...60 <30
34 33
30...60 <55
610 610 636 636 636 636
600 750 750 750 750 750
459 459 459 459 459 459
210 275 275 275 275 275
146 158 177 177 210 210
1VCD000240 1VCD000241 1VCD000242
- 5 ... + 40 - 5 ... + 40
14 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering
Withdrawable circuit-breakers

Withdrawable circuit-breakers
for Unigear ZS1 switchgear (15 kV)

Circuit-breaker VD4G-25/16
Standards IEC/IEEE 62271-37-013 •
Rated voltage Ur [kV] 15
Rated insulation voltage Us [kV] 15
Withstand voltage at 50 Hz common value Ud (1 min) [kV] 38
Impulse withstand voltage common value Up [kV] 95
Rated frequency fr [Hz] 50-60
Rated nominal current (40° C) Ir [A] 1250
Symmetrical short-circuit current IscSFF [kA] 25
Rated system-source
DC component of rated short-circuit breaking current * % 74
short-circuit breaking current
Asymmetrical system-source short-circuit current IascSFF [kA] 36.5
symmetrical short-circuit current Iscg Class G1 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 110
Rated generator-source current Class G1
short-circuit breaking current symmetrical short-circuit current Iscg Class G2 IscGFF [kA] 16
DC component of generator-source short-circuit breaking
% 130
current Class G2
Rated breaking current under symmetrical short-circuit current IscOOP [kA] 12.5
out-of-phase conditions DC component of rated short-circuit breaking current % 74
Making current Ip [kA] 68.5
Rated operating sequence during short-circuit interruption CO-10 min-CO
Rated short-time withstand current (3s) Ik [kA] 25
Opening time [ms] 33...60
Maximum arcing time (generator-source fault - 130% DC component at contact separation) [ms] 40
Closing time [ms] 30...60
P P H [mm] 632
Maximum W [mm] 503
overall
H D [mm] 664
dimensions
W D Pole distance P [mm] 150
Weight [kg] 116
Standardized table of dimensions 1VCD000233
Operating temperature [°C] - 5 ... + 40
(1) 4000 A with forced ventilation
M E D I U M V O LTA G E P R O D U C T S 15

Types of withdrawable circuit-breakers available for UniGear ZS1 switchgear

The circuit-breakers can be completed with the optional accessories indicated on the following pages.

Withdrawable VD4AG circuit-breaker (15 kV)


W = Width of circuit-
Ur Isc Rated current (40 °C) [A] breaker.
H = 461 H = 610 H = 636 H = 636 D = Depth of circuit-
breaker.
D = 424 D = 459 D = 459 D = 459 Circuit-breaker type u/l = Distance between
kV kA bottom and
P = 150 P = 210 P = 275 P = 275
top terminal.
W = 450 W = 600 W = 750 W = 750 l/g = Distance between
bottom terminal
25 1250 VD4G/P-25 15.12.25 p150
and bearing
40 2000 VD4G/P-40 15.20.40 p210 surface of
circuit-breaker.
15 40 2000 VD4G/P-40 15.20.40 p275 P = Horizontal center
40 3150 VD4G/P-40 15.32.40 p275 distance of pole.
(1) 4000 A with forced
50 3150 VD4G/P-40 15.32.50 p275 ventilation

VD4G-40/25 VD4G-50/50
• •
15 15
15 15
38 38
95 95
50-60 50-60
2000 2000 3150 4000(1) 3150 4000(1)
40 50
74 74
58.5 73
25 50

110 110

25 37

130 130

20 25
74 74
115 137
CO-10 min-CO CO-10 min-CO
40 50
33...60 <30
34 33
30...60 <55
691 691 730 730 735 735
681 853 853 853 851 851
643 643 643 643 650 650
210 275 275 275 275 275
190 205 221 221 270 270
1VCD000234 1VCD000243 1VCD000244
- 5 ... + 40 - 5 ... + 40
16 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering
Optional accessories

Accessories with the same number are alternatives to each other.

(*) The minimum current 1 Shunt opening release (-MBO1) 2 Additional shunt opening release (-MBO2)
that the relay with TCS
function (used for mon-
Allows opening command of apparatus to be Similarly to shunt opening release -MBO1, this
itoring coil continuity) enabled by remote control. allows the opening command of the apparatus
detects as a condition
denoting that the trip
This release is suitable for both instantaneous to be transmitted by remote control. It can be
circuit is operating and permanent duty. However, an auxiliary powered by the same circuit as main shunt
correctly (specified for
each relay in the relative
contact -BGB1 de-energizes it after circuit- opening release -MBO1 or by a circuit that is
manual), must be breaker has opened. In the case of completely separate from release -MBO1.
sensibly higher than the
current consumption of
instantaneous service, the current impulse This release is suitable for both instantaneous
the actual coil (~1.5 mA). must last at least 100 ms. and permanent duty. However, an auxiliary
If this fails to occur, al-
ways add, in parallel to
This release can be controlled by the following contact -BGB1 de-energizes it after the circuit-
the TCS, a circuit able devices: coil continuity control (CCC), opening breaker has opened.
to absorb sufficient
current to compensate
circuit supervision (TCS)(*) or the ABB STU To guarantee the release action, the current
the gap while prevent- functionality control device (see accessory 21, impulse must last at least 100 ms.
ing the total current
in the TCS circuit
supplied on request). Continuity functionality can be checked with a
from rising above the continuity control device (CCC), opening
maximum threshold
(Itcs <10 mA for High
circuit supervision (TCS)(*) or the STU
Characteristics
Voltage coils - from functionality control device (see accessory 21,
110V to 250V, and Itcs 24-30-48-60-110...132-
Un supplied on request).
<50 mA for Low Voltage 220...250 V DC
coils from 24 V to 60 V). 48-60-110...127-220...250 • MBO2 has the same electrical and operating
A simple resistor Un
can be sized for the
V AC 50-60 Hz characteristics as release -MBO1.
purpose, depending on Operating limits 65 … 120% Un
the parameters of the
Inrush power (Ps) 60...100 W / VA
TCS and the auxiliary
voltage range used. Continuous power
1.5 W
consumption (Pc)

Electronics self-consumption
(no coil supplied); value
1.5 mA
independent of voltage
applied

Opening time 33...60 ms


Insulation voltage 2000 V 50 Hz (for 1 min)
M E D I U M V O LTA G E P R O D U C T S 17

(*) The minimum current 3 Opening solenoid (-MO3) 4 Shunt closing release (-MC)
that the relay with TCS
function (used for mon-
The opening solenoid (-MO3) is a special Allows closing command of apparatus to be
itoring coil continuity) demagnetization release to be used in transmitted by remote control.
detects as a condition
denoting that the trip
conjunction with a self-supplied overcurrent This release is suitable for both instantaneous
circuit is operating protection relay. and permanent duty. An auxiliary contact that de-
correctly (specified for
each relay in the relative
It is situated in the operating mechanism (left- energizes it after the circuit-breaker has closed is
manual), must be hand side) and is not an alternative to the not envisaged.
sensibly higher than the
current consumption of
additional shunt opening release (-MO2). The permanently supplied release provides the
the actual coil (~1.5 mA). It is not available for 40 and 50 kA circuit- electrical anti-pumping function with both
If this fails to occur,
always add, in parallel
breakers. electrical opening and re-closing commands
to the TCS, a circuit able Should this accessory be required, it must be maintained. To guarantee the closing action, the
to absorb sufficient cur-
rent to compensate the
requested at the time of order since subsequent current impulse must last at least 100 ms.
gap while preventing the application by the customer is not possible. If there is the same supply voltage for shunt
total current in the TCS
circuit from rising above
Note: the compatible protection relays are listed closing release -MBC and under-voltage
the maximum threshold in document: Data sheet 1VCD600854. release -MBU and the circuit-breaker must
(Itcs < 10 mA for High
Voltage coils - from
The opening solenoid (-MBO3) is available in two close automatically when auxiliary voltage
110V to 250V, and Itcs < versions: returns, there must be a delay of at least 50 ms
50 mA for Low Voltage
coils from 24 V to 60 V).
– For DC (release by discharging energy stored in between under-voltage release energizing and
A simple resistor protection relay against self-supplied energizing of the shunt closing release to allow
can be sized for the
purpose, depending on
overcurrent) the closing operation to take place. Continuity
the parameters of the – For AC (release by means of the energy supplied functionality can be checked with a continuity
TCS and the auxiliary
voltage range used.
by an adder transformer on the secondaries of control device (CCC), opening circuit
the protection current transformers (CT is at supervision (TCS)(*) or the STU functionality
customer's charge) control device (see accessory 21, supplied on
request).

Characteristics
24-30-48-60-110...132-
Un
220...250V DC
48-60-110...127-220...250V
Un
AC 50-60Hz
Operating limits 65 … 120% Un
Inrush power (Ps) 60...100 W/VA
Continuous power
1.5 W
consumption (Pc)
Electronics self-consumption
(no coil supplied; value
1.5 mA
independent of voltage
applied
Opening time 33...60 ms
Insulation voltage 2000V 50Hz (for 1 min)
18 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering

Optional accessories

5 Auxiliary contacts of the circuit-breaker • non-wired auxiliary contacts; wiring to the ter-
(-BGB1) for 12 to 24 kV versions minals of the contacts is at the customer's
Electrical signaling of circuit-breaker open/closed charge (photo below left; the terminal box to
can be obtained with a group of 10, 16 or 20 which the other electrical accessories are wired
auxiliary contacts for the fixed version and 10 or is at the top); ask for instructions 1VCD601204
16 auxiliary contacts for the withdrawable (available in the main languages) which describe
version. The standard equipment comprises 10 how to remove, wire the auxiliary contacts more
auxiliary contacts. easily and fit the auxiliary contacts unit back
into its housing;
Note • auxiliary contacts already wired to the terminal
The following are available using the standard box (see photo at top right)
group of ten auxiliary contacts and the maximum
number of electrical accessories:
• for fixed circuit-breakers: three closing contacts Consult circuit diagrams 1VCD400151 for fixed
"a" for signaling circuit-breaker open and five circuit-breakers and 1VCD400155 for
opening contacts "b" for signaling cir- withdrawable circuit-breakers.
cuit-breaker closed;
• for withdrawable circuit-breakers: three closing Note
contacts "a" for signaling circuit-breaker open The main shunt opening release and/or the
and four opening contacts "b" for signaling cir- additional shunt opening release use 1 and/or 2
cuit-breaker closed; closing contacts "a", thereby reducing the number
• Fixed circuit-breakers are available with two fin- of auxiliary contacts available. Always check the
ishing accessories (to be specified when order- maximum number of contacts available if the
ing): equipment is non-standard.
M E D I U M V O LTA G E P R O D U C T S 19

The new layouts can be interchanged with the Electrical characteristics (according to IEC 60947)
existing ones, with the following exceptions: Breaking capacity
Rated current Un
• diagram 1VCD400151 (substitutes 1VCD400046 (10000 interruptions)
and 1VCD400099) 220 V AC Cosj = 0.70 20 A
• fig. 34 on the previous diagrams is represented 220 V DC Cosj = 0.45 10 A
by fig. 31 + fig. 32 on the new diagram; 1 ms 12 A
• fig. 33 and fig. 35 on the previous diagrams are 24 V DC
15 ms 9A
not available with the new layout 50 ms 6A
• diagram 1VCD400155 (substitutes 1 ms 10 A
1VCD400047) 60 V DC
15 ms 6A
50 ms 4.6 A
Auxiliary contacts –BGB1 conform to the 1 ms 7A
following standards/regulations/directives: 110 V DC 15 ms 4.5 A
• IEC 62271-100
50 ms 3.5 A
• IEEE C37.54
1 ms 2A
• EN 61373 cat.1 class B / impact and vibration
220 V DC 15 ms 1.7 A
test
50 ms 1.5 A
• Germanish Loyd regulation / vibrations envis-
1 ms 2A
aged by the shipping registers
250 V DC 15 ms 1.4 A
• UL 508
50 ms 1.2 A
• EN 60947 (DC-21A DC-22A DC-23A AC-21A)
• RoHS Directive

General characteristics Electrical characteristics


(according to IEC 62271-100 class 1)
Insulation voltage to standard 660 V AC
Rated current Un Breaking capacity
VDE 0110, Group C 800 V DC
24 V DC 20 ms 18.8 mA
Rated voltage 24 V ... 660 V
60 V DC 20 ms 7.4 mA
Test voltage 2 kV for 1 min
110 V DC 20 ms 4.2 mA
Maximum rated current 10 A - 50/60 Hz
250 V DC 20 ms 1.8 mA
Breaking capacity Class 1 (IEC 62271-1)
Number of contacts 5
Groups of contacts 10 / 16 / 20
Contact travel 90°
Actuating force 0.66 Nm
Resistance <6.5 mΩ
Storage temperature –30 °C ... +120 °C
–20 °C ... +70 °C
Operating temperature
(-30° ref. ANSI 37.09)
Contact overtemperature 10 K
30,000 mechanical
Mechanical life
operations
Protection class IP20
Cable section 1 mm2
20 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering

Optional accessories

6 Transient contact (-BGB4) 7 Position contact (-BGT3)


This contact closes momentarily (duration > 30 This contact is used together with the locking
ms) upon circuit-breaker opening controlled magnet in operating mechanism (-RLE1) to
remotely with a shunt opening release. prevent remote closing during racking into the
The indication is not provided when opening is unit.
manual and local. A contact (–BGB11) is activated It is only supplied for withdrawable circuit-
by the manual push-button and cuts off the breakers for UniGear ZS1 switchgear and
transient contact closure (–BGB4). PowerCube modules.
The transient contact is activated directly from It cannot be supplied when the transmitted
the main operating shaft when the indication is contacts are required in the truck (-BGT1; -BGT2).
provided only on actual opening of the main
circuit-breaker contacts.
M E D I U M V O LTA G E P R O D U C T S 21

8 Transmitted contacts in truck (-BGT1; -BGT2) 9 Motor operator (-MAS)


Transmitted contacts of withdrawable circuit- The motor operator automatically loads the
breaker (installed in circuit-breaker truck - only closing spring of the circuit-breaker operating
for VD4/P withdrawable circuit-breaker). mechanism. After the circuit-breaker has closed,
These contacts are provided either in addition or the geared motor immediately reloads the closing
as an alternative to the position contacts (for springs.
signaling circuit-breaker racked out) located in In a power failure or during maintenance work,
the unit. They also perform the function of the closing spring can always be loaded by hand
position contact (-BGT3). (using the special crank handle built into the
Contacts -BGT1 and BGT2 have the same general operating mechanism).
and electrical characteristics as auxiliary
contacts "7b. -BGB1, -BGB2, -BGB3". Characteristics
Un 24...30 - 48...60 - 110...130 - 220...250 V–
Un 100...130 - 220...250 V~ 50/60 Hz
Operating limits 85 … 110% Un
≤ 40 kA 50 kA
Power on
inrush (Ps) DC = 600 W; DC = 900 W;
AC = 600 VA AC = 900 VA
DC = 200 W; DC = 350 W;
Rated power (Pn)
AC = 200 VA AC = 350 VA
Loading time 0.2 s 0.2 s
Loading time 6-7 s 6-7 s
2000 V 50 Hz 2000 V 50 Hz
Insulation voltage
(for 1 min) (for 1 min)
22 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering

Optional accessories

10 Contact for signaling closing spring loaded/ 11 Locking magnet on operating mechanism
discharged (-BGS2) (-RLE1)
Consists of a microswitch which remotely Only allows activation of the command with the
signals the state of the closing spring of the supplied electromagnet.
circuit-breaker operating mechanism. The locking electromagnet in the operating
The following signals can be transmitted: mechanism has the same electrical
• contact open: signaling spring loaded characteristics as shunt closing release -MBC.
• contact closed: signaling spring discharged
The two signals must be used for circuits with the
same power supply voltage.
M E D I U M V O LTA G E P R O D U C T S 23

Protections and locks

12 Locking magnet on truck (-RLE2) 13 Interlock for fixed circuit-breaker


This accessory is compulsory for withdrawable Device for fixed circuit-breakers converted into
circuit-breakers for UniGear ZS1 switchgear withdrawable ones by the customer. It allows the
and PowerCube modules. Prevents circuit- customer to make a mechanical lock to prevent
breaker racking into the switchgear when the racking-out/in with the circuit-breaker closed,
auxiliary circuit plug is disconnected. and the circuit-breaker from closing as it travels.
This plug also acts as an anti-insertion lock Note: The device must be requested when
when the rated currents differ from each other. ordering since it must be assembled and tested
Special striker pins prevent the plug from being in the factory.
fitted into the socket if the rated current of the
circuit-breaker is lower than the rated current
of the panel.
Note: a specific version for the circuit-breakers
of ZS8.4 switchgear is available on request.
This accessory is not available when the motor-
operated truck is required.

Characteristics
24 - 30 - 48 - 60 - 110 - 125 -
Un
127 - 132 - 220 - 240 V–

24 - 30 - 48 - 60 - 110 - 125 - 127 -


Un
220 - 230 ... 240 V~ 50/60 Hz
Operating limits 85 … 110% Un
Nominal power (Pn) DC 250 W; AC = 250 VA
Continuous power (Pc) DC = 5 W; AC = 5 VA
Inrush duration 150 ms
Insulation voltage 2000 V 50 Hz (for 1 min)
24 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


3. Selection and ordering

Protections and locks

14 Mechanical door interlock 15 Motor-operated truck (-MAT)


This device prevents circuit-breaker racking-in Allows the circuit-breaker to be racked into and
when the switchgear door is open. It is only out of the switchgear via remote control (only
provided for circuit-breakers used in UniGear ZS1 withdrawable circuit-breakers for UniGear ZS1
switchgear and PowerCube modules fitted with a and ZS8.4 switchgear and PowerCube modules).
special actuator on the door. The motor version with clutch can be ordered on
request and allows racking-in/ out to be
performed in an emergency if the truck motor
fails to operate.

Characteristics
Un 24 - 30 - 48 - 60 - 110 - 220 V–
Operating limits 85 … 110% Un
Rated power (Pn) 40 W
M E D I U M V O LTA G E P R O D U C T S 25

16 STU Shunt Test Unit Two relays and a changeover contact are also
Owing to their construction, the functionality of available on the unit for remote signaling of the
the shunt closing (-MBC) and opening (-MBO1, following two events:
-MBO2) releases cannot be checked with • test failure (resetting occurs automatically
dedicated relays (e.g. TCS Test Control when the alarm stops)
Supervision, CCC Control Coil Continuity) or with • failure of three tests (resetting can only be per-
the REF control and protection unit. The only formed by means of the manual - RESET – but-
device able to check this functionality is the STU ton from the front of the unit).
Shunt Test Unit. Please contact us if you want to
check this functionality using devices other than There is also a manual - RESET – button on the
STU. front of the unit.
This device can be used in conjunction with shunt
opening release (-MBO1; -MBO2) or shunt closing Characteristics
release (-MBC) for the purpose of checking Un 24 ... 250 V AC/DC
functionality and continuity. Maximum interrupted current 6A
The Shunt Test Unit is used to check the Maximum interrupted voltage 250 V AC
continuity of releases with rated operating
voltage between 24 V and 250 V (AC and DC), as
well as the functionality of the electronic circuit
of the release.
Continuity is checked cyclically with an interval of
20 seconds between one test and the next.
LEDs on the front provide optical signals. The
following information is given:
• POWER ON: power supply present
• (-MO) TESTING: test in progress
• TEST FAILED: signal given if a test fails or in the
absence of auxiliary power supply
• ALARM: signal given after three failed tests.
26 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


4. Specific product characteristics

Environmental protection program Spare parts for VD4G up to 40 kA


VD4 circuit-breakers are manufactured in • Shunt opening release
accordance with ISO 14000 Standards (Guidelines • Additional shunt opening release
for environmental management). • Shunt closing release
The manufacturing processes take place in • Geared motor for spring loading with electrical
compliance with the environmental protection signaling of spring loaded
standards as to reduced energy consumption, • Contact for signaling geared motor protection
use of raw materials and the production of waste. circuit-breaker open/closed
Production complies with the environmental • Contact for signaling closing spring loaded/dis-
management system implemented in the medium charged
voltage apparatus manufacturing facility. • Transient contact with momentary closing
Assessment of the environmental impact of every during circuit-breaker opening
stage in a product's life cycle is a method used by • Circuit-breaker auxiliary contacts
ABB to develop environmentally compatible • Locking electromagnet on operating mecha-
components and systems. This goal is pursued by nism
minimizing energy consumption and the overall • Position contact of withdrawable truck
use of raw materials. A policy that begins when • Contacts for signaling connected/isolated
the products are designed by targeted selection • Opening solenoid
of materials, processes and packing. • Key lock for open position
This means that components can be reused and • Isolating door interlock
materials recycled when a product has reached • Protection for opening push-button
the end of its useful life. • Protection for closing push-button
• Locking electromagnet on withdrawable truck
• Set of six isolating contacts.

Designation Item Rated supply Ordering


No. voltage Please contact our Service department and
Auxiliary switch -BGS1 specify the circuit-breaker serial number to order
(with clamp-type terminal) -BGB1
-BGB2
spare parts and check availability.
-EGB3
Auxiliary switch on locking magnet -BGL1
Auxiliary switch for fault signaling -BGB4
1st shunt release OFF -MBO1 24 V ··· 240 V DC
2nd shunt release OFF -MBO2 110 V ··· 240 V AC
Shunt release ON -MBC 24 V ··· 240 V DC
Locking magnet -RLE1 110 V ··· 240 V AC
Undervoltage release with spring mechanism -MBU 24 V ··· 240 V DC
Delayed undervoltage release with spring -MBU see RNSU for supply
mechanism voltage
Indirect overcurrent release with intermediate -MBO3 24 V ··· 240 V DC
current transformer and spring mechanism
Intermediate current transformer for indirect 24 V ··· 220 V DC
overcurrent release
Magnet holder, complete (with integrated 24 V ··· 220 V DC
rectifiers -TB4, -TB1, -TB3, -TB2)
Series rectifier -TB6/-TB7
Loading motor (with gearing) -MAS 24 V ··· 240 V DC
110 V ··· 240 V AC
Push-on sleeve 4.8-2.5 for push-on blade 0.8 thick
(for additional external connections)
M E D I U M V O LTA G E P R O D U C T S 27


5. Overall dimensions

Fixed circuit-breakers
450
VD4G 248

52
95 32
TN 1VCD003891
Ur 15 kV
Ir 1250 A

205
IscSFF 25 kA
30

52
IscGFF 16 (G2)

475
16

451
435

IscOOP 12.5 kA
56

16

217,5
171

77,5
96

56
33 227,5 28,5
49 28,5
24 402 24 45 250 109
406
150 150
417,5 0,8

M10 DEEP.18 M12 DEEP.25

45
22

22

Fixed circuit-breakers
VD4G 600
323
TN 1VCD000240
210 210 130
Ur 15 kV
Ir 2000 A
119

IscSFF 40 kA 32
IscGFF 25 (G2)
IscOOP 20 kA
310
609
30

119

475
435
16

56

15

237,5
171

77,5
97

368 28,5
2,5
24

28,5
172 142 109
48 504 48
424

20 436 1
40
24

2xM10 Deep .18


4xM12 Deep .25
28 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


5. Overall dimensions

Fixed circuit-breakers
VD4G 750
396
TN 1VCD000241
275 275 119 99
Ur 15 kV
Ir 2000 A

119
IscSFF 40 kA
32
IscGFF 25 (G2)
IscOOP 20 kA

310
609
30

119

474
435

56

15

238
16
171

77,5
97
28,5

24
69 270 84
49 28,5
429 424
58 634
440 0,8

M10 Deep .18 20 98


24
40

40 M12 Deep .25

Fixed circuit-breakers
750
VD4G
398
TN 1VCD000242 375 454
275 275 240
Ur 15 kV
189 119
69
Ir 3150 A
IscSFF 40 kA
118
119

IscGFF 25 (G2)
32
IscOOP 20 kA
310
29,5

119

475
16
435

56

237,5
171

2,5

116 28,5
77,5
24

165 28,5 69 270 84


30,5 689 30,5 423
40 435 0,8
4xM12 deep 25
12
40
8

20 2xM10 deep 20
M E D I U M V O LTA G E P R O D U C T S 29

Fixed circuit-breakers
643 Transportbohrung
VD4G 750 beidseitig
459 transport boring
TN 1VCD000285 275 275 on both sides 194 98 166
130 125
Kabeleinführung
Ur 15 kV cable entry

88
Ir 3150 A
IscSFF 50 kA

310
IscGFF 50/37(G2)

40°
431,5
434

IscOOP 25 kA

80°
237,5

4xM12 M 42,5

24
77,5
545
25 700 25
39 274 72 80 M M

550
100

M = Mindestabstand nach DIN VDE 0101


M = minimum distance acc. to DIN VDE 0101

35 M12 / 30 tief

30
695 530 40 M12 / depth 30
750 670

40

Withdrawable circuit-breakers
123
VD4G
492 121
TN 1VCD000233 233 43 110 150 ±1 150 ±1

Ur 15 kV
100

10

Ir 1250 A
78

296

IscSFF 25 kA
IscGFF 16 (G2)
205 ±1

IscOOP 12.5 kA
627
626
619

64

29
260 ±1

78
154 ±1

23
19

341
4
21,5

503 14 25 468
34 302
37 492
531 320 500
382

437

573 ±1,5 max

610

662
30 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


5. Overall dimensions

Withdrawable circuit-breakers
314
VD4G 636
123
44,5 220 25 110 16
TN 1VCD000234

10
Ur 15 kV

119
Ir 2000 A
20
IscSFF 40 kA

310
IscGFF 25 (G2)

698
689

IscOOP 20 kA

119
281
11 23

165
12,5
19

76

26
21,5
19,5
605

4
4

302
14 653 14
25 320 37
359
650
382
640
626 590 52
550 642
210 210
29
590
359

302

Withdrawable circuit-breakers
331
VD4G 842
313
230 48 110
TN 1VCD000243
Ur 15 kV
Ir 2000 A
20

IscSFF 40 kA
310

IscGFF 25 (G2)
698
689

681

IscOOP 20 kA
29
280

89
164
19

19,5

853 13,5 123


4
21,5

880 34 302
320
374 359
275 275 416
590 52
144
695

750
806
836
M E D I U M V O LTA G E P R O D U C T S 31

Withdrawable circuit-breakers
331
VD4G 842
313
230 48 110
TN 1VCD000243
Ur 15 kV
Ir 2000 A
20

IscSFF 40 kA

310
IscGFF 25 (G2)

698
689

681

IscOOP 20 kA
29

280

89
164
19

19,5
853 13,5 123

4
21,5
880 34 302
320
374 359
275 275 416
590 52
144
695

750
806
836

Withdrawable circuit-breakers
124 122 144
VD4G 36
43
36 127 125 76
35
TN 1VBM700160
30 30
Ur 15 kV
158

Ir 3150 A
2)
IscSFF 50 kA
310

424
IscGFF 50/37(G2) 393
384
735
735

353
IscOOP 25 kA 325
307

175 Riegel
Bar
157
280

*)
165
76

22
0
25 320 4
22

383
383 53
735 389
752
294 303
843 **)
851
275 275

16

16
55
32 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram

State of operation represented

The diagrams illustrate the following conditions:


• Circuit-breaker open and connected (only withdrawable circuit-breaker)
• Circuits de-energized
• Closing springs discharged

Graphical symbols for circuit diagrams

Thermal effect Mass, frame Capacitor (gen- Passing make contact


eral symbol) closing momentar-
ily during release

Electromagnetic effect Conductors in Motor Closing position


shielded cable (two (general symbol) contact (limit switch)
conductors shown)

Timing Connection of Opening position


Rectifier with two
conductors contact (limit switch)
half-waves (bridge)

Push-button control Terminal or clamp Make contact Power circuit-breaker


with automatic opening

Key control Socket and plug Break contact Control coil


(female and male) (general symbol)

Earth Resistor Change-over break Lamp


(general symbol) (general symbol) before make contact (general symbol)
M E D I U M V O LTA G E P R O D U C T S 33

Circuit diagram of 15 kV 1VCD400151 fixed circuit-breakers


The circuit diagram shown in this section refers to 15 kV fixed circuit-breakers.
34 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 35
36 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram

Caption Description of the figures


= Figure number of the diagram. Fig. 1 = Circuit of motor for loading closing
* = See note indicated by the letter. springs (see note C).
-BER = SOR Test Unit for monitoring continuity Fig. 2 = Shunt closing release (anti-
of shunt opening and closing release pumping is achieved mechanically),
winding (see note D) (see note D).
-BGB1 = Auxiliary contacts of circuit-breaker. Fig. 3 = Locking magnet. Mechanically
-BGB4 = Auxiliary let-through contact of circuit- inhibits circuit-breaker closing if
breaker with de-energized.
momentary closing during circuit- Consumption can be limited by
breaker opening. connecting a delayed operation
-BGB6 = Contact for electrical signaling of enabling push-button in series.
undervoltage Fig. 5 = Instantaneous undervoltage release
release de-energized. (see note B).
-BGB11 = Contact for cutting off electrical signal Fig. 6, 66 = Circuit of third shunt opening
-BGB4 if opening release with possibility of
operation is performed in the manual continuous control of winding (see
mode. note D).
-BGS1 = Limit contact of spring loading motor. Fig. 7, 67 = Circuit of first shunt opening
-BGS2 = Contact for signaling closing spring release with possibility of
loaded- discharged. continuous control of winding (see
-MAS = Motor for loading closing springs (see note D).
note C). Fig. 9, 69 = Circuit of second shunt opening
-MBC = Shunt closing release (see note D). release with possibility of
-MBO1 = First shunt opening release (see note D). continuous control of winding (see
-MBO2 = Second shunt opening release (see note note D).
D). Fig. 10 = Opening solenoid for release
-MBO3 = Opening solenoid for release outside outside circuit-breaker.
circuit- breaker (see Fig. 11 = Opening solenoid for release
note F). outside circuit-breaker with AC
-MBO4 = Third shunt opening release (see note supply.
D). Fig. 26 = Electrical signaling of closing
-MBU = Under-voltage release (see note B). springs loaded and discharged.
-QAB = Circuit-breaker applications. Fig. 30 = Auxiliary let-through contact of
-RLE1 = Locking magnet. Mechanically inhibits circuit-breaker with momentary
circuit- breaker closing during circuit-breaker
closing if de-energized. opening.
(Consumption can be limited by Fig. 31, 91 = Available auxiliary contacts of
connecting a circuit-breaker (see note E).
delayed operation enabling push- Fig. 32, 92 = Available auxiliary contacts of
button in circuit-breaker (see note E).
series). Fig. 33, 93 = Available auxiliary contacts of
-SFC = Push-button or contact for closing circuit-breaker (see note E).
circuit- breaker. Fig. 60 = Contact for electrical signaling of
-SFO = Push-button or contact for opening undervoltage release de-energized.
circuit- breaker.
-TB7 = Rectifier for release -MBO3.
-XDB = Terminal box of circuit-breaker circuits.
-XDB1 = Connector of circuit-breaker circuits.
-XDB10, ...,17 = Connectors of applications.
M E D I U M V O LTA G E P R O D U C T S 37

Incompatibility E) When fig. 6 is required, contact -BGB1 (23-24) of


fig.32 is not available.
The circuits indicated in the following figures
When fig. 7 is required, contact -BGB1 (3-4) of
cannot be supplied at the same time in the same
fig. 31 is not available.
circuit-breaker:
When fig. 9 is required, contact -BGB1 (7-8) of
fig. 31 is not available.
5-6-66 7-67 9-69 31-91 32-92 33-93
When fig. 32 is required, it is obligatory to
10-11
supply the auxiliary contacts of fig. 31.
When fig. 33 is required, it is obligatory to
supply the auxiliary contacts of fig. 32.
Notes When fig. 66 is required, contact -BGB1 (23-24)
of fig. 92 is not available.
A) The circuit-breaker is equipped solely with the
When fig. 67 is required, contact -BGB1 (3-4) of
applications specified in the order confirmation.
fig. 91 is not available.
Consult this catalog for information about how
When fig. 69 is required, contact -BGB1 (7-8) of
to make out an order.
fig. 91 is not available.
B) The undervoltage release can be supplied
When fig. 92 is required, it is obligatory to
for energizing with voltage derived from the
supply the auxiliary contacts of fig. 91.
supply side of the circuit-breaker or from an
When fig. 93 is required, it is obligatory to
independent source.
supply the auxiliary contacts of fig. 92.
Circuit-breaker closing is only enabled when the
Figs. 33 and 93 are not available for VD4 50 kA.
release is energized (closing lock is obtained
F) Figs. 10 and 11 are only available for VD4 up to
mechanically). If there is the same power supply
31.5 kA.
for the shunt closing and under-voltage releases
G) The energizing voltage must be the same for
and the circuit-breaker must close automatically
both signals.
when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage
release's enabling instant and energizing of the
shunt closing release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out
whether several motors for loading the closing
springs can be operated at the same time. To
prevent excessive power draw, the springs must
be loaded by hand before the auxiliary circuit is
powered.
D) The circuit for monitoring the continuity of the
release windings must only be used for that
purpose. The SOR Test Unit can be used for
checking the continuity of the various different
releases.
-MBO4 incompatible with -MBU.
-MBO4 not available for VD4 50 kA.
38 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram

Circuit diagram of withdrawable circuit-breakers for UniGear switchgear


15 kV 1VCD 400155
M E D I U M V O LTA G E P R O D U C T S 39

The circuit diagram given in this section refers to withdrawable circuit-breakers for UniGear switchgear.
See diagram 1VCD400156 for withdrawable circuit-breakers with motor-operated truck.
40 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 41
42 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S


6. Electric circuit diagram

Caption -SFC = Push-button or contact for closin


circuit-breaker
= Figure number of the diagram.
-SFO = Push-button or contact for closing
* = See note indicated by the letter.
circuit-breaker.
-BER = SOR Test Unit for monitoring continuity
-TB7 = Rectifier for release -MBO3.
of shunt opening and closing release
-XDB = Terminal box of circuit-breaker circuits.
winding (see note D)
-XDB10, ... , 27 = Connectors of applications
-BGB1 = Auxiliary contacts of circuit-breaker.
-XDB28 = Connector of applications.
-BGB4 = Auxiliary let-through contact of circuit-
breaker with momentary closing during
circuit-breaker opening.
-BGB6 = Contact for electrical signaling of Description of the figures
undervoltage release de-energized.
Fig. 1 = Circuit of motor for loading closing
-BGB11 = Contact for cutting off electrical
springs (see note C).
signal -BGB4 if opening operation is
Fig. 2 = Shunt closing release (anti-pumping is
performed in the manual mode.
achieved mechanically). (see note D).
-BGD1 = Enclosure door position contact.
Fig. 3 = Locking magnet. Mechanically inhibits
-BGS1 = Limit contact of spring loading motor.
circuit-breaker closing if de-energized.
-BGS2 = Contact for signaling closing springs
(If -RL1 is required, provide this
loaded-discharged.
figure when fig.31 or 32 are selected).
-BGT1 = Electrical signaling contacts for circuit-
Consumption can be limited by
breaker in racked-in position (see note
connecting a delayed push-button in
F)
series so as to enable the operation.
-BGT2 = Electrical signaling contacts for circuit-
Fig. 4 = Locking magnet. Mechanically inhibits
breaker in isolated position (see note F)
circuit-breaker closing if de-energized.
-BGT3 = Circuit-breaker position contact, open
(If -RL1 is required, provide this
during isolating travel.
figure when fig.33 or 34 are selected).
-MAS = Motor for loading closing springs (see
Consumption can be limited by
note C).
connecting a delayed push-button in
-MBC = Shunt closing release (see note D).
series so as to enable the operation.
-MBO1 = First shunt opening release (see note
Fig. 5 = Instantaneous undervoltage release (see
D).
note B).
-MBO2 = Second shunt opening release (see note
Fig. 6 = Circuit of third opening release with
D).
continuous control of winding (see note
-MBO3 = Opening solenoid for release outside
D).
circuit-breaker.
Fig. 7 = Circuit of first opening release with
-MBO4 = Third shunt opening release (see note
continuous control of winding (see note
D).
D).
-MBU = Under-voltage release (see note B).
Fig. 8 = Locking magnet (on truck). Mechanically
-QAB = Circuit-breaker applications.
inhibits circuit-breaker racking-in and
-RLE1 = Locking magnet. Mechanically inhibits
isolating if de-energized. (Consumption
circuit-breaker closing if de-energized.
can be limited by connecting a delayed
(Consumption can be limited by
push-button in series so as to enable the
connecting a delayed push-button in
operation).
series so as to enable the operation).
Fig. 9 = Circuit of second opening release with
-RLE2 = Locking magnet (on truck).
continuous control of winding (see note
Mechanically inhibits circuit-breaker
D).
racking-in and isolating if de-
Fig. 10 = Opening solenoid for release outside
energized. (Consumption can be limited
circuit-breaker.
by connecting a delayed push-button in
Fig. 11 = Opening solenoid for release outside
series so as to enable the operation).
circuit-breaker with AC supply.
M E D I U M V O LTA G E P R O D U C T S 43

Fig. 26 = Electrical signaling of closing springs C) Check power of auxiliary circuit to find out
loaded and discharged. whether several motors for loading the closing
Fig. 30 = Auxiliary let-through contact of circuit- springs can be operated at the same time. To
breaker with momentary closing during prevent excessive power draw, the springs must
circuit-breaker opening. be loaded by hand before auxiliary circuit is
Fig. 31, ... , 34 = Available auxiliary contacts of powered.
circuit-breaker (see note E). D) The circuit for monitoring the continuity of the
Fig. 51 = Contacts for electrical signaling of release windings must only be used for that
circuit-breaker in racked-in and isolated purpose. The SOR Test Unit can be used for
positions located on circuit-breaker checking the continuity of the various different
truck (obligatory when fig. 31 or 32 are releases:
required). -MBO4 incompatible with -MBU.
Fig. 52 = Contacts for electrical signaling -MBO4 not available on Vmax and VD4 50kA.
of circuit-breaker in racked-in and E) When fig. 6 is required, contact -BGB1 (23-24) of
isolated positions located on circuit- fig. 32-34 is not available.
breaker truck (supplied on request when When fig. 7 is required, contact -BGB1 (3-4) of
fig. 33 or 34 are required). fig. 31-32-33-34 is not available.
Fig. 60 = Contact for electrical signaling When fig. 9 is required, contact -BGB1 (7-8) of
of undervoltage release de-energized. fig. 31-32-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB1
(31-32) of fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB1 (25-26)
Incompatibility of fig. 32 and 34 is not available.
The circuits indicated in the following figures
F) The contacts for electrical signaling of circuit-
cannot be supplied at the same time in the same
breaker in isolated and racked-in position
circuit-breaker:
(-BGT1 and BGT2) shown in fig. 51-52 are
3-4 3-33-34 4-31-32 5-6 10-11 installed on circuit-breaker truck (movable
31-32-33-34 31-32-52 33-34-51 51-52 part).
G) Fig. 3 is supplied when fig. 31 or 32 are required.
Fig. 4 is supplied when fig. 33 or 34 are required
(in this case, it is obligatory to supply –BGT3).
Notes H) Fig. 10 is only available for VD4 up to 31.5 kA and
A) Circuit-breaker is equipped solely with the Vmax.
applications specified in the order confirmation. Fig. 11 is only available for VD4 up to 31.5 kA.
Consult this catalog for information about how I) The energizing voltage must be the same for
to make out an order. both signals.
B) The undervoltage release can be supplied
for energizing with voltage derived from the
supply side of the circuit-breaker or from an
independent source.
Circuit-breaker closing is only enabled when the
release is energized (closing lock is obtained
mechanically). If there is the same power supply
for the shunt closing and under-voltage releases
and the circuit-breaker must close automatically
when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage
release's enabling instant and energizing of the
shunt closing release.
Incompatible with -MBO4.
44 V D 4 G M E D I U M V O LTA G E VA C U U M C I R C U I T- B R E A K E R S
M E D I U M V O LTA G E P R O D U C T S 45

Contact us

ABB S.p.A.
ABB SACE Division
Medium Voltage Products
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: info.mv@it.abb.com

ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
D-40472 Ratingen
1VCP000671 - Rev. A, en - Technical catalog - 2017.04 (VD4-50 kA) (gs)

Phone: +49(0)2102/12-1230
Fax: +49(0)2102/12-1916
E-mail: powertech@de.abb.com

www.abb.com

The data and illustrations are not binding. We reserve


the right to make changes without notice in the course
of technical development of the product.

© Copyright 2017 ABB. All rights reserved.