Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

32 V D 4 G M E D I U M V O LTA G E VA C U UM C I R C U I T- B R E A K E R S


6. Electric circuit diagram

State of operation represented

The diagrams illustrate the following conditions:


• Circuit-breaker open and connected (only withdrawable circuit-breaker)
• Circuits de-energized
• Closing springs discharged

Graphical symbols for circuit diagrams

Thermal effect Mass, frame Capacitor (gen- Passing make contact


eral symbol) closing momentar-
ily during release

Electromagnetic effect Conductors in Motor Closing position


shielded cable (two (general symbol) contact (limit switch)
conductors shown)

Timing Connection of Opening position


Rectifier with two
conductors contact (limit switch)
half-waves (bridge)

Push-button control Terminal or clamp Make contact Power circuit-breaker


with automatic opening

Socket and plug Break contact Control coil


(female and male) (general symbol)

Earth Resistor Change-over break Lamp


(general symbol) (general symbol) before make contact (general symbol)
38 V D 4 G M E D I U M V O LTA G E VA C U UM C I R C U I T- B R E A K E R S


6. Electric circuit diagram

Circuit diagram of withdrawable circuit-breakers for UniGear switchgear


15 kV 1VCD 400155
M E D I U M V O LTA G E P R O D U C T S 39

The circuit diagram given in this section refers to withdrawable circuit-breakers for UniGear switchgear.
See diagram 1VCD400156 for withdrawable circuit-breakers with motor-operated truck.
40 V D 4 G M E D I U M V O LTA G E VA C U UM C I R C U I T- B R E A K E R S


6. Electric circuit diagram
M E D I U M V O LTA G E P R O D U C T S 41
42 V D 4 G M E D I U M V O LTA G E VA C U UM C I R C U I T- B R E A K E R S


6. Electric circuit diagram

Caption -SFC = Push-button or contact for closin


circuit-breaker
= Figure number of the diagram.
-SFO = Push-button or contact for closing
* = See note indicated by the letter.
circuit-breaker.
-BER = SOR Test Unit for monitoring continuity
-TB7 = Rectifier for release -MBO3.
of shunt opening and closing release
-XDB = Terminal box of circuit-breaker circuits.
winding (see note D)
-XDB10, ... , 27 = Connectors of applications
-BGB1 = Auxiliary contacts of circuit-breaker.
-XDB28 = Connector of applications.
-BGB4 = Auxiliary let-through contact of circuit-
breaker with momentary closing during
circuit-breaker opening.
-BGB6 = Contact for electrical signaling of Description of the figures
undervoltage release de-energized.
Fig. 1 = Circuit of motor for loading closing
-BGB11 = Contact for cutting off electrical
springs (see note C).
signal -BGB4 if opening operation is
Fig. 2 = Shunt closing release (anti-pumping is
performed in the manual mode.
achieved mechanically). (see note D).
-BGD1 = Enclosure door position contact.
Fig. 3 = Locking magnet. Mechanically inhibits
-BGS1 = Limit contact of spring loading motor.
circuit-breaker closing if de-energized.
-BGS2 = Contact for signaling closing springs
(If -RL1 is required, provide this
loaded-discharged.
figure when fig.31 or 32 are selected).
-BGT1 = Electrical signaling contacts for circuit-
Consumption can be limited by
breaker in racked-in position (see note
connecting a delayed push-button in
F)
series so as to enable the operation.
-BGT2 = Electrical signaling contacts for circuit-
Fig. 4 = Locking magnet. Mechanically inhibits
breaker in isolated position (see note F)
circuit-breaker closing if de-energized.
-BGT3 = Circuit-breaker position contact, open
(If -RL1 is required, provide this
during isolating travel.
figure when fig.33 or 34 are selected).
-MAS = Motor for loading closing springs (see
Consumption can be limited by
note C).
connecting a delayed push-button in
-MBC = Shunt closing release (see note D).
series so as to enable the operation.
-MBO1 = First shunt opening release (see note
Fig. 5 = Instantaneous undervoltage release (see
D).
note B).
-MBO2 = Second shunt opening release (see note
Fig. 6 = Circuit of third opening release with
D).
continuous control of winding (see note
-MBO3 = Opening solenoid for release outside
D).
circuit-breaker.
Fig. 7 = Circuit of first opening release with
-MBO4 = Third shunt opening release (see note
continuous control of winding (see note
D).
D).
-MBU = Under-voltage release (see note B).
Fig. 8 = Locking magnet (on truck). Mechanically
-QAB = Circuit-breaker applications.
inhibits circuit-breaker racking-in and
-RLE1 = Locking magnet. Mechanically inhibits
isolating if de-energized. (Consumption
circuit-breaker closing if de-energized.
can be limited by connecting a delayed
(Consumption can be limited by
push-button in series so as to enable the
connecting a delayed push-button in
operation).
series so as to enable the operation).
Fig. 9 = Circuit of second opening release with
-RLE2 = Locking magnet (on truck).
continuous control of winding (see note
Mechanically inhibits circuit-breaker
D).
racking-in and isolating if de-
Fig. 10 = Opening solenoid for release outside
energized. (Consumption can be limited
circuit-breaker.
by connecting a delayed push-button in
Fig. 11 = Opening solenoid for release outside
series so as to enable the operation).
circuit-breaker with AC supply.
M E D I U M V O LTA G E P R O D U C T S 43

Fig. 26 = Electrical signaling of closing springs C) Check power of auxiliary circuit to find out
loaded and discharged. whether several motors for loading the closing
Fig. 30 = Auxiliary let-through contact of circuit- springs can be operated at the same time. To
breaker with momentary closing during prevent excessive power draw, the springs must
circuit-breaker opening. be loaded by hand before auxiliary circuit is
Fig. 31, ... , 34 = Available auxiliary contacts of powered.
circuit-breaker (see note E). D) The circuit for monitoring the continuity of the
Fig. 51 = Contacts for electrical signaling of release windings must only be used for that
circuit-breaker in racked-in and isolated purpose. The SOR Test Unit can be used for
positions located on circuit-breaker checking the continuity of the various different
truck (obligatory when fig. 31 or 32 are releases:
required). -MBO4 incompatible with -MBU.
Fig. 52 = Contacts for electrical signaling -MBO4 not available on Vmax and VD4 50kA.
of circuit-breaker in racked-in and E) When fig. 6 is required, contact -BGB1 (23-24) of
isolated positions located on circuit- fig. 32-34 is not available.
breaker truck (supplied on request when When fig. 7 is required, contact -BGB1 (3-4) of
fig. 33 or 34 are required). fig. 31-32-33-34 is not available.
Fig. 60 = Contact for electrical signaling When fig. 9 is required, contact -BGB1 (7-8) of
of undervoltage release de-energized. fig. 31-32-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB1
(31-32) of fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB1 (25-26)
Incompatibility of fig. 32 and 34 is not available.
The circuits indicated in the following figures
F) The contacts for electrical signaling of circuit-
cannot be supplied at the same time in the same
breaker in isolated and racked-in position
circuit-breaker:
(-BGT1 and BGT2) shown in fig. 51-52 are
3-4 3-33-34 4-31-32 5-6 10-11 installed on circuit-breaker truck (movable
31-32-33-34 31-32-52 33-34-51 51-52 part).
G) Fig. 3 is supplied when fig. 31 or 32 are required.
Fig. 4 is supplied when fig. 33 or 34 are required
(in this case, it is obligatory to supply –BGT3).
Notes H) Fig. 10 is only available for VD4 up to 31.5 kA and
A) Circuit-breaker is equipped solely with the Vmax.
applications specified in the order confirmation. Fig. 11 is only available for VD4 up to 31.5 kA.
Consult this catalog for information about how I) The energizing voltage must be the same for
to make out an order. both signals.
B) The undervoltage release can be supplied
for energizing with voltage derived from the
supply side of the circuit-breaker or from an
independent source.
Circuit-breaker closing is only enabled when the
release is energized (closing lock is obtained
mechanically). If there is the same power supply
for the shunt closing and under-voltage releases
and the circuit-breaker must close automatically
when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage
release's enabling instant and energizing of the
shunt closing release.
Incompatible with -MBO4.

You might also like