1 Design Stipulation :
a. Charectristic Stregth of Concrete (fck) : 30 Mpa
b. Maximum Size of Aggregate (MSA) : 20 mm
c. Minimum Cement Content (including mineral admixture) : 300 kg (As per IS 456: 2000, Table 5)
d. Mineral Admixture, if any : 0 kg
e. Maximum Cement Content (excluding mineral admixture) : 450 kg (As per IS 456: 2000, Table 5)
f. Exposure Condition : Severe (As per IS 456:2000, Table 3)
g. Workability required at the time of placement : 50-100 mm slump
i. Method of Placing : chute and manual
j. Degree of Quality Control : Good
k. Standard Deviation (S) : 6.5 (Assumed as per IS 10262:2019, Table 2)
l. Any Other Specific Requirement : -
m. Material Details :
Ingredients Type Source / Make Remarks
Cement OPC-43 Birla uttam -
Water Drinking Water Borewell -
Coarse Aggregate Crushed and Angular Tirupati Crusher Nalkheda -
Fine Aggregate River Sand Hoshangabad -
Chemical Admixture - - -
Page 1 of 4
RCC CONCRETE MIX DESIGN
3 Target Mean Strength of Concrete for Mix Proportioning (fck') : (IS 10262:2019, Clause No. 4.2)
4 Selection of Water - Cement (or, Cementitious) Ratio, W/C : (IS 10262:2019, Clause No. 5.1)
Maximum Water-Cement Ratio for Durability Requirement : 0.42 As per fig. 1 of IS 10262:2019
Water-Cement Ratio for Target Mean Strength : 0.45 As per IS 456: 2000, Table 5
Adopt Lower Water-Cement Ratio from above : 0.42
Here, we are taking : 0.40 (Based on trials done)
Check: Here w/c ratio : 0.40 < 0.420 HENCE O.K.
5 Selection & Adujstment of Water content & Admixture content : (IS 10262:2019, Clause No. 5.3)
Maximum Water Content for Nominal MSA 20mm : 186 kg (for 50mm slump) As per IS 10262:2019, Table 4
Adjustments for Workability Requirement : 11.16 kg (for 100mm slump) As per IS 10262:2019, Clause No. 5.3
(Total 6% water increased for slump requirement of
50-100mm)
Hence, Total Water Content : 197.16 kg
As water reducing Admixture is used, water content can be reduced up to 30 %.
Hence, arrived water content : 197 kg (Here, 0.00% water reduction is done.)
% by weight of total Cementitious
Admixture : 0
(Cement + mineral admixture, if any)
Total Water content : 158 (Based on several trials)
6 Cementitious Content : (IS 10262:2019, Clause No. 5.4)
Total Cementitious Content : 395 kg (Based on several trials)
Cement Content : 395 kg
Check: The selected cementitious content is more than the specified minimum cementitious content & cement content is less than maximum cement
content given in above design stipulation.
HENCE O.K.
Page 2 of 4
RCC CONCRETE MIX DESIGN
7 Selection & Adjustments of Coarse Aggregate : (IS 10262:2019, Clause No. 5.5 & Table 5)
Volume of CA for volume of Total Aggregate : 0.62 (for 20mm agg. & zone 2 sand, W/C - 0.5)
Adjustment for change in shape of aggregate : 0.00
Adjustment for change in zone of fine aggregate : 0.00
For Water-Cement Ratio = 0.45 : 0.63 (volume of CA is increase rate of +/- 0.01 for every +/- 0.05 change
in W/C Ratio)
For Pumpable Cocrete : 0.630 (Aggregate volume decreased 0% for pumpable concrete)
CA of total aggregate by absolute volume : 63.0 %
Here, we are adopting CA of total aggregate : 59.0 % (Based on several trials done)
Hence, volume of FA of total aggregate : 41.0 %
8 Combination of Different Coarse Aggregate Fractions & Estimation of Fine Aggregate Proportion : As per IS 10262:2019, Clause No. 5.6
Page 3 of 4
RCC CONCRETE MIX DESIGN
Notes:
1 The mix design is based on the samples of the material & the materials were tested as per relevant Indian Standard.
2 Admiture Dosage can be adjust at site as per requirement for workability, depends upon the site environment conditions. But it should not be more than
2.00% in any case.
3 Coarse Aggregate & Fine Aggregate ratio can be adjusted according to its actual grading at the time of mix production, subjected to confirming the
requirements of Table 7 & Table 10, IS 383:2016.
Page 4 of 4