Welding Inspection Report

FRM-SCTS/INS/VI-01 REV.00 20/04/2021

Date Of Inspection: 10-10-2021 Job order No.: INS/003-10/2021 Report No.: INS/003-01/2021
Client Name: CHICAGO MAINTANENCE AND CONSTRUCTION CO.LLC

Requested By: Arkan Shade Systems , Contact No.: 065301556

Email Address: arkan1emirates.net@ae Location: ABHUDHABI , UAE

EQUIPMENT USED

Instruments Make Tag / Serial N o Certificate


Weld gauge Insize SCTS/WG-01 QMC/L456-01/2020
Magnifier 20x Augesto SCTS/MGL-01 QMC/L456-12/2020
Lux meter Extech SCTS/LM-01 QMC/L456-26/2020
THERMO CRAYONS Markal NA NA
TESTED MATERIAL
Description: SHADE STRUCTURE WELD
Detail : Collums & Eyepads Company ID: Registration No.

Surface Condition : GOOD Dimension: ø 8" * 12.7 thick & 400 x 400
mm baseplate - 8mm full weld

METHOD DESCRIPTION
Examination Method VISUAL
Order No./ Drg. No. Joint Welder No. Tested Length Evaluation Result Remarks
No.

P 1 TO 6 ;- FULL WELD NSD ACC NA

ARN-SD-003

E 1 TO 6 ;- FULL WELD NSD ACC NA

NOTE: NSD: No Standard Deviation C : Crack CP : Clustered porosity S : Slag IP : Incomplete Penetration UC : Under cut
IP : Iincomplete Penetration
Reference Procedure Specification : ASME Section V Acceptance Criteria: ASME B31.3
Test Procedure No.: SCTS/INS/VBT-02
TESTED BY APPROVED BY
Engg EBIN ELDHO Authorized Approved Signatory
NDT LEVEL II

*This Report becomes invalid, if any alteration/major repair/ modification made on the equipment. Electronic signature and stamp are not allowed.

This report is granted subject to the condition that is understood and agreed that nothing herein contained shall be deemed to relieve any designer, manufacturer, seller,
supplier, repairer or operator of any warranty, express or implied, and Spectex calibration & Testing services liability shall be limited to the acts or omissions of its
employees, agents and subcontractors. Under no circumstances whatsoever shall Spectex calibration & Testing services be liable for any injury or damage to any
person or occurring by reason of negligent operation or any defect in materials, machinery, equipment or other items other than such defects ascertainable by normally
accep ted standards and only those items actually inspected by Spectex calibration & Testing services and which are covered by this report. This report shall not be
reproduced except in full without the approval of the Inspection Body and the client.
PAINTING
INSPECTION REPORT
FRM-SCTS/INS/PAI-01 REV.00 20/04/2021

Date Of Inspection: 10-10-2021 Job order No.: INS /003-10/2021 Report No.: SCTS/INS/003-02/2021

Client : CHICAGO MAINTANENCE AND CONSTRUCTION CO.LLC


Sub Contractor : ARKAN SHADES SYSTEMS Contact No.: 065301556
Email Address: arkan1emirates.net@ae
Location: ABU DHABI

JOB Description: Paint Details


Drawing No : 57870-00SIT-AL-AIC-ASS-SPD-001
SHS 100 × 100 × 6 mm
Primer Final Coat
SHS 100 × 50 × 4 mm
National paint RL9001 National paint RL9001

SHS 50 × 50 × 4 mm Batch No Batch No

2322797-1-*-1 2326660-1-*-1

EQUIPMENT USED
Equipment for inspection : DFT GAUGE
Make : Elcometer Range 0-1500 µm
Model : 456 F Serial No 2282-01

PAINTING INSPECTION DETAIL

DFT Minimum Microns


ITEM Humidity (%) Temp(°C)
1 2 3 Avg

Primer 1 Coat 63% 34 °C 97 98 99 98

Primer 2 Coat 62% 33 °C 199 198 199 199

Final 1 Coat 64% 32 °C 301 302 301 301

Final 2 Coat 63% 34 °C 401 399 402 401

Test Procedure No.: SCTS/INS/07


TESTED BY APPROVED BY
Eng JITHIN JAYADAS Authorized Approved Signatory

This report is granted subject to the condition that is understood and agreed that nothing herein contained shall be deemed to relieve an y designer, manufacturer, seller, supplier, repairer or
operator of any warranty, express or implied, and Spectex calibration & Testing services liability shall be limited to the acts or omissions of its employees, agents and subcontractors. Under no
circumstances whatsoever shall Spectex calibration & Testing services be liable for any injury or damage to any person or occurring by reason of negligent operation or any defect in materials,
machinery, equipment or other items other than such defects ascertainable by normally accep ted standards and only those items actually inspected by Spectex calibration & Testing services
and which are covered by this report. This report shall not be reproduced except in full without the approval of the Inspection Body and the client.