Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TECHNICAL DATA SHEET

APOSTAR
AR Single+ 3
Output
Rated power kVA 3
Rated active power kW 2,7
Rated Power factor 0,9
Rated current A 14
Rated voltage V 220 / 230 / 240 adjustable
Voltage tolerance
static % ± 1,5
dynamic % ±5
Settling time ms 20
Rated frequency Hz 50 / 60
Frequency tolerance
line commutation % ±1
self commutation % ± 0,1

Voltage distortion (EN 62040-1)


linear load % ≤2
non linear load % ≤4

Overload capability
125% s 4
150% s 0,5
Maximum short-circuit current (rms) 27A / 300ms
Maximum crest factor 3:1

Input
Rated voltage V 184 - 276
Rated frequency Hz 50 / 60
Rated current A 11
Maximum current A 14
cos φ ≥ 0,99

www.piller.com
Issue:
12.Mrz.18

Modifications reserved
TECHNICAL DATA SHEET
APOSTAR
AR Single+ 3

General data
efficiency at 100% load % 92
Dimensions
Width mm 87(2U)
Depth mm 625
Height mm 450

Weight kg 32
Wall-distance backside mm 100
Noise level dB(A) ≤ 40
Standard colour black
Ambient temperature °C 0-40
Ambient humidity (without condensation) % 0-90
Protection type IP 20
Interfaces (Standard)
Communication 1x RS232 & 1x USB
Potential free changeover contacts
Radio interference level (for general applications) EMC IEC 62040-2 / C2
UPS classification VFI SS 111
Customer Interfaces LC Display

Battery
Nominal number of cells 36

Voltage per Cell V 2


Automatic battery test adjustable