Recommended Relay Settings For GPR
Recommended Relay Settings For GPR
ZZZ-ZZZZ
FCF50001B
5G2F0406
[1] General
This document is applied for relay setting of generator protection relay for OLKARIA Ⅳ GEOTHERMAL
POWER PLANT.
The each relay setting values are applied for M-3425A and SEL-300G relay.
The relay setting values shown in following are recommendation, so it is requested that final
setting value will be decided by customer.
Device Protection relay
No. Description Page
No. M-3425A SEL-300G
1 21 Phase distance relay ○ Not use 4
2 24 3Phase Volt per hertz relay ○ ○ 6
3 27 Under-voltage relay ○ ○ 8
4 27TN Third-harmonic Under-voltage relay ○ ○(64G2) 9
5 32 Reverse power relay ○ ○ 10
6 40 Loss of field relay ○ ○ 11
7 46 Negative Phase sequence over current relay ○ ○ 13
49 Winding thermal protection Not use Not use
50 Instantaneous over-current relay Not use Not use
8 50/27 Inadvertent energizing relay ○ ○ 15
9 50BF Breaker failure ○ ○ 16
50DT Definite time over-current relay Not use Not use
50N Instantaneous neutral over-current relay Not use Not use
51N Inverse time neutral over-current relay Not use Not use
10 51V Inverse time over-current with voltage restraint ○ ○ 17
11 59 Over-voltage relay ○ ○ 19
59D Third Harmonic Voltage Differential Not use Not use
12 59N Neutral over-voltage relay ○ ○(64G1) 20
59X Multipurpose over-voltage relay Not use Not use
13 60FL VT fuse loss detection relay ○ ○ 21
67N Residual Directional Over-current Not use Not use
14 78 Out-of step relay ○ ○ 22
15 81 Frequency relay ○ ○ 24
81A Under frequency Accumulation Not use Not use
81R Rate of change Frequency relay Not use Not use
16 87 Gen. Differential relay ○ ○ 26
87GD Ground differential relay Not use Not use
―― Configuration I/O Matrix (M-3425A) 27
―― SEL-300G Relay Settings Sheet Group Settings (SEL-300G) 29
Note :
(1) Relay element marked with ○ is included in the relay, and is applied.
(2) “―” means the relay function is not included in the relay.
1
5G2F0406
2
5G2F0406
3
5G2F0406
GENERATOR
TRANSFORMER
GEN. TR. ; 90 MVA
VT 220 / 11 kV
%IZ = 12 %
GEN ; 88.55 MVA
11 kV
G 50 Hz
VT ;11,000 / 110 V
CT ; 5,000 / 1 A
CT
21
4
5G2F0406
1.3 Setting
(1) Impedance setting
VT ratio rv = 11,000 / 110 = 100
CT ratio rc = 5,000 / 1 = 5,000
88.55 11²
Impedance of generator transformer : Zt = 90 × 11² × 12 = 11.81 %
11²
× 0.1181 = 0.161 Ω
88.55
Offset : 0.0Ω
Therefore, Circle Diameter #1 = 8.1 + 0.0 = 8.1 Ω
5
5G2F0406
GEN;88.55 MVA
11 kV
VT 50 Hz
VT; 11,000/110 V
24
2.3 Setting
As per coordination curve of next page, the relay is set as above item 2.1.
6
5G2F0406
#24 Curves
1.5 1.5
1.4 1.4
#24
Volt/Hertz(P.U)
1.1 1.1
7
5G2F0406
3. Under-voltage relay ( 27 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-23
Purpose : under voltage protection
VT
27 GEN;88.55 MVA
11 kV
50 Hz
VT ;11,000/110 V
3.3 Setting
8
5G2F0406
4. Third-harmonic Under-voltage relay ( 27TN )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-24
Purpose : for 100% stator ground-fault protection
VT
G GEN;88.55 MVA
11 kV
50 Hz
NGT; 11,000/190 V
NGT 27TN
VT ; 11,000/110 V
4.3 Setting
Setting will be done after measuring of third harmonic voltage during commissioning at site.
(1) Trip setting
Pickup #1 will set at approx. 50 % of measured minimum voltage.
Time delay #1 will set at 150 cycles ( 3 sec ).
9
5G2F0406
5. Reverse power relay ( 32 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-28
Purpose : for generator motoring protection
VT
G GEN;88.55 MVA
11 kV
50 Hz
CT VT; 11,000/110V = 100
32 CT; 5,000/1A = 5,000
5.3 Setting
Total loss of turbine and generator is as follows ;
Loss of turbine is 750 kW.
Loss of generator is 430 kW.
Total loss is 1,180 kW.
10
5G2F0406
6. Loss of field relay ( 40 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-33
Purpose : protection for loss of field
GENERATOR
TRANSFORMER
VT GEN;88.55 MVA
11 kV
50 Hz
Xds = 189 %
G Xd’s = 27 %
VT; 11,000/110V = 100
CT; 5,000/1A = 5,000
CT
40
11
5G2F0406
6.3 Setting
12
5G2F0406
7. Negative phase sequence over current relay ( 46 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-37
Purpose : for protection against possible rotor overheating and damage due to unbalanced
system conditions
7.3 Setting
(1) Definite time(Alarm setting)
Pickup : 9 %
Time Delay : 150 cycles ( 3 sec )
13
5G2F0406
#46 Curves
Pickup
9%,1000sec
1000
100
Gen.Permissible
Time(sec)
Negative Phase
I22T(K)=10 Sequence Current
I22T(K)=15
10
Alarm 9%,3sec
0.1
0.1 1 10
Negative Sequence Current(P.U.)
14
5G2F0406
8. Inadvertent energizing relay ( 50/27 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-48
Purpose : for inadvertent energizing protection
VT
GEN;88.55 MVA
11 kV
4,648 A
50 Hz
VT; 11,000/110V
CT; 5,000/1A
G
CT
50/27
50
Overcurrent
I>P.U
AND
Pick up
27 Delay
Undervoltage
V<P.U Dropout
Delay
8.3 Setting
(1) 50 Over-current setting
Pickup is set at 0.1A
15
5G2F0406
G
GEN;88.55 MVA
11 kV
50BF
50 Hz
CT; 5,000/1A
50BF
16
5G2F0406
10. Inverse time over-current with voltage restraint relay ( 51V )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-51
Purpose : Over-current protection with voltage restraint
VT
GEN;88.55 MVA
11 kV
50 Hz
VT ;11,000/110 V = 100
CT ;5,000/1 A = 5,000
G
CT
51V
10.3 Setting
(1) Pick up
88,550kVA
Generator rated current : 4,648 A
3 11kV
CT secondary current : 4,648 A × 1 / 5,000 = 0.93 A
Pick up is set 110% of rated current.
0.93 A × 1.1 = 1.02 A
(2) Characteristic curve : Extremely inverse time is used.
(3) Time dial : 3.0 ( Curve is shown on instruction book of M-3425A )
17
5G2F0406
#51V Setting Curves
2
AT 100 percent
voltage #51V Inverse Curve
1.8 AT 50 percent
Extremely Inverse Time
Overcurrent Curve
voltage
Time Dial = 3.0
1.6 AT 25 percent
voltage
1.4
Time in Seconds
1.2
SHORT CIRCUIT CURRENT
1 (FOR 3 PHASE)
(FOR LINE TO LINE)
0.8
0.6
0.4
0.2
0 2 4 6 8 10
P.U. of Nominal Current
100
of Tap Settting at
Tap Setting as %
Rated Voltage
75
50
25
0 25 50 75 100
Input Voltage(% of rated voltage)
18
5G2F0406
11. Over-voltage relay ( 59 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-53
Purpose : protection for rms overvoltage 3-phase
GEN;88.55 MVA
11 kV
VT
50 Hz
59
VT ; 11,000/110V
11.3 Setting
(1) Alarm setting
Pickup is set at 105% of generator rated voltage.
110 V× 1.05 = 115.5 V
Therefore, pickup-voltage #1 is 116 V
Time delay #1 : 100 cycles ( 2 sec )
19
5G2F0406
12. Neutral over-voltage relay ( 59N )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-56
Purpose : protection for rms overvoltage, neutral circuit or zero sequence
G GEN;88.55 MVA
11 kV
50Hz
NGT NGT; 11,000/190 V
59N
12.3 Setting
Secondary voltage of NGT in case of ground fault is as follows.
11000 190
Vo = × = 109.7 V
√3 11000
(1) Trip setting #1
Pickup is set at 10 %.
0.10 × 109.7 V = 10.97 V
pickup-voltage #1 is set 11.0 V
Time delay #1 : 150 cycles ( 3 sec)
20
5G2F0406
13. VT fuse loss detection relay ( 60FL )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-59
Purpose : VT fuse-loss detection
VT
GEN;88.55 MVA
11 kV
50 Hz
VT ; 11,000/110 V
60FL
21
5G2F0406
14. Out-of-step relay ( 78 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-70
Purpose : generator protection from out-of-step or pole slip conditions
VT
GEN. TR. ; 90 MVA
220 / 11 kV
%IZ = 12 %
GEN;88.55 MVA
11 kV
50 Hz
G Xds = 189 %
Xd’s = 27 %
CT VT ; 11,000/110 V
78
CT ; 5,000/1 A
22
5G2F0406
14.3 Setting
23
5G2F0406
15. Frequency relay ( 81 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-73
Purpose : for protection against under or over frequency
VT GEN;88.55 MVA
81 11 kV
50 Hz
VT ; 11,000/110 V
15.3 Setting
(1) Under Frequency Trip setting 1(81U-1)
Pickup #1 is set at 47.0 Hz.
Time delay #1 ; 50 cycles ( 1 sec )
24
5G2F0406
25
5G2F0406
16. Gen. differential relay ( 87 )
Reference : M-3425A Instruction Book Chapter 2, Clause 2.3, Page 2-78
Purpose : Generator Internal Fault Protection
GEN;88.55 MVA
11 kV
50 Hz
G 87 CT ;5,000/1A
16.3 Setting
Pickup is 10% of nominal current.
88550kVA 1
Nominal Current = = 0.93 A
3 11kV 5000
0.93 A × 10% = 0.09 A
26
Configuration I/O Matrix ( M-3425A : GPR-2 )
BLOCKING INPUT:●
PROTECTION OUTPUT
INPUT INITIATE:○
FUNCTION FL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 REMARKS
ACTIVE INPUT
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
86G2-3(TRG OSC)
86G2-4(TRG OSC)
SETTING(NOTE1) -
ANY TRIP
86G2-1
52G-1
52G-2
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
TURBINE
TRG_OSC
24-1
46-1
60FL
50BF
60FL
Device
81O
52G
27
59
#21 #1 ● ● ● ● ● ● ●
#2 Disable
#3 Disable
#24 Def.T #1 ● ● ● ●
Def.T #2 ●
Inv.T ● ● ● ●
#27 #1 ● ● ●
#2 Disable
#3 Disable
#27TN #1 ● ● ● ●
#2 Disable
27
#32 #1 ● ● ● ● ● ● ● ●
#2 ● ● ● ● ● ● ●
#3 Disable
#40 #1 ● ● ● ● ●
#2 Disable
#40VC #1 Disable
#2 Disable
#46 Def.T ●
Inv. T ● ● ● ●
#49 #1 Disable
#2 Disable
#50 #1 Disable
#2 Disable
#50/27 ● ● ● ● ●
5G2F0406
#50BF ○ ○ ● ● ● ●
#50N Disable
#50DT #1 Disable
#2 Disable
#51N Disable
#51V ● ● ● ● ● ●
Configuration I/O Matrix ( M-3425A : GPR-2 )
BLOCKING INPUT:●
PROTECTION OUTPUT
INPUT INITIATE:○
FUNCTION FL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 REMARKS
ACTIVE INPUT
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
86G2-3(TRG OSC)
86G2-4(TRG OSC)
OPEN
SETTING(NOTE1) -
ANY TRIP
86G2-1
52G-1
52G-2
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
TURBINE
TRG_OSC
24-1
46-1
60FL
50BF
60FL
Device
81O
52G
27
59
#59 #1 ●
#2 Disable
#3 Disable
#59D Disable
#59N #1 ● ● ● ●
#2 Disable
#3 Disable
#59X #1 Disable
#2 Disable
#60FL ○ ●
#67N Disable
28
#78 ● ● ● ● ● ●
#81 #1 ● ● ● ● ● ● ●
#2 ● ● ● ● ● ● ●
#3 ● ● ●
#4 ● ● ●
#81A #1 Disable
#2 Disable
#3 Disable
#4 Disable
#5 Disable
#6 Disable
#81R #1 Disable
#2 Disable
#87 #1 ● ● ● ●
5G2F0406
#2 Disable
#87GD Disable
IPS #1 Disable
#2 Disable
#3 Disable
5G2F0406
29
5G2F0406
30
5G2F0406
31
5G2F0406
32
5G2F0406
50_87 Elements for Models 300G1 and 300G3 (hidden when E50_87 = N)
Level 1 Phase O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50H1P = 0.09
Level 1 Phase O/C Time Delay (0.00–400.00 s)
(hidden when 50H1P = OFF) 50H1D = 0.00
Level 2 A-Phase O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50H2PA = -
Level 2 B-Phase O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model})
(hidden when 50H2PA = OFF) 50H2PB = -
Level 2 C-Phase O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model})
(hidden when 50H2PA = OFF) 50H2PC = -
Level 2 Phase O/C Time Delay (0.00–400.00 s)
(hidden when 50H2PA = OFF) 50H2D = -
Level 1 Negative-Sequence O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50Q1P = -
Level 1 Negative-Sequence O/C Time Delay (0.00–400.00 s)
(hidden when 50Q1P = OFF) 50Q1D = -
Level 2 Negative-Sequence O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50Q2P = -
Level 2 Negative-Sequence O/C Time Delay (0.00–400.00 s)
(hidden when 50Q2P = OFF) 50Q2D = -
Level 1 Residual O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50R1P = -
Level 1 Residual O/C Time Delay (0.00–400.00 s)
(hidden when 50R1P = OFF) 50R1D = -
Level 2 Residual O/C Pickup
(OFF, 0.25–100.00 A {5 A model}; OFF, 0.05–20.00 A {1 A model}) 50R2P = -
Level 2 Residual O/C Time Delay (0.00–400.00 s)
(hidden when 50R2P = OFF) 50R2D = -
33
5G2F0406
34
5G2F0406
35
5G2F0406
36
5G2F0406
37
5G2F0406
38
5G2F0406
39
5G2F0406
Demand Ammeter
Demand Meter Time Constant (5, 10, 15, 30, 60 min) DMTC = 15
Phase Pickup
(OFF, 0.50–16.00 A {5 A model}; OFF, 0.10–3.20 A {1 A model}) PDEMP = 5.50
Neutral Ground Pickup
(OFF, 0.50–16.00 A {5 A model}; OFF, 0.10–3.20 A {1 A model}) NDEMP = 1.00
Residual Ground Pickup
(OFF, 0.50–16.00 A {5 A model}; OFF, 0.10–3.20 A {1 A model}) GDEMP = 1.00
Negative-Sequence Pickup
(OFF, 0.50–16.00 A {5 A model}; OFF, 0.10–3.20 A {1 A model}) QDEMP = 2.50
40
5G2F0406
41
5G2F0406
Latch Bits Set/Reset Equations (only set those variables enabled by ESL)
Set Latch Bit LT1 (SELOGIC Control Equation)
SET1 = -
Reset Latch Bit LT1 (SELOGIC Control Equation)
RST1 = -
Set Latch Bit LT2 (SELOGIC Control Equation)
SET2 = -
Reset Latch Bit LT2 (SELOGIC Control Equation)
RST2 = -
42
5G2F0406
43
5G2F0406
44
5G2F0406
45
5G2F0406
Date Format
Date Format (MDY, YMD) DATE_F = MDY
46
5G2F0406
47
5G2F0406
48
5G2F0406
49
5G2F0406
Display Points
Display Point DP1 (SELOGIC Control Equation)
DP1 = IN101
Display if DP1 = logical 1 (16 characters) DP1_1 = GCB OPEN
Display if DP1 = logical 0 (16 characters) DP1_0 = GCB CLOSED
Display Point DP2 (SELOGIC Control Equation)
DP2 = IN103
Display if DP2 = logical 1 (16 characters) DP2_1 = TURBINE TRIPPED
Display if DP2 = logical 0 (16 characters) DP2_0 = -
Display Point DP3 (SELOGIC Control Equation)
DP3 = IN104
Display if DP3 = logical 1 (16 characters) DP3_1 = OSC TRIGGER
Display if DP3 = logical 0 (16 characters) DP3_0 = -
Display Point DP4 (SELOGIC Control Equation)
DP4 = 0
Display if DP4 = logical 1 (16 characters) DP4_1 = -
Display if DP4 = logical 0 (16 characters) DP4_0 = -
Display Point DP5 (SELOGIC Control Equation)
DP5 = 0
Display if DP5 = logical 1 (16 characters) DP5_1 = -
Display if DP5 = logical 0 (16 characters) DP5_0 = -
Display Point DP6 (SELOGIC Control Equation)
DP6 = 0
Display if DP6 = logical 1 (16 characters) DP6_1 = -
Display if DP6 = logical 0 (16 characters) DP6_0 = -
Display Point DP7 (SELOGIC Control Equation)
DP7 = 0
Display if DP7 = logical 1 (16 characters) DP7_1 = -
Display if DP7 = logical 0 (16 characters) DP7_0 = -
Display Point DP8 (SELOGIC Control Equation)
DP8 = 0
Display if DP8 = logical 1 (16 characters) DP8_1 = -
Display if DP8 = logical 0 (16 characters) DP8_0 = -
Display Point DP9 (SELOGIC Control Equation)
DP9 = 0
Display if DP9 = logical 1 (16 characters) DP9_1 = -
Display if DP9 = logical 0 (16 characters) DP9_0 = -
50
5G2F0406
51
5G2F0406
Sequential Events Recorder settings are comprised of three trigger lists. Each trigger list can
include up to 24 Relay Word bits delimited by spaces or commas. See Sequential Events
Recorder (SER) Report in Section 11: Event Reports and SER Functions.
SER Trigger List 1 SER1 =/TRIP1+/TRIP2+/24D1T+/46Q1T+/81D3T+/81D4T+/SV2T
+/SV3T+/SV4T
SER Trigger List 2 SER2 = -
SER Trigger List 3 SER3 = -
SER Trigger List 4 SER4 = -
Relay Word Bit Aliases (ALIAS# > EALIAS setting are hidden)
Enable ALIAS Settings (0, 10, 20, 30, 40) EALIAS = 10
ALIAS1 = IN101, GCB,ASSERTED,DEASSERTED
ALIAS2 = IN103,”TURBINE TRIP”,ASSERTED,DEASSERTED
ALIAS3 = NA
ALIAS4 = NA
ALIAS5 = NA
ALIAS6 = NA
ALIAS7 = NA
ALIAS8 = NA
ALIAS9 = NA
ALIAS10 = NA
ALIAS11 = -
ALIAS12 = -
ALIAS13 = -
ALIAS14 = -
ALIAS15 = -
ALIAS16 = -
ALIAS17 = -
ALIAS18 = -
ALIAS19 = -
ALIAS20 = -
ALIAS21 = -
ALIAS22 = -
ALIAS23 = -
ALIAS24 = -
ALIAS25 = -
ALIAS26 = -
ALIAS27 = -
ALIAS28 = -
ALIAS29 = -
ALIAS30 = -
ALIAS31 = -
ALIAS32 = -
ALIAS33 = -
ALIAS34 = -
52
5G2F0406
53
5G2F0406
Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400) SPEED = 19200
Note: The highest baud rate for Modbus RTU protocol is 19200
Data Bits (7, 8) BITS = 8
Parity (0, E, N) {Odd, Even, None} PARITY = N
Stop Bits (1, 2) STOP = 1
54
5G2F0406
変 更 記 録 REVISIONS
変更記号
REV.MARK
ページ 変 更 箇 所 ・ 変 更 内 容 承 認 調 査 担 当 保 管
変更発行日 PAGE CHANGED PLACE AND CONTENTS APPROVED BY CHECKED BY PREPARED BY REGISTERED
REV.ISSUED
配布先 部数 発行 承 認 Y.Urai
ISSUED APPROVED BY 30.Nov.’12
DISTRIBUTION COPY
(発SE)
Power Generation 調査 Y.Urai
Systems Control CHECKED BY 30.Nov.’12
Dept.
担当 T.Suzuki
PREPARED BY 30.Nov.’12
F 保管 REGISTERED
55E