Modulating, Non-Spring Return, 230 V, For 2 To 10VDC or 4 To 20 Ma
Modulating, Non-Spring Return, 230 V, For 2 To 10VDC or 4 To 20 Ma
Modulating, Non-Spring Return, 230 V, For 2 To 10VDC or 4 To 20 Ma
Application
SY Series actuators are fractional horsepower devices, and utilize full-wave
power supplies. Observe wire sizing and transformer sizing requirements.
Proportional models CANNOT be connected to Belimo direct coupled (AF,
AM, GM…etc) actuator power supplies or any type of half-wave device. You
MUST use a separate, dedicated transformer or power supply to power the SY
actuator. Please do not connect other automation equipment to the dedicated
SY supply source. You MUST use four wires (plus a ground) to control a
proportional control SY actuator (See SY Wiring Section).
Wiring Diagrams
INSTALLATION NOTES 60 61 62 63
Do not change sensitivity or dip switch setting with power applied. G G Ground
60
Power supply Common/Neutral and Control Signal “-”wiring to a N L1 4 Power Supply Com
61
common is prohibited. Terminals 4 and 6 need to be wired separately.
H L2 5 Power Supply Hot
Isolation relays must be used in parallel connection of multiple
62 6 Control Signal (-)
actuators using a common control signal inputs. The relays should be
DPDT. Control signal
7 Control Signal (+)
Isolation relays are required in parallel applications. The reason parallel
63 8 Internal Use Only
applications need isolation relays is that the motor uses two sets of
windings, one for each direction. When one is energized to turn the 9 Internal Use Only
actuator in a specific direction a voltage is generated in the other due to 10 Internal Use Only
the magnetic field created from the first. It’s called back EMF. This is not
an issue with one actuator because the voltage generated in the second 11 Feedback (-)
Feedback
winding isn’t connected to anything so there is no flow. On parallel 12 Feedback (+)
applications without isolation, this EMF voltage energizes the winding it
is connected to on the other actuators in the system, the actuators are
A
tying to turn in both directions at once. The EMF voltage is always less LS3
than the supply voltage due to the resistance of the windings, so while B
the actuator still turns in the commanded direction, the drag from the A-B (Open Indication)
C
other reduces the torque output and causes overheating. Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E
! WARNING! LIVE ELECTRICAL COMPONENTS! LS4
During installation, testing, servicing and troubleshooting of this F A-E (Closed Indication)
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been SY1 -110P (220P)
properly trained in handling live electrical components perform these 110/120 or 220/230 VAC
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
60 61 62 63
Actuator B
G G Ground
11 Feedback (-)
Feedback (B)
12 Feedback (+)
A LS3
B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4
Actuator A
G G Ground
11 Feedback (-)
Feedback (A)
12 Feedback (+)
A LS3
Date created, 12/13/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.
B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4
60 61 62 63
A LS3 A LS3
B B
A-B (Open Indication) A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max. 3A 250 VAC Max.
E LS4
E LS4