SY1-220P

Modulating, Non-Spring Return, 230 V, for 2 to 10VDC or 4 to 20 mA

Application
SY Series actuators are fractional horsepower devices, and utilize full-wave
power supplies. Observe wire sizing and transformer sizing requirements.
Proportional models CANNOT be connected to Belimo direct coupled (AF,
AM, GM…etc) actuator power supplies or any type of half-wave device. You
MUST use a separate, dedicated transformer or power supply to power the SY
actuator. Please do not connect other automation equipment to the dedicated
SY supply source. You MUST use four wires (plus a ground) to control a
proportional control SY actuator (See SY Wiring Section).

Technical Data 2417


Power Supply 230 VAC, ±10%, 50/60 Hz
Transformer sizing 92 VA (class 2 power source)
Electrical Connection terminal blocks
Overload Protection thermally protected 135°C cut-out
Operating Range DC 2...10 V (default), ,
Input Impedance 100 kΩ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to
20 mA, 1500 Ω for On/Off
Position Feedback DC 2...10 V
Angle of rotation 90°
Torque motor 310 in-lbs [35 Nm]
Duty cycle 75%
direction of rotation motor reversible with built-in switch
Position indication top mounted domed indicator
Manual override use a 8mm wrench to override
Running time motor 12 sec
Internal Humidty Control resistive heating element
Ambient humidity 5 to 95% RH non condensing (EN 60730-1)
Ambient temperature -22...150 °F [-30...65 °C]
Date created, 12/13/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.

Non-operating temperature -40...176 °F [-40...80 °C]


Degree of Protection IP66/67, NEMA 4X, UL Enclosure Type 4X
Housing material die cast aluminum alloy
Gear train high alloy steel gear sets, self locking
Agency Listing ISO, CE, cCSAus
Noise level, motor <45 dB (A) 
Maintenance maintenance free
Quality Standard ISO 9001
Weight 5.5 lb [2.5 kg]
Auxiliary switch 2 x SPDT, 3A resistive (0.5A inductive) @ 250
VAC, one set at 10°, one set at 85°

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


SY1-220P
Modulating, Non-Spring Return, 230 V, for 2 to 10VDC or 4 to 20 mA

Wiring Diagrams
INSTALLATION NOTES 60 61 62 63

Do not change sensitivity or dip switch setting with power applied. G G Ground
60
Power supply Common/Neutral and Control Signal “-”wiring to a N L1 4 Power Supply Com
61
common is prohibited. Terminals 4 and 6 need to be wired separately.
H L2 5 Power Supply Hot
Isolation relays must be used in parallel connection of multiple
62 6 Control Signal (-)
actuators using a common control signal inputs. The relays should be
DPDT. Control signal
7 Control Signal (+)
Isolation relays are required in parallel applications. The reason parallel
63 8 Internal Use Only
applications need isolation relays is that the motor uses two sets of
windings, one for each direction. When one is energized to turn the 9 Internal Use Only
actuator in a specific direction a voltage is generated in the other due to 10 Internal Use Only
the magnetic field created from the first. It’s called back EMF. This is not
an issue with one actuator because the voltage generated in the second 11 Feedback (-)
Feedback
winding isn’t connected to anything so there is no flow. On parallel 12 Feedback (+)
applications without isolation, this EMF voltage energizes the winding it
is connected to on the other actuators in the system, the actuators are
A
tying to turn in both directions at once. The EMF voltage is always less LS3

than the supply voltage due to the resistance of the windings, so while B
the actuator still turns in the commanded direction, the drag from the A-B (Open Indication)
C
other reduces the torque output and causes overheating. Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E
! WARNING! LIVE ELECTRICAL COMPONENTS! LS4

During installation, testing, servicing and troubleshooting of this F A-E (Closed Indication)
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been SY1 -110P (220P)
properly trained in handling live electrical components perform these 110/120 or 220/230 VAC
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.

Date created, 12/13/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


SY1-220P
Modulating, Non-Spring Return, 230 V, for 2 to 10VDC or 4 to 20 mA

60 61 62 63
Actuator B
G G Ground

N L1 4 Power Supply Com


H L2 5 Power Supply Hot
6 Control Signal (-)
7 Control Signal (+)
8 Internal Use Only
9 Internal Use Only
10 Internal Use Only

11 Feedback (-)
Feedback (B)
12 Feedback (+)

A LS3

B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4

F A-E (Closed Indication)

SY1 -110P (220P)

Actuator A
G G Ground

4 Power Supply Com


5 Power Supply Hot
6 Control Signal (-)
Control Signal
7 Control Signal (+)
8 Internal Use Only
9 Internal Use Only
10 Internal Use Only

11 Feedback (-)
Feedback (A)
12 Feedback (+)

A LS3
Date created, 12/13/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.

B
A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max.
E LS4

F A-E (Closed Indication)

SY1 -110P (220P)

110/120 or 220/230 VAC

60 61 62 63

A LS3 A LS3

B B
A-B (Open Indication) A-B (Open Indication)
C Contact Rating: 5A 125 VAC Max.
C Contact Rating: 5A 125 VAC Max.
3A 250 VAC Max. 3A 250 VAC Max.
E LS4
E LS4

F A-E (Closed Indication)


F A-E (Closed Indication)

SY1 -24 SY1-110 (220)

SY1 Contact Arrangements