Instruction Sheet 102-418

SR501-HC-4 Switching Relay, High Current Capacity


SUPERSEDES: June 1, 2010 EFFECTIVE: June 1, 2012

Plant ID# 9300-2795


Typical
Features: Wiring 24 VAC THERMOSTAT

External Indicator Lights


Simplified Wiring
Sealed Relays
100% Factory Tested 24
R W1 W2 VAC
Contractor Friendly PC Board Layout T T T COM
Universal Thermostat Compatibility ONE ZONE HC
LED
UL Approved SWITCHING RELAY
INDICATORS

Extended 3 Year Warranty POWER

RELAY 1
120 VAC Application: RELAY 2
1 zone switching relay with boiler enable or
SR 501-HC-4
2 zone without boiler enable.
240 VAC Application:
1 zone switching relay when switching both 120 VAC
INPUT RELAY 1 RELAY 2
of the circulator hot leads (L1 & L2). N H X1 X1 X2 X2
Operation:
Connect a thermostat to the R & W1 and/or W2 terminals on BOILER
POWER N
the switching relay. When the thermostat(s) call for heat, the INPUT
CONTROL
relays are energized and power is given to the circulator(s). (120 VAC) H
120 VAC
Zone Control Power Input: CIRCULATOR
Connect 120 volt AC power input to terminals N and H.
Neutral wire to terminal N. Hot wire to terminal H. Alternative
Wiring
External Diagnostics: 24 VAC THERMOSTAT

The external lights show full functionality of the switching


relay. The green light should always be on, indicating that
power is connected. When either thermostat calls for heat,
both the appropriate relay and red indicating light are 24
R W1 W2 VAC
energized. T T T COM

ONE ZONE HC
The Taco Connection: SWITCHING RELAY LED
INDICATORS
Combine the reliability of the Taco Zone Valves, Priority POWER
Zoning Circulators, Thermostats, and the “00” family of cir- RELAY 1
culators with the advanced features of the Taco Zone Controls RELAY 2
to achieve total system integration. No matter the applica- SR 501-HC-4
tion, Taco now provides the products to maximize system
performance while simplifying both installation and service.
Terminal Description: 120 VAC
INPUT RELAY 1 RELAY 2
R Hot side of transformer. Connect to R on thermostat. N H X1 X1 X2 X2
W1 Switched R signal from thermostat #1. Connect to W on thermostat.
W2 Switched R signal from thermostat #2. Connect to W on thermostat.
POWER INPUT N 120 VAC
C Common side of transformer. Connect to COM CIRCULATOR
(120 VAC) H
on thermostat (optional).
N Neutral wire of power input. ZR

H Hot wire of power input. ZC

X1 Dry contacts for relay 1 (W1).


X1 Dry contacts for relay 1 (W1). NOTE: When using Alternative Wiring diagram, the boiler operating
X2 Dry contacts for relay 2 (W2). control’s ZC terminal will see the load of the circulator(s).
X2 Dry contacts for relay 2 (W2). WARNING: When using Alternative Wiring diagram, wiring instruc-
tions must be followed so power originates from the boiler aquastat.
Failure to follow these wiring instructions may result in a secondary
source of power being connected to the boiler that may activate it
under certain circumstances, causing injury or death.
Specifications:
PRODUCT NUMBER INPUT TYPE 1 ENCLOSURE
NUMBER OF ZONES VOLTAGE WIDTH HEIGHT DEPTH WARNING: Wiring connections must be made in accordance with all
SR501-HC-4 1 or 2 120/60/1 VAC, 90 mA 47/8" 65/8" 23/8" applicable electrical codes. Use copper wire only. Failure to follow this
RELAY RATING: 3/4 HP (13.8 FLA, 82.8 LRA at 120 VAC) (6.9 FLA, 41.4 LRA at 240 VAC) instruction can result in personal injury or death and/or property
The thermostat connection supplies a 24 VAC class 2 output. damage. 12-18 gauge wire recommended for 120/240 VAC connec-
tions, 14-22 gauge wire for thermostat connections, and 14-22 gauge
wire for 24 VAC source connections.

Free Datasheet http://www.datasheet-pdf.com/


THERMOSTAT #1 THERMOSTAT #2
(24 VAC) (24 VAC)
24 VAC THERMOSTAT

24
24
R W1 W2 VAC R W1 W2 VAC
T T T COM T T T COM

ONE ZONE HC ONE ZONE HC


LED
SWITCHING RELAY LED SWITCHING RELAY
INDICATORS
INDICATORS
POWER
POWER
RELAY 1
RELAY 1
RELAY 2
RELAY 2

SR 501-HC-4 SR 501-HC-4

120 VAC
120 VAC
RELAY 1 RELAY 2 24 VAC THERMOSTAT INPUT RELAY 1 RELAY 2
INPUT

N H X1 X1 X2 X2 N H X1 X1 X2 X2
CIRCULATOR #2
(120 VAC)
POWER
INPUT
(120 VAC)
N
H
24
R W1 W2 VAC
CONTROL POWER
INPUT (120 VAC) { H1N
CIRCULATOR #1
T T T COM
ONE ZONE HC
(240 VAC) { H2 240 VAC
CIRCULATOR
LED
(120 VAC) SWITCHING RELAY
INDICATORS

TWO ZONE, NO BOILER ENABLE


POWER ONE ZONE, NO BOILER ENABLE
RELAY 1 (CONTROL & CIRCULATOR SAME POWER SOURCE)
RELAY 2

SR 501-HC-4

120 VAC
INPUT RELAY 1 RELAY 2
N H X1 X1 X2 X2

240 VAC
CONTROL POWER
INPUT (120 VAC) { NH CIRCULATOR

H1
(240 VAC) { H2
ONE ZONE, NO BOILER ENABLE
(CONTROL & CIRCULATOR DIFFERENT POWER SOURCE)

LIMITED WARRANTY STATEMENT


Taco, Inc. will repair or replace without charge has been subject to misuse, misapplication, the NESS IS IN EFFECT ONLY FOR THE DURATION
(at the company’s option) any product or part addition of petroleum-based fluids or certain OF THE EXPRESS WARRANTY SET FORTH IN
which is proven defective under normal use chemical additives to the systems, or other THE FIRST PARAGRAPH ABOVE.
within three (3) years from the date of start-up or abuse, will not be covered by this warranty. THE ABOVE WARRANTIES ARE IN LIEU OF
three (3) years and six (6) months from date of If in doubt as to whether a particular substance ALL OTHER WARRANTIES, EXPRESS OR
shipment (whichever occurs first). is suitable for use with a Taco product or part, or STATUTORY, OR ANY OTHER WARRANTY
In order to obtain service under this warranty, it for any application restrictions, consult the OBLIGATION ON THE PART OF TACO.
is the responsibility of the purchaser to promptly applicable Taco instruction sheets or contact TACO WILL NOT BE LIABLE FOR ANY SPE-
notify the local Taco stocking distributor or Taco Taco at [401-942-8000]. CIAL, INCIDENTAL, INDIRECT OR CONSE-
in writing and promptly deliver the subject prod- Taco reserves the right to provide replacement QUENTIAL DAMAGES RESULTING FROM THE
uct or part, delivery prepaid, to the stocking dis- products and parts which are substantially sim- USE OF ITS PRODUCTS OR ANY INCIDENTAL
tributor. For assistance on warranty returns, the ilar in design and functionally equivalent to the COSTS OF REMOVING OR REPLACING
purchaser may either contact the local Taco defective product or part. Taco reserves the DEFECTIVE PRODUCTS.
stocking distributor or Taco. If the subject prod- right to make changes in details of design, con-
uct or part contains no defect as covered in this This warranty gives the purchaser specific
struction, or arrangement of materials of its rights, and the purchaser may have other rights
warranty, the purchaser will be billed for parts products without notification.
and labor charges in effect at time of factory which vary from state to state. Some states do
examination and repair. TACO OFFERS THIS WARRANTY IN LIEU OF not allow limitations on how long an implied
ALL OTHER EXPRESS WARRANTIES. ANY warranty lasts or on the exclusion of incidental
Any Taco product or part not installed or operat- WARRANTY IMPLIED BY LAW INCLUDING or consequential damages, so these limitations
ed in conformity with Taco instructions or which WARRANTIES OF MERCHANTABILITY OR FIT- or exclusions may not apply to you.

Do it Once. Do it Right.® Printed in USA


TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2012
TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc.
Visit our web site at: http://www.taco-hvac.com

Free Datasheet http://www.datasheet-pdf.com/

You might also like