1- State Calculation

a. 74°Fbs/50%HR

State Properties
SI Units IP Units
Atmospheric Pressure (P): 101.3 kPa 14.7 psi
Dry Bulb Temperature (Tdb): 23.3 C 74 F
Wet Bulb Temperature (Twb): 16.5 C 61.7 F
Relative Humidity (rh): 50 % 50 %
Humidity Ratio (w): 8.9 g/kg 0.0089 lbm/lbm
Specific Volume (v): 0.85 m^3/kg 13.65 ft^3/lbm
Specific enthalpy (h): 46.19 kJ/kg 27.53 BTU/lbm

Psychrometric Chart
0.03

0.025

0.02

Humidity Ratio (lbm/lbm)


0.015

0.01
Series8

0.005

0
32 42 52 62 72 82 92 102 112
Dry Bulb Temperature (F)

2- Mixing Process
a. Aire exterior: 2000 cfm, 100°Fbs/75°Fbh

b. Retorno: 1000 cfm, 60°Fbs/50°Fbh

Mixing Process
System
Atmospheric Pressure (kPa|psi): 101.3 14.7

State 1 State 2 State 3


Volumetric Flow (m^3/s|cfm): 0.944 2000 0.472 1000 1.416 3000.1
Mass Flow (kg/s|lbm/s): 1.05 2.314 0.572 1.261 1.622 3.576
Dry Bulb Temperature (C|F): 37.8 100 15.6 60 30 86
Wet Bulb Temperature (C|F): 23.9 75 10 50 19.8 67.6
Relative Humidity (%): 31.42 48.91 38.62
Humidity Ratio (g/kg|lbm/lbm): 12.9 0.0129 5.4 0.0054 10.2 0.0102
Specific Volume (m^3/kg|ft^3/lbm): 0.8991 14.4 0.8249 13.21 0.8729 13.98
Specific enthalpy (kJ/kg|BTU/lbm): 71.17 38.26 29.19 20.22 56.36 31.9

Psychrometric Chart
0.03

0.025

0.02

Humidity Ratio (lbm/lbm)


0.015

S1

0.01
S3

0.005
S2

0
32 42 52 62 72 82 92 102 112
Dry Bulb Temperature (F)
3- Heating Process

a. 1500 cfm, 60°Fbs, 90%HR hasta 120°Fbs

Heating Process
System
Atmospheric Pressure (kPa|psi): 101.3 14.7
Mass Flow (kg/s|lbm/s): 0.852 1.878
Heat Transfer Rate (kW|BTU/s): 29.094 30.696

State 1 State 2
Volumetric Flow (m^3/s|cfm): 0.708 1500 0.79 1673.2
Dry Bulb Temperature (C|F): 15.6 60 48.9 120
Wet Bulb Temperature (C|F): 14.5 58.2 24.9 76.8
Relative Humidity (%|%): 90 90 13.61 13.61
Humidity Ratio (g/kg|lbm/lbm): 9.9 0.0099 9.9 0.0099
Specific Volume (m^3/kg|ft^3/lbm): 0.8309 13.31 0.9268 14.85
Specific enthalpy (kJ/kg|BTU/lbm): 40.74 25.19 74.89 39.85

Psychrometric Chart
0.03

0.025

0.02

Humidity Ratio (lbm/lbm)


0.015

S1 0.01
S2

0.005

0
32 42 52 62 72 82 92 102 112
Dry Bulb Temperature (F)
4- Evaporative cooling (Heating-Humidifying)

a. 2000 cfm, 100°Fbs/10%HR hasta 50%HR

Cooling & humidifying Process


System
Atmospheric Pressure (kPa|psi): 101.3 14.7
Mass Flow (kg/s|lbm/s): 1.065 2.347
Apparatus Dew Point (C|F): 17.3 63.2
Sensible Heat Ratio : -36.812
Heat Transfer Rate (kW|BTU/s): 0.4 0.38
Moisture Removal Rate (g/s|lbm/s): 5.829 0.013

State 1 State 2
Volumetric Flow (m^3/s|cfm): 0.944 2000 0.911 1930.6
Dry Bulb Temperature (C|F): 37.8 100 24.4 75.9
Wet Bulb Temperature (C|F): 17.4 63.3 17.4 63.3
Relative Humidity (%): 10 50
Humidity Ratio (g/kg|lbm/lbm): 4 0.004 9.5 0.0095
Specific Volume (m^3/kg|ft^3/lbm): 0.8866 14.2 0.8558 13.71
Specific enthalpy (kJ/kg|BTU/lbm): 48.41 28.47 48.79 28.64

Psychrometric Chart
0.03

0.025

0.02

Humidity Ratio (lbm/lbm)


0.015

ADP

0.01
S2

0.005

S1

0
32 42 52 62 72 82 92 102 112
Dry Bulb Temperature (F)
5- Cooling and Dehumidifying

a. 9000 cfm, entrando 77.3°Fbs/63.1°Fbh

b. Se debe enfriar hasta 53°Fbs/52°Fbh


Cooling & Dehumidifying Process
System
Atmospheric Pressure (kPa|psi): 101.3 14.7
Mass Flow (kg/s|lbm/s): 4.954 10.921
Apparatus Dew Point (C|F): 10.5 50.9
Sensible Heat Ratio : 0.835
Heat Transfer Rate (kW|BTU/s): -81.8 -77.54
Moisture Removal Rate (g/s|lbm/s): -5.311 -0.012

State 1 State 2
Volumetric Flow (m^3/s|cfm): 4.248 9000 4.048 8578.1
Dry Bulb Temperature (C|F): 25.2 77.3 11.7 53
Wet Bulb Temperature (C|F): 17.3 63.1 11.1 52
Relative Humidity (%): 45.49 93.73
Humidity Ratio (g/kg|lbm/lbm): 9.1 0.0091 8 0.008
Specific Volume (m^3/kg|ft^3/lbm): 0.8574 13.73 0.8172 13.09
Specific enthalpy (kJ/kg|BTU/lbm): 48.42 28.48 31.91 21.39

Psychrometric Chart
0.03

0.025

0.02

Humidity Ratio (lbm/lbm)

0.015

0.01

ADP S1
S2
0.005

0
32 42 52 62 72 82 92 102 112
Dry Bulb Temperature (F)