Generation
NATIONAL
ACCREDITATION
Integrated unit with control panel,
FI
ST OF CERTIFICATION
I
ERED BODIES
starting system and other accessories
Quality Assurance
Cummins Engine Registered Firm Certificate Number FM509 in accordance with:
BS EN ISO 9001
● Heavy duty 4 cycle water cooled
Quality Assurance Schedule 3420/1
engine
● MCM700/SSM558 full authority One
Sourc
e
ernator
electronic management Alt
Co
●
ntrols
e r a ti n g S e
t
Ratings
Model 50 Hz 1500 rpm 14 bar(g) Model 60 Hz 1200 rpm 14 bar(g)
kWe kVA @ 0.8pf kWe kVA @ 0.8pf
QSV91-G 1540 1925 QSV91-G 1250 1562
50 Hz 1500 rpm 16 bar(g) 60 Hz 1800 rpm 16 bar(g)
QSV91-G 1750 2187 QSV91-G 1760 2200
Engine
Cummins QSV91G spark ignited lean burn Control Starting
gas combustion engines. 18-cylinder, Fully integrated controls and monitoring Pneumatic start system through single air
V form. including fuel system, ignition system and starter motor.
Type governing. Ignition
Water cooled, four cycle, turbo charged and MCM700 provides engine protection, control Individual coil on plug arrangement.
aftercooled. and governing.
SSM558 caters for fuel and ignition Cooling
Construction protection and control. Separate LT and HT cooling circuits.
Four valves per cylinder, forged steel CENSE provides detailed engine monitoring. Coolant heater, water circulating pump and
crankshaft and connecting rods, cast iron thermostat. Engine driven water pumps.
block, replaceable wet liners. Filters
Dry element air filters with restriction
Fuel System indicator. Spin-on full flow paper element
Safety shutdown solenoid valve, pressure combination lube oil filters fitted. Spin-on
regulator valve, manual shut-off valve, corrosion resistor filter.
dust filter. Flexible fuel line.
Alternator
Type Epoxy coated stator winding. Exciter
Brushless, two bearing, revolving field, Rotor and exciter impregnated with tropical Triple dipped in moisture, oil and acid
4-pole, drip proof, screen protected. grade insulating oil and acid resisting resisting polyester varnish and coated with
Class H insulation (LV), Class F insulation polyester resin. Dynamically balanced rotor anti-tracking varnish.
(MV & HV). to BS5625 grade 2.5. PMG self-exciting.
Enclosed to minimum IP22 as standard. Sealed for life bearings. Output windings with 2/3 pitch for improved
IC 01 cooling system. Layer wound mechanically wedged rotor. harmonics and paralleling ability.
Fully interconnected damper winding. Engine and alternator coupled via a flexible
AC exciter and rotating rectifier unit. coupling.
Chassis
Fabricated and welded steel chassis General Testing
Spring anti-vibration mountings supplied Complete set of operating and instruction Fully tested against a resistive load. Copy of
loose manuals test certificate provided.
Finish
Etch undercoated and finished in high gloss
durable green
Compliance Standards
To BS4999/5000 pt 99,
VDE 0530, UTE5100,
NEMA MG1-22, CEMA,
IEC 34, CSA A22.2,
AS1359, BSS5514,
ISO 3046 and ISO 8528
Stand-alone or Parallel
Operation
● Single or multi-set isolated bus
operation Plant Screens
● Single set base load utility paralleling
● Isolated bus paralleling control
● Base load utility paralleling control
H.M.I. (Touchscreen)
● Micro-processor based graphic
interface (touchscreen)
● Layered menus for ease of operation
System Screen
Other Screens
● Systems Data (restricted access)
● Engineers Data (restricted access)
— all MCM700 data
● Fault Management Screens
— reports and logs faults
— summary/historical data
— real time recording of faults
● Plant status
● Electrical data
● Mechanical data
● Test
● Access to other screens
PowerCommand® Supervisor
Control with AmpSentry™
Protection
● Integrated automatic voltage
regulator. Speed/load bias to
MCM700
● AmpSentry Protection guards the PCS PowerCommand Supervisor standard configuration
electrical integrity of the
alternator and power system from
the effects of overcurrent,
over/under voltage, under Standard Performance Data ● Phase Rotation
frequency and overload AC Alternator Data ● CB Fail to Close
conditions ● Current by Phase ● Live Bus
● Control components designed to ● Kilowatts ● Up to Four Customer Fault Inputs
withstand the vibration levels ● Kilowatt Hours ● Weak Battery (electric start
typical in generator sets ● Power Factor option)
● Voltage Line to Line Shutdowns
Standard Control ● Voltage Line to Neutral ● EEPROM Failure
Engine Data ● Loss of Excitation
Description ● Battery Voltage (for electric start ● Reverse Power
● Analog % of current meter option) ● Fail to Synchronise
(amps) ● Coolant Temperature ● Magnetic Pickup Failure
● Analog AC frequency meter ● Engine Running Hours ● Underfrequency
● Analog AC voltage meter ● Engine Starts counter ● Overcurrent
● Analog % of load meter (kW) ● Oil Pressure ● Overspeed
● Digital display panel ● RPM ● Short Circuit
● Emergency stop switch ● Oil Temperature ● Low AC Voltage
● Menu switch ● High/Low AC Voltage
● Panel backlighting
Reset switch EMC Compliance
●
Voltage Regulation
● Run-Off-Auto switch The PCS control system meets
● Sealed front panel, gasketed EMC Shield Regulations. –0.5% with PowerCommand fitted.
door
● Self diagnostics Standard Protection PLC Auxiliary Control
● Separate customer Functions
● Communication handling
interconnection box procedures
● Voltmeter/Ammeter phase Warnings ● Protocol interfaces
selector switch ● Analogue Sender Failure ● Control of plant auxiliaries
● High DC Voltage
● EEPROM Failure
● Low DC Voltage AC Auxiliaries Enclosure
● Over Current ● Incoming auxiliary a.c. supply for
set
● Control/monitors/protects
generator set a.c. systems not
located in the GCP
DC Engine Interface
Enclosure
● Interfaces between GCP and
genset
Other Items
● Battery charger and batteries for
GCP
C O/A
A B