SERVICE REPORT

Inspection / Work Report No. Date : 28 May 2019

Name of Plant Sukorejo Trigen Plant

Location of Inspection Sukorejo – Jawa Timur

Mode of operation Mains Parallel

Customer Name PT. HM SAMPOERNA Tbk


Installed / Euroasiatic Date of
Commissioned by Commissioning
Engine Model Engine Serial No. Operating Hour
TCG 2020V20 2211420 11960

Output Speed/Revolution Last service done


P = 2000 Kw N = 1500 1/min NA

Lube Oil Type Fuel Type Cooling Water Additives


Pegasus 1005 Natural Gas

Alternator Type & Model Alternator Serial No. Alternator Power Alternator Voltage
Marelli Generator MA21511

Technician : Date of Service Insurance Claim No. ( If application)


- Harryanto Febrino 13 – 05 – 2019 s/d -
- Oka Situmeang 15 – 05 – 2019

Type Service :
- Troubleshooting cylinder B5 found measure value valve lag was limits
- Troubleshooting intake manifold bank B found flange & bush joint intake manifold bank B corrosion
Activities Working :
- Maintenance E40
- Check & set valve clearance inlet & outlet all cylinder
- Measuring valve lag all cylinder
- Found cylinder B5 measure value valve lag was limits
- Found flange & bush joint intake manifold bank B corrosion
- Test Running & load 2000 Kw (100%) (Ok!)

DOCUMENTATION
 Condition flange & bush joint intake manifold  Condition inlet valve 2 cylinder B5
bank B

Value valve lag 2


was limits
Conclusion :
- Flange & bush joint intake manifold bank B corrosion because it happened condensation in the
fuel gas
- Found cylinder B5 measure value valve lag was limits because valve seat and valve stem were
uneven (71,60 mm)

Recommendation :
- Renew flange & bush joint intake manifold bank A & B
- Renew / exchange cylinder head B5

Prepared by : Approved by :

(Harryanto Febrino) (SLV Prasad)


Service Division Service Division
PT. Euroasiatic Jaya PT. Euroasiatic Jaya