Customer Basis:
ELVIAL S.A.
EN ISO 12567–1 : 2000-09
Aluminium Extrusion Determination of thermal
transmittance by hot box
26th km national road method – Part 1: Complete
windows and doors
GR-61100 Thessaloniki-Kilkis Corresponds to the national
version of DIN EN ISO.
External Dimen-
sions (W x H) 800 mm x 1000 mm
(Frame)
Material Aluminium profile
Type of Opening Turn
Insulating glass unit, Single-Window Instructions for use
Construction: 5/12/4 mm, This test report may be used to
classify the thermal transmit-
Gas filling: Air tance UW.
Coating: no IR reflecting coating
Glazing spacer aluminium
*) This test report is a translation of the test report 403 25652/1 Validity
Specials dated 22 October 2002. The data and results given re-
late solely to the described,
tested object.
Testing the thermal transmit-
tance does not allow any
Thermal transmittance statement to be made on fur-
ther characteristics of the pre-
sent structure which could de-
fine performance and quality.
UW = 5,0 W/(m2 ⋅ K)
Notes on publication
The ift Notice "Notes on the
use of ift Test Reports" applies.
The cover sheet can be used
as a summary.
ift Rosenheim
27. November 2002
Contents
The report contains 6 pages in
total
Dr. Helmut Hohenstein pp. Hans-Jürgen Hartmann 1 Object
Director Head of the Heat Insulation & 2 Procedure
Energy Technology Division 3 Detailed results
02-06/384
Classification report Energy Saving and Heat Insulation
Page 2 of 6
Test report 403 25652/1e from 27. November 2002
Customer ELVIAL S.A., GR-61100 Thessaloniki-Kilkis
1 Object
Q:\BAUPHYS\PROJEKTE\403\25652\pdf\25652-1e.doc
Classification report Energy Saving and Heat Insulation
Page 3 of 6
Test report 403 25652/1e from 27. November 2002
Customer ELVIAL S.A., GR-61100 Thessaloniki-Kilkis
Mounting of filling
Sealing system prefabricated profiles
interior
Type / Material Drafted sealing
exterior
Type / Material Drafted sealing
Vapour pressure balance Bottom 2 holes Ø 6 mm
Hardware
Opening Turn
Type / Producer GU
Hinges / pivots 2
Number of lockings Top: 2 Bottom: 1
Specials
The description is based on the documentation of ift. Numbers and names of material are
given by the customer. (Further data from customer are marked with *).
The structural details were examined solely on the basis of the characteristics to be
proven.
The illustrations are based on unchanged documentation provided by the Client.
Figure 1 Cross-section
Q:\BAUPHYS\PROJEKTE\403\25652\pdf\25652-1e.doc
Classification report Energy Saving and Heat Insulation
Page 4 of 6
Test report 403 25652/1e from 27. November 2002
Customer ELVIAL S.A., GR-61100 Thessaloniki-Kilkis
2 Procedure
2.1 Sample
2.2 Process
Technical basics
EN ISO 12567–1 : 2000-09 Determination of thermal transmittance by hot box method –
Part1: complete windows and doors
Similar to national German version:
DIN EN ISO 12567–1 : 2001-02
Determination of thermal transmittance by hot box method –
Part1: complete windows and doors
boundary conditions Up to the standard.
Deviation There are no deviations from the test procedure or test con-
ditions
Test equipment
Guarded hot box Appliance number: 22762
External dimensions Width 3 m, height 3 m, depth 2.3 m
Emissivities of
inner surfaces εn ≥ 0.95
Position of test specimen vertical
Direction of heat flow horizontal
Sensor layout as specified in EN ISO 12567-1
Q:\BAUPHYS\PROJEKTE\403\25652\pdf\25652-1e.doc
Classification report Energy Saving and Heat Insulation
Page 5 of 6
Test report 403 25652/1e from 27. November 2002
Customer ELVIAL S.A., GR-61100 Thessaloniki-Kilkis
3 Detailed results
Designation
θci Air temperature, warm side °C 22,5
2
5,0
Ust Thermal transmittance with standardized total surface W/(m · K)
resistance
UW = Ust
Q:\BAUPHYS\PROJEKTE\403\25652\pdf\25652-1e.doc
Classification report Energy Saving and Heat Insulation
Page 6 of 6
Test report 403 25652/1e from 27. November 2002
Customer ELVIAL S.A., GR-61100 Thessaloniki-Kilkis
8,6
8,5
8,4
Rsur in m K/W
8,3
2
8,2
8,1
8,0
2 4 6 8 10 12 14 16
Surround panel mean temperature in °C
0,20
Rs,t in m²K/W
0,15
0,10
0,05
0,00
0 10 20 30 40 50 60 70
Density of heat flow rate qsp(ca) in W/m²
0,80
Convective fraction Fc
0,60
0,40
0,20
0,00
0 10 20 30 40 50 60 70
ift Rosenheim
27. November 2002
Q:\BAUPHYS\PROJEKTE\403\25652\pdf\25652-1e.doc