Professional Documents
Culture Documents
Sub Module 3.17 AC GEN
Sub Module 3.17 AC GEN
MODULE 3
Sub Module 3.17
AC GENERATORS
CONTENTS
INTRODUCTION --------------------------------------------------------------------- 2
WHAT IS A GENERATOR----------------------------------------------------------- 2
WHAT IS A.C GENERATOR -------------------------------------------------------- 2
PRINCIPLE OF AC GENERATOR -------------------------------------------------- 2
ELECTROMAGNETIC INDUCTION ----------------------------------------------- 2
CONSTRUCTION OF AC GENERATOR------------------------------------------- 5
ROTATING-ARMATURE ALTERNATORS---------------------------------------- 5
WORKING OF AC GENERATOR -------------------------------------------------- 6
GENERATOR TYPES ----------------------------------------------------------------- 9
ROTATING ARMATURE GENERATOR ------------------------------------------- 9
ROTATING FIELD GENERATOR --------------------------------------------------10
SINGLE-PHASE ALTERNATORS --------------------------------------------------13
TWO-PHASE ALTERNATORS -----------------------------------------------------14
THREE-PHASE ALTERNATOR ----------------------------------------------------15
THREE PHASE INTERCONNECTIONS -------------------------------------------19
STAR CONNECTION ---------------------------------------------------------------19
DELTA CONNECTION --------------------------------------------------------------20
ADVANTAGES OF DELTA-STAR CONNECTION -------------------------------20
THE BRUSHLESS (PERMANENT MAGNET) AC GENERATOR --------------23
INTRODUCTION Mathematically:
Before we discuss theory and construction of an ac generator ∅
e= N
we should define some basic and vital concepts for better
understanding.
where
WHAT IS A GENERATOR
e = induced voltages / emf
A generator is device that converts mechanical energy into
electrical energy. Ø = magnetic flux
As the name implies, an AC generator is that, which produces now this leads us to 2 conditions. Flux can be changed in 2
alternating current. ways around the conductor, as shown in fig 3.17-1 & 3.17-2:
It is interesting to know that all generators (also called a) A changing magnetic field is produced around the
alternators) are basically ac generators i.e. they only produce ac conductor
current. The system of how we take output makes it an AC or b) The conductor or field moves to cut the magnetic lines of
DC generator. forces.
ELECTROMAGNETIC INDUCTION
According to the Michael Faraday’s Law of Electromagnetic
induction
FIG 3.17.1B SIMPLE AC GENERATOR Fig 3.17-2 Conductor cutting the field
When two of these three factors are known, the third can be
determined by the use of this rule as can be seen from the fig
below.
CONSTRUCTION OF AC GENERATOR the two slip rings that are welded to the both ends of coil and
rotate with the coil. The slip rings are then further connected
A simple ac generator is shown in the fig 3.17-4.
through carbon brushes, to the terminals of the load.
ROTATING-ARMATURE ALTERNATORS
The rotating-armature alternator, fig 3.17-5, is similar in
construction to the dc generator in that the armature rotates in a
stationary magnetic field as shown in figure. In the alternator,
the generated ac is brought to the load unchanged by means of
slip rings (C1 and C2). The rotating armature is found only in
alternators of low power rating and generally is not used to
supply electric power in large quantities.
ROTATING-FIELD ALTERNATORS
Position 1
Position 2
The conductor A moves parallel to the lines of force. Since it
cuts no lines of force, the induced voltage is zero. As the The conductor is now moving in a direction perpendicular to the
conductor advances from position 1 to position 2, the induced flux and cuts a maximum number of lines of force;
voltage gradually increases. therefore, a maximum voltage is induced. As the conductor
moves beyond position 2, it cuts a decreasing amount of flux,
and the induced voltage decreases.
Position 3
Position 4
At this point, the conductor has made half a revolution and
again moves parallel to the lines of force, and no voltage is Like position 2, the conductor is again moving perpendicular to
induced in the conductor. As the A conductor passes position3, the flux and generates a maximum negative voltage. From
the direction of induced voltage now reverses since the A position 4 to position 5, the induced voltage gradually decreases
conductor is moving downward, cutting flux in the opposite until the voltage is zero, and the conductor and wave are ready
direction. As the A conductor moves across the south pole, the to start another cycle.
induced voltage gradually increases in a negative direction until
it reaches position 4.
ROTATING FIELD GENERATOR with a greater current the output windings must also be larger.
Consequently, these heavier windings are not subject to
The rotating field or fields do not change their flux direction with centrifugal forces.
respect to the rotor. Fig 3.17.8 shows a schematic diagram of a
rotating field generator.
The slip rings only carry the field supply which is the smaller dc
voltage and current.
FIG 3.17.8 ROTATING FIELD GENERATOR
Some advantages of the rotating field type generator are:
This principle is illustrated in figure; a two-pole generator must If revolutions completed in 1 sec = 10
rotate at four times the speed of an eight-pole generator to Then revolutions completed in 1min = 10 x 60
produce the same frequency of generated voltage. The Therefore RPM = 60 x RPS
frequency of any ac generator is in hertz(Hz), which is the RPS = .
number of cycles per second, is related to the number of poles
and the speed of rotation, as expressed by the equation and fig
3.17-7:
Thereby:
f = NP
60
SINGLE-PHASE ALTERNATORS
TWO-PHASE ALTERNATORS induced in phase A decreases from its maximum value, and the
voltage induced in phase B increases from zero. In the right-
hand schematic, the rotor poles are opposite the windings of
Two phase implies two voltages if we apply our new definition of
phase B. Now the voltage induced in phase B is maximum,
phase. And, it's that simple. A whereas the voltage induced in phase A has dropped to zero.
two-phase alternator is designed to produce two completely Notice that a 90-degree rotation of the rotor corresponds to one-
separate voltages. Each voltage, by itself, may be considered
quarter of a cycle, or 90 electrical degrees. The waveform
as a single-phase voltage. Each is generated completely picture shows the voltages induced in phase A and B for one
independent of the other. cycle. The two voltages are 90º out of phase. Notice that the
Certain advantages are gained. These and the mechanics of
two outputs, A and B, are independent of each other. Each
generation will be covered in the following paragraphs. output is a single-phase voltage, just as if the other did not exist.
The obvious advantage, so far, is that we have two separate
output voltages. There is some saving in having one set of
GENERATION OF TWO-PHASE POWER
bearings, one rotor, one housing, and so on, to do the work of
two. There is the DISADVANTAGE OF HAVING TWICE AS
Figure 3.17-9 shows a simplified two-pole, two-phase alternator. MANY STATOR COILS, WHICH REQUIRE A LARGER AND
Note that the windings of the two MORE COMPLEX STATOR.
phases are physically at right angles (90º) to each other. You
would expect the outputs of each phase to be 90º apart, which
they are. The graph shows the two phases to be 90º apart, with
A leading B. Note that by using our original definition of phase
(from previous modules), we could say that A and B are 90º out
of phase i:e there will always be 90º between the phases of a
two-phase alternator. This is by design.
The stator in figure consists of two single-phase windings
completely separated from each other.
Each winding is made up of two windings that are connected in
series so that their voltages add. The rotor is identical to that
used in the single-phase alternator. In the left-hand schematic,
the rotor poles are opposite all the windings of phase A.
Therefore, the voltage induced in phase A is maximum, and the
voltage induced in phase B is zero. As the rotor continues
rotating counterclockwise, it moves away from the A windings
and approaches the B windings. As a result, the voltage
THREE-PHASE ALTERNATOR
RESISTIVE LOADS
REACTIVE LOADS
POWER FACTOR
The purpose of rating is to ensure that the generator is not THREE PHASE INTERCONNECTIONS
overheated when operated into a given load circuit, whether
continuously or intermittently, at its maximum real load. Although it is possible to run a three-phase system with the
phases completely separate, using two conductors for each
phase, it is unusual to do so since interconnection makes
possible considerable savings in line conductor materials. The
terms star and delta are the general terms applied to the
interconnection of three phase AC phases.
STAR CONNECTION
A star connection is an arrangement in which the corresponding
ends of phases, either start or finish, are connected to a
common terminal known as the star point. The other end of
each phase is connected to a separate terminal.
The circuits is shown in fig 3.17.15 .Since three of the phase
winding ends are joined at the star point, then only one terminal
(n) is required for these ends. Thus a star connected 3-phase
system requires a maximum number of four conductors to
transfer energy from source to load.
Grounding Bank: It provides a local source of ground Easy Relaying of Ground Protection: Protective relaying is
current at the secondary that is isolated from the primary MUCH easier on a delta-wye transformer because ground faults
circuit. For suppose an ungrounded generator supplies a on the secondary side are isolated from the primary, making
simple radial system through ∆-Y transformer with grounded coordination much easier. If there is upstream relaying on a
Neutral at secondary as shown Figure. The generator can delta-wye transformer, any zero-sequence current can be
supply a single-phase-to-neutral load through the -grounded assumed to be from a primary ground fault, allowing very
Y transformer. sensitive ground fault protection. On a wye-wye, a low-side
Let us refer to the low-voltage generator side of the ground fault causes primary ground fault current, making
transformer as the secondary and the high-voltage load side coordination more difficult. Actually, ground fault protection is
of the transformer as the primary. Note that each primary one of the primary advantages of delta-wye units.
winding is magnetically coupled to a secondary winding The .
magnetically coupled windings are drawn in parallel to each
other.
.
FIG 3.18.20
BRUSHLESS ALTERNATORS main alternator, which are also located on the rotor as shown in
fig 3.17-18. With this arrangement, brushes and slip rings are
CONSTRUCTION not required to feed current to the rotating field coils.
A brushless alternator is composed of two alternators built end-
MAIN ALTERNATOR
to-end on one shaft, as shown in figure 3.17-17. Smaller
brushless alternators may look like one unit but the two parts The main alternator has a rotating field as described above and
are readily identifiable on the large versions. The larger of the a stationary armature (power generation windings). This is the
two sections is the main alternator and the smaller one is the part that can be confusing so take note that in this case, the
exciter. The exciter has stationary field coils and a rotating armature is the stator, not the rotor.
armature (power coils). The main alternator uses the opposite With the armature in the stationary portion of the alternator, the
configuration with a rotating field and stationary armature. high current output does not have to go through brushes and
slip rings. Although the electrical design is more complex, it
results in a very reliable alternator because the only parts
subject to wear are the bearings.
EXCITER
The exciter field coils are on the stator and its armature is on
the rotor. The AC output from the exciter armature is fed FIG 3.17-22 AN SCHEMATIC OF EXCITER AND
through a set of diodes that are also mounted on the rotor to ALTERNATOR
produce a DC voltage. This is fed directly to the field coils of the