APA Technical Note - Condensation Causes and Control

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

TN,X485.

0 1/16/01 3:54 PM Page 1

T E C H N I C A L N O T E

Condensation
Causes and Control
Number X485M Thus, as air with a given amount of water Condensation Control
December 2000 vapor in it is cooled, the relative humid- The first step in the control of
ity will rise until a temperature known as condensation involves reducing excess
Whenever moist air comes into contact
the “dew point” is reached. At this point moisture inside the home. Vent clothes
with a cooler surface, condensation is
relative humidity becomes 100%, and dryers to the outside and not to the
likely to occur. The cool surface may be
some of the moisture will condense as attic or crawl space.
the underside of roof sheathing or the
“dew.” If moist air contacts a surface at Install range hoods over cooking stoves,
inside of wall sheathing in winter, or the
or below its dew-point temperature, and operate them when any appreciable
underside of a subfloor in summer when
condensation will occur on that surface. amount of steam is being generated.
the building is air conditioned.
Water vapor in the air produces “vapor Install exhaust fans in bathrooms and vent
The only requirements for condensation
pressure,” which is a measure of mois- them to the outside and not to the attic
are moist air and a cool surface. In the
ture concentration. Air with high vapor (consider wiring the fan so that it goes on
winter, the moisture content of the
pressure tries to escape to or seek equi- automatically with the bathroom light).
indoor air (usually measured as relative
librium with air of lower vapor pressure. Methods of moisture control vary with
humidity or vapor pressure) is important,
The vapor can escape either with a flow location in the house. For attics and
as is the temperature of the surface on
of air through cracks or openings in the enclosed cathedral ceilings, the simplest
which this moisture could condense. The
building shell, or without it by direct form of control involves ventilation. A
amount of moisture in the air outdoors is
penetration of building materials. ceiling vapor retarder is recommended in
also sometimes a factor.
“Vapor permeance” is a measure of the conjunction with ventilation for cathedral
Condensation can be controlled three
ease with which vapor can penetrate ceilings. With today’s ever-increasing
ways: (1) reduce the amount of moisture
solid building materials. Materials with amounts of insulation and “tighter” con-
initially in the air; (2) prevent the mois-
low permeance (typically 1 perm or less) struction, a ceiling vapor retarder may not
ture from reaching a cold surface by
are rated as “vapor barriers” or, more be as necessary for attics when adequate
introducing a vapor retarder and sealing
properly, “vapor retarders.” ventilation is provided. Its omission would
penetrations; or (3) carry it away by
Changes in construction due to energy- allow vapor to more easily travel through
ventilation.
saving features have tended to increase the ceiling and out through the attic vents.
Condensation Explained moisture levels within today’s homes. It is important, however, to seal or avoid
Water stays in the air as vapor as long as Washers, dryers, cooking, showers, penetrations for electrical ceiling fixtures,
the temperature of the air and the amount indoor steam rooms and swimming pools which can allow mass movement of moist
of water are such that the air can hold it. are sources of water vapor within houses. air into the roof cavity or attic.
The amount of water in the air, relative to In older houses, air infiltration around For walls, ventilation is impractical, and
the amount which the air can hold, is doors and windows, and often directly condensation controls will generally take
called “relative humidity.” Warm air can through cracks in the walls, more or less the form of vapor retarders. Vapor retarders
hold more water vapor than cold air. automatically eliminated condensation. in walls, and at other locations, should
With the tighter, energy-efficient houses always be on or nearest the winter warm
being built today, control of condensation
must be planned.

A P A
T h e E n g i n e e r e d Wo o d A s s o c i a t i o n

© 2000 APA - The Engineered Wood Association


TN,X485.0 1/16/01 3:54 PM Page 2

side in order to block vapor before it


©2000 APA – THE ENGINEERED WOOD ASSOCIATION • ALL RIGHTS RESERVED. • ANY COPYING, MODIFICATION, DISTRIBUTION OR OTHER USE OF THIS PUBLICATION OTHER THAN AS EXPRESSLY AUTHORIZED BY APA IS PROHIBITED BY THE U.S. COPYRIGHT LAWS.

reaches a portion of the construction with TABLE 1

a temperature below the dew point. (In MINIMUM VENTILATION REQUIREMENTS –


BASED ON ICC INTERNATIONAL RESIDENTIAL CODE
hot, humid climates, a wall vapor retarder
Natural ventilation(a)
is sometimes omitted. Check local practice net free area opening
in these areas.) If vapor is allowed to pene- as proportion of floor
Location Construction or attic area
trate a wall, and temperature reaches the
Attic and structural spaces No vapor retarder 1/150
dew point within the wall, the vapor may
condense and cause trouble. Vapor retarder in ceiling 1/300
Wood floors are seldom so cool as to
At least 50% and not more
cause surface condensation of vapor from
than 80% of required vent
within the house. Structural panel floors area in upper portion of space
bonded with exterior adhesives have to be ventilated at least 3 feet 1/300
above eave or cornice vents(b)
sufficiently low vapor permeance (1 perm
or less) to prevent excessive indoor mois- Crawl space No vapor retarder 1/150
ture from escaping into the crawl space,
when penetrations or openings are ade- Vapor-retarder ground cover and
one vent opening within three feet 1/1500
quately sealed. This is particularly impor-
of each corner
tant when insulation is applied to the
(a) Note that where power attic vents are used, they should provide at least 0.7 cfm per square foot of
underfloor area. attic area (15% more for dark roofs), and air intake of one square foot of free opening should be
provided for each 300 cfm of fan capacity. Although intended to exhaust warm summer air, power
Use a vapor-retarder ground cover to vents should also operate during cold months to help prevent condensation.
prevent introduction of moisture from (b) Certainly the code provision should not be interpreted to violate a reasonable balance between low
and high vents. (For natural ventilation systems, some experts recommend that 60% of net free area
the ground beneath the house to the should be provided at eaves and 40% at the ridge or high gables. To meet the code provision for
minimum 50% high vents, this would require that the free opening of high vents total 1/600 and low
crawl space or interior. This is easy in vents total 1/400 of attic area, for an overall ratio of 1/240.)

crawl-space houses, where a layer of


6-mil polyethylene over the ground
In modern basement houses, ventilation third column of the table by the appropri-
in the crawl space is usually all that is
is usually inherent with forced-air heating ate floor or attic area of the building. Note
required. It is more difficult in basement
systems. Ventilation and air movement that these are minimum code require-
houses, where vapor retarders should be
should be given separate consideration ments, which have been found to be
installed under basement floors and
when heating systems are used that do adequate under most normal residential
outside foundation walls.
not provide air circulation, such as base- circumstances. However, ventilation in
Condensation in the crawl space is board heaters. excess of these minimums may be neces-
unlikely in winter when a ground cover is sary when unplanned moisture is intro-
used and adequate drainage is provided Ventilation Requirements duced by venting an appliance, such as a
around the foundation to prevent mois- Minimum ventilation requirements are clothes dryer, into the space (which is not
ture accumulation. Thus, foundation usually covered in building codes. The recommended), or by misdirected surface
vents may be closed during the winter for requirements in Table 1 are based on the or rainwater. Care should also be taken to
energy savings. Closure of vents in winter ICC International Residential Code (simi- provide adequate extra attic vent area
for energy saving is particularly effective lar provisions also appear in the ICC when moisture-laden air is introduced to
when foundation walls, rather than the International Building Code, the ICC the attic by “whole-house” fans. In such
underside of floors, are insulated. This International One and Two Family Dwell- cases, attic vent area should be increased
technique is also more effective than ing Code, and the CABO One and Two in accordance with manufacturer’s recom-
floor insulation for preventing summer Family Dwelling Code), and may be used mendations. Attic ventilation strategy
condensation, particularly when the as a guide for residential construction. should also consider location of vents to
building is air-conditioned. The required net free area of vents can minimize dead air spaces.
be found by multiplying the value in the

2
TN,X485.0 1/16/01 3:54 PM Page 3

are four louver-type foundation vents


TABLE 2 (46 sq. in. free area per vent). Triangular
NET FREE AREA GUIDELINES FOR VENTS AND SCREENS(a) gable vents (155 sq. in. free area per
Ventilator Type Area (in.2 ) Net Free Area (in.2 ) vent) are at the top of the gables at each
Roof (screened “jacks,” Vent pipe area (πd2/4, where Area x 0.6 end of the house for natural attic ventila-
“button caps”) d = pipe diameter in inches)
tion. Does this meet the code minimum
Ridge 18 x lin. ft.
ventilation criteria?
1. Determine minimum required
Gable or foundation (louvered ventilation area:
and screened)
Rectangular Height x width Area x 0.44 Ratio for attic with at least 50% of vent
Triangular 1/2 x height x width Area x 0.44 area in upper half of space to be vented
is 1/300. Note, however, that in this case
Soffit Length x width Area x 0.3
100% of vent area is in the upper half
Screens(b)
of the attic, reducing effectiveness of the
1/16" mesh Height x width Area x 0.5 ventilation and requiring that a ratio
1/8" mesh Height x width Area x 0.8 of 1/150 be used.
1/16" mesh and louvers Height x width Area x 0.33
1/8" mesh and louvers Height x width Area x 0.44 Vertical
Attic vent = projection x Ratio
(a) Estimates only. Check vent manufacturer for actual net free area. area required of roof area
(b) The model building codes specify corrosion-resistant wire mesh with the least dimension being
1/8 inch (maximum 1/4 inch).
= (30' x 45') x 1/150
= 9.0 sq. ft. = 1296 sq. in.
Ventilation in excess of minimums may Measure vents to be certain of size and
Ratio for crawl space with vapor-retarder
be necessary in high occupancy structures check vent manufacturer’s data for their
ground cover is 1/1500.
or in structures that contain moisture- net free area.
producing activities, such as commercial Crawl space vent area required
The free ventilation area published by
kitchens or laundry facilities. It is tradi- = Floor area x Ratio
vent manufacturers varies slightly, so any
tionally the responsibility of the building calculations regarding vent area provided = (30' x 45') x 1/1500
design professional to determine the will be approximate. In some cases, the = 0.9 sq. ft. = 130 sq. in.
amount and location of ventilation to net free area may be marked on the vent. 2. Determine total net free area of vents:
assure satisfactory performance. When manufacturer’s data is not avail- Attic vent area = 155 sq. in./vent
able, Table 2 may be used to estimate x 2 vents = 310 sq. in. (Free area of attic
Ventilation Check List
net free vent area. vents is less than that required.)
It is sometimes necessary to inspect an
existing building for adequate ventilation A vent may actually have zero free area Crawl space vent area = 46 sq. in./vent
where there are signs of unusual mois- and thus may be ineffective, either per- x 4 vents = 184 sq. in. (Free area of crawl
ture. When checking for ventilation, be manently or intermittently. Examples space vents is more than that required.)
sure to note the following information: include closed foundation vents, covered
3. Conclusion:
roof ventilators, inoperative power vents,
1. Area of floor and attic to be ventilated. Crawl space vents meet minimum venti-
and eave vents which are clogged or
2. Presence of ground cover and ceiling lation requirements, but attic vents are
blocked by insulation or paint.
vapor retarder. less than 1/4 of the required area. Addi-
5. Compare actual ventilation with tional attic venting is required, and could
3. Signs of moisture accumulation, minimum requirements, as shown in be accomplished by using larger gable
including decay, water stains, blistered the following example. vents or adding vents along eaves. Eave
paint, water standing in crawl space,
rusty fasteners or mold growth. Example vents are recommended.

4. Quantity, size, type, location, and A 30' x 45' house has a vapor-retarder
condition of roof and foundation vents. ground cover in the crawl space. There

© 2000 APA - The Engineered Wood Association


TN,X485.0 1/16/01 3:54 PM Page 4

We have field representatives in most


major U.S. cities and in Canada who can
help answer questions involving APA trade-
marked products. For additional assistance
in specifying APA engineered wood products,
contact us:

APA – THE ENGINEERED


WOOD ASSOCIATION
HEADQUARTERS
7011 So. 19th St. ■ P.O. Box 11700
Tacoma, Washington 98411-0700
(253) 565-6600 ■ Fax: (253) 565-7265

Addres
eb s
W
@
:
www.apawood.org

PRODUCT SUPPORT HELP DESK


(253) 620-7400
E-mail Address: help@apawood.org

(Offices: Bournemouth, United Kingdom;


Hamburg, Germany; Mexico City, Mexico;
Tokyo, Japan.)

The product use recommendations in this


publication are based on APA – The
Engineered Wood Association’s continuing
programs of laboratory testing, product
research, and comprehensive field experi-
ence. However, because the Association has
no control over quality of workmanship or
the conditions under which engineered wood
products are used, it cannot accept responsi-
bility for product performance or designs as
actually constructed. Because engineered
wood product performance requirements
vary geographically, consult your local archi-
tect, engineer or design professional to
assure compliance with code, construction,
and performance requirements.

Form No. X485M


Revised December 2000/0100

A P A
T h e E n g i n e e r e d Wo o d A s s o c i a t i o n

© 2000 APA - The Engineered Wood Association

You might also like