Professional Documents
Culture Documents
Minimizing Orifice Meter Installation Lengths: C C C C
Minimizing Orifice Meter Installation Lengths: C C C C
The recent revision of the orifice flow meter standard used in the United States (i.e.,
Chapter 14.3 of the American Petroleum Institute (API) Manual of Petroleum Measurement
Standards (MPMS) or American Gas Association (AGA) Report No. 3) includes changes in the
upstream length requirement for orifice meter installations. When no flow conditioning is used,
the minimum recommended length of straight pipe upstream of an orifice meter may now be as
long as 145 pipe diameters. The financial impact of these new installation length requirements
on the U.S. oil and gas industry is yet to be determined, but could be substantial. For instance, a
square foot of floor space on an offshore platform can cost upwards of $100,000 or more. It is
easy to see how significant increases in orifice meter installation lengths could quickly impact
the construction cost of a new platform. The new installation length requirements could also
limit future expansion of existing meter stations. For example, if extensive plumbing
modifications are required to accommodate longer meter runs, such modifications may be too
costly. Or, existing land-based sites may be “land locked” and additional real estate may not be
available to accommodate meter station expansion.
A research project was recently conducted at the GRI (formerly the Gas Research
Institute) Metering Research Facility (MRF) located at Southwest Research Institute (SwRI) in
San Antonio, Texas to address the need for short orifice meter installations (both single- and
multi-tube configurations) that are not assessed a penalty in measurement uncertainty. Tests
were run in the MRF Low Pressure Loop (LPL) to evaluate the feasibility of reducing the size,
footprint, and weight of a multi-tube meter/header installation by approximately 50%. Capital
savings due to such a size reduction for typical offshore flow meter installations are estimated to
be on the order of $250,000 to $500,000 (U.S. dollars) per offshore structure. Following is a
summary of this research project.
Historical perspective.
In the fall of 1996, Savant Measurement Corporation proposed a research project to
Southwest Research Institute aimed at developing a compact multi-tube orifice flow
meter/header installation configuration. At that time, a series of flow conditioner tests had been
performed in the MRF using a 10-inch diameter orifice meter tube with an upstream length (i.e.,
the A' dimension from Chapter 14.3 of the API MPMS) of 17 pipe diameters (D) installed
downstream of a tee.[1] (A flow conditioner is a device placed in the meter run upstream of the
orifice. It is intended to “condition” the flow by eliminating distortions in the velocity profile
that can be produced by the upstream piping configuration. Measurement biases associated with
such flow distortions are, thus, eliminated.) During the flow conditioner installation effects tests,
values of orifice discharge coefficient, Cd, were measured and compared to values measured for
a “baseline” (or reference) meter tube configuration. The difference in Cd values was expressed
as a percentage of the baseline value.
Figure 1 shows results for one of the flow conditioners (i.e., a Savant Measurement
Gallagher Flow Conditioner (GFC)) evaluated during these tests. As Figure 1 shows, the GFC
reduced the installation error to less than ±0.20% for orifice beta ratios between 0.20 and 0.75.
Figure 1. Flow conditioner test results for a 10-inch Gallagher Flow Conditioner (GFC) in
an A' = 17D meter tube downstream of a tee.[1]
In 1989, Dr. P. L. Wilcox,[2] Scientific Manager at K-Lab in Norway, stated that short gas
metering systems, complying with the requirements of ISO 5167,[3] had been developed using a
new type of flow conditioner. His work was later supported by the research conducted by Dr. E.
M. Laws[4] of Salford University. In 1990, Laws wrote that “a flow conditioner could be
designed to give fully-developed flow conditions, irrespective of the nature and quality of the
upstream flow…” Laws followed that paper with a series of research investigations[5],[6],[7] to
develop a flow conditioner for compact orifice meter installations. Section 6.4 of ISO 5167[3]
provides a general requirement for acceptable flow conditions at the primary device:
Acceptable velocity profile conditions can be presumed to prevail when, at each point
across the pipe cross-section, the ratio of the local axial velocity to the maximum axial velocity
at the cross-section agrees to within ±5% with that which would be achieved in swirl-free flow at
the same radial position at a cross-section located at the end of a very long straight length (over
100D) of similar pipe.
Additional orifice meter installation effects tests with flow conditioners were performed
at the MRF in 1997. The aim of this work was to develop a flow conditioner performance test[8]
for API MPMS, Chapter 14.3, Part 2. Flow conditioner performance tests were run for upstream
meter tube lengths of A' = 17D, A' = 29D, and A' = 45D for four different types of installation
configurations: (1) “good” flow conditions, (2) two 90° elbows out-of-plane, (3) a gate valve
closed 50% against the flow, and (4) a strongly swirling flow transported through a tee. The
flow conditioner performance test results of most interest were those for the A' = 17D meter
tube. These results suggested the GFC flow conditioner, the NOVA #50E flow conditioner, and
The header and meter tubes are turned 90°, from horizontal to vertical, to reduce the
width and footprint area. Two 6-inch diameter meter runs are arranged one above the other, with
gas flowing from left to right in the figure. Gas enters through an 8-inch diameter inlet then
moves into a 10-inch diameter vertical header. The flow leaves the header through either an
upper or a lower branch outlet, passing through a 4-inch diameter valve and into the center
branch of the tee. A blind flange that can be removed to allow for cleaning and maintenance
terminates one side branch of the tee. The other side branch is connected to the meter tube inlet.
The spacer distance between the header outlet and the center branch of the tee is short, allowing
space only for the 4-inch valve. The upstream meter tube length is 25D. A 19-tube bundle flow
conditioner is located 10D upstream of the orifice plate. The downstream meter tube length is
approximately 7D. The total meter tube length between headers is approximately 32D. The goal
The second was a perforated plate without the anti-swirl device (GFC NAS) shown in
Figure 5. The length of the GFC NAS was just the thickness of the perforated plate. The rods
and crosspiece that provided support and stability to the plate did not significantly obstruct the
upstream flow.
The third was the GFC perforated plate (in this case, it was the GFC NAS flow
conditioner installed in the meter tube) in combination with a vane-type anti-swirl device (shown
in Figure 6) installed at the inlet to the central branch of the tee in the compact header.
The combination of the GFC perforated plate and the vane-type anti-swirl device was
designated the GFC VAS. The GFC perforated plate had a 3-8-16 hole pattern with a porosity of
approximately 49.9%.
Figure 6. Front and back views of the vane anti-swirl device used together with the GFC
perforated plate to form the GFC VAS Flow Conditioner System.
The NOVA #50E prototype flow conditioner performed well two years ago in the MRF
flow conditioner performance tests[8], but the surface of the plate had rusted when the flow
conditioner was returned to NOVA at the end of the test program. CPA elected to wire-brush the
NOVA #50E prototype plate to remove the rust before shipping it to the MRF for the compact
meter tests. Surprisingly, the ∆Cd test results and the velocity profile measurements in good
flow conditions, indicated that the flow conditioning performance had changed. We speculate
that the cleaning process may have caused this. The diameter and location of the holes in the
perforated plate were unchanged. The ∆Cd results were discussed with CPA, but it was too late
to substitute a new CPA CL 14.3 K-Lab/NOVA #50E flow conditioner. Consequently, the entire
suite of tests was not run on the available NOVA #50E conditioner.
K-Lab Laws flow conditioner[15] Laws has described several flow conditioner designs,
including one that combines vanes and tabs as an integral part of the perforated plate.[16] K-Lab
in Kårstø, Norway, holds the patent rights[17] to the Laws flow conditioner.
Figure 9. Front and back views of the K-Lab Laws Flow Conditioner with tabs (front) and
vanes (back).
Stuart C-3 tube bundle straightening vane.[18] This device meets the 3rd Edition of API
MPMS, Chapter 14.3, Part 2, Section 2.5.5.1 specifications for a tube bundle straightening vane.
It differs from the concentric 19-tube bundle straightening vane in that there are 22 tubes rather
than 19, and that the tubes are not all the same diameter. The straightening vane design is
covered by a patent[19] held by Pacific Gas and Electric Company. The C-3 straightening vane
performed better than the concentric 19-tube bundle in the MRF flow conditioner performance
evaluation tests.[8] The Stuart C-3 straightening vane is shown in Figure 10.
In the tests, the flow conditioners were traversed upstream of the orifice plate to
determine optimum location. The minimum distance between the orifice plate and the flow
conditioner was C = 1D. The maximum distance varied between C = 7.5D and C = 10D,
depending on the length of the test flow conditioner.
This method has been used in previous research investigations[8] to minimize the effects
of laboratory measurement bias errors. For example, a bias error in the flow rate measured by
the reference flow meter will normally affect both the installation effects test and the baseline
calibration test by the same amount. Therefore, when ∆Cd is calculated as shown above, the
laboratory biases are correlated and their effects cancel out. Coleman and Steele[22] consider the
effect of non-independent (correlated) bias errors in the estimation of experimental uncertainty.
The desired value for ∆Cd is 0%. This means that a particular test piping configuration
introduces no measurable bias error, compared to the baseline configuration. However,
experience in performing baseline calibration experiments at the MRF has shown that baseline
Cd values are typically repeatable to within approximately ±0.1%. In a similar manner, orifice
meter installation effects tests, such as flow conditioner tests, are also repeatable to within
approximately ±0.1%. If the baseline and installation effects test Cd values are at opposite
extremes of this range, the total measurement uncertainty would then be approximately ±0.2%.
As a side note, the API MPMS Chapter 14.3, Part 2 Working Group previously selected
an installation effects acceptance interval equal to half of the 95% confidence interval for the R-
G orifice equation. The acceptance interval varies from ±0.22% for ß = 0.50 to ±0.28% for ß =
0.75.
0.2
0.0
-0.2
-0.4
- 95% Confidence Limit
-0.6
-0.8
-1.0
0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75
β, Orifice Diameter Ratio
Figure 15a. Deviation of baseline calibration data from the R-G orifice equation.
1.0
Baseline Calibration Test on 4/14/99
0.8 Upstream Meter Tube Length A = 100 D
∆Cd, Deviation from RG Equation, %
tap #1
0.6 tap #2
+ 95% Confidence Interval
0.4
0.2
0.0
-0.2
-0.4
-95% Confidence Interval
-0.6
-0.8
-1.0
0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75
β, Orifice Diameter Ratio
Figure 15b. Deviation of baseline calibration data from the R-G orifice equation.
Figure 16a. Comparison of flow conditioner results for good flow conditions using the
GFC TAS.
Figure 16b shows the ∆Cd results for the K-Lab flow conditioner without tabs or vanes in
good flow conditions for ß = 0.67. The ∆Cd results lie within the acceptance interval for C
between 3D and 10D.
Figure 16b. Flow conditioner results for good flow conditions using the K-Lab Flow
Conditioner without tabs or vanes.
During the flow conditioner tests in good flow conditions, a set of data was also taken
with each flow conditioner pulled back a distance C = 50D upstream of the orifice plate. These
results can be used to check the baseline Cd values for each value of beta ratio. The results are
presented in the Topical Report.[23] With a few exceptions, the data for each flow conditioner
and C = 50D lie within the acceptance interval for the beta ratio used. No significant bias shifts
in ∆Cd were seen for any of the flow conditioners.
Figure 17a. Flow conditioner results for the GFC TAS in a compact header with upstream
meter tube length, A' = 10D, for ß = 0.67.
Figure 17b shows the ∆Cd test results for the K-Lab flow conditioner without tabs or
vanes installed in the compact header for ß = 0.67. The total length of this device was just the
thickness of the perforated plate, 0.13D, so the maximum distance from the orifice plate to the
perforated plate was about 10D. ∆Cd values lie at the lower limit, -0.23%, of the acceptance
interval for C = 5D.
K-Lab Flow Conditioner - Without Tabs or Vanes
1.2
1.0 Sliding flow conditioner tests
A' = 10 D meter tube in a compact header configuration
∆Cd, % Deviation from Baseline Cd Value
0.8 β = 0.67
0.6 tap #1
tap #2
0.4
0.2
+ 0.23%
0.0
-0.2 - 0.23%
-0.4
-0.6
-0.8
-1.0
-1.2
-1.4
-1.6
-1.8
0 1 2 3 4 5 6 7 8 9 10
Figure 17b. Flow conditioner results for the K-Lab Flow Conditioner without tabs or
vanes in a compact header with upstream meter tube length, A' = 10D, for ß = 0.67.
Since the compact header tests were the most important performed on this project, great
care was taken to assure that differences in flow conditioner performance were not caused by
day-to-day variations in the measurement and control systems at the MRF. This was
Discussion of results.
The orifice meter tube and orifice fitting used in this investigation were manufactured to
comply with the specifications in API MPMS, Chapter 14.3, Part 2.[9] These specifications were
not verified during the compact header project. However, the baseline values of Cd lie well
within the uncertainty interval for the R-G orifice equation, as expected for an AGA orifice
meter installation. This result gave confidence that the meter tubes still met the specifications in
API MPMS, Chapter 14.3, Part 2.
A baseline flow condition was established mechanically using a long upstream length,
100D, of straight pipe with a tee at the inlet to the meter tube. The measured values were
defined as the baseline Cd values. The flow conditioners were then expected to give the same Cd
values in a short length (i.e., A' = 10D) of meter tube. The baseline Cd tests were performed both
before and after the installation tests. In addition, it was possible to check the baseline Cd values
when the flow conditioners were placed at C = 50D during the good flow condition tests.
However, the different flow conditioners evaluated on this project were not necessarily
developed to produce the same baseline velocity profile or the same range of ∆Cd values for the
Reynolds number range from 1.2(10)6 to 3.5(10)6 in D = 4-inch pipe, as used on this project.
The relative performance of the different flow conditioners might change if the tests are repeated
in larger diameter meter tubes and for a higher range of Reynolds number.
The tests performed on this project produced real orifice meter installation effects. The
∆Cd values were not caused by bias errors in the measurement of pressure, temperature, or flow
rate. If measurement errors were present, they would have been obvious at ß = 0.50, as well as ß
= 0.75. The absence of a ∆Cd bias for ß = 0.50 confirms that the pressure and temperature
transmitters were in calibration. The tests with C = 50D in good flow conditions and the tests
with the GFC TAS artifact installed during the compact header tests also confirmed that day-to-
day measurement variations were negligible.
Why aren’t flow conditioner results shown for beta ratios lower than 0.67? In the
absence of swirl, Reader-Harris, et al.[24] have shown that the magnitude of the installation error
caused by a distortion in the velocity profile varies approximately as ß3.5. All of the flow
conditioners tested during this research project were effective at removing swirl that may have
been present upstream of the conditioner. Therefore, installation effects tests were best
performed using a large beta ratio, such as 0.67. If the performance of a flow conditioner was
acceptable for ß = 0.67, it should be acceptable at lower beta ratios as well.
Conclusions.
The test results from this investigation suggest that it is quite possible that short orifice
meter tube lengths (i.e., A' = 10D, or possibly less) can be used without increasing measurement
uncertainty. This can be accomplished through the judicious selection and installation of an
appropriate flow conditioner upstream of the orifice. Additional test work is needed to fully
Acknowledgements
The work described herein was funded by GRI. The GRI Program Manager who
oversaw the research was Mr. Charles E. French. The flow conditioner manufacturers provided
test articles at no cost to the project. Mr. James E. Gallagher of Savant Measurement
Corporation also provided technical assistance. A paper on this subject, entitled Development of
a Compact Header Orifice Meter Station, was presented at the American Gas Association
Operations Conference held in Denver, Colorado in June 2000.
REFERENCES
1. Morrow, T. B., “Orifice Meter Installation Effects: Ten-Inch Sliding Flow Conditioner
Tests,” GRI Technical Memorandum No. GRI-96/0391, November 1996.
2. Wilcox, P. L., “Comparison Between ISO 5167 and New Non-Fiscal Metering Installations,”
Gas Transport Symposium, Norwegian Petroleum Society, Haugesund, Norway, Jan. 30-31,
1989.
3. Measurement of Fluid Flow by Means of Orifice Plates, Nozzles and Venturi Tubes Inserted
in Circular Cross-Section Conduits Running Full, ISO 5167-1980 (E), Geneva, Switzerland.
4. Laws, E. M., “The Development of an Efficient Flow Conditioner,” Flow Metering of
Commercially Important Fluids, London, Feb. 1990.
5. Laws, E. M., “Compact Installations for Differential Flowmeters,” Flow Measurement and
Instrumentation, Vol. 5, No. 2, 1994, pp. 79-85.
6. Laws, E. M., “The Design of Flow Control Devices,” Forum on Industrial and
Environmental Applications of Fluid Mechanics, ASME FED-Vol. 221, 1995, pp. 163-168.
7. Laws, E. M. and A. K. Ouazzane, “A Further Investigation into Flow Conditioner Design
Yielding Compact Installations for Orifice Plate Flow Metering,” Flow Measurement and
Instrumentation, Vol. 6, No. 3, 1995, pp. 187-199.
8. Morrow, T. B., “Orifice Meter Installation Effects: Development of a Flow Conditioner
Performance Test,” GRI Technical Memorandum No. GRI-97/0207, December 1997.
9. Orifice Metering of Natural Gas and Other Related Hydrocarbon Fluids - Specification and
Installation Requirements, Manual of Petroleum Measurement Standards, Chapter 14.3, Part
2, 3rd Edition, American Petroleum Institute, February, 1991, Washington, D.C.
10. Gallagher, J. E. and P. J. LaNasa, “Field Performance of the Gallagher Flow Conditioner,”
3rd International Symposium on Fluid Flow Measurement, Gas Research Institute, March 20-
22, 1995, San Antonio, TX.
11. Gallagher, J. E., R. E. Beaty, and P. J. LaNasa, “Flow Conditioner for More Accurate
Measurement of Fluid Flow,” U. S. Patent 5,495,872, March 5, 1996.
12. Gallagher, J. E., R. E. Beaty, and P. J. LaNasa, “Flow Conditioner Profile Plate for More
Accurate Measurement of Fluid Flow,” U. S. Patent 5,529,093, June 25, 1996.