Transformer technical data sheet

ABB Ltd. Chonan Korea


Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: 9020415-1 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 400
Rated High Voltage [V] 380
Rated Low Voltage [V] 220 (Voltage ratio error tolerance: ±2.0%)
Tapping on HV (Off circuit tap changer) No tap
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 1100 +15% IEC tolerance
Load loss [W] 4700 +15% IEC tolerance
Impedance [%] 5 (for reference)
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] - / -
Power Frequency withstand Level (HV/LV) [kV] 3 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 60

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 1500
Width (±5% allowance) [mm] 600
Height (±5% allowance) [mm] 1250
Weight (±5% allowance) [kg] 1850

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
Transformer technical data sheet
ABB Ltd. Chonan Korea
Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: SDV-1000 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 1000
Rated High Voltage [V] 380
Rated Low Voltage [V] 220 (Voltage ratio error tolerance: ±2.0%)
Tapping on HV (Off circuit tap changer) No tap
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 2300 +15% IEC tolerance
Load loss [W] 10600 +15% IEC tolerance
Impedance [%] 5 (for reference)
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] - / -
Power Frequency withstand Level (HV/LV) [kV] 3 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 64

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 1590
Width (±5% allowance) [mm] 1000
Height (±5% allowance) [mm] 1690
Weight (±5% allowance) [kg] 2800

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
Transformer technical data sheet
ABB Ltd. Chonan Korea
Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: Q16582-2 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 1500
Rated High Voltage [V] 22000
Rated Low Voltage [V] 220
Tapping on HV (Off circuit tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 3500 +15% IEC tolerance
Load loss [W] 13700 +15% IEC tolerance
Impedance [%] 6 ±10% IEC tolerance
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] 125 / -
Power Frequency withstand Level (HV/LV) [kV] 50 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 65

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 1950
Width (±5% allowance) [mm] 1200
Height (±5% allowance) [mm] 2100
Weight (±5% allowance) [kg] 4450

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
Transformer technical data sheet
ABB Ltd. Chonan Korea
Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: SDV3-1502 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 1500
Rated High Voltage [V] 6000
Rated Low Voltage [V] 220
Tapping on HV (Off circuit tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 3200 +15% IEC tolerance
Load loss [W] 13000 +15% IEC tolerance
Impedance [%] 6 ±10% IEC tolerance
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] 60 / -
Power Frequency withstand Level (HV/LV) [kV] 20 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 65

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 1710
Width (±5% allowance) [mm] 1200
Height (±5% allowance) [mm] 1980
Weight (±5% allowance) [kg] 3900

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
Transformer technical data sheet
ABB Ltd. Chonan Korea
Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: Q15878-20 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 2000
Rated High Voltage [V] 22000
Rated Low Voltage [V] 380
Tapping on HV (Off circuit tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 4100 +15% IEC tolerance
Load loss [W] 13600 +15% IEC tolerance
Impedance [%] 6 ±10% IEC tolerance
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] 125 / -
Power Frequency withstand Level (HV/LV) [kV] 50 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 66

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 2094
Width (±5% allowance) [mm] 1200
Height (±5% allowance) [mm] 2190
Weight (±5% allowance) [kg] 5800

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
Transformer technical data sheet
ABB Ltd. Chonan Korea
Project No. Date Rev
Project: 유성-삼성 베트남 박닌-스페어 변압기 Q16881 2017-02-20 0

Design no.: 1LKR201151 Dgn. by: R KIM


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated Power [kVA] 2500
Rated High Voltage [V] 22000
Rated Low Voltage [V] 380
Tapping on HV (Off circuit tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation class (HV/LV) F/F
Average Winding Temp. rise (HV/LV) [K] 100/100
Conductor Material (HV/LV) Al/Al
Ambient Temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1
Winding type (HV/LV) Encapsulated/Impregnated

Technical Characteristic at AN, 120°C


No load loss [W] 4700 +15% IEC tolerance
Load loss [W] 17900 +15% IEC tolerance
Impedance [%] 6 ±10% IEC tolerance
BIL (Basic Impulse Withstand Level) (HV/LV) [kV] 125 / -
Power Frequency withstand Level (HV/LV) [kV] 50 / 3
Sound Pressure Level (LpA) at 1.0m dB(A) 68

Design note
k-factor (harmonic loss factor for nonsinusoidal current)7

Overall Dimension TR./ Enclosure(if any)


Length (±5% allowance) [mm] 2130
Width (±5% allowance) [mm] 1200
Height (±5% allowance) [mm] 2270
Weight (±5% allowance) [kg] 6300

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805
- Temperature sensor: PT-100Ω (1 pc/phase, total 3 pc)
- Earthing screen between LV and HV

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Tests: Routine tests according IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.