I. STRUCTURAL DESIGN II. CONSTRUCTION NOTES E.

FOUNDATION

1. THE STRUCTURAL ENGINEER-OF-RECORD, UPON NOTIFICATION, SHALL CONDUCT A THOROUGH


A. CODES AND STANDARDS A. GENERAL INSPECTION OF THE FOUNDATION WORKS AFTER EXCAVATION FOR FOOTINGS ARE COMPLETE
AND ANY REQUIRED REINFORCING STEEL ARE IN PLACE.
1. GOVERNING CODES 1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE SPECIFICATIONS, THE
ACI 318R-95 (REVISED 1995) BUILDING CODE REQUIREMENTS FOR REINFORCED 2. FORMWORKS SHALL BE IN PLACE PRIOR
ARCHITECTURAL, CIVIL, PLUMBING, ELECTRICAL AND MECHANICAL DRAWINGS.
CONCRETE, TO INSPECTION. CONCRETE POURING OF THE FOUNDATION SYSTEM SHALL NOT BE ALLOWED
AMERICAN CONCRETE INSTITUTE 2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE, WHICH SHALL WITHOUT FIRST OBTAINING WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER-OF-RECORD,
UBC 1991 EDITION UNIFORM BUILDING CODE INCLUDE THE DIMENSION AND LOCATION OF OPENINGS, GROOVES, REGLETS, PIPE SLEEVES,
NSCP 2002 EDITION NATIONAL STRUCTURAL CODE OF THE 3. ALL FILL AND BACKFILL MATERIALS SHALL BE COMPACTED IN LIFTS NOT EXCEEDING 200 MM
CONDUITS AND EMBEDDED OR ATTACHED ITEMS TO CONCRETE, ET CETERA.
PHILIPPINES, VOLUME I THICK WITH ACCEPTABLE EQUIPMENT TO ACHIEVE A MINIMUM 95% MDD BASED ON ASTM D-698.
AISC 9TH EDITION MANUAL OF STEEL CONSTRUCTION, 3. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT EXISTING AND IN-PLACE DENSITY SHALL BETESTED BY THE APPROVED INDEPENDENT TESTING LABORATORY
ALLOWABLE STRESS DESIGN, NEW CONSTRUCTION. THIS SHALL INCLUDE BUT NOT LIMITED TO BRACING AND SHORING FOR USING ASTM D-1556 SAND CONE APPARATUS.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION LOAD IMPOSED DURING CONSTRUCTION.
4. FILL AND BACKFILL MATERIALS SHALL BE FREE FROMDEBRIS, WOOD, ROOTS, VEGETABLE
2. GOVERNING STANDARDS 4. ALL FOUNDATIONS SHALL REST ON 50MM THICK LEAN CONCRETE AT f'c = 6.895 MPA (1000 PSI) MATTER, REFUSE, UNSOUND PARTICLES, DELETERIOUS OR OBJECTIONABLE MATERIALS.
ASTM A36 STRUCTURAL STEEL UNLESS NOTED OTHERWISE. ACCEPTABLE MATERIALS SHALL BE CLASSIFIED AS GW, GM, GP, SW AND SM BY ASTM D-2467
ASTM 611 STEEL SHEET, CARBON, COLD-ROLLED STRUCTURAL AND CONFORM TO THE FOLLOWING:
ALLOY 5. GENERAL NOTES AND TYPICAL DETAILS SHALL APPLY TO ALL DRAWINGS UNLESS SHOWN OR
ASTM 615 / PNS 49 SPECIFICATION FOR STEEL BARS FOR STEEL NOTED OTHERWISE. LIQUID LIMIT = SHALL NOT EXCEED 25
REINFORCEMENT ACCORDANCE WITH ASTM D-423
ASTM C33 / PNS 18 STANDARD SPECIFICATION FOR CONCRETE 6. ALL BAR DIAMETERS AND SPACINGS ARE IN MILLIMETER UNLESS OTHERWISE NOTED. PLASTICITY INDEX = SHALL NOT EXCEED 12 % WHEN TESTED IN
AGGREGATES ACCORDANCE WITH ASTM D-424
ASTM C39 STANDARD TEST METHOD FOR COMPRESSIVE 7. ALL DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON PLANS, SECTIONS AND NO MORE THAN 25% BY WEIGHT AND SHALL BE FINER THAN NO. 200 SIEVE WHEN TESTED
STRENGTH OF CYLINDRICAL CONCRETE SPECIMENS DETAILS. ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE NOTED. IN ACCORDANCE WITH ASTM D-1140.
ASTM C94 / PNS 46 STANDARD SPECIFICATION FOR READY-MIXED
CONCRETE SOIL COMPACTION REQUIREMENTS
ASTM C150 / PNS 07 STANDARD SPECIFICATION FOR PORTLAND CEMENT
B. CONCRETE AND REINFORCING STEEL 90 % FDT = INSIDE THE BUILDING
PNS 16 PHILIPPINE NATIONAL STANDARD FOR CONCRETE 95 % FDT = PARKING AREA
HOLLOW BLOCKS 1. MINIMUM CONCRETE COVER TO ALL REINFORCING BARS FOR NON-CORROSIVE ENVIRONMENT 85 % FDT = LANDSCAPING
SG 671 SPECIFICATION FOR THE DESIGN OF COLD-FORMED SHALL BE AS FOLLOWS:
STRUCTURAL STEEL MEMBERS BY AMERICAN IRON A. CONCRETE CAST AGAINST AND PERMANENTLY F. CONSTRUCTION JOINTS
AND STEEL INSTITUTE EXPOSED TO EARTH 75 MM
B. FORMED SURFACES EXPOSED TO EARTH OR WEATHER 1. CONSTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS TO LEAST IMPAIR THE
D16MM DIA. BARS OR SMALLER STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO APPROVAL OF THE ENGINEER.
B. DESIGN LOADS 40 MM
OTHER BARS 50 MM
C. FORMED SURFACE NOT EXPOSED DIRECTLY TO WEATHER OR EARTH 2. SLAB ON GRADE SHALL HAVE CONTROL JOINTS AT 6.00M MAXIMUM CENTER TO CENTER
1. ROOF DEAD LOAD SLABS, WALLS AND JOISTS 20 MM UNLESS OTHERWISE SHOWN.
TRUSSES 240 PA (5 PSF) BEAMS, GIRDERS AND COLUMNS 40 MM
METAL ROOFING AND PURLINS 144 PA (3 PSF)
CEILING 240 PA (5 PSF) 2. MINIMUM CONCRETE COVER FOR CORROSIVE ENVIRONMENT NOT EXPOSED TO EARTH
ALL FIXTURES 96 PA (2 PSF) OR GROUND WITH FORM:
A. REINFORCED CONCRETE WALL 50 MM
III. SITE SPECIFIC DESIGN PARAMETERS
2. ROOF LIVE LOAD B. SLAB 50 MM ZONE = __________
4
TRIBUTARY AREA (SQM) LOAD (PA) C. BEAMS/COLUMNS 65 MM BASIC WIND SPEED = __________
TA < 20 800 PA
EXPOSURE = __________
20 < TA < 60 700 PA 3. MINIMUM CONCRETE COVER FOR CORROSIVE ENVIRONMENT EXPOSED TO EARTH ALLOWABLE SOIL BEARING CAPACITY = 2500 psi
__________
TA > 60 600 PA OR GROUND WITH FORM: MINIMUM DEPTH OF FOOTING EMBEDMENT
A. REINFORCED CONCRETE WALL 62 MM BELOW NATURAL GRADE LINE = __________
3. FLOOR DEAD LOAD B. SLAB 62 MM
PARTITIONS 960 PA (20 PSF) C. BEAMS/COLUMNS 80 MM SOIL TEST REPORT:
FLOOR TILES 1,200 PA (25 PSF) D. FOOTING 100 MM BY = __________
MASONRY WALLS 3,255 PA (68 PSF)
DATE = __________
4. REINFORCING BARS SHALL BE FREE OF RUST, GREASE OR OTHER MATERIALS THAT ARE
4. FLOOR LIVE LOAD LIKELY TO IMPAIR BOND WITH CONCRETE.
ROOMS 2,400 PA (50 PSF)
5. ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE POURING

L
5. WIND LOAD
A. BASIC WIND SPEED (REFER TO 2.3A OF NSCP)
CONCRETE OR APPLYING MORTAR OR GROUT. BAR SIZE D 180° 135°
ZONE I 250 MPH 6. BAR SPLICES SHALL BE SECURELY WIRED TOGETHER. SPLICES IN REINFORCED CONCRETE
(MM) (MM) L (MM) L (MM)

D
ZONE II 200 MPH BEAMS/GIRDERS, COLUMNS AND WALLS SHALL BE SHOWN IN THE DETAILS. FOR NON-STRUCTURAL
B. EXPOSURE WALLS, MASONRY WALLS AND SLABS, SPLICES SHALL LAP A MINIMUM OF 40 BAR DIAMETER AND
EXPOSURE B HAS TERRAIN WITH BUILDINGS, FOREST OR SURFACE D10MM Ø 40 75 75
SHALL BE STAGGERED WHEREVER POSSIBLE.
IRREGULARITIES, 6.0 METERS OR MORE IN HEIGHT, DETAILING DIMENSION
COVERING AT LEAST 20 % OF THE AREA EXTENDING 7. SPLICES REQUIRED IN THE REINFORCEMENT OF BEAMS/GIRDERS FRAMING INTO COLUMNS
1.50 KM OR MORE FROM SITE.
D12MM Ø 48 75 75 135° HOOK
SHALL NOT BE LOCATED WITHIN THE COLUMN NOR WITHIN A DISTANCE OF TWICE THE BEAM/
EXPOSURE C HAS TERRAIN WHICH IS FLAT AND GENERALLY OPEN, GIRDER DEPTH FROM THE FACE OF THE COLUMN. AT LEAST TWO CLOSED STIRRUP TIES SHALL
EXTENDING 800 METERS OR MORE FROM THE SITE IN BE PROVIDED AT ALL SPLICES.
ANY FULL QUADRANT.
C. DESIGN WIND PRESSURE 8. LAP SPLICES SHALL BE MADE WITHIN THE CENTRAL HALF OF COLUMN HEIGHT AND THE SPLICE STIRRUPS AND LATERAL TIES
P = Ce Cqʆ WHERE P = DESIGN WIND PRESSURE LENGTH SHALL NOT BE LESS THAN 1.30 TIMES THE DEVELOPMENT LENGTH.
Ce = COMBINED HEIGHT, EXPOSURE AND
GUST FACTOR COEFFICIENT 9. CAMBER ALL BEAMS AT LEAST 0.006M FOR EVERY 4.50M BUT IN NO CASE LESS THAN 0.019M FOR
0.63 AT EXPOSURE B EVERY 3.00M.
1.08 AT EXPOSURE C BAR SIZE D 180° 90°

L
Cqʆ = PRESSURE COEFFICIENT FOR THE STRUCTURE (MM) (MM) L (MM) L (MM)

D
OR PORTION OF STRUCTURE UNDER 10. SPECIAL TIES/TRANSVERSE HOOP REINFORCEMENT SHALL BE PROVIDED WITHIN THE BEAM
CONSIDERATION AND COLUMN JOINT.
D10MM Ø 60 65 120
6. EARTHQUAKE FORCE C. STRUCTURAL STEEL
V = (Z I C / Rw) W WHERE Z = 0.40 FOR SEISMIC ZONE 4 DETAILING DIMENSION
I= 1.00 IMPORTANCE FACTOR D12MM Ø 72 65 145
C= 2.75 MAXIMUM 1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE AMERICAN INSTITUTE OF 90° HOOK
Rw = 8.00 DUAL SYSTEM STEEL CONSTRUCTION (AISC) MANUAL 9TH EDITION UNLESS OTHERWISE SHOWN OR NOTED.
D16MM Ø 96 65 195 L
W= 0.1375 MAXIMUM, TOTAL SEISMIC LOAD 2. THE CONTRACTOR SHALL FURNISH ALL PLATES, CLIP ANGLES, CONNECTORS ETC. FOR THE
COMPLETION OF THE STRUCTURE EVEN IF SUCH ITEM IS NOT SHOWN ON DRAWINGS.
C. DESIGN MATERIAL STRESSES NOTED. D20MM Ø 120 80 240

D
3. WELDING SHALL BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY CODE (AWS D1.1)
1. CONCRETE ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS f'c= 21 MPA (3,000 PSI) UNLESS INDICATED OTHERWISE. WELDING ELECTRODES SHALL BE E70XX. D25MM Ø 150 100 300
DETAILING DIMENSION
2. REINFORCING STEEL YIELD STRENGTH fy= 275 MPA (40,000 PSI) 4. ALL BOLTS AND THREADED FASTENERS SHALL CONFORM WITH ASTM A-325 UNLESS OTHERWISE
D28MM Ø 224 115 340 180° HOOK
3. STRUCTURAL STEEL YIELD STRENGTH fy= 250 MPA (36,000 PSI)
D. MASONRY
4. COLD-FORMED STEEL YIELD STRENGTH fy= 230 MPA (33,000 PSI)

5. MASONRY ULTIMATE COMPRESSIVE STRENGTH fm'= 4.83 MPA (700 PSI) 1. ALL MASONRY WALLS/CONCRETE HOLLOW BLOCKS SHALL BE LAID IN FLEMISH BOND
MAIN BARS
FOR BUILDING WALLS, PERIMETER FENCES AND TRENCHES (INTERLOCKING COURSE) WITH FULL MORTAR BEDDING. STACK BOND SHALL BE USED ONLY WHEN
SPECIFIED.
6. MASONRY CONCRETE GROUT COMPRESSIVE STRENGTH f'c= 13.8 MPA (2,000 PSI)
2. ALL CELLS SHALL BE FULLY FILLED WITH CONCRETE GROUT.
7. MASONRY REINFORCING STEEL YIELD STRENGTH fy= 275 MPA (40,000 PSI)
3. THE MINIMUM COMPRESSIVE STRENGTH OF CONCRETE HOLLOW BLOCK AT 28 DAYS SHALL BE
STANDARD HOOKS AND DIMENSIONS
8. STEEL PIPE YIELD STRENGTH fy= 250 MPA (36,000 PSI) 4.83 MPA (700 PSI) UNLESS OTHERWISE SPECIFIED.

PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CONSTRUCTION NOTES
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 15
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 1 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
1.0 GENERAL INSTRUCTIONS
CHB WALL WALL THICKNESS 1.1 THE ARCHITECT IN-CHARGE/CIVIL ENGINNER SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE AND SHALL NOTIFY THE ARCHITECT/ENGINEER OF
DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND INFORMATION SHOWN IN THE DRAWINGS BEFORE PROCEEDING WITH THE WORK.THIS SHALL INCLUDE THE

200
2-12mm Ø HOR. BARS
10mmØ TIES @ 150mm O.C. LOCATION AND DIMENSION OF GROOVES, REGLETS, SLEEVES , CURVES , OPENINGS , EMBEDDED OR ATTACHED ITEMS ,ETC.REFER TO ARCHITECTURAL ,MECHANICAL,

(MIN)
(MIN)

200
10mmØ TIES @ 150 O.C. 2-12mm Ø HOR. BARS ELECTRICAL AND PLUMBING DRAWINGS.
WALL THICKNESS CHB WALL 1.2 ALL WORK AND MATERIALS SHALL CONFORM TO THE MINIMUM STANDARDS OF THE LATESTS EDITION OF THE UNIFORM BUILDING CODE AND SUCH REGULATING
AGENCIES EXERCISING AUTHORITY OVER ANY PORTION OF WORK.

1.3 THE ARCHITECT IN-CHARGE/CIVIL ENGINEER SHALL PROVIDE ERECTION BRACING AND SHORING FOR ALL STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE
STABILITY DURING ALL PHASES OF CONSTRUCTION.
LINTEL BEAM BOND BEAM 1.4 ALL SLABS,BEAMS,GIRDERS,AND OTHER STRUCTURAL ELEMENTS WHICH ARE NOT INDICATED DETAILED,DESIGNATED OR INADVERTENTLY OMITTED BUT ARE
NECESSARY BUT TO BE COORDINATED WITH THE ARCHITECTURAL AND OTHER ALLIED ENGINNERING AS WELL TO COMPLETE THE STRUCTURAL WORKS IN ACCORDANCE
WITH THE INTENT OF THE PLANS AND SPECIFICATIONS SHALL BE BROUGHT UP DURING MEETINGS.

1.5 IN THE INTERPRETATION OF THESE DRAWINGS INDICATED DIMENSIONS SHALL GOVERN AND DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES.

STANDARD BEAM DETAILS 1.6 SPECIFICATION NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.

1.7 ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE NOTED.

1.8 SHOP DRAWINGS FOR STEEL AND CONCRETE CONSTRUCTION SHALL BE BE SUBMITTED FOR APPROVAL PRIOR TO FABRICATION.
BAR SIZE BASIC LENGTH
1.9 ALL SPECIFICATIONS REFFERED TO IN THE DRAWINGS MUST BE THE LATEST EDITIONS UNLESS OTHERWISE NOTED.
ℓ db (MM) ℓ db (MM)
ℓ db (150MM MIN.) ℓ db (150MM MIN.)

D10MM Ø 150 2.0 FOUNDATION


2.1 FOOTINGS ARE DESIGNED FOR A NET ALLOWABLE SOIL BEARING PRESSURE OF 2000 Psf. AT A MINIMUM DEPTH OF (SEE DRAWING) FROM A NATURAL GRADE LEVEL.
D12MM Ø 175
THE ARCHITECT IN-CHARGE/CIVIL ENGINNER SHALL REPORT IN WRITING TO THE DESIGNER ON ACTUAL CONDITIONS UNCOVERED AND CONFIRM ACTUAL BEARING
CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE.
D16MM Ø 234 CRITICAL CRITICAL
SECTION SECTION
2.2 NO FOOTING SHALL REST ON FILL. FOOTINGS FOR CONCRETE HOLLOW BLOCKS WALLS AND OTHER MINOR STRUCTURE SHALL BE EMBEDDED AT LEAST 750 MM.
db

db
FROM THE NATURAL GRADE LEVEL UNLESS OTHERWISE NOTED.
D20MM Ø 292
2.3 PROVIDE TEMPORARY MEANS FOR REMOVAL OF WATER FROM ANY SOURCE DURING CONSTRUCTION DEWATERING SHALL BE CAREFULLY AND PROPERLY
D25MM Ø 365 PERFORMED TO AVOID DISTURBING FOUNDATIONS SLAB BEARING SURFACES.

2.4 THE ARCHITECT IN-CHARGE/CIVIL ENGINEER SHALL DESIGN, INSTALL, AND MONITOR ALL EXCAVATION RETENTION SYSTEMS AS REQUIRED FOR PROTECTION OF
D28MM Ø 409
180° HOOK 90° HOOK ADJACENT PROPERTIES AND PROVIDE ALL MEASURES AND PRECAUTIONS TO MINIMIZE SETTLEMENT OF AND PREVENT DAMAGE TO ADJACENT EXISTING OR NEW
CONSTRUCTION.
D32MM Ø 467
2.5 DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL GROUND FLOOR HAVE BEEN PLACED AND THE CONCRETE HAS ATTAINED THE REQUIRED STRENGTH.
D36MM Ø -
2.6 REFER TO ARCHITECTURAL DRAWINGS ELEVATIONS, DETAILS, REFER TO ARCHITECTURAL ,MECHANICAL, PLUMBING, AND OTHER TRADES FOR SUB-SOIL DRANAIGE
SYSTEM , MACHINERY ANCHORS AND OTHER EMBEDDED ITEMS , DEPRESSIONS ,FINISHES , DOWELS FOR MASONRY WALLS , CURBS, ETC.
DEVELOPMENT LENGTHS SHALL BE AS FOLLOWS:
2.7 ALL STRUCTURAL FILL MATERIALS SHALL BE COMPACTED TO 95% RELATIVE COMPACTION WITH ASTM D698. FILL SHOULD BE PLACED IN LIFTS NOT TO EXCEED 300MM.
A. USE 0.70 ℓ db FOR BARS WITH SIDE COVER (NORMAL TO PLANE OF HOOK) NOT LESS THAN 65MM, AND FOR
2.8 WHERE LOOSE MATERIAL IS ENCOUNTERED AT DEPTH OF EMBEDMENT INDICATED EXCAVATE TO FIRM LAYER.
90° HOOK, COVER ON BAR EXTENSION BEYOND HOOK NOT LESS THAN 50MM.

B. USE 0.80 ℓ db FOR BARS WITH HOOKS ENCLOSED VERTICALLY OR HORIZONTALLY WITHIN LATERAL TIES OR
STIRRUPS - TIES SPACED ALONG THE FULL DEVELOPMENT LENGTH ℓ dh NOT GREATER THAN 3db. 3.0 REINFORCING STEEL
C. USE 0.80 ℓ db FOR BARS NOT INCLUDED IN A AND B.
3.1 GRADE :
ASTM A 615 GRADE 40 12 DIA. TO 25 DIA. ASTM A 615 GRADE 33 10 DIA. 10 DIA. AND SMALLER ASTM A 185 OR BS 4483 SLAB ON GRADE
STANDARD HOOK BARS DEFORMED BARS (fy= 276 Mpa) DEFORMED BARS (fy=230 Mpa) WELDED WIRE FABRIC (fy= 500Mpa)
3.2 ALL BARS SHALL BE BENT COLD UNLESS PERMITTED BY THE STRUCTURAL ENGINEER.

3.3 THE MINIMUM LAP LENGHT ARE SHOWN THE TABULATION. (SEE TABLE 1).
BAR SIZE BASIC LENGTH MINIMUM LENGTH
ℓ db (MM) ℓ db (MM) ℓ db (MM) 3.4 ALL REINFORCING SHALL BE SUPPORTED IN CONFORMANCE WITH THE MANUAL OF STANDARD PRACTICE DETAILING REINFORCED CONCRETE STRUCTURE
(ACI 315 LATEST EDITION).

TOP BARS OTHERS 3.5 ALL REINFORCING BARS SHALL BE CLEANED THOUROUHLY OF ALL LOOSE RUST, SOIL OR OTHER MATERIAL IMMEDIATELY PROIR TO PLACING CONCRETE.
ℓ db (300MM MIN.)
3.6 ALL WELDING OF REINFORCEMENT SHALL CONFORM TO THE PROVISIONS OF THE STRUCTURAL WELDING CODE REINFORCING STEEL , AWS D 1.4.
D10MM Ø 90 395 300
3.7 A FULL MECHANICAL CONNECTION (REBAR SPLICER) SHALL DEVELOP IN TENSION OR COMPRESSION AS REQUIRED AT LEAST 125% OF THE SPECIFIED YIELD
D12MM Ø 130 470 350 STRENGHT fy OF THE REBAR IF USED, SUBMIT SAMPLE FOR APPROVAL OF THE DESIGNER.

3.8 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES , SHALL BE LOCATED AS FOLLOWS:


D16MM Ø 231 630 465 CRITICAL a.) INTERMEDIATE BEAMS, TOP BARS SHOULD BE SPLICED AT MIDSPAN AND BOTTOM BARS AT THE SUPPORT.
SECTION
b.)BEAMS FRAMING TO COLUMNS : TOP AND BOTTOM BARS SHALL NOT BE SPLICED WITHIN THE COLUMN
db

D20MM Ø 361 785 585 OR WITHIN A DISTANCE OF TWICE THE MEMBER DEPTH FROM THE FACE OF THE COLUMN. THE SPLICE LENGHT SHALL
NOT BE LESS THAN 1.3 x THE DEVELOPMENT LENGHT (Ld).
D25MM Ø 565 1185 915
c.) COLUMNS LAP SPLICES SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT AND THE SPLICE BAR SPLICE SHALL BE 0.60 M. IF STAGGARD SPLICING
IS USED.
d.) CMU WALLS: PROVIDE DOWELS ON R.C COLUMNS , BEAMS, FOOTINGS , AND FOOTINGS TIE- BEAMS TO MATCH CMU WALL REINFORCEMENT.
D28MM Ø 708 1330 1020
STRAIGHT 3.7 UNLESS INDICATED OTHERWISE ALL BEAMS TERMINATING AT COLUMN SHALL HAVE TOP & BOTTOM BARS EXTENDING TO THE FAR FACE OF THE COLUMN.
D32MM Ø 925 1520 1170 TERMINATING IN A STANDARD 90DEGRESS HOOK OF ANCHORAGE SHALL NOT BE LESS THAN 0.60 M.

STRAIGHT BARS

STANDARD DEVELOPMENT OF BARS


PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CONSTRUCTION NOTES
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 16
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 2 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
4.0 CONCRETE TABLE 1.0
4.1 UNLESS OTHERWISE INDICATED IN PLANS OR NOTED IN THE SPECIFICATIONS THE MINIMUM 28-DAYS CYLINDER COMPRESSIVE OF CONCRETE fc' SHALL BE
AS FOLLOWS;
a.) FOOTINGS , FOOTING TIE BEAMS , RETAINING WALLS 20.7Mpa(3000 Psi). MINIMUM EMBEDMENT AND LAP SPLICE (mm.)
AND BASEMENT WATER TANK.
b.) COLUMNS , PEDESTALS , AND SHEAR WALLS 20.7Mpa(3000 Psi).
c.) FLOOR SLABS, BEAMS AND GIRDERS
d.) DECK FLOORS , CANOPIES
20.7Mpa(3000 Psi).
20.7Mpa(3000 Psi).
fc' = 20.7 Mpa TO 40 Mpa
e.) PARTITIONS , CURTAIN WALLS ,BEDDED SLABS 17.0Mpa(2500 Psi).
OTHER THAN TOP BARS TOP BARS (W/IN 300 OF CONCRETE CAST BELOW)
SIDEWALKS , CURBS, AND GUTTER & OTHER BAR EMBEDMENT
NON-STRUCTURAL ELEMENTS
SIZE STRAIGHT LENGHT E CLASS A
f.) LEAN CONCRETE 10.0Mpa(1500 Psi). CLASS B CLASS C STRAIGHT CLASS A CLASS B CLASS C
EMBEDMENT W/ STD. END Tension SPLICE
Ld. ALSO FOR Tension SPLICE Tension SPLICE EMBEDMENT Tension SPLICE Tension SPLICE Tension SPLICE
4.2 a.) CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION , RE -HANDLING OR FLOWING, PLACING SHALL BE DONE PREFERABLY WITH HOOK H (1.3 x LD.) (1.7 x LD.)
COMPRESSION (1.4 x LD.) (1.4 x LD.) (1.82 x LD.) (2.38 x LD.)
BUGGIES , BUCKETS OR WHEEL BARROWS. SPLICE
b.) NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR
USUAL CONDITIONS WHERE VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH. E = 25
10 dia. 250 E = 150 300 400 500 350 350 450 600
c.) AGGREGATE SIZE SHALL BE AS FOLLOWS:
a.) 20 mm. SUSPENDED SLABS, BEAMS, GIRDERS,WALLS AND COLUMNS.
E = 150
b.) 40 mm. FOOTING , THICKENED SLABS AND SLAB ON GRADE. 12 dia. 300 400 500 600 400 400 600 700
E = 200
d.) MINIMUM COVERING OF CONCRETE FOR REINFORCING BARS SHALL NOT BE LESS THAN:
-75mm. UNIFORMED CONCRETE DEPOSITED AGAINST GROUND. E = 200
-50mm. FORMED CONCRETE AGAINST GROUND OR EXPOSED TO WEATHER FOR BARS 16 dia. 400 E = 250 500 600 700 500 500 700 900
LARGER THAN 16MM. IN DIAMETER.
-40mm. FORMED CONCRETE AGAINST GROUND OR EXPOSED TO WEATHER FOR BARS
16MM. IN DIAMETER AND SMALLER. E = 250
20 dia. 500 E = 300 600 700 900 700 700 900 1200
-40mm. BEAMS AND COLUMNS NOT EXPOSED TO GROUND OR TO WATER.
-20mm. SLABS AND WALLS NOT TO EXPOSED TO GROUND OR TO WEATHER.
-75mm. CONCRETE EXPOSED TO WEATHER. E = 300
25 dia. 800 E = 400 800 1000 1400 1100 1100 1500 1900
e.) CONCRETE CYLINDERS SHALL BE TAKEN FOR EACH DAYS POUR AND EACH 50cu.m. OR FRACTION THEREOF CAST IN ACCORDANCE WITH ASTM C31 AND TESTED
IN ACCORDANCE WITH ASTM C39.

f.) WELDED WIRE FABRIC SHALL BE MADE OF COLD DRAWN WIRE AND SHALL CONFORM TO ASTM A185. END END FOR COLUMNS BEAM BOT. FOR CONCRETE FOR BEAMS BEAM TOP BEAM TOP FOR CONCRETE
ANCHORAGE ANCHORAGE VERT. BARS BARS WHERE WALL VERT. INTO WALLS. BARS WHERE BARS WHERE WALL HOR.
g.) PRIOR TO PLACING CONCRETE , ALL REINFORCING STEEL ANCHOR BOLTS , DOWELS , EMBEDDED STRUCTURAL STEEL SHAPES , BARS, PLATES , OR OTHER FOR BOTTOM FOR BOTTOM BEAM BOTTOM TENSILE STRESS BAR SLAB & TENSILE STRESS TENSILE STRESS BAR BEAM

REMARKS
INSERTS SHALL BE WELL SECURED IN POSITION AND APPROVED BY THE ENGINEER. BARS OF SLAB BARS OF SLAB & BARS WHERE IN BARS SLAB & BEAMS IN IN TOP BARS
& BEAMS,WALLS TENSILE STRESS <(0.5fy) BARS WHERE BARS <(0.5fy) BARS <(0.5fy) WHERE
h.) EXPOSED EDGES OF CONCRETE SHALL HAVE 25 MM.(1") CHAMFER UNLESS OTHERWISE NOTED OR DETAILED. BEAMS. ,COLUMNS IN & % of BAR TENSILE STRESS & % of BAR & % of BAR TENSILE STRESS
DOWELS TO BAR<(0.5fy) SPLICE >75%. IN BARS<(0.5fy)& SPLICE >50%. SPLICE >75%. IN BARS<(0.5fy)&
i.) CONSTRUCTION JOINTS IN ALL FLOORS SHALL BE LOCATED WITHIN THE MIDDLE THIRD OF SPANS OF SLABS ,BEAMS , JOINTS, GIRDERS SHALL BE OFFSET A FOOTINGS. & % of BAR % of BARS % of BARS
MINIMUM DISTANCE OF TWO TIMES THE WIDTH OF INTERSECTING LINES. SPLICE > SPLICE 100%. SPLICE= 100%.
50%.

5.0 MASONRY WALLS


5.1 CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 GRADE N.

5.2 MORTAR AND GROUT FOR ALL- REINFORCED MASONRY SHALL CONFORM TO ASTM 270-TYPE M AND SHALL HAVE A MINIMUM 28-DAYS STANDARD CYLINDER
COMPRESSIVE STRENGHT OF 20.7 Mpa (3000 Psi).

5.3 ALL MASONRY WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF CONCRETE HOLLOW BLOCKS REINFORCEMENT UNLESS
OTHERWISE INDICATED ON PLANS.

SCHEDULE OF CONCRETE HOLLOW BLOCK REINFORCEMENTS


6.0 REFERENCES
BLOCK REINFORCEMENT BLOCK REINFORCEMENT THE FOLLOWING SHALL GOVERN THE DESIGN FABRICATION AND CONSTRUCTION OF THE PROJECT:
THICKNESS THICKNESS
(mm) HORIZONTAL VERTICAL (mm) HORIZONTAL VERTICAL
6.1 AMERICAN CONCRETE INSTITUTE (ACI) PUBLICATIONS.
100 10mm.dia.AT 600 O.C. 10mm.dia.AT 600 O.C. 150 12mm.dia.AT 600 O.C. 12mm.dia.AT 600 O.C.
ACI 318- 89 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE.
ACI 315- 83 MANUAL OF STANDARD PRACTICE FOR DETAILING OF CONCRETE REINFORCEMENT.
NOTE:
6.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) PUBLICATION.
a. MINIMUM LAP SPLICES =250MM.
MANUAL OF STEEL CONSTRUCTION.,9TH EDITION.
b. PROVIDE RIGHT ANGLE REINFORCEMENT 700 MM.LONG.
c. WHERE CHB WALLS ADJOIN COLUMNS RC BEAMS AND WALLS ,DOWELS, WITH THE SAME SIZE AND SPACING AS VERTICAL OR HORIZONTAL
REINFORCEMENT SHALL BE PROVIDED. 6.3 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) 4TH. EDITION. , 1992.
d. PROVIDE BEAM BLOCKS AT EVERY FOURTH COURSE AND POST AT 300 O.C.

5.4 UNLESS INDICATED OTHERWISE CMU WALLS USED IN THIS SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGHT AT 28 DAYS , f'm=4.83 Mpa.

5.5 UNLESS INDICATED OTHERWISE , ALL CMU WALLS SHALL BE FILLED SOLIDLY WITH GROUT.

PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS CONSTRUCTION NOTES
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 17
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 3 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
A B C LEGEND

WALL FOOTING ONE


WF1 INTERIOR WALL
6.00 M.

3.00 M. 3.00 M.
COLUMN ONE - FOOTING
C1F1 C1F1 C1F1 C1F1
ONE
FTB-2 FTB-2

6
COLUMN TWO - FOOTING

W1F1
C2F2
TWO

3.21 M.

3.21 M.
FTB-2

FTB-2
W1F1
ELEV. 0 +175 ELEV. 0 +175
C1F1 C1F1

5
FTB-1

3.21 M.

3.21 M.
FTB-2

FTB-2
ELEV. 0+ 225

C1F1 C1F1

4
FTB-1

15.00 M.

15.00 M.
3.21 M.

3.21 M.
FTB-2

FTB-2
SLAB ON FILL
THICKNESS = 100 MM + FINISH W/
10 MM Ø TEMP. BARS SPACED @
C1F1 400 MM O.C. BOTHWAYS C1F1
3

3
FTB-1
3.21 M.

3.21 M.
FTB-2

FTB-2
ELEV. 0+ 225

C1F1 C2F2 C2F2 C1F1 C1F1

FTB-2
2

2
RAMP
2.15 M.

2.15 M.
ELEV. 0+ 200
C2F2 C2F2
RAMP
1

1
UP
1.50 M. 3.00 M. 1.50 M.

6.00 M.

A B C D

S - 100 SCALE
1 4
FOUNDATION PLAN 1 100
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS FOUNDATION PLAN
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 18
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 5 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
COLUMN SCHEDULE
FFL
LEVEL COLUMN ( C - 1 ) COLUMN ( C - 2 ) COLUMN ( C - 3 ) COLUMN ( C - 4 ) COLUMN ( C - 5 ) NAT. GRD. LINE

FTB FTB
ROOF BEAM LEVEL

Y - BAR ( LONGITUDINAL )

DEPTH
X - BAR ( TRANS VERSE )
SIZE : SIZE :
350 mm. x 350 mm. 300 mm. x 300 mm. 100 MM. THK.
MAIN BARS : MAIN BARS : GRAVEL FILL
4 - 25 MM. Ø BARS. 8 - 20 MM. Ø BARS.
ADDITIONAL BARS :

T
8 - 20 MM. Ø BARS.
TIES : TIES : SECTION
3 TIES AT 10 MM. Ø 3 TIES AT 10 MM. Ø
3 @ 50 , 5 @ 100 , 7 @ 150 3 @ 50 , 5 @ 100 , 7 @ 150
REST 200 MM. TO CENTER. REST 200 MM. TO CENTER.

LENGTH

DETAIL OF WF-1
GROUND LEVEL TO
ROOF BEAM LEVEL

2
S 5 SCALE: 1:30 M.
X - BAR ( TRANS VERSE )
SIZE : SIZE :
350 mm. x 350 mm. 300 mm. x 300 mm.
MAIN BARS : MAIN BARS : Y - BAR ( LONGITUDINAL )
4 - 25 MM. Ø BARS. 8 - 20 MM. Ø BARS.
ADDITIONAL BARS :
8 - 20 MM. Ø BARS.

WIDTH
TIES : TIES :
3 TIES AT 10 MM. Ø 3 TIES AT 10 MM. Ø
3 @ 50 , 5 @ 100 , 7 @ 150 3 @ 50 , 5 @ 100 , 7 @ 150
REST 200 MM. TO CENTER. REST 200 MM. TO CENTER.
FOUNDATION LEVEL TO
GROUND FLOOR LEVEL

PLAN
SIZE : SIZE :
350 mm. x 350 mm. 300 mm. x 300 mm.
MAIN BARS :
4 - 25 MM. Ø BARS.
MAIN BARS :
8 - 20 MM. Ø BARS. 1 TYPICAL FOOTING DETAIL
ADDITIONAL BARS :
8 - 20 MM. Ø BARS.
S 5 SCALE: 1:30 M.

TIES : TIES :
3 TIES AT 10 MM. Ø 3 TIES AT 10 MM. Ø
3 @ 50 , 5 @ 100 , 7 @ 150 3 @ 50 , 5 @ 100 , 7 @ 150
REST 200 MM. TO CENTER. REST 200 MM. TO CENTER.

SCHEDULE OF FOOTING
REINFORCEMENTS FOOTING DIMENSIONS

FOOTING MARK REMARKS


BAR " X " BAR " Y " LENGTH WIDTH DEPTH THICKNESS FTB

F1 10 - 16 MM. DIA. 10 - 16 MM. DIA. 1300 1300 1200 250 SQUARE FOOTING
F2 8 - 16 MM. DIA. 8 - 16 MM. DIA. 1200 1200 1200 250 SQUARE FOOTING

3 WALL TO TIE-BEAM CONN. DETAIL


S 5 SCALE: 1:20 M.

PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS COLUMN SCHEDULE
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR SCHEDULE OF FOOTING
CONSTRUCTION OF MULTI-PURPOSE TYPICAL FOOTING DETAIL LEO EDWARD L. OPPURA S 19
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr.
DETAIL OF WF-1
CARIGARA, LEYTE BUILDING WALL TO TIE-BEAM CONNECTION DETAIL
ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 6 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
A B C LEGEND

6.00 M.

3.00 M. 3.00 M.

B-1 B-1

6
3.21 M.

3.21 M.
B-1

B-2

B-1
S-1 S-1

G-1 G-1

5
3.21 M.

3.21 M.
B-1

B-2

B-1
S-1 S-1

G-1 G-1
4

4
STAIR WELL

15.00 M.

15.00 M.
3.21 M.

3.21 M.
B-1

B-2

B-1
S-2 S-1

B-4
S-1
3

3
G-1 G-1
3.21 M.

3.21 M.
B-1

B-2

B-1
S-1 S-1
2

2
B-2 B-1 B-2
2.15 M.

2.15 M.
B-3

B-3
S-1
1

1
B-1

1.50 M. 3.00 M. 1.50 M.

6.00 M.

A B C D

S - 100 SCALE
1 6
SECOND FLOOR FRAMING PLAN 1 100
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS SECOND FLOOR FRAMING PLAN
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 20
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 7 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
BEAM & GIRDER SCHEDULE SCHEDULE OF SLAB
BEAM DIMENSIONS REINFORCEMENT BARS
BAR ARRANGEMENT STIRRUPS SIZE REINFORCEMENT BARS
FLOOR LEVEL BEAM MARK SUPPORTS MIDSPAN & SPACING MARK THICKNESS REMARKS
b h WEB BARS
(mm) (mm) PARALLEL TO LONG SPAN PARALLEL TO SHORT SPAN
TOP BOTTOM TOP BOTTOM SUPPORTS MIDSPAN
10 mmØ @ 250 mm O.C. 10 mmØ @ 190 mm O.C.
10mm Ø, 1@50 BENT-UP 2 OUT OF 3 @ BENT-UP 2 OUT OF 3 @
5-20 mmØ 4-20 mmØ 4-20 mmØ 4-20 mmØ 7@100, REST @ S-1 125 MM TWO-WAY
RB - 1 250 400 L/4 FROM THE FACE OF L/4 FROM THE FACE OF
LEVEL
ROOF

200mm O.C. THE SUPPORT THE SUPPORT

10 mmØ @ 250 mm O.C.


10mm Ø, 1@50 10 mmØ @ 250 mm O.C. BENT-UP 2 OUT OF 3 @
S-2 125 MM ONE-WAY
RB - 2 200 300 2-16 mmØ 2-16 mmØ 2-16 mmØ 2-16 mmØ 6@100, REST @ TEMP. BARS L/4 FROM THE FACE OF
200mm O.C. THE SUPPORT

10mm Ø, 1@50
G-1 300 500 6-20 mmØ 4-20 mmØ 4-20 mmØ 6-20 mmØ 2-16 mmØ 10@100, REST @
200mm O.C.
2 3
1
4
10mm Ø, 1@50
B-1 250 350 4-20 mmØ 2-20 mmØ 2-20 mmØ 4-20 mmØ 2-16 mmØ 8@100, REST @ COL. COL.
200mm O.C.
SECOND FLOOR
LEVEL

10mm Ø, 1@50
B-2 250 350 4-16 mmØ 2-16 mmØ 2-16 mmØ 4-16 mmØ 2-16 mmØ 8@100, REST @
200mm O.C.

10mm Ø, 1@50
B-3 250 350 3-16 mmØ 2-16 mmØ 2-16 mmØ 3-16 mmØ 7@100, REST @
200mm O.C.

10mm Ø, 1@50
SB - 1 200 300 2-16 mmØ 2-16 mmØ 2-16 mmØ 2-16 mmØ 3@100, REST @
200mm O.C.

10mm Ø, 1@50
FTB - 1 300 500 4-20 mmØ 4-20 mmØ 4-20 mmØ 4-20 mmØ 2-16 mmØ 10@100, REST @
200mm O.C.
BEAM
TIE

10mm Ø, 1@50
FTB - 2 250 350 5-20 mmØ 2-20 mmØ 3-20 mmØ 2-20 mmØ 8@100, REST @
COL. COL.
200mm O.C.

SPAN RANGES 3.50 M. ( VERIFY )


SEE FLOOR FRAMING PLAN

L1 L2 L3 A B

2D
TYPICAL TWO - WAY SLAB DETAIL
L2/3 L2/3 L3/3 L3/3

2D 2D 2D 2D
LAP SPLICES ARE ALLOWED LAP SPLICES ARE ALLOWED
ONLY ON THIS PORTION
ONLY ON THIS PORTION
A B
SHORT SPAN = S

S/4
CONTINOUS

L2/5 L2/5 L2/5 L3/6


2 - 16 mm Ø SIDE BARS

RC DISCONTINOUS EDGE RC CONTINOUS


BEAM BEAM

BEAM SECTION DETAIL

RC SLAB SECTION DETAIL


PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS BEAM AND GIRDER SCHEDULE
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR SCHEDULE OF SLAB
CONSTRUCTION OF MULTI-PURPOSE S 21
LEYTE SECOND ENGINEERING DISTRICT BEAM SECTION DETAIL REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING TYPICAL TWO-WAY SLAB DETAIL ENGINEERING ASSISTANT B
RC SLAB SECTION DETAIL ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 8 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
A B C LEGEND

6.00 M.

3.00 M. 3.00 M.

RB- 2 RB- 2

6
TRUSS 1 TRUSS 1

C PURLIN

C PURLIN
GUTTER

GUTTER
RB- 2
3.21 M.

3.21 M.
RB- 2
RB- 1 RB- 1

5
TRUSS 1 TRUSS 1

RB- 2
3.21 M.

3.21 M.
RB- 2
GUTTER

GUTTER
RB- 1 RB- 1
4

4
TRUSS 1 TRUSS 1
15.00 M.

15.00 M.
RB- 2
3.21 M.

3.21 M.
RB- 2
RB- 1 RB- 1
3

3
TRUSS 1 TRUSS 1
RB- 2

C PURLIN

C PURLIN
3.21 M.

3.21 M.
RB- 2
GUTTER

GUTTER
TRUSS 1 RB- 2 TRUSS 1
2

2
TRUSS 2
2.15 M.

2.15 M.
RB- 2

CB- 1 RB- 2
CB- 1
GUTTER

GUTTER
1

1
TRUSS 2

1.50 M. 3.00 M. 1.50 M.

6.00 M.

A B C D

S - 100 SCALE
1 8
ROOF FRAMING PLAN 1 100
PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS ROOF FRAMING PLAN
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 22
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 9 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
6 mm. thk. GUSSET GA 26 ( .6mm thk. ) PRE - PAINTED
PLATE PRE - FORMED 50 mm. x 100 mm. x 2.0 mm. C - PURLINS
G.I.RIDGE ROLL. @ 700 mm. ON CENTER.
7981

965 1008 1008 1008 1008 1008 1008 965

APEX OF LINE

GA 26 ( .5mm thk. ) PRE - PAINTED


LONG SPAN CORRUGATED
G.I. SHEET ROOFING.

2007
50 mm. x 50 mm. x 6 mm.
CLIP ANGLE BAR.

2617
12 mm. dia. ROUND BAR
SAG ROD ( Bolt Type at Ends )
STAGGARD.

2- 65 mm. x 65 mm. x 6 mm. thk.

615
ANGLE BAR 2- 65 mm. x 65 mm. x 6 mm. thk.
ANGLE BAR GA 26 ( .6mm thk. ) PRE - PAINTED
TOP & BOTTOM CHORD. PRE - FORMED
WEB / STRUT MEMBER. 250 mm. x 300 mm. x 12 mm.
4 - 20 mm. dia. x 300 mm. thk. STEEL BASE PLATE. G.I. GUTTER.
184 ANCHOR BOLT.
75 mm. dia. PVC
DOWNSPOUT CLASS
T - 1 DETAIL 100.

50 mm. x 100 mm. x 2.0 mm. C - PURLINS


2- 65 mm. x 65 mm. x 6 mm. thk. GA 26 ( .6mm thk. ) PRE - PAINTED @ 700 mm. ON CENTER.
ANGLE BAR PRE - FORMED
TOP & BOTTOM CHORD. RIDGE ROLL.
5100
1050 300 600 600 600 600 300 1050
1151

GA 26 ( .5mm thk. ) PRE - PAINTED


LONG SPAN CORRUGATED
G.I. SHEET ROOFING.
1787

2- 65 mm. x 65 mm. x 6 mm. thk.


637

ANGLE BAR GA 26 ( .6mm thk. ) PRE - PAINTED


WEB / STRUT MEMBER. PRE - FORMED
G.I. GUTTER.
2- 65 mm. x 65 mm. x 6 mm. thk.
184

ANGLE BAR
TOP & BOTTOM CHORD.

T - 2 DETAIL
TRUSS DETAILS
SCALE 1: 20 M.

PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS TRUSS DETAILS
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 23
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 10 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE:
4 3

4 3 50 mm. x 100 mm.


WOOD HANDRAIL.

900
SECOND FIN. FLR. LINE LANDING SECOND FIN. FLR. LINE

13
20 mm. SQUARE
BAR RAILINGS.
12
250
11 RUN
STAIRS BRASS
250 NOSING.

RUN
200
RUN 12 mm. dia. 10
BENT / REINFORCING BARS
SPACED AT 150 mm. ON
RUN
200

CENTER. 9
S

12 mm. dia.
S
NE

REINFORCING BARS 8
K
AB 125
IC

SPACED AT SHOWN.

650
TH

7
SL

12 mm. dia.
REINFORCING BARS
SPACED AT 150 mm. ON
CENTER. 6

100
12 mm. dia. 12 mm. dia.
TEMPERATURE BARS REINFORCING BARS.
SPACED AT 150 mm. ON
5
CENTER BOTHWAYS.
4

125 3

900
2

1
SECTION ELEVATION DETAIL
FIN. FLR. LINE FIN. FLR. LINE

SECTION ELEVATION DETAIL


200

FINISH GRADE

16 mm. dia.
VERTICAL BARS
500

SPACED AT 150
10 mm. dia. mm. ON CENTER.
STIRRUPS
5 - 16 mm. dia.
SPACED AT 3 - 50 ,
STRAIGHT BARS /
4 - 100 REST AT
REINFORCING
200 mm. ON CENTER.
SPACED AT SHOWN.
250

100 mm. thk.


GRAVEL FILL. 16 mm. dia.
STRAIGHT BARS /
800 REINFORCING

STAIRS DETAILS
SCALE 1: 20 M.

PROJECT NAME AND LOCATION: SHEET CONTENTS: DRAFTED/PREPARED BY: REVIEWED: SUBMITTED: RECOMMENDED: APPROVED: SET NO. SHEET NO.
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS STAIRS DETAILS
REGIONAL OFFICE NO. 8 DETAILED ENGINEERING DESIGN PLAN FOR
CONSTRUCTION OF MULTI-PURPOSE S 24
LEYTE SECOND ENGINEERING DISTRICT REGAREE M. SILOT CRESCENTE KIM N. BODO , Jr. ROCHEL D. HERMANO FRANCISCO E. ROBIN , Jr. LEO EDWARD L. OPPURA
CARIGARA, LEYTE BUILDING ENGINEERING ASSISTANT B ENGINEERING ASSISTANT (ARCHITECT) OIC-CHIEF, PLANNING & DESIGN SECTION OIC-ASSISTANT DISTRICT ENGINEER OIC-DISTRICT ENGINEER 11 11 37
BARANGAY DISTRICT 3 , PASTRANA , LEYTE DATE: DATE: DATE: DATE: