STORM DRAINAGE
SYSTEM
Stction 1101- GENERAL
1103.1 Materials
1103.1.1 Strainers
1103.1.1.1 Roof drains shall be equipped
with strainers extending not less than
102 mm above the surface of the roof
immediately adjacent to the drain,
Dome-Type Strainers shall have a
minimum total net inlet area of one and
one-half ( 1 1/2) times the area of the
outlet pipe to which it is connected.
Section 1103 - ROOF DRAIN
1103.1.1.2
Roof deck strainers for use on sun decks,
parking decks and similar occupied
areas shall be an approved flat-surface
type which is level with the deck. Such
drains shall have a total net inlet area not
tess than two (2) times the area of the
outlet pipe to which the drain is
connected.
Section 1103 - ROOF DRAIN
1103.1.1.3
Roof drains passing through the roof into
the interior of a building shall be
made watertight at the roof level by the
usc of C.l. drain with integrally cast
waterstop ring around the outside of
body and placed at mid-depth of the
concrete roof slab and the installation of
a clamped suitable flashing material
around the drain.
Section 1103 - ROOF DRAIN
1103.1.1.4
In all cases the outlet connections are
inside-caulk or female screwed.
Section 1104- SIZING OF
RAINWATER PIPING
3 Factors to Consider
• Roof Area
• Slope
• Rainfall Intensity
Section 1104- SIZING OF
RAINWATER PIPING
1104.1 Vertical rainwater piping shall be
sized in accordance with Table 11-1,
which is based upon maximum depth in
mm or rainfall per hour falling upon a
g i v e n r o o f a r e a i n s q u a r e m e t e r.
Consult local rainfall figures to
determine maximum rainfall per hour.
N o r m a l l y, a 1 0 2 m m / h o u r r a i n f a l l
intensity is used around Manila area.
TABLE 11-1
Section 1104- SIZING OF
RAINWATER PIPING
Find area in column under 127 mm and at slope of 0.02 and read
561.1 m2 (closet). choose 152 mm as size of leader and
downspout at leftmost column.
Section 1104- SIZING OF
RAINWATER PIPING
1104.4. Roof Gutter. The size of semi-circular
bottom roof gutters shall be based on the
maximum roof area, in accordance with Table 11-3
Example: Table 11-3
Roof Area = 186 m 2
Max Rainfall/hr. = 102 mm
Pipe Laid at 10.4 mm/m slope or s = 0.01
Find area in column under 102 mm rainfall
intensity on Table with s = .01 and read 181 .4 m 2
(as closest) move to left and read 177.8 mm
diameter gutter.
Section 1104- SIZING OF
RAINWATER PIPING
1104.5 If the rainfall is more or less than those
shown in Table 11-2 and 11-3. then adjust the
figures in the 50.8 mm rainfall by multiplying by two
(2) and dividing by the maximum rate of rainfall .in
mm/hour.
TABLE 11-4
Sizing Roof Drains, Leaders, and Vertical Rainwater
Piping
Chapter 12
HOUSE DRAINS
AND HOUSE
SEWERS
(continuation)
Section 1202 - DAMAGE TO PUBLIC SEWER
OR PRIVATE SEW AGE DISPOSAL SYSTEM
4 Streams 15.2 m 2