Direct Design Method Dr. Muhaned A.

Shalall

Direct Design Method


Ex. No. 4: For two-way slab was showing below, Design interior frame A by D.D.M.

Data:
# columns 400 x 400,
# drop size = 2.0x2.0 m,
6.0 m

# drop thickness = 50 mm,


# Slab thickness = 200 mm,
# column capitals = 1x1 m,

Frame A
# capital depth = 500 mm,
# column height= 4.5 m,
6.0 m

# f`c = 28 MPa,
# fy = 420 Mpa,
# DL= 5.0 kN/m2, (without slab weight)
# LL= 2.5 kN/m2.
5.0 m 6.0 m 5.0 m

Sol:
Factored moment slab

𝐷𝐿 = 5.0 + 0.2 + 0.05 ∗ ∗ 24 = 9.96 kN/m2

𝑞𝑢 = 2.5 ∗ 1.6 + 9.96 ∗ 1.2 = 15.952 ≈ 16.0 kN/m2

𝑙𝑛1 = 5.0 − 1.0 = 4.0 𝑚, 𝑙𝑛2 = 6.0 − 1.0 = 5.0 𝑚, 𝑙2 = + = 6.0 𝑚


∗ . ∗ .
𝑀𝑜1 = 16 = 192 kN.m 𝑀𝑜2 = 16 = 300 kN.m

C=0 → 𝛽𝑡 = 0
. .
𝛼1 = 0.0 = = 1.0 = = 1.2
. .

Interpolation
1:- Interior negative
𝑙2
𝛼1 = 0.0 → 𝐶. 𝑆. % = 75%
𝑙1
2:- Exterior negative

𝛼1 = 0, 𝛽𝑡 = 0.0 → 𝐶. 𝑆. % = 100%

1:- Interior positive

26
‫ محاضرات الخرسانة المسلحة‬/ ‫ المرحلة الرابعة‬/ ‫ قسم الهندسة المدنية‬/ ‫كلية الهندسة جامعة القادسية‬
Direct Design Method Dr. Muhaned A. Shalall

𝑙2
𝛼1 = 0.0 → 𝐶. 𝑆. % = 60%
𝑙1

qu 16.0 16.0 16.0

Ln 4.0 5.0 5.0

Mo 192 300 192

D.F 0.26 0.52 0.70 0.65 0.35 0.65 0.70 0.52 0.26

Mu( - ) 49.92 134.4 195 195 134.4 49.92

Mu( +) 99.84 105 99.84


L2
1
L1
0 0 0
bt 0 0
L2/L1 1.2 1.0 1.2
(-) 100 75 75 100

Col. strip
D.F
(+) 60 60 60

Col. strip
Mu( - ) 49.92 100.8 146.25 146.25 100.8 49.92

Slab
Mu( +) 59.9 63.0 59.9

Mid. strip
Mu( - ) 0 33.6 48.75 48.75 33.6 0

Slab
Mu( +) 39.94 42.0 39.94

27
‫ محاضرات الخرسانة المسلحة‬/ ‫ المرحلة الرابعة‬/ ‫ قسم الهندسة المدنية‬/ ‫كلية الهندسة جامعة القادسية‬
Direct Design Method Dr. Muhaned A. Shalall

𝑀𝑢 𝑓𝑦 1 2𝑚𝑅
𝑅= 𝑚= 𝜌= 1− 1−
∅𝑏𝑑 0.85𝑓′𝑐 𝑚 𝑓𝑦

Compute of steel reinforcement for column strip

Mu 146.25
49.92 59.9 100.8 146.25 63.0 100.8 59.9 49.92
L/2 Or drop size
(kN.m)
b (mm) 2000 2500 2000 2000 3000 2000 2000 2500 2000

d (mm) 220 170 220 170 220 170 220

R (MPa) 0.573 0.922 1.679 0.808 1.679 0.922 0.573

r (%) 0.138 0.224 0.415 0.196 0.415 0.224 0.138


As=rbd 1826
608 952 1826 1000 952 608
(mm2)

As=0.0018bt 900
900 900 900 1080 900 900
(mm2)
As (max.) 1826
900 952 1826 1080 952 900
(mm2)
No. bar 16.6
7.97 8.43 16.16 9.56 8.43 7.97
As/As(bar)
No. bar
4 6.25 4 7.5 4 6.25 4
b/S(max)
No. bar 17
8 9 17 10 9 8
use

S (mm) 250 277.7 117.65 300 117.65 277.7 250

28
‫ محاضرات الخرسانة المسلحة‬/ ‫ المرحلة الرابعة‬/ ‫ قسم الهندسة المدنية‬/ ‫كلية الهندسة جامعة القادسية‬
Direct Design Method Dr. Muhaned A. Shalall

𝑀𝑢 𝑓𝑦 1 2𝑚𝑅
𝑅= 𝑚= 𝜌= 1− 1−
∅𝑏𝑑 0.85𝑓′𝑐 𝑚 𝑓𝑦

Compute of steel reinforcement for Middle strip

Mu 48.75
0 39.94 33.6 48.75 42.0 33.6 39.94 0
(kN.m)
‫ االصلية من‬b ‫باملدل سترب ناخذ‬
b (mm) 3500 3500 3500 3000 3000 3000 3500 3500 3500
‫مثل الكولوم سترب‬

d (mm) 170 170 170 170 170 170 170

R (MPa) 0.0 0.439 0.625 0.539 0.625 0.439 0

r (%) 0.0 0.106 0.151 0.13 0.151 0.106 0


As=rbd 771
0.0 631 771 663 631 0
(mm2)

As=0.0018bt
1260 1260 1260 1080 1080 1080 1260 1260 1260
(mm2)
As (max.) 1260
1260 1260 1260 1080 1260 1260
(mm2)
No. bar 11.15
11.15 11.15 11.15 9.56 11.15 11.15
As/As(bar)
No. bar
8.75 8.75 8.75 7.5 8.75 8.75 8.75
b/S(max)
No. bar 12
12 12 12 10 12 12
use

S (mm) 291.6 291.6 291.6 300 291.6 291.6 291.6

29