Problem
What is the reason for PanelView
Component and PanelView 800 error:

Data Access Error for Alias xxx,
Controller yyy, Address is zzz

PanelView Component or PanelView 800 in


run mode returns the errors:

Data access Error Communication flag
is 0 on all the tags

Data Access Error for Alias xxx,
Controller yyy, Address is zzz

Solution 1
This error can occur if the Ethernet IP
address as configured in the PanelView
Component Communication, Driver,
or Address field does not match the actual
IP address of the intended target PLC.

Solution 2
It can also be because of a project created in
an older version of CCW downloaded into a
newer version of Micro 800.In that case we
need to export all the program
components,create a new project with new
controller revision and re import it back.To
check we need to view Controller-General

1 of 4 1/16/2019, 4:40 PM
66192 - PanelView Component/80... https://rockwellautomation.custhel...

tab and look for Controller project version.

Solution 3
On the terminal itself, the Ethernet driver on
the Communications tab had the Port set to
0 and not 44818. Change that Port value
back to 44818.

Solution 4
Make sure that the correct Controller
Type is chosen on the Communications tab

Solution 5
The PLC serial port is not set the same as
the PanelView Component port.

Check baud, DF1 vs DH-485 etc.

Solution 6
The error can occur if External Access of
the PLC tag is set to None, it should be set
to Read/Write

2 of 4 1/16/2019, 4:40 PM
66192 - PanelView Component/80... https://rockwellautomation.custhel...

Solution 7
If you are using a CompactLogix controller,
make sure that the PanelView 800 is not in
the Logix 5000 IO three

Attachments

DISCLAIMER
This knowledge base web site is intended to
provide general technical information on a
particular subject or subjects and is not an
exhaustive treatment of such subjects.
Accordingly, the information in this web site
is not intended to constitute application,
design, software or other professional
engineering advice or services. Before
making any decision or taking any action,
which might affect your equipment, you
should consult a qualified professional
advisor.

ROCKWELL AUTOMATION DOES NOT


WARRANT THE COMPLETENESS,
TIMELINESS OR ACCURACY OF ANY OF
THE DATA CONTAINED IN THIS WEB SITE
AND MAY MAKE CHANGES THERETO AT
ANY TIME IN ITS SOLE DISCRETION
WITHOUT NOTICE. FURTHER, ALL
INFORMATION CONVEYED HEREBY IS
PROVIDED TO USERS "AS IS." IN NO
EVENT SHALL ROCKWELL BE LIABLE
FOR ANY DAMAGES OF ANY KIND
INCLUDING DIRECT, INDIRECT,
INCIDENTAL, CONSEQUENTIAL, LOSS
PROFIT OR DAMAGE, EVEN IF
ROCKWELL AUTOMATION HAVE BEEN
ADVISED ON THE POSSIBILITY OF SUCH
DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS


ALL WARRANTIES WHETHER
EXPRESSED OR IMPLIED IN RESPECT
OF THE INFORMATION (INCLUDING
SOFTWARE) PROVIDED HEREBY,

3 of 4 1/16/2019, 4:40 PM
66192 - PanelView Component/80... https://rockwellautomation.custhel...

INCLUDING THE IMPLIED WARRANTIES


OF FITNESS FOR A PARTICULAR
PURPOSE, MERCHANTABILITY, AND
NON-INFRINGEMENT. Note that certain
jurisdictions do not countenance the
exclusion of implied warranties; thus, this
disclaimer may not apply to you.

This page is best viewed in Internet Explorer 11,


Edge, Firefox 41, Chrome 46, Safari 9 or newer.

4 of 4 1/16/2019, 4:40 PM

You might also like