Perhitungan Kebutuhan Air Panas
Perhitungan Kebutuhan Air Panas
Kebutuhan Air Panas
All Season Hotel
Pangkal Pinang
PERHITUNGAN KEBUTUHAN AIR PANAS
1. DATA DATA PROYEK
Jumlah kamar = 170 Kamar
Kamar mandi shower = 170 Kamar
Kamar mandi wastafel = 170 Kamar
Jumlah penghuni / kamar = 2 Orang
Volume mandi / hari = 2 Orang
Volume mandi shower (40º C) = 50 Liter
Volume mandi wastafel (40º C) = 10 Liter
2. ASUMSI PERENCANAAN AIR PANAS
Temperatur air panas = 60 º C
Temperatur air dingin = 30 º C
Temperatur air hangat = 38 º C
Perubahan temperatur air panas = 32 º C
Tingkat hunian = 80 %
Loses pipa sirkulasi = 20 %
Peak Periode = 20 %
Page 1 of 2
3. PERHITUNGAN KEBUTUHAN AIR PANAS
TOTAL KEBUTUHAN AIR PANAS (60 ºC) = 38 ºC ‐ 30 ºC 43,200
__________________ x
60 ºC ‐ 30 ºC
= 11,520 Liter
TINGKAT HUNIAN 80% = 9,216 Liter
4. KEBUTUHAN TANGKI
Kebutuhan Air Panas = 9.216 m3/day
Peak Periode = 2 Jam
Total Air Panas / Peak = 4.608 Liter
Kapasitas Tangki WIKA = 1,000 Liter
Jumlah Tangki WIKA = 4 Unit
5. HEAT PUMP
Input = 4.11 kW
Output = 14.8 kW
Rate Hot Water = 398 Liter / Jam
Jumlah Unit = 4 Unit
Total Input = 16 kW
Total Output = 59 kW
Total Rate Water = 1592 Liter / Jam
Page 2 of 2